HomeMy WebLinkAboutH001 - LEGEND, GENERAL NOTES, AND SCHEDULESPLUMBING CONTRACTOR
P.C.
HVAC CONTRACTOR
H.C.
ELECTRICAL CONTRACTOR
E.C.
GENERAL CONTRACTOR
G.C.
NOT IN HVAC CONTRACT
N.I.H.C.
THERMOSTAT - MOUNTING HEIGHT 46",TO MEET ADA REQUIREMENTS. WHEN
MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
T
S SPACE TEMPERATURE SENSOR.
123 ROOM NUMBER.
EQUIPMENT ITEM. (TO BE USED AS AID IN COORDINATING THE VARIOUS TRADES.)
APPROXIMATE ELEVATION FROM FLOOR TO BOTTOM OF DUCT, PIPE, DEVICE OR
9'-8"
SECTION "A" DESIGNATION , SHOWN ON SHEET H1.01.
H1.01
A
DETAIL "A", SHOWN ON SHEET H1.01.
H1.01
A
8"D = NECK SIZE. 300 = REQUIRED CFM. 3 = AIR DISCHARGE IF OTHER
AIR DEVICE A3 = DESIGNATION - REFER TO AIR DEVICE SCHEDULE.
THAN 4-WAY. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING
MOUNTED DEVICES.
A3-8"D
300-3
WALL OR DUCT MOUNTED AIR DEVICE. G1 = DESIGNATION - REFER TO AIR
DEVICE SCHEDULE. 24"x16" = DUCT CONNECTION SIZE. 200 = REQUIRED
CFM. 9'-4" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF DEVICE.
200-9'-4"
G1-24x16
FACE AREA IN SQ. FT.
DL-2 DOOR LOUVER BY GENERAL CONTRACTOR. NUMBER INDICATES MINIMUM GROSS
DOOR UNDERCUT BY GENERAL CONTRACTOR.
U/C
R DUCT RISE IN DIRECTION OF AIR FLOW.
D DUCT DROP IN DIRECTION OF AIR FLOW.
DUCT WITH 1" ACOUSTICAL LINER. DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.
DUCT CONSTRUCTED OF SPECIAL MATERIAL AS NOTED.
FLEXIBLE DUCT CONNECTION.
AIR TURNING VANES.
MANUAL BALANCING VOLUME DAMPER WITH LOCKING DEVICE.
M.D.
FIRE DAMPER - LETTER "A", "B", OR "C" INDICATES TYPE REQUIRED, LETTER "D" OR "S"
INDICATES DYNAMIC OR STATIC - SEE DETAIL.
A-D
SMOKE DAMPER.
S
COMBINATION FIRE SMOKE DAMPER.
FS
PRESSURE GAUGE.
P
UNION.
CLEAN OUT.
STRAINER.
SHUTOFF VALVE
SHUTOFF AND BALANCING VALVE
CHECK VALVE
D DRAIN PIPE.
DIRECTION OF FLOW
PITCH DOWN
EP EXPANSION TANK PIPE.
GENERAL NOTES
FANS
DUCT CONSTRUCTION & SEALING
INDEX OF DRAWINGS
AIR SUPPLY ROOFTOP UNITS AIR DISTRIBUTION DEVICES
AIR CONTROL UNITS-HOT WATER
ROOM HEATING UNITS
COOLING SPLIT SYSTEM
COOLING-HEATING SPLIT SYSTEMS
SOUND ATTENUATORS
SHEET DESCRIPTION
OUTDOOR UNIT INDOOR UNIT
GENERAL CONTRACTOR.
WALL LINTEL FOR WALL OPENING BY
WHERE REQUIRED FOR DECK SUPPORT AND
STEEL FRAMING AROUND ROOF OPENING.
PHASE
CONSIDERED MINIMUM.
MOTOR HORSEPOWERS LISTED ARE TO BE
300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.
SONES VALUES BASED ON A.M.C.A. BULLETINS
DESCRIPTION
UNIT
GENERAL NOTES
CONTRACTOR.
VERIFY SIZE & COORDINATE WITH GENERAL
ROOF & WALL OPENINGS ARE APPROXIMATE.
SERVICE
SONES
STATIC WHEEL MAX.
PRESS
CFM
DIA.
MOTOR
H.P. VOLT
REMARKS
APPROX. ROOF/
WALL OPG.
CLASS CLASS
STRUCT.
S.P. CON-
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR INSULATION;
REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION OPTIONS:
DUCT SYSTEM
ETC.
GENERAL NOTES
LEAKAGE
S.M.A.C.N.A. CLASS.
SEAL REMARKS
O.W.B.E.
FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL,
"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.
SUPPLY AIR DIFFUSERS SHALL BE 4-WAY
BLOW UNLESS OTHERWISE NOTED ON DWGS.
DESCRIPTION
REFER TO SPECIFICATIONS FOR OTHER
ALL LAY-IN AIR DEVICES SHALL FIT IN
24"X24" LAY-IN CEILING SYSTEM.
SYMBOL
GENERAL NOTES
MANUFACTURERS.
TYPE MOUNTING MATERIAL
LAY-IN SURFACE STEEL
PROVIDE AUX. FRAMES FOR AIR DEVICES IN
PLASTER, GYPSUM BOARD, GLAZED TILE OR
CERAMIC TILE SURFACES.
FINISH CATALOG NUMBER SEE
ACCESSORIES NOTE
A1
A2
D1
D2
D3
D4
D5
F1
G1
H1
J1
J2
K1
K2
S1
SUPPLY CLG. SQ. DIFFUSER
SUPPLY CLG. SQ. DIFFUSER
ROUND FLOOR FLOW DIFFUSER
IN-WALL DISPLACEMENT DIFFUSER
RECTANGLE 3-WAY DISPLACEMENT DIFFUSER
STAIRCASE SWIRL DIFFUSER
HALF-ROUND 180 DISPLACEMENT DIFFUSER
DOUBLE DEFLECTION SUPPLY REGISTER
RETURN GRILLE
RETURN/EXHAUST REGISTER
RETURN CLG. GRILLE
RETURN CLG. GRILLE
RETURN CLG. REGISTER
RETURN CLG. REGISTER
ALUM. PRICE
SCDA
SCDA
TROX "FB200"
TROX "QLE-U"
TROX "QLK-90"
TROX "SDRF-5"
TROX "QLK-180"
5200
90
530D
80
80
80D
80D
---
---
8" DIA.
48"W x 24"H
36"W x 60"H
20" x 3"H
24" DIA. x 48"H
O.B.D.
---
O.B.D.
---
---
O.B.D.
O.B.D.
-
-
-
-
-
-
-
-
-
-
-
-
-
-
SUPPLY DUCT UPSTREAM OF ROOFTOP
UNITS (RTU-1,2,3,4)
SUPPLY DUCT DOWNSTREAM OF VAV
REHEAT BOXES
SUPPLY DUCT RUNOUTS TO FLOOR
FLOW DIFFUSERS
RETURN AIR DUCTWORK
TRANSFER AIR DUCTWORK
GENERAL/TOILET EXHAUST
ANY DUCTWORK NOT LISTED ABOVE
+3.0"
+1.0"
+1.0"
-1.0"
-1.0"
-1.0"
+1.0"
B
B
B
B
B
B
B
12
24
24
24
24
24
24
-
-
-
-
-
-
-
EF-1
EF-2
EF-3
EF-4
AUTOMATIC TEMP. CONTROLS SUBCONTRACTOR
A.T.C.
H HOT WATER SUPPLY PIPE
H HOT WATER RETURN PIPE
WATER MAKE-UP PIPE
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
L REFRIGERANT - LIQUID
S REFRIGERANT - SUCTION
HG REFRIGERANT - HOT GAS
"CONNECT TO EXISTING" SYMBOL - DUCTS OR PIPES
A ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE
INSTALLED HOLD TIGHT TO STRUCTURE.
B THIS CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL THE PIPES, DUCTS,
UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFF-SETS WHERE NECESSARY.
C COORDINATE THE LOCATION OF ALL AIR DEVICES LOCATED IN THE CEILING WITH THE
ARCHITECTS REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING PLAN.
D SPACE ABOVE CEILING SHALL BE USED AS A RETURN AIR PLENUM. (RTU-4)
E ALL EXPOSED DUCTWORK, PIPING, (VAV-REHEAT BOXES, AIR DEVICES SHALL BE
GALVANNEALED OR BONDERIZED COATING (PAINT GRIP) IN ORDER TO ACCEPT PAINT.
FINISH PAINTING WILL BE DONE BY OTHERS.
F BRANCH DUCTS FROM VAV-REHEAT BOXES AND AIR DEVICES SHALL BE SAME SIZE
INLET OF UNIT OR DEVICE UNLESS NOTED OTHERWISE.
G BRANCH PIPING TO VAV-REHEAT BOXES SHALL BE SAME SIZE INDICATED ON AIR
CONTROL UINIT SCHEDULE.
H COORDINATE EXPOSED DUCT LOCATIONS WITH ARCHITECTURAL DRAWINGS IN
ADDITION TO SPECIFIC HVAC PLAN NOTES.
I ALL SQUARE CORNER DUCT FITTINGS, EXCEPT RETURN AIR TRANSFER BOOTS SHALL
BE EQUIPPED WITH AIRFOIL TYPE TURNING VANES.
J ALL PENETRATIONS FOR ATC DEVICES SHALL BE REPAIRED AND REINSULATED.
K ATC COMPONENTS, POINTS, OR HARDWARE NOT SHOWN BUT REQUIRED TO ACHIEVE
THE SPECIFIED SEQUENCE OF CONTROL SHALL BE INCLUDED.
L THIS CONTRACTOR SHALL COORDINATE WITH AUDIO/VISUAL TECHNOLOGY DRAWINGS
FOR ALL CABLE TRAY, CONDUITS, PROJECTORS, ETC. LOCATED ABOVE CEILINGS
REQUIRING ACCESS SPACE.
M THIS CONTRACTOR SHALL COORDINATE WITH ALL TRADES PRIOR TO TRENCHING,
INSTALLATION OF UNDERFLOOR DUCTWORK, BACKFILL AND ALL RISERS THRU FLOOR
SLAB. REFER TO DETAILS AND SPECIFICATIONS.
N IN WORSHIP CENTER, THIS CONTRACTOR SHALL PROVIDE SLEEVE FOR 8" DIA. FLOOR
DIFFUSER AT SLAB AND EXTEND 3" A.F.F. AND PROVIDE TEMPORARY DUCT CAP DURING
CONSTRUCTION PERIOD. COORDINATE FINAL DEVICE LAYOUT WITH G.C. AND SEATING CONTRACTOR.
MAX. AIR P.D. INCHES W.G.
ROW / FINS
STAGES - COOLING
PRESS. DROP IN. W.G. (CLEAN)
LEAV. AIR TEMP. (DB/WB)(COIL)
MAX. WATER P.D.- FT.
AUTO. VALVE SIZE & TYPE
ENT. AIR TEMP. (DB/WB)
UNIT FILTERS
HOUSING
DX-COOLING COIL
TYPE
TOTAL (MBH)
COOLANT
SENSIBLE (MBH)
GPM
ENT. AIR (DB)
LEAV. AIR (DB)
HEATING COIL
HEATING COIL CAPACITY BASED ON 180 ENT. WATER
TOTAL S.P.- INCHES W.G.
MIN. FACE AREA (SF)
MOTOR (MIN. H.P.)
UNIT CONFIGURATION
SUPPLY FAN
CAPACITY (MBH)
WHEEL TYPE
WHEEL DIA.
CFM (TOTAL)
UNIT NUMBER
AREA SERVED
UNIT LOCATION
GENERAL NOTES MOTOR - 208V - 3 PHASE UNLESS NOTED
OTHERWISE.
RTU-2
STAGE AREA
ROOF
VERTICAL DISCHARGE
8,750
4.9"/3.0"
27"
PLENUM
15 HP
YES
BALCONY'S
ROOF
VERTICAL DISCHARGE
4.9"/3.0"
2 @ 27"
PLENUM
2 @ 15 HP
YES
RTU-1
PIT LEVEL ROOMS
ROOF
VERTICAL DISCHARGE
8,750
4.9"/3.0"
27"
PLENUM
15 HP
YES
RTU-4
196.0
54.0
5.0
11.7
515.0
34.0
5.0
31.7
128.0
45.0
3.0
10.5
19.5
227.3
345.0
78.5 / 66.8
53.3 / 53.3
44.0
531.7
715.0
86.6 / 69.1
54.1 / 54.0
285.0
358.0
87.7/69.3
55.7/55.7
TOTAL S.P.- INCHES W.G./E.S.P.
MOTOR (MIN. H.P.)
WHEEL TYPE
WHEEL DIA.
CFM (TOTAL)
VFD
3 NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH NOTE IS SHOWN.
EXHAUST AIR THRU WHEEL-CFM
O.A. ENT. AIR DB/WB-SUMMER
WHEEL OUTSIDE AIR CFM
O.A. LEAV. AIR DB/WB-SUMMER
EXH. ENT. AIR DB/WB-SUMMER
EXH. LEAV. AIR DB/WB-SUMMER
MAX. AIR P.D- INCHES W.G
TYPE
PRESS. DROP IN. W.G. (CLEAN)
HOUSING
MINIMUM OUTSIDE AIR CFM
ISOLATOR ROOF CURB
8,000 1,500 1,500
WHEEL FILTER(2) ENERGY RECOVERY WHEEL EXH. FAN
8,750
2.1" / 1.5"
PLENUM
7.5
YES
16,000
2.5" / 1.5"
PLENUM
2 @ 7.5
YES
8,750
1.8" / 1.5"
22"
PLENUM
7.5
YES
700 150 49.0 3.3 0.75" 1.4 1
INLET
TYPES - "V.V." VARIABLE VOLUME;
"V.V.R." VARIABLE VOLUME REHEAT;
"C.V.R." CONSTANT VOLUME REHEAT.
UNIT & COIL AT MAX. CFM.
.50"S.P. MAX. PRESS. DROP THRU
UNIT
NO.
TYPE
DIA.
GENERAL NOTES
REHEAT COIL CAPACITY BASED ON
WINTER MIN. CFM, 55 ENT. AIR &
180 ENT. WATER TEMPERATURE.
MBH
CFM
WINTER
MAX. MIN. MIN.
SUMMER
REHEAT COIL
GPM RUNOUT
SIZE
NOTE
SEE
V.V.R.
4-1
4-2
4-3
4-4
4-5
4-6
4-7
4-8
4-9
4-10
4-11
4-12
10"
10"
8"
12"
12"
12"
6"
8"
6"
6"
1000
450
1325
1275
1200
1770
275
535
285
200
CV
2-WAY CONTROL VALVE, UNLESS
NOTED
NOTES:
1. 3-WAY CONTROL VALVE
BY GEN. CONT'R.
LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENINGS PROVIDED
RECESSED UNITS TO HAVE FOUR(4) SIDE
OVERLAP UNLESS OTHERWISE NOTED.
APPROX. CABINET DIMENSIONS
HEATING CAPACITY BASED ON 60 ENT. AIR &
180 ENT. WATER
MAXIMUM WATER PRESS. DROP THRU COIL
DESCRIPTION
NO.
UNIT
10.0 FT.
GENERAL NOTES
VERIFY/COORDINATE CABINET DIMENSIONS,
MOUNTING & RECESS REQUIREMENTS WITH
ARCHITECTURAL DWGS. PRIOR TO ORDERING.
MOTOR: 115V.-1PH. UNLESS OTHERWISE
CFM
STAIRS
SERVICE
NOTED.
RUNOUT
MBH
HTG.
GPM
3.0
SIZE
0.75"
VALVE LENGTH
0.50"
AUTO.
47"
DEPTH
10" -
RECESS
-
HEIGHT
540 45.4 25"
NOTES
CUH-1
UH-1 UNIT HEATER - HORIZONTAL
CABINET UNIT HEATER - MODEL B
COST FOR INCREASE OR CHANGE OF ELECTRICAL SERVICE
MODEL NO. (OUTDOOR UNIT)
BASIS OF DESIGN (MFR. & NO.)
MOUNTING
VOLTAGE & PHASE
DESCRIPTION
UNIT NUMBER
MAX. FUSE SIZE (FLA / MOP)
CAPACITY
ENTERING AIR DB
REFRIGERANT (LIQUID & SUCTION)
REFRIGERANT LIQUID TYPE
KW / VOLTAGE
HUMIDIFIER
TYPE
SENSIBLE (MBH)
COOLING
REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE
DISCRIPTION
FAN
MOTOR HP
TOTAL (MBH)
UNIT CONFIGURATION
EXTERNAL S.P.
CFM
INDOOR UNIT NUMBER
AREA SERVED
GENERAL NOTES:
FOR EQUIPMENT SELECTED SHALL BE BORNE BY H.C.
BE VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER.
CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST
SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL.
ELECTRIC SERVICES FOR OUTDOOR AND INDOOR UNIT -
AC-3
SIZES, NUMBER OF PIPES AND CIRCUITS, ARRANGEMENT,
ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
INDOOR UNIT
ENTERING AIR WB
HTG.
KW / VOLTAGE
ELECTRIC REHEAT - (MBH)
MODEL NO. (INDOOR UNIT)
MAX. FUSE SIZE (FLA / MOP)
NOMINAL TONS
(APPROX. SIZES)
OUTDOOR UNIT
VOLTAGE
33.5 FLA / 45.0
MMD36E-A
CU-3
CONDENSING UNIT
3.0
19.3 FLA / 40.0
208 / 1
ROOF
PFC037A
3/8" & 7/8"
R134A
LIEBERT
37.2
28.5
80.0
67.0
16.0
4.7 / 208-1
208 / 1
AIR-COOLED
HORIZ. CONCEALED
1200
0.4"
SPLIT SYSTEM
1/2
A/V RACK
2 @ 27"
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
V.V.R.
EF-5
POWER ROOF VENTILATOR TOILET ROOMS 1095
POWER ROOF VENTILATOR TOILET ROOMS 700
POWER ROOF VENTILATOR STORAGE ROOM
SIDEWALL EXHAUSTER
POWER ROOF VENTILATOR TOILET ROOMS
ELEVATOR EQUIP. ROOM
300
EF-6 POWER ROOF VENTILATOR MECHANICAL ROOM
4-13 6" 200
V.V.R.
4-14 6" 380
V.V.R.
460 140 24.0 1.6 0.75" 0.8
915
-
300 70 22.0 1.5 0.75" 0.7 -
690 200 34.0 2.3 0.75" 0.9 -
640 195 31.0 2.1 0.75" 0.9 -
600 180 29.0 2.0 0.75" 0.8 -
885 270 43.0 2.9 0.75" 1.2 1
175 55 9.0 0.6 0.75" 0.3 1
150 45 7.0 0.5 0.75" 0.2 -
280 85 14.0 1.0 0.75" 0.4 -
145 45 7.0 0.5 0.75" 0.2 -
100 30 5.0 0.5 0.75" 0.2 -
100 30 5.0 0.5 0.75" 0.2 -
190 60 10.0 0.7 0.75" 0.3 1
250 45 12.0 0.9 0.75" 0.4 1
14"
6" 350
4-15 6" 300
V.V.R.
ALUM. E.C.L.
0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,3
0.5 10" 10.0 1/4 115 1 14.5"x14.5" 1,3
0.375 12" 10.0 1/4 115 1 14.5"x14.5" 1,4
0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4
0.5 9" 8.0 1/4 115 1 14.5"x14.5" 1,3
0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,4
500
1000
1000
STAIRS
340 29.4 2.0 38" 10" 25" - -
CUH-2 CABINET UNIT HEATER - MODEL B
CORRIDOR
540 45.4 3.0 47" 10" 25" - -
CUH-3 CABINET UNIT HEATER - MODEL B
UH-2 UNIT HEATER - HORIZONTAL
DELIVERY
FIRE PUMP ROOM
1100 32.1 3.3 23" 17" 17" - -
815 27.4 2.8 23" 17" 17" - -
TONS - COOLING 60 30 30
16,000
VFD
18.8 7.3 7.3
91.0 95.2 65.5
0.5" 0.5" 0.5"
1.WAY5"/2-WAY 1.5"/3-1.5"/2-WAY
MIN. FACE AREA (SF) 19.5
R-410A R-410A R-410A
6 / 12 FPI 6 / 12 FPI 6 / 12 FPI
4 2 2
2" - 30% PLEATED
4" - MERV 13
2" - 30% PLEATED
4" - MERV 13
2" - 30% PLEATED
4" - MERV 13
0.55
SIDE ACCESS
0.55
SIDE ACCESS
0.55
SIDE ACCESS
22"
1,500
1,500
91.0 / 75.0
80.0 / 68.1
78.0 / 66.5
88.9 / 73.6
0.50"
8,000
8,000
91.0 / 75.0
87.3 / 70.3
86.0 / 68.0
89.7 / 72.9
0.75"
2" - 30% PLEATED
0.55"
SIDE ACCESS
2" - 30% PLEATED
0.55"
SIDE ACCESS
MISC.
UNIT MOUNTED
YES YES YES
DISCONNECT SWITCH YES YES YES
CONTROL PANEL WITH
LON INTERFACE
MODULATING HOT GAS
REHEAT COIL
YES YES YES
YES YES NO
HOT GAS LEAD & LAG
ELECTRICAL - (FLA / MOP)
YES YES YES
UNIT WEIGHTS
BASIS OF DESIGN
407.0/450.0 204.0 / 250.0 165.0 / 225.0
9800 LBS. 4500 LBS. 4000 LBS.
AAON "RN-060" AAON "RM-030" AAON "RM-030"
ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT -
VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER. COST FOR
DX-COOLING
POWER CCT. (A.)
ENTERING AIR TEMP. (WB)
BASIS OF DESIGN (MFR.)
HOT GAS BY-PASS
(APPROXIMATE SIZES)
REFRIG. LIQUID & SUCTION
VOLTAGE & PHASE
POWER CIRCUIT (FLA / MOP)
ENTERING AIR TEMP.
HEATING OUTPUT (MBH)
KW
VOLT.
PIPE
RUNOUT
GPM
ENTERING AIR TEMP. (DB)
MOUNTING
NOMINAL TONS
DESCRIPTION
OUTSIDE AIR
LEAVING AIR TEMP.
HEATING
ELECTRIC
COIL
COIL
WATER
HOT
WATER
PHASE
STAGES
(MIN.)
AUTO
VALVE
ENTERING
IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE
AND ARE BASED ON SINGLE CIRCUITING. SIZING, NUMBER
REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE
SENSIBLE (MBH)
VOLTAGE & PHASE
EXTERNAL S.P./TOTAL
UNIT CONFIGURATION
DESCRIPTION
FAN
TOTAL (MBH)
MOTOR HP
CFM
AREA SERVED
SYSTEM NUMBER
GENERAL NOTES:
SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL
CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST BE
INCREASE OR CHANGE OF ELECTRICAL SERVICE FOR
MENT SELECTED SHALL BE BORNE BY HVAC CONTRACTOR.
EQUIP-
AC-1
PROJECTION ROOM
CABINET C
7.5
AIR HANDLING
DRAW-THRU
HORIZONTAL
TONS - COOLING
AC-2
PROJECTION ROOM
CABINET C
7.5
AIR HANDLING
DRAW-THRU
HORIZONTAL
3,000
0.75" / 2.0"
2 HP
208/3
81.5
69.9
75.0
62.0
3,000
0.75" / 2.0"
2 HP
208/3
81.5
69.9
75.0
62.0
105.3
5.0 / 180
1.0" / 0.75"
103 F
INDOOR UNIT ELECTRIC
8.0 FLA / 15.0 MOP / 208-3
0
105.3
5.0 / 180
1.0" / 0.75"
103 F
0
CU-1 CU-2
7.5
20.0 / 40.0
208/3
ROOF
7/8" & 3/8"
YES
AAON
7/8" & 3/8"
YES
AAON
7.5
20.0 / 40.0
208/3
ROOF
0.75" 0.50"
0.75" 0.50"
0.75" 0.50"
0.75" 0.50"
AC-4
33.5 FLA / 45.0
MMD36E-A
CU-4
CONDENSING UNIT
3.0
19.3 FLA / 40.0
208 / 1
ROOF
PFC037A
3/8" & 7/8"
R134A
LIEBERT
37.2
28.5
80.0
67.0
16.0
4.7 / 208-1
208 / 1
AIR-COOLED
HORIZ. CONCEALED
1200
0.4"
SPLIT SYSTEM
1/2
SERVER ROOM
REFRIGERANT
R-410A R-410A
STAIRS/CORRIDOR
540 45.4 3.0 47" 10" 25" - -
CUH-4 CABINET UNIT HEATER - MODEL B 0.75" 0.50"
RTU-3
WORSHIP CENTER
ROOF
VERTICAL DISCHARGE
21,000
6.3"/3.0"
2 @ 30"
PLENUM
2 @ 20 HP
662.0
34.0
10.0
41.7
44.0
654.0
840.0
86.8 / 69.4
56.3 / 56.2
10,500
21,000
2.25" / 1.0"
2 @ 27"
PLENUM
2 @ 7.5
YES
70
18.8
89.8
0.5"
1.5"/2-WAY
YES
R-410A
6 / 12 FPI
4
2" - 30% PLEATED
4" - MERV 13
0.55
SIDE ACCESS
10,500
10,500
91.0 / 75.0
87.6 / 70.8
86.0 / 68.0
89.4 / 72.5
0.90"
2" - 30% PLEATED
0.55"
SIDE ACCESS
YES
YES
YES
YES
YES
425.0 / 450.0
9800 LBS.
AAON "RN-070"
NO. SERVICE
UNIT
REMARKS
L W H
SIZE
CFM
S.P.
MAX
SA-1 RTU-3 SUPPLY
CEILING SLOT DIFFUSER-48" LONG-1 SLOT
S2 CEILING SLOT DIFFUSER-24" LONG-1 SLOT
60 30 36 10,500 0.25"
SA-1A RTU-3 SUPPLY 60 30 36 10,500 0.25"
SA-2 RTU-3 RETURN 60 30 36 10,500 0.25"
SA-2A RTU-3 RETURN 60 30 36 10,500 0.25"
CAPACITY (MBH)
LEAVING AIR TEMP. (DB/WB)
RH
REHEAT
302.0
72.0 / 60.8
53 %
173.0
72.0 / 60.4
52 %
348.0
72.0 / 61.9
57 %
150.0
72.0 / 61.7
56 %
70 F 70 F
LEAVING AIR TEMP. (DB / WB)
52.7 / 52.1 52.7 / 52.1
8.0 FLA / 15.0 MOP / 208-3
F2 SPIRAL DUCT GRILLE SDGE ---
TBDI-2100 INSUL. PLENUM
TBDI-2100 INSUL. PLENUM
-
-
EF-7 SIDEWALL EXHAUSTER FIRE PUMP ROOM 500 0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4
REMARKS
1 PROVIDE FAN WITH 12" HIGH ROOF CURB AND DISCONNECT SWITCH.
2 PROVIDE FAN WITH WALL COLLAR, MOTOR SIDE GUARD, DAMPER AND TERMINATE WITH WALL LOUVER. LOUVER EQUAL TO GREENHECK MODEL "EDJ-430".
3 FAN SHALL BE CONTROLLED BY DDC. PROVIDE OCCUPIED/UNOCCUPIED SCHEDULE.
4 FAN SHALL BE CONTROLLED BY LINE VOLTAGE THERMOSTAT, FURNISHED BY H.C. AND INSTALLED BY E.C.
--
--
--
--
SA-3 RTU-1 SUPPLY 60 30 30 8,000 0.25" --
SA-3A RTU-1 SUPPLY 60 30 30 8,000 0.25" --
SA-4 RTU-1 RETURN 60 30 30 8,000 0.25" --
SA-4A RTU-1 RETURN 60 30 30 8,000 0.25" --
SA-5 RTU-2 SUPPLY 60 30 30 8,750 0.25" --
SA-6 RTU-2 RETURN 60 30 30 8,750 0.25" --
VFD'S FOR FANS ARE UNIT MOUNTED.
-3.0 / -4.0
34.0
-3.0 / -4.0
34.0
-3.0 / -4.0
34.0
O.A. ENT. AIR DB/WB-WINTER
O.A. LEAV. AIR DB-WINTER
EXH. ENT. AIR DB/WB-WINTER
EXH. LEAV. AIR DB-WINTER
75.0 / 62.0 75.0 / 62.0 75.0 / 62.0
38.0 38.0 38.0
HEATING CFM 8,000 4,375 10,500 5,665
T
THERMOMETER WITH THERMOWELL.
UNIT SHALL HAVE INSULATED PIPE CHASE FOR HW
COIL CONNECTIONS.
UH-3 UNIT HEATER - HORIZONTAL STORAGE AREA
1100 32.1 3.3 0.75" 0.50" 23" 17" 17" - -
H001 LEGEND, GENERAL NOTES, AND SCHEDULES
DETAILS
H201 PIT LEVEL FLOOR PLAN
H211 FIRST LEVEL FLOOR PLAN
H221 FIRST LEVEL BALCONY FLOOR PLAN
H231 SECOND LEVEL BALCONY FLOOR PLAN
H300 MECHANICAL ROOM
H301 ROOFTOP EQUIPMENT SECTIONS
H400 HOT WATER PIPING SCHEMATIC AND DATA
H002 DETAILS
H003 DETAILS
H100 EXISTING FIRST LEVEL PLAN-DEMOLITION
RETURN TRANSFER DUCTWORK/SOUND BOOTS
RETURN DUCT UPSTREAM OF ROOFTOP UNITS (RTU-1,2,3&4)
INTERIOR DESIGN AREA
SUPPLY DUCT DOWNSTREAM OF ROOFTOP UNITS (RTU-1,2,3&4)
LINED EXTERNAL
NOTES
INSULATION
SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-RECTANGULAR
DUCT
GENERAL/TOILET EXHAUST
SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-ROUND
RETURN DUCTWORK
NOTES
1 REFER TO SPECIFICATIONS. 23 07 13
1
1
1
1
1
1
-3 DEG. DB WINTER
75 DEG. WB SUMMER
91 DEG. DB SUMMER
OUTSIDE DESIGN TEMPERATURES DESIGN ALTITUDE 792 FT.
ALL AREAS EXCEPT LISTED BELOW
INTERIOR DESIGN AREA
WINTER
DB % HUMIDITY DB
75 50
SUMMER
% HUMIDITY
N/A
ELEC./TECH. RM./IT CLOSETS 80 50 N/A N/A
WORSHIP CENTER
75 50 N/A
RECORDING STUDIO
75 50 N/A
VIDEO/AUDIO CONTROL
75 50 N/A
BALCONY 1&2
75 50 72 N/A
72
72
72
72
1
LEGEND
DUCT INSULATION SCHEDULE
HVAC DESIGN DATA
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
1 SCHEMATIC DESIGN 10.18.07
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
5 ADDENDUM #2 05.16.08
No. Description Date
6 ADDENDUM #3 05.22.08
7 ADDENDUM #5 06.04.08
8 PERMIT SET 06.10.08
6/10/2008 1:53:15 PM
C:\Drawings\REVIT\Northview\2007-06019-Central-local.rvt
H001
LEGEND, GENERAL
NOTES, AND
SCHEDULES
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019