HomeMy WebLinkAboutH001 - LEGEND, GENERAL NOTES, AND SCHEDULESPLUMBING CONTRACTOR P.C. HVAC CONTRACTOR H.C. ELECTRICAL CONTRACTOR E.C. GENERAL CONTRACTOR G.C. NOT IN HVAC CONTRACT N.I.H.C. THERMOSTAT - MOUNTING HEIGHT 46",TO MEET ADA REQUIREMENTS. WHEN MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT. T S SPACE TEMPERATURE SENSOR. 123 ROOM NUMBER. EQUIPMENT ITEM. (TO BE USED AS AID IN COORDINATING THE VARIOUS TRADES.) APPROXIMATE ELEVATION FROM FLOOR TO BOTTOM OF DUCT, PIPE, DEVICE OR 9'-8" SECTION "A" DESIGNATION , SHOWN ON SHEET H1.01. H1.01 A DETAIL "A", SHOWN ON SHEET H1.01. H1.01 A 8"D = NECK SIZE. 300 = REQUIRED CFM. 3 = AIR DISCHARGE IF OTHER AIR DEVICE A3 = DESIGNATION - REFER TO AIR DEVICE SCHEDULE. THAN 4-WAY. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING MOUNTED DEVICES. A3-8"D 300-3 WALL OR DUCT MOUNTED AIR DEVICE. G1 = DESIGNATION - REFER TO AIR DEVICE SCHEDULE. 24"x16" = DUCT CONNECTION SIZE. 200 = REQUIRED CFM. 9'-4" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF DEVICE. 200-9'-4" G1-24x16 FACE AREA IN SQ. FT. DL-2 DOOR LOUVER BY GENERAL CONTRACTOR. NUMBER INDICATES MINIMUM GROSS DOOR UNDERCUT BY GENERAL CONTRACTOR. U/C R DUCT RISE IN DIRECTION OF AIR FLOW. D DUCT DROP IN DIRECTION OF AIR FLOW. DUCT WITH 1" ACOUSTICAL LINER. DUCT SIZES ARE INSIDE CLEAR DIMENSIONS. DUCT CONSTRUCTED OF SPECIAL MATERIAL AS NOTED. FLEXIBLE DUCT CONNECTION. AIR TURNING VANES. MANUAL BALANCING VOLUME DAMPER WITH LOCKING DEVICE. M.D. FIRE DAMPER - LETTER "A", "B", OR "C" INDICATES TYPE REQUIRED, LETTER "D" OR "S" INDICATES DYNAMIC OR STATIC - SEE DETAIL. A-D SMOKE DAMPER. S COMBINATION FIRE SMOKE DAMPER. FS PRESSURE GAUGE. P UNION. CLEAN OUT. STRAINER. SHUTOFF VALVE SHUTOFF AND BALANCING VALVE CHECK VALVE D DRAIN PIPE. DIRECTION OF FLOW PITCH DOWN EP EXPANSION TANK PIPE. GENERAL NOTES FANS DUCT CONSTRUCTION & SEALING INDEX OF DRAWINGS AIR SUPPLY ROOFTOP UNITS AIR DISTRIBUTION DEVICES AIR CONTROL UNITS-HOT WATER ROOM HEATING UNITS COOLING SPLIT SYSTEM COOLING-HEATING SPLIT SYSTEMS SOUND ATTENUATORS SHEET DESCRIPTION OUTDOOR UNIT INDOOR UNIT GENERAL CONTRACTOR. WALL LINTEL FOR WALL OPENING BY WHERE REQUIRED FOR DECK SUPPORT AND STEEL FRAMING AROUND ROOF OPENING. PHASE CONSIDERED MINIMUM. MOTOR HORSEPOWERS LISTED ARE TO BE 300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S. SONES VALUES BASED ON A.M.C.A. BULLETINS DESCRIPTION UNIT GENERAL NOTES CONTRACTOR. VERIFY SIZE & COORDINATE WITH GENERAL ROOF & WALL OPENINGS ARE APPROXIMATE. SERVICE SONES STATIC WHEEL MAX. PRESS CFM DIA. MOTOR H.P. VOLT REMARKS APPROX. ROOF/ WALL OPG. CLASS CLASS STRUCT. S.P. CON- SHEET METAL DUCT; INTERIOR LINING; EXTERIOR INSULATION; REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION OPTIONS: DUCT SYSTEM ETC. GENERAL NOTES LEAKAGE S.M.A.C.N.A. CLASS. SEAL REMARKS O.W.B.E. FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL, "E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED. SUPPLY AIR DIFFUSERS SHALL BE 4-WAY BLOW UNLESS OTHERWISE NOTED ON DWGS. DESCRIPTION REFER TO SPECIFICATIONS FOR OTHER ALL LAY-IN AIR DEVICES SHALL FIT IN 24"X24" LAY-IN CEILING SYSTEM. SYMBOL GENERAL NOTES MANUFACTURERS. TYPE MOUNTING MATERIAL LAY-IN SURFACE STEEL PROVIDE AUX. FRAMES FOR AIR DEVICES IN PLASTER, GYPSUM BOARD, GLAZED TILE OR CERAMIC TILE SURFACES. FINISH CATALOG NUMBER SEE ACCESSORIES NOTE A1 A2 D1 D2 D3 D4 D5 F1 G1 H1 J1 J2 K1 K2 S1 SUPPLY CLG. SQ. DIFFUSER SUPPLY CLG. SQ. DIFFUSER ROUND FLOOR FLOW DIFFUSER IN-WALL DISPLACEMENT DIFFUSER RECTANGLE 3-WAY DISPLACEMENT DIFFUSER STAIRCASE SWIRL DIFFUSER HALF-ROUND 180 DISPLACEMENT DIFFUSER DOUBLE DEFLECTION SUPPLY REGISTER RETURN GRILLE RETURN/EXHAUST REGISTER RETURN CLG. GRILLE RETURN CLG. GRILLE RETURN CLG. REGISTER RETURN CLG. REGISTER ALUM. PRICE SCDA SCDA TROX "FB200" TROX "QLE-U" TROX "QLK-90" TROX "SDRF-5" TROX "QLK-180" 5200 90 530D 80 80 80D 80D --- --- 8" DIA. 48"W x 24"H 36"W x 60"H 20" x 3"H 24" DIA. x 48"H O.B.D. --- O.B.D. --- --- O.B.D. O.B.D. - - - - - - - - - - - - - - SUPPLY DUCT UPSTREAM OF ROOFTOP UNITS (RTU-1,2,3,4) SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES SUPPLY DUCT RUNOUTS TO FLOOR FLOW DIFFUSERS RETURN AIR DUCTWORK TRANSFER AIR DUCTWORK GENERAL/TOILET EXHAUST ANY DUCTWORK NOT LISTED ABOVE +3.0" +1.0" +1.0" -1.0" -1.0" -1.0" +1.0" B B B B B B B 12 24 24 24 24 24 24 - - - - - - - EF-1 EF-2 EF-3 EF-4 AUTOMATIC TEMP. CONTROLS SUBCONTRACTOR A.T.C. H HOT WATER SUPPLY PIPE H HOT WATER RETURN PIPE WATER MAKE-UP PIPE EXISTING PIPE TO REMAIN EXISTING PIPE TO BE REMOVED L REFRIGERANT - LIQUID S REFRIGERANT - SUCTION HG REFRIGERANT - HOT GAS "CONNECT TO EXISTING" SYMBOL - DUCTS OR PIPES A ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE INSTALLED HOLD TIGHT TO STRUCTURE. B THIS CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL THE PIPES, DUCTS, UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFF-SETS WHERE NECESSARY. C COORDINATE THE LOCATION OF ALL AIR DEVICES LOCATED IN THE CEILING WITH THE ARCHITECTS REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING PLAN. D SPACE ABOVE CEILING SHALL BE USED AS A RETURN AIR PLENUM. (RTU-4) E ALL EXPOSED DUCTWORK, PIPING, (VAV-REHEAT BOXES, AIR DEVICES SHALL BE GALVANNEALED OR BONDERIZED COATING (PAINT GRIP) IN ORDER TO ACCEPT PAINT. FINISH PAINTING WILL BE DONE BY OTHERS. F BRANCH DUCTS FROM VAV-REHEAT BOXES AND AIR DEVICES SHALL BE SAME SIZE INLET OF UNIT OR DEVICE UNLESS NOTED OTHERWISE. G BRANCH PIPING TO VAV-REHEAT BOXES SHALL BE SAME SIZE INDICATED ON AIR CONTROL UINIT SCHEDULE. H COORDINATE EXPOSED DUCT LOCATIONS WITH ARCHITECTURAL DRAWINGS IN ADDITION TO SPECIFIC HVAC PLAN NOTES. I ALL SQUARE CORNER DUCT FITTINGS, EXCEPT RETURN AIR TRANSFER BOOTS SHALL BE EQUIPPED WITH AIRFOIL TYPE TURNING VANES. J ALL PENETRATIONS FOR ATC DEVICES SHALL BE REPAIRED AND REINSULATED. K ATC COMPONENTS, POINTS, OR HARDWARE NOT SHOWN BUT REQUIRED TO ACHIEVE THE SPECIFIED SEQUENCE OF CONTROL SHALL BE INCLUDED. L THIS CONTRACTOR SHALL COORDINATE WITH AUDIO/VISUAL TECHNOLOGY DRAWINGS FOR ALL CABLE TRAY, CONDUITS, PROJECTORS, ETC. LOCATED ABOVE CEILINGS REQUIRING ACCESS SPACE. M THIS CONTRACTOR SHALL COORDINATE WITH ALL TRADES PRIOR TO TRENCHING, INSTALLATION OF UNDERFLOOR DUCTWORK, BACKFILL AND ALL RISERS THRU FLOOR SLAB. REFER TO DETAILS AND SPECIFICATIONS. N IN WORSHIP CENTER, THIS CONTRACTOR SHALL PROVIDE SLEEVE FOR 8" DIA. FLOOR DIFFUSER AT SLAB AND EXTEND 3" A.F.F. AND PROVIDE TEMPORARY DUCT CAP DURING CONSTRUCTION PERIOD. COORDINATE FINAL DEVICE LAYOUT WITH G.C. AND SEATING CONTRACTOR. MAX. AIR P.D. INCHES W.G. ROW / FINS STAGES - COOLING PRESS. DROP IN. W.G. (CLEAN) LEAV. AIR TEMP. (DB/WB)(COIL) MAX. WATER P.D.- FT. AUTO. VALVE SIZE & TYPE ENT. AIR TEMP. (DB/WB) UNIT FILTERS HOUSING DX-COOLING COIL TYPE TOTAL (MBH) COOLANT SENSIBLE (MBH) GPM ENT. AIR (DB) LEAV. AIR (DB) HEATING COIL HEATING COIL CAPACITY BASED ON 180 ENT. WATER TOTAL S.P.- INCHES W.G. MIN. FACE AREA (SF) MOTOR (MIN. H.P.) UNIT CONFIGURATION SUPPLY FAN CAPACITY (MBH) WHEEL TYPE WHEEL DIA. CFM (TOTAL) UNIT NUMBER AREA SERVED UNIT LOCATION GENERAL NOTES MOTOR - 208V - 3 PHASE UNLESS NOTED OTHERWISE. RTU-2 STAGE AREA ROOF VERTICAL DISCHARGE 8,750 4.9"/3.0" 27" PLENUM 15 HP YES BALCONY'S ROOF VERTICAL DISCHARGE 4.9"/3.0" 2 @ 27" PLENUM 2 @ 15 HP YES RTU-1 PIT LEVEL ROOMS ROOF VERTICAL DISCHARGE 8,750 4.9"/3.0" 27" PLENUM 15 HP YES RTU-4 196.0 54.0 5.0 11.7 515.0 34.0 5.0 31.7 128.0 45.0 3.0 10.5 19.5 227.3 345.0 78.5 / 66.8 53.3 / 53.3 44.0 531.7 715.0 86.6 / 69.1 54.1 / 54.0 285.0 358.0 87.7/69.3 55.7/55.7 TOTAL S.P.- INCHES W.G./E.S.P. MOTOR (MIN. H.P.) WHEEL TYPE WHEEL DIA. CFM (TOTAL) VFD 3 NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH NOTE IS SHOWN. EXHAUST AIR THRU WHEEL-CFM O.A. ENT. AIR DB/WB-SUMMER WHEEL OUTSIDE AIR CFM O.A. LEAV. AIR DB/WB-SUMMER EXH. ENT. AIR DB/WB-SUMMER EXH. LEAV. AIR DB/WB-SUMMER MAX. AIR P.D- INCHES W.G TYPE PRESS. DROP IN. W.G. (CLEAN) HOUSING MINIMUM OUTSIDE AIR CFM ISOLATOR ROOF CURB 8,000 1,500 1,500 WHEEL FILTER(2) ENERGY RECOVERY WHEEL EXH. FAN 8,750 2.1" / 1.5" PLENUM 7.5 YES 16,000 2.5" / 1.5" PLENUM 2 @ 7.5 YES 8,750 1.8" / 1.5" 22" PLENUM 7.5 YES 700 150 49.0 3.3 0.75" 1.4 1 INLET TYPES - "V.V." VARIABLE VOLUME; "V.V.R." VARIABLE VOLUME REHEAT; "C.V.R." CONSTANT VOLUME REHEAT. UNIT & COIL AT MAX. CFM. .50"S.P. MAX. PRESS. DROP THRU UNIT NO. TYPE DIA. GENERAL NOTES REHEAT COIL CAPACITY BASED ON WINTER MIN. CFM, 55 ENT. AIR & 180 ENT. WATER TEMPERATURE. MBH CFM WINTER MAX. MIN. MIN. SUMMER REHEAT COIL GPM RUNOUT SIZE NOTE SEE V.V.R. 4-1 4-2 4-3 4-4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 10" 10" 8" 12" 12" 12" 6" 8" 6" 6" 1000 450 1325 1275 1200 1770 275 535 285 200 CV 2-WAY CONTROL VALVE, UNLESS NOTED NOTES: 1. 3-WAY CONTROL VALVE BY GEN. CONT'R. LINTELS IN MASONRY WALLS FOR FULL & SEMI-RECESSED UNIT WALL OPENINGS PROVIDED RECESSED UNITS TO HAVE FOUR(4) SIDE OVERLAP UNLESS OTHERWISE NOTED. APPROX. CABINET DIMENSIONS HEATING CAPACITY BASED ON 60 ENT. AIR & 180 ENT. WATER MAXIMUM WATER PRESS. DROP THRU COIL DESCRIPTION NO. UNIT 10.0 FT. GENERAL NOTES VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING & RECESS REQUIREMENTS WITH ARCHITECTURAL DWGS. PRIOR TO ORDERING. MOTOR: 115V.-1PH. UNLESS OTHERWISE CFM STAIRS SERVICE NOTED. RUNOUT MBH HTG. GPM 3.0 SIZE 0.75" VALVE LENGTH 0.50" AUTO. 47" DEPTH 10" - RECESS - HEIGHT 540 45.4 25" NOTES CUH-1 UH-1 UNIT HEATER - HORIZONTAL CABINET UNIT HEATER - MODEL B COST FOR INCREASE OR CHANGE OF ELECTRICAL SERVICE MODEL NO. (OUTDOOR UNIT) BASIS OF DESIGN (MFR. & NO.) MOUNTING VOLTAGE & PHASE DESCRIPTION UNIT NUMBER MAX. FUSE SIZE (FLA / MOP) CAPACITY ENTERING AIR DB REFRIGERANT (LIQUID & SUCTION) REFRIGERANT LIQUID TYPE KW / VOLTAGE HUMIDIFIER TYPE SENSIBLE (MBH) COOLING REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE DISCRIPTION FAN MOTOR HP TOTAL (MBH) UNIT CONFIGURATION EXTERNAL S.P. CFM INDOOR UNIT NUMBER AREA SERVED GENERAL NOTES: FOR EQUIPMENT SELECTED SHALL BE BORNE BY H.C. BE VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER. CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL. ELECTRIC SERVICES FOR OUTDOOR AND INDOOR UNIT - AC-3 SIZES, NUMBER OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. INDOOR UNIT ENTERING AIR WB HTG. KW / VOLTAGE ELECTRIC REHEAT - (MBH) MODEL NO. (INDOOR UNIT) MAX. FUSE SIZE (FLA / MOP) NOMINAL TONS (APPROX. SIZES) OUTDOOR UNIT VOLTAGE 33.5 FLA / 45.0 MMD36E-A CU-3 CONDENSING UNIT 3.0 19.3 FLA / 40.0 208 / 1 ROOF PFC037A 3/8" & 7/8" R134A LIEBERT 37.2 28.5 80.0 67.0 16.0 4.7 / 208-1 208 / 1 AIR-COOLED HORIZ. CONCEALED 1200 0.4" SPLIT SYSTEM 1/2 A/V RACK 2 @ 27" V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. V.V.R. EF-5 POWER ROOF VENTILATOR TOILET ROOMS 1095 POWER ROOF VENTILATOR TOILET ROOMS 700 POWER ROOF VENTILATOR STORAGE ROOM SIDEWALL EXHAUSTER POWER ROOF VENTILATOR TOILET ROOMS ELEVATOR EQUIP. ROOM 300 EF-6 POWER ROOF VENTILATOR MECHANICAL ROOM 4-13 6" 200 V.V.R. 4-14 6" 380 V.V.R. 460 140 24.0 1.6 0.75" 0.8 915 - 300 70 22.0 1.5 0.75" 0.7 - 690 200 34.0 2.3 0.75" 0.9 - 640 195 31.0 2.1 0.75" 0.9 - 600 180 29.0 2.0 0.75" 0.8 - 885 270 43.0 2.9 0.75" 1.2 1 175 55 9.0 0.6 0.75" 0.3 1 150 45 7.0 0.5 0.75" 0.2 - 280 85 14.0 1.0 0.75" 0.4 - 145 45 7.0 0.5 0.75" 0.2 - 100 30 5.0 0.5 0.75" 0.2 - 100 30 5.0 0.5 0.75" 0.2 - 190 60 10.0 0.7 0.75" 0.3 1 250 45 12.0 0.9 0.75" 0.4 1 14" 6" 350 4-15 6" 300 V.V.R. ALUM. E.C.L. 0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,3 0.5 10" 10.0 1/4 115 1 14.5"x14.5" 1,3 0.375 12" 10.0 1/4 115 1 14.5"x14.5" 1,4 0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4 0.5 9" 8.0 1/4 115 1 14.5"x14.5" 1,3 0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,4 500 1000 1000 STAIRS 340 29.4 2.0 38" 10" 25" - - CUH-2 CABINET UNIT HEATER - MODEL B CORRIDOR 540 45.4 3.0 47" 10" 25" - - CUH-3 CABINET UNIT HEATER - MODEL B UH-2 UNIT HEATER - HORIZONTAL DELIVERY FIRE PUMP ROOM 1100 32.1 3.3 23" 17" 17" - - 815 27.4 2.8 23" 17" 17" - - TONS - COOLING 60 30 30 16,000 VFD 18.8 7.3 7.3 91.0 95.2 65.5 0.5" 0.5" 0.5" 1.WAY5"/2-WAY 1.5"/3-1.5"/2-WAY MIN. FACE AREA (SF) 19.5 R-410A R-410A R-410A 6 / 12 FPI 6 / 12 FPI 6 / 12 FPI 4 2 2 2" - 30% PLEATED 4" - MERV 13 2" - 30% PLEATED 4" - MERV 13 2" - 30% PLEATED 4" - MERV 13 0.55 SIDE ACCESS 0.55 SIDE ACCESS 0.55 SIDE ACCESS 22" 1,500 1,500 91.0 / 75.0 80.0 / 68.1 78.0 / 66.5 88.9 / 73.6 0.50" 8,000 8,000 91.0 / 75.0 87.3 / 70.3 86.0 / 68.0 89.7 / 72.9 0.75" 2" - 30% PLEATED 0.55" SIDE ACCESS 2" - 30% PLEATED 0.55" SIDE ACCESS MISC. UNIT MOUNTED YES YES YES DISCONNECT SWITCH YES YES YES CONTROL PANEL WITH LON INTERFACE MODULATING HOT GAS REHEAT COIL YES YES YES YES YES NO HOT GAS LEAD & LAG ELECTRICAL - (FLA / MOP) YES YES YES UNIT WEIGHTS BASIS OF DESIGN 407.0/450.0 204.0 / 250.0 165.0 / 225.0 9800 LBS. 4500 LBS. 4000 LBS. AAON "RN-060" AAON "RM-030" AAON "RM-030" ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT - VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER. COST FOR DX-COOLING POWER CCT. (A.) ENTERING AIR TEMP. (WB) BASIS OF DESIGN (MFR.) HOT GAS BY-PASS (APPROXIMATE SIZES) REFRIG. LIQUID & SUCTION VOLTAGE & PHASE POWER CIRCUIT (FLA / MOP) ENTERING AIR TEMP. HEATING OUTPUT (MBH) KW VOLT. PIPE RUNOUT GPM ENTERING AIR TEMP. (DB) MOUNTING NOMINAL TONS DESCRIPTION OUTSIDE AIR LEAVING AIR TEMP. HEATING ELECTRIC COIL COIL WATER HOT WATER PHASE STAGES (MIN.) AUTO VALVE ENTERING IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE AND ARE BASED ON SINGLE CIRCUITING. SIZING, NUMBER REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE SENSIBLE (MBH) VOLTAGE & PHASE EXTERNAL S.P./TOTAL UNIT CONFIGURATION DESCRIPTION FAN TOTAL (MBH) MOTOR HP CFM AREA SERVED SYSTEM NUMBER GENERAL NOTES: SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST BE INCREASE OR CHANGE OF ELECTRICAL SERVICE FOR MENT SELECTED SHALL BE BORNE BY HVAC CONTRACTOR. EQUIP- AC-1 PROJECTION ROOM CABINET C 7.5 AIR HANDLING DRAW-THRU HORIZONTAL TONS - COOLING AC-2 PROJECTION ROOM CABINET C 7.5 AIR HANDLING DRAW-THRU HORIZONTAL 3,000 0.75" / 2.0" 2 HP 208/3 81.5 69.9 75.0 62.0 3,000 0.75" / 2.0" 2 HP 208/3 81.5 69.9 75.0 62.0 105.3 5.0 / 180 1.0" / 0.75" 103 F INDOOR UNIT ELECTRIC 8.0 FLA / 15.0 MOP / 208-3 0 105.3 5.0 / 180 1.0" / 0.75" 103 F 0 CU-1 CU-2 7.5 20.0 / 40.0 208/3 ROOF 7/8" & 3/8" YES AAON 7/8" & 3/8" YES AAON 7.5 20.0 / 40.0 208/3 ROOF 0.75" 0.50" 0.75" 0.50" 0.75" 0.50" 0.75" 0.50" AC-4 33.5 FLA / 45.0 MMD36E-A CU-4 CONDENSING UNIT 3.0 19.3 FLA / 40.0 208 / 1 ROOF PFC037A 3/8" & 7/8" R134A LIEBERT 37.2 28.5 80.0 67.0 16.0 4.7 / 208-1 208 / 1 AIR-COOLED HORIZ. CONCEALED 1200 0.4" SPLIT SYSTEM 1/2 SERVER ROOM REFRIGERANT R-410A R-410A STAIRS/CORRIDOR 540 45.4 3.0 47" 10" 25" - - CUH-4 CABINET UNIT HEATER - MODEL B 0.75" 0.50" RTU-3 WORSHIP CENTER ROOF VERTICAL DISCHARGE 21,000 6.3"/3.0" 2 @ 30" PLENUM 2 @ 20 HP 662.0 34.0 10.0 41.7 44.0 654.0 840.0 86.8 / 69.4 56.3 / 56.2 10,500 21,000 2.25" / 1.0" 2 @ 27" PLENUM 2 @ 7.5 YES 70 18.8 89.8 0.5" 1.5"/2-WAY YES R-410A 6 / 12 FPI 4 2" - 30% PLEATED 4" - MERV 13 0.55 SIDE ACCESS 10,500 10,500 91.0 / 75.0 87.6 / 70.8 86.0 / 68.0 89.4 / 72.5 0.90" 2" - 30% PLEATED 0.55" SIDE ACCESS YES YES YES YES YES 425.0 / 450.0 9800 LBS. AAON "RN-070" NO. SERVICE UNIT REMARKS L W H SIZE CFM S.P. MAX SA-1 RTU-3 SUPPLY CEILING SLOT DIFFUSER-48" LONG-1 SLOT S2 CEILING SLOT DIFFUSER-24" LONG-1 SLOT 60 30 36 10,500 0.25" SA-1A RTU-3 SUPPLY 60 30 36 10,500 0.25" SA-2 RTU-3 RETURN 60 30 36 10,500 0.25" SA-2A RTU-3 RETURN 60 30 36 10,500 0.25" CAPACITY (MBH) LEAVING AIR TEMP. (DB/WB) RH REHEAT 302.0 72.0 / 60.8 53 % 173.0 72.0 / 60.4 52 % 348.0 72.0 / 61.9 57 % 150.0 72.0 / 61.7 56 % 70 F 70 F LEAVING AIR TEMP. (DB / WB) 52.7 / 52.1 52.7 / 52.1 8.0 FLA / 15.0 MOP / 208-3 F2 SPIRAL DUCT GRILLE SDGE --- TBDI-2100 INSUL. PLENUM TBDI-2100 INSUL. PLENUM - - EF-7 SIDEWALL EXHAUSTER FIRE PUMP ROOM 500 0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4 REMARKS 1 PROVIDE FAN WITH 12" HIGH ROOF CURB AND DISCONNECT SWITCH. 2 PROVIDE FAN WITH WALL COLLAR, MOTOR SIDE GUARD, DAMPER AND TERMINATE WITH WALL LOUVER. LOUVER EQUAL TO GREENHECK MODEL "EDJ-430". 3 FAN SHALL BE CONTROLLED BY DDC. PROVIDE OCCUPIED/UNOCCUPIED SCHEDULE. 4 FAN SHALL BE CONTROLLED BY LINE VOLTAGE THERMOSTAT, FURNISHED BY H.C. AND INSTALLED BY E.C. -- -- -- -- SA-3 RTU-1 SUPPLY 60 30 30 8,000 0.25" -- SA-3A RTU-1 SUPPLY 60 30 30 8,000 0.25" -- SA-4 RTU-1 RETURN 60 30 30 8,000 0.25" -- SA-4A RTU-1 RETURN 60 30 30 8,000 0.25" -- SA-5 RTU-2 SUPPLY 60 30 30 8,750 0.25" -- SA-6 RTU-2 RETURN 60 30 30 8,750 0.25" -- VFD'S FOR FANS ARE UNIT MOUNTED. -3.0 / -4.0 34.0 -3.0 / -4.0 34.0 -3.0 / -4.0 34.0 O.A. ENT. AIR DB/WB-WINTER O.A. LEAV. AIR DB-WINTER EXH. ENT. AIR DB/WB-WINTER EXH. LEAV. AIR DB-WINTER 75.0 / 62.0 75.0 / 62.0 75.0 / 62.0 38.0 38.0 38.0 HEATING CFM 8,000 4,375 10,500 5,665 T THERMOMETER WITH THERMOWELL. UNIT SHALL HAVE INSULATED PIPE CHASE FOR HW COIL CONNECTIONS. UH-3 UNIT HEATER - HORIZONTAL STORAGE AREA 1100 32.1 3.3 0.75" 0.50" 23" 17" 17" - - H001 LEGEND, GENERAL NOTES, AND SCHEDULES DETAILS H201 PIT LEVEL FLOOR PLAN H211 FIRST LEVEL FLOOR PLAN H221 FIRST LEVEL BALCONY FLOOR PLAN H231 SECOND LEVEL BALCONY FLOOR PLAN H300 MECHANICAL ROOM H301 ROOFTOP EQUIPMENT SECTIONS H400 HOT WATER PIPING SCHEMATIC AND DATA H002 DETAILS H003 DETAILS H100 EXISTING FIRST LEVEL PLAN-DEMOLITION RETURN TRANSFER DUCTWORK/SOUND BOOTS RETURN DUCT UPSTREAM OF ROOFTOP UNITS (RTU-1,2,3&4) INTERIOR DESIGN AREA SUPPLY DUCT DOWNSTREAM OF ROOFTOP UNITS (RTU-1,2,3&4) LINED EXTERNAL NOTES INSULATION SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-RECTANGULAR DUCT GENERAL/TOILET EXHAUST SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-ROUND RETURN DUCTWORK NOTES 1 REFER TO SPECIFICATIONS. 23 07 13 1 1 1 1 1 1 -3 DEG. DB WINTER 75 DEG. WB SUMMER 91 DEG. DB SUMMER OUTSIDE DESIGN TEMPERATURES DESIGN ALTITUDE 792 FT. ALL AREAS EXCEPT LISTED BELOW INTERIOR DESIGN AREA WINTER DB % HUMIDITY DB 75 50 SUMMER % HUMIDITY N/A ELEC./TECH. RM./IT CLOSETS 80 50 N/A N/A WORSHIP CENTER 75 50 N/A RECORDING STUDIO 75 50 N/A VIDEO/AUDIO CONTROL 75 50 N/A BALCONY 1&2 75 50 72 N/A 72 72 72 72 1 LEGEND DUCT INSULATION SCHEDULE HVAC DESIGN DATA Date: Scale Drawn By Checked By Project Number ARCHITECTURE PLANNING INTERIOR DESIGN STRUCTURAL ENGINEERING 424 East Fourth Street Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m tel: 513/241/4474 fax: 513/241/0081 ISSUANCES COMPUTER FILE 1400 West Dorothy Lane Dayton, Ohio 45409-1310 Tel: (937) 224-0861 Fax: (937) 224-5777 3417 South Sherman Drive Beech Grove, IN 46107 Tel: (317) 780-1555 Fax: (317) 780-6525 750 North Orleans, Suite 400 Chicago, IL 60610 Tel: (312) 944-8230 Fax: (312) 944-8297 117 East Washington Street, Suite 200 Indianapolis, IN 46204 Tel: (317) 637-2222 Fax: (317) 637-2260 1137 West Taylor St. Suite 316 Chicago, IL 60607 Tel: (312) 224-8460 Fax: (312) 224-8961 1025 N.Watery Ln. Brigham City, UT 84302 TEL: (453) 723-5000 FAX: (453) 538-5506 6622 Kingspointe Parkway Orlando, FL 33819 Tel: (407) 816-9400 Fax: (407) 816-9300 1 SCHEMATIC DESIGN 10.18.07 2 DESIGN DEVELOPMENT 01.18.08 3 CD 50% 03.14.08 4 PERMIT SET 04.25.08 5 ADDENDUM #2 05.16.08 No. Description Date 6 ADDENDUM #3 05.22.08 7 ADDENDUM #5 06.04.08 8 PERMIT SET 06.10.08 6/10/2008 1:53:15 PM C:\Drawings\REVIT\Northview\2007-06019-Central-local.rvt H001 LEGEND, GENERAL NOTES, AND SCHEDULES New Worship Center ARC CSR/GSS 05-22-08 2007-06019