Loading...
HomeMy WebLinkAboutE003 - ELECTRICAL DETAILSSCALE: NONE NOTES 6" MIN. 6" MIN. 12" 12" 6 7.5 24 16.5 15 6 6 6 27 27 27 63 63 27 63 63 6 6 1 EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL GROUND WIRE. NO DAISY CHANING PERMITTED. 2 THIS DRAWING IS FOR INFORMATION ONLY. REFER TO ELECTRICAL DRAWINGS FOR CONSTRUCTION DETAILS. 3 ONLY SOUND EQUIPMENT TO BE SERVED FROM THIS PANEL AND TRANSFORMER. 4 BOTH BUS BARS ISOLATED FROM PANEL ENCLOSURE. NO BONDING BETWEEN NEUTRAL AND GROUND. NOTE 4 ISOLATED GROUND BUS "XIT" TECHNICAL GROUND NOTE 4 ISOLATED GROUND BUS CONDUIT GROUNDING FITTING (TYPICAL) FERROUS CONDUIT MCB 20A 20A CORE SHIELD N G N G H G N 42" SCALE: NONE B E003 76.5" H. BASE BY THE E.C. 1.5" HIGH CONCRETE 42" 42" SCALE: NONE A E003 9/32"D. (TYP. OF 12) NOTE: ASSEMBLY AS MADE BY NEWTON INSTRUMENT COMPANY BUTNER, NC. (THIS WORK IS BID UNDER DIV. 26) 3 1-1/8"O.C. 2 9/16"D. 5 6/32"D. (TYP. OF 6) 1-1/8"O.C. 2 4"X1/4"X10" MIN. LENGTH GROUNDING BAR #A-6163 ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND WALL MOUNTING BRACKET #A-6056. CONNECTIONS. 5/8" LOCKWASHER INSULATORS #3061-4. 5/8-11X1 H.H.C.S. #3012-1 3 1 5 4 2 1 4 6 PROVIDE #6 AWG GROUNDING WIRE FROM TECHNOLOGY GROUND BAR TO SERVICE ENTRANCE GROUND. 6 C E003 2" ABOVE FIN. GRADE OR EVEN WITH SURROUNDING SLAB. GENERATOR ENCLOSURE GENERATOR BASE. SIZE PER MANUFACTURER'S RECOMMENDATIONS. CONCRETE ISOLATION PAD SIZE AND LOCATE ANCHOR BOLTS PER MANUFACTURER'S RECOMMENDATIONS. CRUSHED STONE SUPERVISORY CIRCUIT EM POWER CIRCUIT CONTROL CIRCUIT BLOCK HEATER & BATTERY CHARGER CIRCUITS SCALE: NONE G E003 1'-6" 4' 3000 LB. CONCRETE 3.5" I.D. DUCTS, SCHEDULE 40 PVC. MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3" ENCASEMENT (TYPICAL). 1 2 3 PROVIDE CONDUIT SPACERS 6'-0" O.C. 4 RED DYE, RED DUST OR YELLOW MARKER TAPE ON COMPACTED FILL. 3 TAMPED BACKFILL 4 1'-6" 2'-3" COVER FINISH GRADE 2 1 3 3 3 SCALE: NONE E E003 3 3 SCALE: NONE 3 2 1 YELLOW MARKER TAPE ON COMPACTED FILL. MIN. 3" SAND ENCASEMENT. PVC. SIZE AS NOTED ON PLANS. DIRECT BURIAL DUCT, RIGID SCHEDULE 40 3 BACKFILL TAMPED FINISH GRADE 1'-6" 2'-6" COVER 2 1 F E003 10 9 8 7 6 5 4 3 2 1 WELD ALL METAL PARTS TO ROD.) 5/8" DIA. x 8FT. GROUND ROD. (EXOTHERMICALLY SUMP COVER NEENAH 4055. MANHOLE RISER SECTION. CONFIRM HEIGHT PER MEET OHIO DEPT. OF TRANSPORTATION - H20 CONCRETE TOP, MIN. 6" THICK WITH REINF. TO UNITS. @ 12" C.C. BOTH WAYS FOR POURED IN PLACE WITH MINIMUM 1/2" DIA. REINFORCED STEEL CONCRETE WALLS AND FLOOR MIN. 6" THICK KNOCKOUT FOR PRECAST UNITS. BOTTOM HALF WITH COARSE GRAVEL. PROVIDE SUMP - APPROX. 8" I.D. x 24" DEEP - FILL VERTICALLY AT APPROX. 24" CENTERS, ALL GALVANIZED STEEL CABLE SUPPORTS PLACED EYES. GALVANIZED STEEL LADDER WITH TOP HOOK DUCT BANK CONFIGURATION. DUCT KNOCKOUT AND PULLING EYE TO MATCH SERIES MARK "ELECTRIC" OR "TELEPHONE". APPROXIMATE WEIGHT 625 LB. NEENAH R-1640 M.H. FRAME & COVER 27" DIA. CLEAR OPENING SCALE: NONE 5 9 6 6 4 6 BANK DUCT 3 7 1 36" APPROX. 14" APPROX. 2 2 2 1 2 10 6" 6" 6" 6" __'-0" __'-0" _'-0" 10 SIDES. HEAVY TRAFFIC LOADING. SITE CONDITION. 2 2 2 8 D E003 3 MDP3 SWITCHBOARD RECOMMENDED TECHNICAL SYSTEMS POWER & GROUNDING DIAGRAM GROUND BAR DETAIL UNDERGROUND DUCTS DIRECT BURIAL UNDERGROUND DUCT GENERATOR SET INSTALLATION DETAIL MANHOLE SECTION PLAN SIZE NEUTRAL 2 AWG WIRE SIZES (APPROX. 60%) LARGER THAN PHASE CONDUCTORS A/V RACKS GROUND BUS BAR MAIN BUILDING GROUND AT SERVICE ENTRANCE ALL GROUNDING CONNECTIONS MADE TO COMMON POINT CIRCUIT BREAKER PANEL W/ MAIN BREAKER FERROUS CONDUIT THREE PHASE 225KVA ISOLATION TRANSFORMER NOTE: THIS ISOLATION TRANFORMER IS USED FOR A/V REUIREMENTS ONLY. THIS DETAIL IS GIVEN FOR REFERENCE ONLY. COORDINATE WITH A/V CONSULTANT FOR ALL GROUNDINGREQUIREMENTS PRIOR TO ROUGH-INS. Date: Scale Drawn By Checked By Project Number ARCHITECTURE PLANNING INTERIOR DESIGN STRUCTURAL ENGINEERING 424 East Fourth Street Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m tel: 513/241/4474 fax: 513/241/0081 ISSUANCES COMPUTER FILE 1400 West Dorothy Lane Dayton, Ohio 45409-1310 Tel: (937) 224-0861 Fax: (937) 224-5777 3417 South Sherman Drive Beech Grove, IN 46107 Tel: (317) 780-1555 Fax: (317) 780-6525 750 North Orleans, Suite 400 Chicago, IL 60610 Tel: (312) 944-8230 Fax: (312) 944-8297 117 East Washington Street, Suite 200 Indianapolis, IN 46204 Tel: (317) 637-2222 Fax: (317) 637-2260 1137 West Taylor St. Suite 316 Chicago, IL 60607 Tel: (312) 224-8460 Fax: (312) 224-8961 1025 N.Watery Ln. Brigham City, UT 84302 TEL: (453) 723-5000 FAX: (453) 538-5506 6622 Kingspointe Parkway Orlando, FL 33819 Tel: (407) 816-9400 Fax: (407) 816-9300 1 SCHEMATIC DESIGN 10.18.07 2 DESIGN DEVELOPMENT 01.18.08 3 CD 50% 03.14.08 4 PERMIT SET 04.25.08 5 ADDENDUM #2 05.16.08 No. Description Date 6 ADDENDUM #3 05.22.08 7 ADDENDUM #5 06.04.08 8 PERMIT SET 06.10.08 6/10/2008 1:00:12 PM C:\Drawings\2007-06019-Central-Local.rvt E003 ELECTRICAL DETAILS New Worship Center Checker Author 05-22-08 2007-06019