HomeMy WebLinkAboutH002 - DETAILSSCALE: SCALE: SCALE: SCALE: SCALE: SCALE: NONE NONE NONE NONE NONE NONE FIRESTOPPING AT PIPE PENETRATIONS NOTES (See Note 6) of N.S. caulk. for thicker insulation. Same as for masonry wall above. For Undersized Pipe Sleeve assembly is required on both sides of wall. Same as for floor assembly above except firestopping wrap strip to slab and pipe/pipe insulation with 1/4" bead with anchor bolts to underside of floor slab. Seal interface of Place sheet metal restricting collar over wrap strip and secure with 1" insulation, two layers for 2" insulation, three layers floor slab. One layer for uninsulated pipe and insulated pipe Place wrap strip around pipe/pipe insulation at underside of with foil face. N.S. - non-sag). sleeves or openings. completely vapor sealed as may be appropriate. insulation must be terminated on each side of the assembly and to Specifications. Pipe sleeves are sized for pipe and fiber fill. Pipe plastic pipe or glass pipe - 3/4". Refer to table above for undersized and: uninsulated metal pipe - 1/4"; pipe insulation - 3/4"; uninsulated Wrap-strip-intumescent fire barrier wrap strip, 2" wide x 1/4" thick, Caulk - instumescent fire barrier caulk - (S.L. - self-leveling; F.S. sealant - fire-stop sealant. with Insulation Metal Pipe for 1" pipe insulation, 2" N.S. caulk, both sides. Assembly Fire Rated (except slab-on-grade) Concrete floor slab wall Stud and gypsum wallboard Masonry or concrete wall No Insulation Metal Pipe with Trowel in place, smooth and even. both sides of wool. Place F.S. sealant 1/2" thick, space, full depth of sleeve. Pack mineral wool in annular Trowel in place, smooth and even. annular space on one side of wool. Fill F.S. sealant 1/2" thick in in annular space. Pack mineral wool 3" thick Trowel in place, smooth and even. over wool. Fill F.S. sealant 1/2" deep in annular space. Pack mineral wool 3" deep 1. Refer to Firestopping and Pipe Sleeves paragraphs in the Specifications. Shaft walls - ___2 __ hr. 2. Fireresistance ratings: hour rating where applicable. Floors above grade - _____ hr. Other walls - as noted on ARCHITECTURAL drawings. 3. Pipe sleeves (or core drilling or formed opening) and firestopping are required at pipe penetrations thru fire rated floors, fire rated shaft walls, fire rated floor-ceiling and roof-ceiling assemblies and, where specifically noted, other fire walls of 2-hour or greater fireresistance. Exception: Where piping is installed before concrete pour and it would be appropriate to pour concrete up to the pipe (but not pipe insulation), sleeving and firestopping are not required. 4. Firestopping assemblies in the schedule above utilize materials and methods of Dow-Corning and 3M. These are general descriptions for 2-hour rating and cover most conditions for the project. Installations must conform to manufacturers' detailed instructions for conformance with ASTM E814 to attain required fire ratings of floor and wall assemblies, including 3- 2 annular space with 1/2" deep wrap strip and remainder of wall sleeve. Seal edges of tape and push wrap strip into wrap strip with aluminum faced around pipe insulation. Secure Wrap one layer of wrap strip 2" deep for thicker insulation. deep for 1" pipe insulation, sides of packing material, 1" Fill with N.S. caulk on both backer rod in annular space. Pack fiberglass 1/2" deep or deep for thicker insulation. Fill with S.L. caulk, 1" deep backer rod in annular space. Pack fiberglass 1/2" deep or 7. Pro Set Systems "Firestop Penetrator" assemblies are acceptable. Refer 6. Minimum annular space between pipe sleeve or core drilling 5. Materials: 8 FT. MAXIMUM LENGTH. STRETCH DUCT TO AT LEAST 90% OF FULLY NON-INSULATED ROUND FLEXIBLE DUCT. REFER TO SIZING NOTE BELOW. SHEET METAL PLENUM SAME SIZE AS GRILLE. SPIN-IN TAP FITTING. MANUAL DAMPER. PLACE DAMPER SO THAT SHAFT IS IN HORIZONTAL. DUCT STRAP HANGER. ATTACH TO STRUCTURE. STRAP HANGER REQUIRED AT MID-LENGTH IF LENGTH OF FLEXIBLE DUCT EXCEEDS 4 FT. 5 4 1 2 7 8 RETURN OR CEILING 3 ROUND SHEET METAL BRANCH DUCT. REFER TO SIZING NOTE BELOW. 1 7 1 3 7 8 4 6 6 CEILING T-BAR SUPPORT ON FOUR SIDES BY CEILING CONTRACTOR. GRILLE OR REGISTER 2 5 EXHAUST DUCT 6" MIN. EXTENDED LENGTH. BE SIZED AS FOLLOWS: SIZING NOTE - BRANCH DUCT SIZES, UNLESS NOTED ON PLANS, ARE TO 100 CFM AND LESS - 6" DIA 101 TO 250 CFM - 8" DIA 251 TO 400 CFM - 10" DIA 401 TO 700 CFM - 12" DIA 701 TO 1000 CFM - 14" DIA 9 MINIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER. 9 6 5 4 3 2 1 IS LONGER THAN 3 FT. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT DUCT STRAP HANGER. ATTACH TO STRUCTURE. DAMPER. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO TAP FITTING TO MAIN DUCT WITH INTERNAL INSULATION. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE, WITH 5 3 5 2 6 4 1 CEILING CEILING DIFFUSER SUPPLY DUCT SHEET METAL BOX WITH INTERNAL INSULATION, 2" LARGER EACH DIRECTION THAN DIFFUSER NECK, WITH ADAPTOR CONNECTION TO DIFFUSER. FLEXIBLE DUCT, DIAMETER AS NOTED ON PLAN. 7 FT. MAXIMUM LENGTH. STRETCH FLEXIBLE DUCT TO AT LEAST 90% OF FULLY EXTENDED LENGTH. 7 7 ROUND SHEETMETAL BRANCH DUCT. 4 3 6 5 4 3 2 1 MINIMUM CENTERLINE RADIUS EQUAL TO DUCT DIAMETER. IS LONGER THAN 4 FT. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT DUCT STRAP HANGER. ATTACH TO STRUCTURE. TAP FITTING TO MAIN DUCT WITH INTERNAL INSULATION. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE, WITH AT LEAST 90% OF FULLY EXTENDED LENGTH. 7 FT. MAXIMUM LENGTH. STRETCH FLEXIBLE DUCT TO FLEXIBLE DUCT SAME DIAMETER AS DIFFUSER INLET, IS SQUARE. SQUARE-TO-ROUND ADAPTOR IF DIFFUSER NECK CEILING CEILING DIFFUSER SUPPLY DUCT 7 7 ROUND SHEETMETAL BRANCH DUCT. 1 2 6 4 5 B H002 D H002 7 6 5 4 3 2 1 HIGH VELOCITY DUCT COUPLING. CEILING ACCESS PANEL IF CEILING IS NOT ACCESSIBLE. DUCT ACCESS PANEL OR DOOR. REFER TO SPECIFICATION. SPACING OF FASTENERS PER SMACNA. REQUIRED OVERLAP. BOLT, SCREW OR TACK WELD TO WALL SLEEVE. OVERLAP OF WALL OPENING. LONGER LEG MAY BE REQUIRED TO ATTAIN RETAINING ANGLE ALL FOUR SIDES, GAUGE PER SMACNA. 1" MINIMUM MAY BE RIGID TYPE IF ALLOWED BY CODE AUTHORITY. DUCT/SLEEVE CONNECTION, BREAKAWAY TYPE SHOWN. CONNECTION GAUGE PER SMACNA. GALVANIZED SHEET METAL FOR FIBERGLASS DUCT). SHEET METAL SHEET METAL WALL SLEEVE, SAME MATERIAL AS DUCT (EXCEPT TYPE "D" - CENTER PIVOTED MULTI-BLADE FIRE DAMPER. STREAM; RECTANGULAR, ROUND OR OVAL DUCT CONNECTION. TYPE "C" - HIGH VELOCITY TYPE, BLADES STORED OUT OF AIR TYPE "B" - BLADES STORED OUT OF AIR STREAM. TYPE "A" - BLADES STORED IN AIR STREAM. LOADED TO CLOSE. VERTICAL MOUNT, GRAVITY DROP; HORIZONTAL MOUNT, SPRING FIRE DAMPER, FOLDED BLADE CURTAIN TYPE, EXCEPT AS NOTED. LOCATION. INSTALLATION IN FLOOR SIMILAR. REFER TO PLANS FOR ACCESS DETAILS SHOW INSTALLATION OF FIRE DAMPER IN WALL. DAMPER TO NFPA 90A, SMACNA AND MANUFACTURER'S INSTRUCTIONS. INSTALLATION OF FIRE DAMPERS AND ACCESSORIES SHALL CONFORM FIRE DAMPERS SHALL BE UL LABELED. GENERAL NOTES ROUND/OVAL DUCT 6 1 4 TYPE "C"- 2 7 2 4 5 7 1 6 DUCT 4 4 2 3 3 5 DUCT EXTENSION AT TOP OF DAMPER TYPE "B"- FIRE RATED WALL OR PARTITION 3" MINIMUM DUCT 6 5 1 3 4 4 2 3 TYPE "A"- 3" MINIMUM FIRE RATED WALL OR PARTITION K H002 J H002 H H002 DUCT SIZE, SEE SCHEDULE 24x24 24x12 24x12 12x12 18x18 16x16 22x10 12x12 14x14 10x10 SIZE 8x8 6x6 AIR DEVICE 18x10 16x10 12x10 14x10 12x10 10x10 6x6 8x8 DUCT SIZE AIR SOUND BOOT DUCT. INTERNALLY LINED RETURN RETURN AIR GRILLE DUCT TO BE FULL SIZE OF AIR DEVICE NECK SIZE SCALE: 12" TO PLENUM DUCT OPEN CEILING F NONE H002 MAIN SUPPLY DUCT 1 2 3 4 5 ROUND SHEET METAL BRANCH DUCT. INSULATED FLEXIBLE DUCT. 4 FT. MAXIMUM LENGTH. STRETCH FLEXIBLE DUCT TO 90% OF FULLY EXTENDED LENGTH. AIR TERMINAL UNIT. MINIMUM FOUR STRAP HANGERS FOR UNIT (CORNER POINTS). 1 2 3 4 5 SCALE: NONE SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE, WITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN SUPPLY DUCT WITH INTERNAL INSULATION. E H002 6 TRANSITION WHEN REQUIRED. 6 5 ATTACH TO STRUCTURE. 7 MINIMUM STRAIGHT LENGTH OF DUCT SHALL BE TERMINAL UNIT MANUFACTURER'S REQUIRED LENGTH, BUT AT LEAST 1.5 TIMES UNIT INLET DIAMETER. 8 STRAP HANGER ATTACHED TO STRUCTURE. 8 7 6 9 9 DUCT SHALL BE FULL SIZE OF UNIT OUTLET UNLESS NOTED OTHERWISE ON FLOOR PLANS. TO AIR DEVICES DUCT WALL ROOFING INSULATION COUNTER FLASHING 2 4 3 2 1 FRAMED BY GENERAL CONTRACTOR. CONCRETE ROOF DECK OPENING SHEET METAL SCREW. TO CONCRETE ROOF DECK. THICKNESS ROOF INSULATION. BOLT BLOCK FRAME BY H.C. SAME PRESSURE TREATED RIGID WOOD 12" HIGH INSULATED STEEL CURB. SCALE: NONE 4 3 1 12" G H002 SCALE: NONE A H002 3 LEAST 90% OF FULLY EXTENDED LENGTH. MAXIMUM LENGTH. STRETCH FLEXIBLE DUCT TO AT FLEXIBLE DUCT, DIAMETER AS NOTED ON PLAN. 7 FT. SLOT DIFFUSER ASSEMBLY WITH INTERNALLY INSULATED SUPPLY DUCT CEILING SLOT DIFFUSER 2 6 4 1 3 5 SPIN-IN BRANCH TAP FITTING, STRAIGHT SIDE, WITH MANUAL DAMPER. DAMPER SHAFT IN HORIZONTAL. INTEGRAL INSULATION GUARD SLEEVE REQUIRED FOR TAP FITTING TO MAIN DUCT WITH INTERNAL INSULATION. SPIN-IN TAP FITTING SIMILAR TO EXCEPT NO DAMPER. DUCT STRAP HANGER. ATTACH TO STRUCTURE. STRAP HANGER REQUIRED IF LENGTH OF FLEXIBLE DUCT IS LONGER THAN 3 FT. 1 2 3 4 5 6 C H002 7 ROUND SHEETMETAL DUCT. 5 7 PLENUM 8 CEILING T-BAR SUPPORT. COORDINATE WITH CEILING CONTRACTOR. 8 SCALE: NONE 3 L H002 CEILING DIFFUSER DUCT CONNECTION RET/EXH DEVICE DUCT CONN FIRE DAMPER NOTES RETURN AIR SOUND BOOT FIRE DAMPER TYPE "A" FIRE DAMPER TYPE "B" FIRE DAMPER TYPE "C" AIR TERMINAL UNIT DUCT CONNECTION FAN MOUNTING CURB CEILING DIFFUSER DUCT CONNECTION SLOT DIFFUSER CONNECTION PIPE PENETRATION FOR LIMITED CLEARANCE APPLICATION Date: Scale Drawn By Checked By Project Number ARCHITECTURE PLANNING INTERIOR DESIGN STRUCTURAL ENGINEERING 424 East Fourth Street Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m tel: 513/241/4474 fax: 513/241/0081 ISSUANCES COMPUTER FILE 1400 West Dorothy Lane Dayton, Ohio 45409-1310 Tel: (937) 224-0861 Fax: (937) 224-5777 3417 South Sherman Drive Beech Grove, IN 46107 Tel: (317) 780-1555 Fax: (317) 780-6525 750 North Orleans, Suite 400 Chicago, IL 60610 Tel: (312) 944-8230 Fax: (312) 944-8297 117 East Washington Street, Suite 200 Indianapolis, IN 46204 Tel: (317) 637-2222 Fax: (317) 637-2260 1137 West Taylor St. Suite 316 Chicago, IL 60607 Tel: (312) 224-8460 Fax: (312) 224-8961 1025 N.Watery Ln. Brigham City, UT 84302 TEL: (453) 723-5000 FAX: (453) 538-5506 6622 Kingspointe Parkway Orlando, FL 33819 Tel: (407) 816-9400 Fax: (407) 816-9300 1 SCHEMATIC DESIGN 10.18.07 2 DESIGN DEVELOPMENT 01.18.08 3 CD 50% 03.14.08 4 PERMIT SET 04.25.08 5 ADDENDUM #2 05.16.08 No. Description Date 6 ADDENDUM #3 05.22.08 7 ADDENDUM #5 06.04.08 8 PERMIT SET 06.10.08 6/10/2008 1:53:17 PM C:\Drawings\REVIT\Northview\2007-06019-Central-local.rvt H002 DETAILS New Worship Center ARC CSR/GSS 05-22-08 2007-06019