HomeMy WebLinkAboutE003 - ELECTRICAL DETAILSSCALE: NONE
NOTES
6" MIN. 6" MIN.
12" 12"
6
7.5
24
16.5
15
6
6 6
27 27
27 63 63 27 63 63
6 6
1 EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL
GROUND WIRE. NO DAISY CHANING PERMITTED.
2 THIS DRAWING IS FOR INFORMATION ONLY. REFER TO
ELECTRICAL DRAWINGS FOR CONSTRUCTION DETAILS.
3 ONLY SOUND EQUIPMENT TO BE SERVED FROM THIS PANEL
AND TRANSFORMER.
4 BOTH BUS BARS ISOLATED FROM PANEL ENCLOSURE. NO
BONDING BETWEEN NEUTRAL AND GROUND.
NOTE 4
ISOLATED GROUND BUS
"XIT" TECHNICAL GROUND
NOTE 4
ISOLATED GROUND BUS
CONDUIT
GROUNDING
FITTING
(TYPICAL)
FERROUS
CONDUIT
MCB
20A
20A
CORE SHIELD
N
G
N
G
H
G
N
42"
SCALE: NONE
B
E003
76.5" H.
BASE BY THE E.C.
1.5" HIGH CONCRETE
42" 42"
SCALE: NONE
A
E003
9/32"D. (TYP. OF 12)
NOTE: ASSEMBLY AS MADE BY NEWTON
INSTRUMENT COMPANY BUTNER, NC.
(THIS WORK IS BID UNDER DIV. 26)
3
1-1/8"O.C.
2
9/16"D.
5
6/32"D. (TYP. OF 6)
1-1/8"O.C.
2
4"X1/4"X10" MIN. LENGTH GROUNDING BAR #A-6163
ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND
WALL MOUNTING BRACKET #A-6056.
CONNECTIONS.
5/8" LOCKWASHER
INSULATORS #3061-4.
5/8-11X1 H.H.C.S. #3012-1
3
1
5
4
2
1
4
6
PROVIDE #6 AWG GROUNDING WIRE FROM TECHNOLOGY
GROUND BAR TO SERVICE ENTRANCE GROUND.
6
C
E003
2" ABOVE FIN. GRADE OR EVEN
WITH SURROUNDING SLAB.
GENERATOR ENCLOSURE
GENERATOR BASE. SIZE
PER MANUFACTURER'S
RECOMMENDATIONS.
CONCRETE ISOLATION PAD
SIZE AND LOCATE ANCHOR
BOLTS PER MANUFACTURER'S
RECOMMENDATIONS.
CRUSHED STONE
SUPERVISORY CIRCUIT
EM POWER CIRCUIT
CONTROL CIRCUIT
BLOCK HEATER & BATTERY
CHARGER CIRCUITS
SCALE: NONE
G
E003
1'-6"
4'
3000 LB. CONCRETE
3.5" I.D. DUCTS, SCHEDULE 40 PVC.
MIN. 3" SPACING BETWEEN CONDUITS
AND MIN. 3" ENCASEMENT (TYPICAL).
1
2
3
PROVIDE CONDUIT SPACERS 6'-0" O.C.
4 RED DYE, RED DUST OR YELLOW MARKER
TAPE ON COMPACTED FILL.
3
TAMPED
BACKFILL
4
1'-6"
2'-3" COVER
FINISH GRADE
2
1
3 3
3
SCALE: NONE
E
E003
3 3
SCALE: NONE
3
2
1
YELLOW MARKER TAPE ON COMPACTED FILL.
MIN. 3" SAND ENCASEMENT.
PVC. SIZE AS NOTED ON PLANS.
DIRECT BURIAL DUCT, RIGID SCHEDULE 40
3
BACKFILL
TAMPED
FINISH GRADE
1'-6"
2'-6" COVER
2
1
F
E003
10
9
8
7
6
5
4
3
2
1
WELD ALL METAL PARTS TO ROD.)
5/8" DIA. x 8FT. GROUND ROD. (EXOTHERMICALLY
SUMP COVER NEENAH 4055.
MANHOLE RISER SECTION. CONFIRM HEIGHT PER
MEET OHIO DEPT. OF TRANSPORTATION - H20
CONCRETE TOP, MIN. 6" THICK WITH REINF. TO
UNITS.
@ 12" C.C. BOTH WAYS FOR POURED IN PLACE
WITH MINIMUM 1/2" DIA. REINFORCED STEEL
CONCRETE WALLS AND FLOOR MIN. 6" THICK
KNOCKOUT FOR PRECAST UNITS.
BOTTOM HALF WITH COARSE GRAVEL. PROVIDE
SUMP - APPROX. 8" I.D. x 24" DEEP - FILL
VERTICALLY AT APPROX. 24" CENTERS, ALL
GALVANIZED STEEL CABLE SUPPORTS PLACED
EYES.
GALVANIZED STEEL LADDER WITH TOP HOOK
DUCT BANK CONFIGURATION.
DUCT KNOCKOUT AND PULLING EYE TO MATCH
SERIES MARK "ELECTRIC" OR "TELEPHONE".
APPROXIMATE WEIGHT 625 LB. NEENAH R-1640
M.H. FRAME & COVER 27" DIA. CLEAR OPENING
SCALE: NONE
5
9
6
6
4
6
BANK
DUCT
3 7
1
36" APPROX.
14" APPROX.
2
2
2
1
2
10
6" 6"
6" 6"
__'-0"
__'-0"
_'-0"
10
SIDES.
HEAVY TRAFFIC LOADING.
SITE CONDITION.
2
2 2
8
D
E003
3
MDP3 SWITCHBOARD
RECOMMENDED TECHNICAL SYSTEMS POWER & GROUNDING DIAGRAM
GROUND BAR DETAIL
UNDERGROUND DUCTS DIRECT BURIAL UNDERGROUND DUCT GENERATOR SET INSTALLATION DETAIL
MANHOLE
SECTION
PLAN
SIZE NEUTRAL 2 AWG WIRE
SIZES (APPROX. 60%) LARGER
THAN PHASE CONDUCTORS
A/V RACKS
GROUND BUS
BAR
MAIN BUILDING
GROUND AT
SERVICE ENTRANCE
ALL GROUNDING
CONNECTIONS
MADE TO COMMON POINT
CIRCUIT BREAKER
PANEL W/ MAIN BREAKER
FERROUS
CONDUIT
THREE PHASE 225KVA
ISOLATION TRANSFORMER
NOTE: THIS ISOLATION TRANFORMER IS USED FOR A/V REUIREMENTS ONLY. THIS DETAIL IS GIVEN FOR REFERENCE ONLY. COORDINATE WITH A/V CONSULTANT FOR ALL GROUNDINGREQUIREMENTS
PRIOR TO ROUGH-INS.
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
1 SCHEMATIC DESIGN 10.18.07
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
5 ADDENDUM #2 05.16.08
No. Description Date
6 ADDENDUM #3 05.22.08
7 ADDENDUM #5 06.04.08
8 PERMIT SET 06.10.08
6/10/2008 1:00:12 PM
C:\Drawings\2007-06019-Central-Local.rvt
E003
ELECTRICAL DETAILS
New Worship
Center
Checker
Author
05-22-08
2007-06019