HomeMy WebLinkAboutPermit Revision01J:\535-NVCLC\3581-0\AGENCY APPROVALS\Permit\535-3581 Permit Revision01.doc
Permit Revision No. 01
Indiana Department of Homeland Security - Project #333848
City of Carmel, building & Code Services - Project #08060140
Project: Northview Christian Life Church
New Worship Center
Date: 02.09.09
Project No: 535-3581
This ASI provides information to clarify or adjust construction items which may affect any or all trade contractors.
Directives to proceed with any of the work and all change orders are to be reviewed and approved by the General
Contractor , Architect, Engineer, and Owner. This ASI is for information only and is not an instruction to execute work
nor stop work in progress or portions thereof unless herein written. All work to be in strict accordance with the terms,
stipulations and conditions of contract documents.
PART 1 – ARCHITECTURAL DRAWINGS
A1 SHEET A001
1. Revise plumbing fixture counts to include the entire existing and new building.
A2 SHEET A211-A
2. Revise loading dock layout.
3. Revise partition type at shaft in Workshop #116.
4. Add partition type in Side Platform #120.
5. Revise keynotes #8 and 18. Add keynotes #24-28.
6. Revise layout of stair #2 at level 1.
7. Revise layout of Men’s Restrooms #108, Women’s Restroom #111 and divide Women’s
Restroom #110 into Women’s Restroom #110A & Women’s Restroom #110B.
A3 SHEET A503 & A508
8. Revise Pit Level Entry retaining wall and stair layout. Add guardrail on retaining wall.
PART 2 – PLUMBING DRAWINGS
P1 SHEET P002
9. Modify Water Heater – Pit Level, Detail E – Delete HVAC make-up water backflow preveneter
(note #3).
P2 SHEET P003
10. Modify gas connected load schedules.
P3 SHEET P201
11. Modify underfloor piping to accommodate toilet room changes.
P4 SHEET P202
12. Modify gas piping for revised HVAC equipment. Delete backflow preventer in mechanical
room.
P5 SHEET P203
13. Modify gas piping for revised HVAC equipment. Modify above floor piping and fixtures in
toilet rooms.
J:\535-NVCLC\3581-0\AGENCY APPROVALS\Permit\535-3581 Permit Revision01.doc
P6 SHEET P206
14. Modify gas piping for revised HVAC equipment
P7 SHEET P300
15. Modify Soil, waste and vent diagrams for toilet room revisions.
PART 3 – HVAC DRAWINGS
H1 SHEET H300
16. Delete sheet H300 Mechanical Room.
H2 SHEET H400
17. Delete sheet H400 Hot Water Piping Schematic and Data
H3 SHEET H001
18. Revised these Schedules - Air Control Units-Hot Water to Electric, Room Heating Units (H.W.
to Electric), Sound Attenuators, Cooling/Heating Split Systems (H.W. to Electric), Cooling
Split System, Air Distribution Devices and Air Supply Rooftop Unit Schedule.
H4 SHEET H003
19. Deleted these details – Propeller Unit Heater-HW, Cabinet Unit Heater-HW, Air Terminal
Reheat Coil (2-way and 3-way)-HW, Rooftop unit HW Heating coil(2 details) and Under floor
duct detail. Updated sections 1 & 2.
H5 SHEET H201
20. Pit Level Floor Plan – Modified Heating & A/C system and Deleted Hot Water System and
replaced with Electric Heat source.
H6 SHEET H211
21. First Level Floor Plan – Modified Heating & A/C system and Deleted Hot Water System and
replaced with Electric Heat source. Modified Rooftop unit(s) supply and return air distribution.
H7 SHEET H221
22. First Level Balcony Floor Plan – Modified Heating & A/C system and Deleted Hot Water
System and replaced with Electric Heat source. Modified Rooftop unit(s) supply and return
air distribution.
H8 SHEET H231
23. Second Level Balcony Floor Plan – Modified Heating & A/C system and Deleted Hot Water
System and replaced with Electric Heat source. Modified Rooftop unit(s) supply and return
air distribution.
H9 SHEET H301
24. Rooftop Equipment Sections – Modified Rooftop unit elevations and quantity.
PART 4 – ELECTRICAL DRAWINGS
E1 SHEET E001
25. Revised Motor, Starters, Disconnects & Controls schedule.
J:\535-NVCLC\3581-0\AGENCY APPROVALS\Permit\535-3581 Permit Revision01.doc
E2 SHEET E300
26. VAV boxes have been changed from hot water heating to Electric heating with Electric
heating coils. Circuits have been added.
27. New Electrical panel RP-7 has been added to provide circuits to heating coils for VAV boxes.
28. Boilers and pumps have been deleted. Accordingly feeders to these units have been deleted.
29. HVAC has modified hot water cabinet and unit heaters to Electric. Circuits have been added.
E3 SHEET E301
30. HVAC has modified hot water cabinet and unit heaters to Electric. Circuits have been added.
31. Power device locations were modified to reflect new room layouts in Men’s restroom 108,
Janitor’s room 109, Women’s restroom 110 and Women’s restroom 111.
E4 SHEET E302
32. An additional Rooftop unit has been added (RTU–5) - 208V, 3 Ph., Circuit have been
provided for the same.
E5 SHEET E400
33. Revised single line diagram and main distribution schedule.
E6 SHEET E402
34. Revised panelboard schedule “RP4.”
E7 SHEET E403
35. Revised panelboard schedule “RP6” and added panelboard schedule “RP7”.
END OF PERMIT REVISION
UP
UP UP
F.E.C.
F.E.C.
F.E.C.
DN
UP
F.E.C.
DN
DN
DN
UP
UP
UP
DN
UP DN
DN
UP
F.E.C.
F.E.C.
F.E.C.
F.E.C.
F.E.C.
DN
F.E.C.
UP
DN
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
4.6
M
ND
H1.5
1.5
1.5
H3.2
X
2.0 3.8
H1
0.8 2.6 3.6
Y2
G
X10
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E F
P9
4.1
DN
DN
UP UP
DN
UP
UP
UP
F.E.C.
F.E.C.
F.E.C.
F.E.C.
UP
DN
A301
A301
3
2
1
A411
2
A411
118A
102A
102B
WORKSHOP
116
STORAGE
115
DELIVERY
118
WOMENS'
REST RM.
111
VESTIBULE
102
VEST.
112
107
106
103A 103B
113
112
103C 103D
102D
102C
0"
-3' - 0"
VEST.
107
VESTIBULE
106
VEST.
113
3
118D
116B
STAIR-1
S-11
WOMENS'
REST RM.
UP
DN
F.E.C.
DN
UP
F.E.C.
UP
DN
.
F.E.C.
DN
UP
F.E.C.
UP
UP
P
M
L
L
C
L4
ND
L3
P12
P10
M1
P9
1
A504
FIRST
BALCONY
LEVEL
BELOW
INTERMEDIATE
LANDING ONE
SECOND
BALCONY
LEVEL
STAIR-3
S-33
1' - 0"
1' - 11"
14 TREADS DN @ 11" = 12' - 10"
17 TREADS UP @ 11" = 14' - 8"
1' - 10"
4' - 4"
F4
F4
4' - 6" 4"
A521
13
P
M
L
C
L4
S
L3
P12
P10
42" HIGH TELESCOPING SAFETY
POST WITH EYEHOOK
3'-0" X 8'-0 ROOF HATCH WITH
1" FIBERGLASS INSULATION IN
COVER, COMBINATION LOCK
STRIKE AND PADLOCK HASP AND SPRING LATCH WITH INSIDE-OUTSIDE HANDLES
CURB WITH INTEGRAL
CAPFLASHING AND POSIFLASH
PAINTED ALTERNATING TREAD DEVICE
EXISTING STEEL BEAM
GASKET AT PERIMETER EDGE OF
ROOF HATCH
BRACKET ALTERNATING TREAD
DEVICE OFF OF EXISTING BEAM
CLIP ANGLE AND EXP. BOLT TO
FLOOR, EACH SIDE
21 EQUAL SPACES
PIT ROOF
824' - 7 5/8"
J
6' - 9" V.I.F.
CONTINUOUS PRE-FINISHED
ALUMINUM DRIP EDGE
FULLY ADHERED EPDM ROOF SYSTEM; 2 LAYERS
OF 1.5" RIGID INSULATION ON STEEL DECK;
ADDITIONAL TAPERED INSULATION AS REQUIRED
TO MAINTAIN MINIMUM SLOPE 1/4" PER FT. REF.
A251 FOR TAPERED INSULATION LOCATIONS
CONTINUE ROOF MEMBRANE UP PARAPET
WALL; TERMINATE BENEATH DRIP EDGE
2" RIGID INSULATION; BUILDING WRAP; 1/2" EXTERIOR
GYPSUM SHEATHING & 6" STEEL STUDS @ 16" O.C.;
6" BATT INSULATION & VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
FULLY ADHERED EPDM ROOF SYSTEM; 2 LAYERS
OF 1.5" RIGID INSULATION ON STEEL DECK;
ADDITIONAL TAPERED INSULATION AS REQUIRED
TO MAINTAIN MINIMUM SLOPE 1/4" PER FT. REF.
A251 FOR TAPERED INSULATION LOCATIONS
8"
R 1' - 1"
CONSTRUCT LADDER RAILS FROM 3/8" X3"
BAR STOCK. SPACE SIDES 24"APART.
NOTE: ALL STEEL FOR LADDER, INCLUDING
BRACKETS AND FASTENERS TO BE HOT DIPPED
GALVANIZED STEEL
3/4" DIA. RUNGS AT 12" O.C. TYP.
MOUNTING BRACKETS WITH 3/4" EXP BOLTS INTO
EXTERIOR WALL AT 4'-0" O.C. TYP. BRACKETS TO BE
MADE FROM 3/8" X3" BAR STOCK. PROVIDE NON-COMB.
CONTINUOUS WD BLOCKING AS REQUIRED FOR
BRACKET ATTACHEMENTS
FIRST FLOOR
817' - 7 5/8"
3" X 1" X .122" WELDED WIRE MESH WITH 1" U-CHANNEL
FRAME WELDED TO METAL TUBES, PAINTED, TYPICAL
11 EQUAL 28' PANELS - 5"
2" SQUARE TUBE, PAINTED
3-7/8" MAXIMUM OPEN SPACE FROM
BOTTOM TUBE TO TOP OF RETAINING WALL
SCALE:
S
S
S
S
S
SCALE:
SCALE: SCALE:
NONE NONE
NONE NONE
LIFT PIT FLOOR
2.5" 2.5"
1.25" 1.5"
0.75"
1.25"
1.25"
0.75"
0.75"
4"x3" REDUCING ELL
1.5"
0.75"
0.5"
0.5"
1.5"
1" 1"
MOP BASIN
4" HIGH CONCRETE BASE
PACKAGE FIRE PUMP SYSTEM
FIRE PUMP: 750 GPM @ 108 FT HD
MOTOR: 30 HP, 208 VOLT, 3 PHASE
JOCKEY PUMP: 10 GPM @ 147 FT HD
MOTOR 0.75 HP, 208 VOLT, 3 PHASE
REFER TO SPECIFICATION SECTION 21 31 13
2" MAIN DRAIN
EXTEND ALL DRIPS AND
DRAINS FROM FIRE PUMP
PACKAGE TO FLOOR DRAIN.
6" DOUBLE DETECTOR
CHECK ASSEMBLY
PIT LEVEL
6" TO FIRE RISERS AND
FLOOR CONTROL VALVES
2.5" TO FIRST LEVEL
FIXTURES
1.5" TO PIT LEVEL FIXTURES
3"
6"
6"
FLOOR SINK (BY PC)
1.5"
2.5"
TO WALL MOUNTED
FIRE PUMP
TEST HEADER
LIFT PIT SUMP PUMP
FIRE SERVICE AND PUMP WATER SERVICE
NOTES
ELEVATOR SUMP PUMP
WATER HEATER - PIT LEVEL
NOTES
UP
UP UP
F.E.C.
DN
UP
UP
UP
UP
1
1
CO
CO
4" SANITARY
INV. 809.00'
6" STORM
2,660 SQ.FT.
INV. 809.00'
5" DS
C2
FD1
C2
D1
A1
FD1
A3 A4
B2
B2
D1
FD2
F2
FD2
CO
F1
2
2
INV. 813.50'
INV. 813.80'
VR
3
3
3
3
2.5" DCW UP
2.5" DCW
3
3
6" STORM
4,350 SQ.FT.
INV. 814.00'
1
CO 5" DS
2" GAS SERVICE
@ 2 PSI
4
5" DS
3,170 SQ.FT.
6" ST
INV. 807.50'
INV. 816.00'
1
M
UP
UP
UP UP
F.E.C.
F.E.C.
F.E.C.
DN
UP
UP
UP
UP
4" FR UP,
2.5" FR DN
4" FR UP
2.5" FR DN
FDV
B1 FDV
A4 B1
RD3
5" DS
3,170 SQ.FT.
5" STORM
3,170 SQ.FT.
4,615 SQ.FT.
6" STORM
6" DS
4,615 SQ.FT.
2.5" FR UP
FDV
2.5" FIRE
B2 B2
A3
G1
F1
D1
FD2
FD2
2" GAS
@ 2 PSI
2" GAS
@ 2 PSI
5
4
10
1
0.5" DHW
0.75" DCW
VTR
WH
0.75" DCW
F2
3
6" FR UP
6" FIRE
6" FIRE PUMP
TEST HEADER
PIPING
6" FIRE SERVICE
0.5" DCW
D N
R O F
R D
A C EC SS H TA HC
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
A C EC SS H TA HC
S M O K H E CTA SEH
S UC PP RE
1
1
1
2
2
1
4
4 1
1
2
2
3
4
R UT 53 2 HFC
R UT 2
5 33 HFC
2 R UT
5 33 HFC
2 R UT 22 35 HFC
F
.E .C
R 2 ,065 S 3D Q .TF .
R 2D
1 ,097 S Q .TF .
R 2 ,066 S 3D Q .TF .
R 3D
3 ,570 S Q .TF .
R 3D
3 ,043 S Q .TF .
R 1D
1 ,030 S Q .TF .
R 2D
2 ,041 S Q .TF .
R 2D
2 ,091 S Q .TF .
R 3D
3 ,071 S Q .TF .
R 4D
4 ,516 S Q .TF .
R 1 ,063 S 2D Q .TF .
R 2D
DN
ROOF
RD
ACCESS HATCH
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
SCUPPER
ACCESS HATCH
SMOKE HATCHES
SCUPPER
1
1
1
2
1
4
4 1
1
2
2
4
6
6
5
6
6
6
RTU 2
235 CFH
RTU 5
533 CFH
2 RTU 1
533 CFH
2 RTU 4
150 CFH
G
1.5"
1.25"
1"
RTU 3
533 CFH
5
G
G
G
G
1.25"
1.25"
2"
1"
2"
SOIL WASTE AND VENT DIAGRAM
SCALE: NONE
D2
CO
2"
2"
1.5"
1ST
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
4"
4"
4"
4"
4"
4"
4"
D1
A1
A2
A2
1ST
FD1
1ST
4"
4"
4"
3"
3" 1.5"
2"
2"
2"
2"
C2
C2
C2
C2
2"
2"
3"
2"
1ST
1ST
2"
1.5"
1.5"
1.5"
3"
3"
2"
2"
3"
1ST
1ST
1ST
B1
B1
PLUMBING CONTRACTOR
P.C.
HVAC CONTRACTOR
H.C.
ELECTRICAL CONTRACTOR
E.C.
GENERAL CONTRACTOR
G.C.
NOT IN HVAC CONTRACT
N.I.H.C.
THERMOSTAT - MOUNTING HEIGHT 46",TO MEET ADA REQUIREMENTS. WHEN
MOUNTED NEXT TO WALL SWITCH COORDINATE WITH ARCHITECT.
T
S SPACE TEMPERATURE SENSOR.
123 ROOM NUMBER.
EQUIPMENT ITEM. (TO BE USED AS AID IN COORDINATING THE VARIOUS TRADES.)
APPROXIMATE ELEVATION FROM FLOOR TO BOTTOM OF DUCT, PIPE, DEVICE OR
9'-8"
SECTION "A" DESIGNATION , SHOWN ON SHEET H1.01.
H1.01
A
DETAIL "A", SHOWN ON SHEET H1.01.
H1.01
A
8"D = NECK SIZE. 300 = REQUIRED CFM. 3 = AIR DISCHARGE IF OTHER
AIR DEVICE A3 = DESIGNATION - REFER TO AIR DEVICE SCHEDULE.
THAN 4-WAY. METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING
MOUNTED DEVICES.
A3-8"D
300-3
WALL OR DUCT MOUNTED AIR DEVICE. G1 = DESIGNATION - REFER TO AIR
DEVICE SCHEDULE. 24"x16" = DUCT CONNECTION SIZE. 200 = REQUIRED
CFM. 9'-4" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF DEVICE.
200-9'-4"
G1-24x16
FACE AREA IN SQ. FT.
DL-2 DOOR LOUVER BY GENERAL CONTRACTOR. NUMBER INDICATES MINIMUM GROSS
DOOR UNDERCUT BY GENERAL CONTRACTOR.
U/C
R DUCT RISE IN DIRECTION OF AIR FLOW.
D DUCT DROP IN DIRECTION OF AIR FLOW.
DUCT WITH 1" ACOUSTICAL LINER. DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.
DUCT CONSTRUCTED OF SPECIAL MATERIAL AS NOTED.
FLEXIBLE DUCT CONNECTION.
AIR TURNING VANES.
MANUAL BALANCING VOLUME DAMPER WITH LOCKING DEVICE.
M.D.
FIRE DAMPER - LETTER "A", "B", OR "C" INDICATES TYPE REQUIRED, LETTER "D" OR "S"
INDICATES DYNAMIC OR STATIC - SEE DETAIL.
A-D
SMOKE DAMPER.
S
COMBINATION FIRE SMOKE DAMPER.
FS
PRESSURE GAUGE.
P
UNION.
CLEAN OUT.
STRAINER.
SHUTOFF VALVE
SCALE: NONE
SUPPLY FAN T.S.P. (INCH W.G.) + 2".
CENTERLINE DIMENSION NOT LESS THAN
4" MINIMUM - CENTERLINE TO CENTERLINE.
TEE WITH CLEANOUT PLUG.
PAN CONNECTION.
DRAIN PIPE SAME SIZE AS UNIT DRAIN
ROOFTOP UNIT
SPLASH BLOCK.
ROOF
TRAP
UNIT ROOF CURB. VERIFY REQUIRED
HEIGHT FOR DRAIN PIPE AND TRAP
INSTALLATION. PROVIDE CURB OF
ADEQUATE HEIGHT TO ATTAIN REQUIRED
DIMENSION.
A
H003
2
5
4
3
1
6
6
1 2
3
3
5
ROOFTOP UNIT DRAIN PIPING
DRAW-THRU UNIT
40/26
12' - 8 1/2"
8/8
RTU-3
9' - 1"
AC-3
44/28
10' - 10"
48/20
50/21
14"D
12' - 0"
13' - 11"
13' - 11"
RTU-4
10/6
8"D
10' - 0"
8' - 10 1/2"
24"D
24"D
12"D
8"D
S3 -
105 CFM
6"
(3)
12"D
8"D
UP
UP UP
F.E.C.
F.E.C.
F.E.C.
DN
UP
CUH-2
CUH-1
12"D
4-13
4-12
A1 - 8"
200 CFM
T
A1 - 6"
100 CFM
A1 - 8"
275 CFM
A1 - 6"
100 CFM
A1 - 6"
100 CFM
A1 - 6"
100 CFM
A1 - 6"
100 CFM
A1 - 6"
100 CFM
14"D
F1 - x
100 CFM
12 6
(3)
16"D
A1 - 6"
75 CFM
A1 - 6"
50 CFM
A1 - 6"
50 CFM
8"D
10"D
A1 - 6"
50 CFM
A1 - 6"
50 CFM
A1 - 6"
75 CFM
4-10
A1 - 6"
125 CFM
A1 - 8"
175 CFM
A1 - 6"
75 CFM
A1 - 8"
175 CFM
(2)
A1 - 8"
DN
DN
UP
UP
DN
UP
UP
UP
F.E.C.
F.E.C.
F.E.C.
F.E.C.
DN
UP
DN
A3
A4
A5 A6 A7 A8 A9 A10 A11 A12
A
AA
AB
AD
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
H4
P
4.3
H5
4.8
M
L
C
L4
Q
S
T
ND
U
H1.5
1.5
H3.2
X
2.0
3.8
H1
2.6
3.6
0.8
G Y2
Z
L2
DN
UP
DN
UP
DN
DN
UP
UP
F.E.C.
F.E.C.
A3
A4
A5 A6 A7 A8 A9 A10 A11 A12
A
AA
AB
AD
AE
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
H4
P
4.3
H5
4.8
M
L
C
L4
Q
S
T
ND
U
H1.5
1.5
H3.2
X
2.0
3.8
H1
2.6
3.6
0.8
G Y2
Z
L2
L3
P12
P15
X10
DN
UP
DN
DN
DN
DN DN
DN
A3
A4
A5 A6 A7 A8 A9 A10 A11 A12
A
AA
AB
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
H4
P
4.3
4.8
M
L
C
L4
Q
S
T
ND
U
H1.5
1.5
H3.2
X
2.0
3.8
H1
2.6
3.6
0.8
G Y2
Z
L2
L3
P12
P15
X10
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E
R.A.
E.A.
O.A.
S.A.
R.A.
E.A.
O.A.
S.A. R.A.
E.A.
O.A.
S.A.
R.A.
E.A.
O.A.
S.A.
R.A.
E.A.
O.A.
S.A.
A ALL UNITS SHALL BE SET ON MIN. 14" ROOF CURB. CURBS TO BE
FIELD ASSEMBLED.
B RTU-1,3,5 (40 TONS) SERVE WORSHIP CENTER SHALL BE
APPROX. 255" L. X 92" W. X 64" H. WITH APPROX. WEIGHT OF 6500 LBS.
C RTU-2 (30 TONS) SERVE STAGE SHALL BE APPROX. 240" L. X 92"
W. X 64" H. WITH APPROX. WEIGHT OF 6000 LBS.
D RTU-4 (30 TONS) SERVE PIT LEVEL.
E ROOFTOP STANDARD CLEARANCES SHALL BE - 60" TO FRONT,
RIGHT, LEFT, BACK AND 120" TO TOP.
F ROOFTOP UNIT ACCESS DOORS PER SPEC. AND UNIT MF'R. RECOMMENDATIONS.
G REFER TO ROOFTOP UNIT SCHEDULE, DRAWING H001.
H REFER TO PLUMBING DRAWINGS FOR GAS PIPING TO ROOFTOP UNITS.
J REFER TO DETAIL "A", H003 FOR ROOFTOP DRAIN PIPING.
ROOFTOP UNIT GENERAL NOTES
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1'-0"
PACKAGED ROOFTOP UNIT RTU-3 PLAN VIEW
PACKAGED ROOFTOP UNIT RTU-1 PLAN VIEW PACKAGED ROOFTOP UNIT RTU-2 PLAN VIEW
PACKAGED ROOFTOP UNIT RTU-4 PLAN VIEW
PACKAGED ROOFTOP UNIT RTU-5 PLAN VIEW
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
MOTORS, STARTERS, DISCONNECTS & CONTROLS
LIGHTING FIXTURES
LEGEND
NORMAL/EMERGENCY CIRCUIT SCHEDULE
GENERAL NOTES
WP/GF
J
H1
a
B1
b
LIGHTING FIXTURE; CAPITAL LETTER DENOTES FIXTURE TYPE. LOWER CASE LETTER
DENOTES SWITCHING ARRANGEMENT.
EXIT LIGHTING FIXTURE. COORDINATE EXIT SIGN ARROWS WITH ARCHITECTURAL
EGRESS PATHS - SEE ARCHITECTURAL DRAWINGS.
ELECTRICAL CONNECTION REQUIRED.
~
123 ROOM NUMBER.
2 DETAIL NOTE SYMBOL - APPLIES ONLY TO DETAIL ON WHICH NOTE IS SHOWN.
3 NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH NOTE IS SHOWN.
GROUND FAULT FEED THRU
GFFT
CIRCUIT
CKT
MOUNTING HEIGHT TO CENTERLINE OF ITEM UNLESS INDICATED OTHERWISE ON
MH DRAWINGS.
ABOVE FINISHED FLOOR - TO BOTTOM OF ITEM UNLESS INDICATED OTHERWISE ON
DRAWINGS
AFF
EXISTING
E
SURFACE MOUNTED
S
EMERGENCY
EM
WEATHERPROOF
WP
NOT IN ELECTRICAL CONTRACT
N.I.E.C.
EQUIPMENT SUPPLIER
E.S.
GENERAL CONTRACTOR
G.C.
FIRE PROTECTION CONTRACTOR
F.P.C.
PLUMBING CONTRACTOR
P.C.
HVAC CONTRACTOR
H.C.
ELECTRICAL CONTRACTOR
E.C.
FOUR-WAY WALL SWITCH (46" M.H.).
4
THREE-WAY WALL SWITCH (46" M.H.).
3
SINGLE POLE WALL SWITCH (46" M.H.).
MOTOR STARTER.
DISCONNECT SWITCH.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND
FAULT CIRCUIT INTERRUPTER (18" M.H.), WITH TAYMAC #20310 STANDARD COVER,
F
F
F
F
F
F
F
F
V
V
J J J
F
F
F
F
F
F
L
F
L
L
F
F
F
F
F
S
J
J
J
J
J
J
J
J
J
J
J
J
J
F
F
V
L
F
L
F
F
L
F
F
L
V
V
V
V
V
J
J
J J
S
J
J
J
J
F
F
J
J
S
F
F
L
L
L
L
L
F
F
F
J
J
J
J
OS
F
L
L
L
F
F
L
L
F
F
F
F
F
F
F
F
F
H H H
V
V
V
W
SC SC SC
SC SC SC
SC
SC
SC
SC
SC
F
F F
L F
L
F
L
F
F
F
F
F
J
J
J
J
S
J
J
J
J
F
F
F
V
W
SC SC SC
SC SC SC
H S
V
DN
UP
DN
UP
DN
DN
UP
UP
F.E.C.
F.E.C.
AV
AV AV
PRJ
AV
TL1
6
AV
AV
TL1
6
AV
AV
AV
AV
AV
7
6
7
7
7
7
6
AV
TL1
TL1
AV
AC-2
SCALE: NONE
E N
ATS #1
N E
G
PER NEC 695 - CONNECTION
LOCATED AHEAD OF MSB AND
NOT WITHIN THE 'MSB' ENCLOSURE
CABLES TO BE RUN BELOW THE BUILDING
ENVELOPE PER NEC REQUIREMENTS.
GENERATOR SET
START AND STOP
SIGNAL WIRING
EXISTING
SERVICE
NEW
NEW
M
SIZE
CONDUIT
GROUND
SIZE
FEEDER
FEEDER SIZE:
SPEC. REFERENCE NO.:
NAMEPLATE
UNIT NO.
SWITCH OR
SIZE
BREAKER
POLES
TRIP SIZE
VOLTAGE:
DEMAND LOAD:
CONNECTED LOAD:
OVERCURRENT PROTECTION
MAIN BUSSING:
WIRE
SIZE
APPROX.
CONNECTED
KVA
LOAD
SEE NOTE
NUMBER OF
CONDUCTORS
3000A
-
-
120/208V, 3PH, 4WIRE
1
BOLTED PRESSURE MAIN
- - - -
MAIN SWITCHBOARD "MDP3"
WITH GFP
2
3
4
5
6
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
8 06.10.08
11 CONSTRUCTION SET 08.01.08
7 06.04.08
6 05.22.08
5 ADDENDUM #2 05.16.08
4 PERMIT SET 04.25.08
3 CD 50% 03.14.08
2 DESIGN DEVELOPMENT 01.18.08
1 SCHEMATIC DESIGN 10.18.07
ADDENDUM #3
ADDENDUM #5
PERMIT SET
12 ASI6 12.23.08
PANEL:
CONN. LOAD:
MAINS:
MOUNTING:
DEMAND LOAD:
VOLTAGE:
REMARKS KVA BKR. BKR. KVA REMARKS
1 2
CKT. NO.
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42 41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL: PANEL:
CONN. LOAD:
MAINS:
MOUNTING:
DEMAND LOAD:
VOLTAGE:
REMARKS KVA BKR. BKR. KVA REMARKS
1 2
CKT. NO.
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42 41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL:
ABBREVIATIONS: L-LIGHTS, R-RECEPTACLES, M-MOTORS, H-RESISTANCE HEAT, C-CONTROL, M.L.O.-MAIN
LUGS ONLY, D.S.L.-DOUBLE SET OF LUGS, M.B.-MAIN BREAKER, L.C.-LOCKING CLIP ON BREAKER
THL-1
13.3 KVA
200A
SURFACE
-
120/208V 3PH 4WIRE
- 20/3
THL-2
4.60 KVA
200A
SURFACE
-
120/208V, 3PH, 4WIRE
- -
CKT#1 20/3 - CKT#2 CKT#1 - 20/3 20/3 - CKT#2 - - - -
CKT#3 20/3
CKT#5 20/3
20/3 CKT#4
20/3 CKT#6
CKT#7 20/1
CKT#9
CKT#11
CKT#13
CKT#15
CKT#17
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
CKT#10
CKT#12
CKT#14
CKT#16
CKT#18
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
PANEL:
CONN. LOAD:
MAINS:
MOUNTING:
DEMAND LOAD:
VOLTAGE:
REMARKS KVA BKR. BKR. KVA REMARKS
1 2
CKT. NO.
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42 41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL: THL-6
17.25 KVA
200A
SURFACE
-
120/208V 3PH 4WIRE
- 20/3
-
- - CKT#1 20/3 - CKT#2
CKT#3 20/3
CKT#5 20/3
20/3 CKT#4
20/3 CKT#6
CKT#7 20/1
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
CKT#3
CKT#5
CKT#7
CKT#9
CKT#11
CKT#12
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
CKT#4
CKT#6
CKT#8
CKT#10
CKT#12
CKT#14
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
THL-3
11.5 KVA
200A
SURFACE
120/208V 3PH 4WIRE
THL-4
9.8 KVA
200A
SURFACE
120/208V 3PH 4WIRE
THL-5
14.4 KVA
200A
SURFACE
120/208V 3PH 4WIRE
CKT#1 20/3 20/3 CKT#2
CKT#3 20/3
CKT#5 20/3
20/3 CKT#4
20/3 CKT#6
CKT#7 20/1
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
CKT#1 20/3 20/3 CKT#2
CKT#3 20/3
CKT#5 20/3
20/3 CKT#4
20/3 CKT#6
CKT#7 20/1
CKT#9
CKT#11
CKT#13
CKT#15
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
CKT#10
CKT#12
CKT#14
CKT#16
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
CKT#1 20/3 20/3 CKT#2
CKT#3 20/3
CKT#5 20/3
20/3 CKT#4
20/3 CKT#6
CKT#7 20/1
CKT#9
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
CKT#10
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
PANEL:
CONN. LOAD:
MAINS:
MOUNTING:
DEMAND LOAD:
VOLTAGE:
REMARKS KVA BKR. BKR. KVA REMARKS
1 2
CKT. NO.
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
-
- -
THL-7
10.4 KVA
200A
SURFACE
120/208V 3PH 4WIRE
CKT#1 20/3 20/3 CKT#2
CKT#3 20/3
CKT#5 20/1
20/3 CKT#4
20/1 CKT#6
CKT#7 20/1
CKT#9
CKT#11
CKT#13
CKT#15
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
CKT#8
CKT#10
CKT#12
CKT#14
CKT#16
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL:
-
2.50 2.50
RP3
41.7 KVA
200A
SURFACE
120/208V 3PH 4WIRE
WINCH#1 20/3 20/3 WINCH#2
WINCH#3 20/3
WINCH#5 20/3
20/3 WINCH#4
20/3 WINCH#6
CSL PANEL
SPARE
SPARE
STAGE LIFT
STAGE LIFT
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
2.50
2.50
2.50
2.50
WINCH#7 2.50 20/3 20/3 2.50 WINCH#8
WINCH#9 2.50 20/3 20/3 2.50 TRACK
WINCH CTRL 5.50 20/3 20/3 5.50 TRACK CTRL
1.90 1.90
1.90
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL:
72.9 KVA
3.35
RP6
81.00 KVA
300A
SURFACE
120/208V 3PH 4WIRE
VAV-1 35/3 35/3
30/3
45/3
20/3
25/3
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
20/1
20/1
20/1
20/1
20/1
20/1
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
CKT. NO.
1 2
REMARKS KVA BKR. BKR. KVA REMARKS
VOLTAGE:
DEMAND LOAD:
MOUNTING:
MAINS:
CONN. LOAD:
PANEL:
83.25 KVA
RP7
92.5 KVA
300A
SURFACE
120/208V 3PH 4WIRE
20/3 20/3
20/3
20/3
20/3
20/3
SPARE
SPARE SPARE
20/1
20/1
20/1
20/1
20/1
20/1
20/3 20/3
20/3 20/3
20/1
VAV-2
VAV-3 VAV-5
VAV-4 VAV-6
VAV-7 VAV-8
VAV-9 VAV-10
VAV-11 VAV-12
20/3 50/3
20/3 20/3
20/3 20/3
3.35
3.35
3.35
3.35
3.35
3.0 1.0
3.0 1.0
3.0 1.0
4.33 2.33
4.33 2.33
4.33 2.33
2.0 4.66
2.0 4.66
2.0 4.66
0.66 1.33
0.66 1.33
0.66 1.33
0.66 0.33
0.66 0.33
0.66 0.33
- -
- -
- -
VAV-13 0.33 VAV-14
VAV-15 UH-1
UH-2 UH-3
CUH-2 CUH-1
CUH-4 CUH-3
UH-3 SPARE
1.00
1.33 3.35
2.50 3.35
3.35 5.00
5.00 5.00
-
-
-
-
SPARE
-
-
-
-
-
20/1
20/1
SPARE
SPARE
SPARE
SPARE
0.33 1.00
1.33 3.35
2.50 3.35
3.35 5.00
5.00 5.00
0.33 1.00
1.33 3.35
2.50 3.35
3.35 5.00
5.00 5.00
3.35 20/3
3.35
3.35
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
8 06.10.08
11 CONSTRUCTION SET 08.01.08
7 06.04.08
6 05.22.08
5 ADDENDUM #2 05.16.08
4 PERMIT SET 04.25.08
3 CD 50% 03.14.08
2 DESIGN DEVELOPMENT 01.18.08
1 SCHEMATIC DESIGN 10.18.07
ADDENDUM #3
ADDENDUM #5
PERMIT SET
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
2/3/2009 4:35:29 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E403
PANELBOARD
SCHEDULES
New Worship
Center
Checker
Author
05-22-08
2007-06019
13 PERMIT RE-SUBMISSION 1.28.09
2/3/2009 4:32:25 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E402
PANELBOARD
SCHEDULES
New Worship
Center
Checker
Author
05-22-08
2007-06019
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
15380 VA 16300 VA 18600 VA 50280 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
Power 20 A 1 1 1000 VA / 1000 VA 2 1 20 A Power
Power 20 A 1 3 1000 VA / 1000 VA 4 1 20 A Power
Power Room 016 20 A 1 5 1400 VA / 500 VA 6 1 20 A Power
Power GREEN ROOM
020
20 A 1 7 180 VA / 1400 VA 8 1 20 A Power RECORDING
STUDIO 029
Power 20 A 1 9 1400 VA / 1400 VA 10 1 20 A Power
Power 20 A 1 11 1400 VA / 1500 VA 12 1 20 A
20 A 1 13 1500 VA / 1500 VA 14 1 20 A
20 A 1 15 1500 VA / 1500 VA 16 1 20 A
17 0 VA / 1500 VA 18 1 20 A
20 A 1 19 1500 VA / 2100 VA 20 2 20 A Power
Power 20 A 2 21 2100 VA / 2100 VA 22 --
-- 23 2100 VA / 2100 VA 24 2 20 A Power
Power 20 A 1 25 1600 VA / 2100 VA 26 --
27 28
Power 20 A 1 29 1600 VA / 1200 VA 30 1 20 A Power
Power 20 A 1 31 800 VA / 0 VA 32 --
33 0 VA / 700 VA 34 1 20 A Power PLATFORM
119
Power RECORDING
STUDIO 029
20 A 1 35 700 VA / 1000 VA 36 1 -- Power
Power PLATFORM
119
20 A 1 37 700 VA / 0 VA 38 --
Power SIDE
PLATFORM 120
20 A 2 39 3600 VA / 0 VA 40 2 20 A Power SIDE
PLATFORM 117
-- 41 3600 VA / 0 VA 42 --
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV1 120 V / 208 V Three Phase 4 Wires 200 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
1440 VA 1000 VA 0 VA 2440 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
Power 20 A 1 1 230 VA / 0 VA 2
3 4
5 6
7 0 VA / 750 VA 8 1 20 A EF-7
Power VEST. 107 20 A 1 9 500 VA / 500 VA 10 1 20 A Power WOMENS'
REST RM. 111
Power 20 A 1 11 12 1 20 A Power
20 A 1 13 230 VA / 230 VA 14 1 20 A
Power MECH. ROOM
020
20 A 1 15 16 1 20 A Power WORKSHOP
116
Power STORAGE 115 20 A 1 17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 TRAP ROOM 033
Panel Voltage Phase Wires Mains
RP5 120 V / 208 V Three Phase 4 Wires 200 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
19620 VA 22320 VA 21200 VA 63140 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
20 A 1 1 1800 VA / 1800 VA 2 1 20 A
20 A 1 3 1800 VA / 1800 VA 4 1 20 A
20 A 1 5 1800 VA / 1800 VA 6 1 20 A
20 A 1 7 1800 VA / 1800 VA 8 1 20 A
20 A 1 9 1800 VA / 1800 VA 10 1 20 A
20 A 1 11 1800 VA / 1800 VA 12 1 20 A
20 A 1 13 1800 VA / 1800 VA 14 1 20 A
20 A 1 15 1800 VA / 1800 VA 16 1 20 A
20 A 1 17 1800 VA / 1800 VA 18 1 20 A
20 A 1 19 1800 VA / 1800 VA 20 1 20 A
20 A 1 21 1800 VA / 1800 VA 22 1 20 A
20 A 1 23 1800 VA / 1800 VA 24 1 20 A
Power VIDEO EDIT
027
20 A 1 25 540 VA / 540 VA 26 1 20 A Power VIDEO EDIT
027
Power 20 A 1 27 360 VA / 360 VA 28 1 20 A Power
Power 20 A 1 29 1400 VA / 1800 VA 30 1 20 A
31 0 VA / 540 VA 32 1 20 A Power VIDEO
CONTROL 022
20 A 1 33 1800 VA / 1800 VA 34 1 20 A
20 A 1 35 1800 VA / 1800 VA 36 1 20 A
20 A 1 37 1800 VA / 1800 VA 38 1 20 A
20 A 1 39 1800 VA / 1800 VA 40 1 20 A
41 42
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV4 120 V / 208 V Three Phase 4 Wires 100 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
21400 VA 18280 VA 17700 VA 57380 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
Power 20 A 1 1 1200 VA / 1800 VA 2 1 20 A Power
3 0 VA / 1080 VA 4 1 20 A Power
Power 20 A 1 5 700 VA / 2100 VA 6 2 20 A Power
Power 20 A 2 7 2100 VA / 2100 VA 8
-- 9 2100 VA / 2100 VA 10 2 20 A Power
Power 20 A 2 11 2100 VA / 2100 VA 12
-- 13 2100 VA / 2100 VA 14 2 20 A Power
Power 20 A 2 15 2100 VA / 2100 VA 16
-- 17 2100 VA / 2100 VA 18 2 20 A Power
Power 20 A 2 19 2100 VA / 2100 VA 20
-- 21 2100 VA / 2100 VA 22 2 20 A Power
Power 20 A 2 23 2100 VA / 2100 VA 24
-- 25 2100 VA / 2100 VA 26 2 20 A Power
Power 20 A 1 27 700 VA / 2100 VA 28
Power 20 A 1 29 700 VA / 700 VA 30 1 20 A Power
Power 20 A 1 31 700 VA / 900 VA 32 1 20 A Power
Power 20 A 1 33 900 VA / 900 VA 34 1 20 A Power
Power 20 A 1 35 900 VA / 0 VA 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV3 120 V / 208 V Three Phase 4 Wires 100 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
7400 VA 9800 VA 8000 VA 25200 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
Power BALCONY-1
200
20 A 1 1 1400 VA / 400 VA 2 1 20 A Power BALCONY-1
200
Power BALCONY-1
200
20 A 1 3 1400 VA / 700 VA 4 1 20 A Power SECOND
BALCONY 300
5 0 VA / 2100 VA 6 2 20 A Power PROJECTION
ROOM 221
Power PROJECTION
ROOM 221
20 A 2 7 2100 VA / 2100 VA 8
-- 9 2100 VA / 2100 VA 10 2 20 A Power PROJECTION
ROOM 221
Power BALCONY-1
200
20 A 1 11 800 VA / 2100 VA 12
13 14
Power BALCONY-1
200
20 A 1 15 800 VA / 1200 VA 16 1 20 A Power BALCONY-1
200
Power BALCONY-1
200
20 A 1 17 800 VA / 700 VA 18 1 20 A
20 A 1 19 700 VA / 700 VA 20 1 20 A
Power SECOND
BALCONY 300
20 A 1 21 800 VA / 700 VA 22 1 20 A Power SECOND
BALCONY 300
Power SECOND
BALCONY 300
20 A 1 23 700 VA / 800 VA 24 1 20 A Power SECOND
BALCONY 300
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV2 120 V / 208 V Three Phase 4 Wires 200 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
16560 VA 15120 VA 15120 VA 46800 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
SIDE PLATFORM 120 20 A 1 1 1800 VA / 1800 VA 2 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 3 1800 VA / 1800 VA 4 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 5 1800 VA / 1800 VA 6 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 7 1800 VA / 1800 VA 8 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 9 1800 VA / 1800 VA 10 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 11 1800 VA / 1800 VA 12 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 13 1800 VA / 1800 VA 14 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 15 1800 VA / 1800 VA 16 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 17 1800 VA / 1800 VA 18 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 19 1800 VA / 1800 VA 20 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 21 1800 VA / 1800 VA 22 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 23 1800 VA / 1800 VA 24 1 20 A SIDE PLATFORM 120
SIDE PLATFORM 120 20 A 1 25 1800 VA / 360 VA 26 1 20 A Power
Power 20 A 1 27 360 VA / 360 VA 28 1 20 A Power
Power 20 A 1 29 360 VA / 360 VA 30 1 20 A Power
31 32
33 34
35 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV5 120 V / 208 V Three Phase 4 Wires 100 A
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
6900 VA 8100 VA 7200 VA 22200 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
Room 033 20 A 1 1 540 VA / 360 VA 2 1 20 A TRAP ROOM 033
20 A 1 3 900 VA / 0 VA 4
5 0 VA / 900 VA 6 1 20 A TRAP ROOM 033
20 A 1 7 900 VA / 900 VA 8 1 20 A
TRAP ROOM 033 20 A 1 9 900 VA / 2100 VA 10 2 20 A Power PLATFORM
119
Power PLATFORM
119
20 A 2 11 2100 VA / 2100 VA 12
-- 13 2100 VA / 2100 VA 14 2 20 A Power PLATFORM
119
Power PLATFORM
119
20 A 2 15 2100 VA / 2100 VA 16
-- 17 2100 VA / 0 VA 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 CORR. C-005
Panel Voltage Phase Wires Mains
RPAV6 120 V / 208 V Three Phase 4 Wires 100 A
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
BATTERY CHARGER 20 A 1 1 20 A BLOCK HEATER
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
SPARE 20 A 1 1 20 A SPARE
Mfg. / Type Modifications Amps RMS. Sym.
-- -- --
Phase A Phase B Phase C Total VA
39933 VA 34333 VA 39933 VA 114200 VA
Load Name Trip Poles Ckt. No. A B C Ckt. No. Poles Trip Load Name
AC-2 125 A 3 1 11667 VA / 11667 VA 2 3 125 A AC-1
-- 3 11667 VA / 11667 VA 4 --
-- 5 11667 VA / 11667 VA 6 --
AC-3 45 A 2 7 3500 VA / 2000 VA 8 3 30 A MECH. ROOM 020
-- 9 3500 VA / 2000 VA 10 --
CU-3 40 A 2 11 2100 VA / 2000 VA 12 --
-- 13 2100 VA / 0 VA 14 2 40 A CU-4
AC-4 45 A 2 15 3500 VA / 0 VA 16 --
-- 17 3500 VA / 2000 VA 18 3 --
CU-1 40 A 3 19 7000 VA / 2000 VA 20 --
-- 21 0 VA / 2000 VA 22 --
-- 23 0 VA / 7000 VA 24 3 40 A CU-2
25 26 --
27 28 --
29 30
31 32
33 34
35 36
37 38
39 40
41 42
Mount Enclosure Location
Surface Type 1 TRAP ROOM 033
Panel Voltage Phase Wires Mains
RP4 120 V / 208 V Three Phase 4 Wires 200 A
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
SERVICE SPD
ATS #1
ROOF TOP UNIT #1
ROOF TOP UNIT #2
ROOF TOP UNIT #3
ROOF TOP UNIT #4
ELEVATOR
STAGE LIFT
PANEL "RP1"
PANEL "RP2"
PANEL "RP3"
PANEL "RP4"
PANEL "THL1"
PANEL "THL2"
PANEL "THL3"
PANEL "THL4"
PANEL "THL5"
PANEL "THL6"
PANEL "THL7"
TRANSFORMER
DP #1
DP #2
PANEL "LP2"
30
31
32
33
34
PANEL "LP1"
PANEL "EP"
AC-2
SPARE
SPARE
30
83
75
83
75
83
82.5
35
30
11
40
40
42
48
60
100
250
250
250
250
250
300
125
150
50
200
200
200
200
200
200
200
200
200
200
200
800
200
200
200
200
200
100
125
200
200
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
- - -
60
150
250
250
250
250
250
300
125
150
50
200
200
200
200
200
200
200
200
200
200
200
800
200
200
200
200
200
100
125
200
200
3
4
3
3
3
4
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
6
2/0
4/0
4/0
4/0
350
1
3/0
6
3/0
3/0
3/0
3/0
250
250
250
250
250
250
250
250
250
250
3/0
3/0
10
3
4
4
4
4
6
6
10
6
6
6
6
3
3
3
3
3
3
3
3
3
3
6
6
2 SETS - 3 #400 AND
1 #1/0 IN 3"C EACH SET
100
8 SETS - 4#600 IN 3.5"C CONDUIT
EACH SET +(2) SPARE 3.5" CONDUITS
0.75
2.0
2.5
2.5
2.5
-
3
1.5
2.0
1.5
2.5
2.5
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.5
2.5
GFP
SPD
ELEV.
SERVICE
3000A, 208/120V-3PH-4W
SWBD
METERING
POWER
MODULE
UTILITY
PRIMARY
ELECTRICAL
FEEDER
POWER COMPANY
PAD MOUNTED TRANSFORMER
12.47 KV/208/120V-3PH-4W
ELEC. METER
PER UTILITY
REQUIREMENT
TRANSITION
CABINET
TO EXISTING SWITCHBOARD 'MDP'
TO EXISTING SWITCHBOARD 'MDP2'
EXISTING
AC-1
4
BUSSMANN
SWITCH
30HP
STAGE LIFT
10HP
STARTER
CABINET
EMERGENCY GENERATOR
WITH AUTO. TRANFER SWITCH
FIRE PUMP CONTROLLER
PUMP
FIRE
208/120V
STAND-BY
60KW NATURAL GAS
400/300
B
B
A
B
(FP1)
110/3 100/3
100/3P, 4 WIRE
30HP
EBP
RPAV1 RPAV2 RPAV3 RPAV4 RPAV5 RPAV6
RP1
2 3 5 6 7 8 9 10 11 12 13 14
RP2
15
RP3
16
RP4
17
THL1
18
THL2
19
THL3
20
THL4
21
THL5
22
THL6
23 24
33 32 31
LP1
30
LP2
29 28
DP#1
27
DP#2
26 25
11 10 9 8 7 6 5 4 3 2 1
PRIMARY : 208V, 3Ph., Delta
SECONDARY: 208V, 3 Ph., Wye
ISOLATION TRANSFORMER
FOR A/V APPLICATION ONLY
SPARE SPARE SPARE SPARE
1
60 100 250 250 250 250 250 300 300 125 150 50 200 200 200 200 200 200 200 200 200 200 200
125 200 200 200 200 200 200 800
225KVA
100 100 200 200 200 200 200 200 200 200
800A, 208/120V-3PH-4W
DP#3 THL7
RP5
34
SPARE
200
(OPTIO 9) (OPTIO 9) (CAPIO)
(PLUS)
A
PANEL "RP5"
48 200 3 200 4 3/0 6 2.5
35
DP #3
1
2
3 4 5 6 7 8 9 10 11 12 13
36
35
34
33
10757
8163
8163
8163
8163
8163
8163
21
22
23
24
25
26
27
28
29
30
31
32
29445
29445
10044
10044
10044
13454
13454
13454
20
19
18
17
16
15
14
13
12
11
10 13454
9 13454
8 13454
5 23096
7 23096
6 23096
4 27158
3 27158
2 41894
1 48331
AVAILABLE SHORT
CIRCUIT AMPS
POINT
REF.
DESCRIPTION
SECONDARY - SERVICE TRANSFORMER
MAIN SWITCHBOARD 'MDP3'
PANEL 'RP2'
PANEL 'RP3'
PANEL 'RP4'
PANEL 'RP5'
PANEL 'THL1'
PANEL 'THL2'
PANEL 'RP1'
PANEL 'THL3'
PANEL 'THL4'
PANEL 'THL5'
PANEL 'THL6'
PANEL 'THL7'
DIMMER RACK DP#3
XFMR 225KVA PRIMARY
DIMMER RACK DP#2
DIMMER RACK DP#1
PANEL 'LP2'
PANEL 'LP1'
XFMR 225KVA SECONDARY
PANEL 'RPAV6'
PANEL 'RPAV5'
PANEL 'RPAV4'
PANEL 'RPAV3'
PANEL 'RPAV2'
PANEL 'RPAV1'
13454
35824
9702
DISTRIBUTION PANEL 'DPL1'
PANEL 'EP' 27158
29
EXISTING
EXISTING
EXISTING
32
100
EP
TRANSFER SWITCH
TO RELAY LOADS
TO DIMMING LOADS
4 1 8 1.5
EMERGENCY
UC700
TRANSFER SWITCH
EMERGENCY
UC700
A - 4#2/0, 1#3 IN 2" C.
B - 3#2/0, 1#3 IN 2" C.
ROOF TOP UNIT #5
PANEL "RP6"
PANEL "RP7"
AC-1
81 300 3 300
3 4/0 4 2.5
35 3 1 6 1.5
14
21
19
14
18
RP6 RP7
AC-2 EP
29 20 19 18 17 16 15
14
21
22
28 27 26 25 24 23
225
4 350 4 3
3 4/0 4 2.5
"THL1" THRU "THL7"
TOTAL
RTU-1 RTU-2 RTU-3 RTU-4 RTU-5
125
ELECTRIC SINGLE-LINE DISTRIBUTION DIAGRAM FAULT CURRENT SCHEDULE
MAIN SWITCHBOARD 'MDP3'
DISTRIBUTION PANEL "DPL1
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
2/3/2009 4:29:28 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E400
SINGLE-LINE
DISTRIBUTION
DIAGRAM
New Worship
Center
Checker
Author
05-22-08
2007-06019
AC-1
2
1
3
GF
R
V1 AV
RPAV2 - 1
RPAV2 - 2
RPAV2 - 3
A G E1
A C E1
A G E1
A G E1
A G E1
RPAV2 - 6,8 RPAV2 - 7,9 RPAV2 - 10,12
E F1 E F1 E F1
PRJ PRJ
A C1
A
A A
A
C C1
A A
C C1 RPAV2 - 11
RPAV2 - 15
RPAV2 - 16
RPAV2 - 17
RP1 - 5
RP1 - 6
RP1 - 7
RP1 - 8
RP1 - 9
5
MDP3 - 16
EP - 16
EP - 17
RP5 - 11
EF-4
EF-3
RP5 - 12
RP5 - 13
GF/WP
RTU-5
RP5 - 14
GF/WP
RP4 - 1,3,5
RP4 - 2,4,6
4 4 4
6 (TYP.)
A A
A A
A
A C1
7 7
7
221
200
S-21 S-22
S-23
203
201
204
202
S-24
8 8
10 11
7 10 11
9 9
12
R R
13 13
WP
WP
7 10 11
RTU-1
MDP3-8
MDP3-5
RTU-2
GF/WP
WP
RP5 - 1
MDP3-4
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
2/3/2009 4:29:28 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E302
BALCONY ONE -
POWER PLAN
New Worship
Center
Checker
Author
05-22-08
2007-06019
1/8" = 1'-0"
1
POWER & SYSTEMS - BALCONY ONE -
NEW WORK
GENERAL NOTES
A E.C. TO COORDINATE WITH A/V DRAWINGS:
AV201, AV211, AV202, AV212, AV203, AV213, AV204, AV205, AV215, AV251, AV252, AV253,
AV301, AV302
FOR BOX TYPE, MOUNTING HEIGHT, EXACT LOCATION FOR A/V DEVICES AND A/V
EQUIPMENT AND ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
A/V CONSULTANT: CRAIG COMPTON
PRO-SOUND
PH: 407-816-9400
E-MAIL: CCOMPTON@PROSOUND.NET
PLAN NOTES
1 PROVIDE 240V, 1P, 30A FUSED DISCONNECT WITH 20A FUSE AND 120V, 20A DEDICATED
CIRCUIT FOR ELEVATOR CAB LIGHT. PROVIDE WIRING TO ELEVATOR CONTROLLER PER
MANUFACTURER'S REQUIREMENTS.
2 PROVIDE BUSSMAN POWER MODULE SWITCH WITH SHUNT-TRIP CONTROL.
TRANSFORMER WITH FUSES AND BLACKS, FIRE SAFETY INTERFACE RELAY,
MECHANICALLY INTERLOCKED AUXILIARY CONTACT, FIRE ALARM VOLTAGE
MONITORING RELAY IN NEMA 1 ENCLOSURE. PROVIDE ELEVATOR POWER CIRCUIT
#MDP3-_ (208V, 3PH, 60HZ, 30HP). COORDINATE EXACT SWITCH SIZE WITH ELEVATOR
EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
3 PROVIDE 120V, 20A GFCI RECEPTACLE IN THE ELEVATOR EQUIPMENT ROOM (46"M.H.).
4 PROVIDE RECEPTACLE WITH NEMA CONFIGURATION - 6-20R. COORDINATE EXACT
REQUIREMENTS WITH A/V CONSULTANT PRIOR TO ROUGH-IN.
5 SINGLE GANG BOX WITH 3/4" CONDUIT TO "CONTROL EQUIPMENT RACK" IN CATWALK.
PROVIDE BLANK COVER PLATE. DATA OUTLET AND CABLE BY OTHERS. INTENT IS TO
MOUNT BOX ON FACE OF BALCONY FLOOR. COORDINATE EXACT LOCATION AND
MOUNTING HEIGHT WITH LIGHTING CONSULTANT / SYSTEM INTEGRATOR PRIOR TO
ROUGH-IN.
6 INTENT IS TO MOUNT SPEAKERS CENTERED WITH BEAM (TYPICAL OF 5 SPEAKERS).
COORDINATE EXACT LOCATION WITH A/V CONSULTANT PRIOR TO ROUGH-IN.
7 PROVIDE DUCT MOUNTED SMOKE DETECTOR ON RETURN DUCT AND INTERFACE WITH
FACP TO SHUT-DOWN UNIT UPON ALARM.
8 PROVIDE SINGLE GANG BOX WITH 3/4" CONDUIT TO THE SERVER ROOM. PROVIDE A BLANK
COVER PLATE. RJ45 OUTLET AND CAT5 CABLING BY OTHERS. OVERALL LENGTH SHOULD
NOT EXCEED 285'.
9 AIR CONDITIONING UNIT. MOUNT FUSED DISCONNECT ON THE UNIT AND WIRE PER
REQUIREMENTS. SEE HVAC DRAWINGS FOR LOCATION AND MOUNTING ARRANGEMENT.
10 ROOFTOP UNIT. PROVIDE FUSED DISCONNECT NEMA 3R AND WIRE PER REQUIREMENTS.
COORDINATE LOCATION WITH HVAC DRAWINGS.
11 PROVIDE GFI/WP RECEPTACLE AND VAPORPROOF APPLETON LIGHT FIXTURE FOR
ROOFTOP UNIT. PROVIDE WEATHERPROOF LIGHT SWITCH.
12 EXHAUST FAN. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
WITH HVAC DRAWINGS FOR LOCATION AND CONTROLS.
13 CONDUITS FROM MAIN LEVEL, BOOTH, 1ST BALCONY, AND 2ND BALCONY ARE TO BE
ROUTED THRU THE CHASE SPACE AVAILABLE AT THE BACK OF THE NEW WORSHIP CENTER
NEAR THE REST ROOMS, STAIRS, ETC., DOWN BELOW THE UNDERFLOOR DUCT WORK
BELOW THE SEATING IN THE MAIN LEVEL TO THE STAGE RACK LOCATION, RACK LOCATION
IN THE PIT LEVEL, ELECTRICAL PANELS, SWITCHBOARD "MDP3", ETC. E.C. TO COORDINATE
WITH PLUMBING AND HVAC CONTRACTORS PRIOR TO INSTALLING THE CONDUITS TO
PREVENTCONFLICTS BETWEEN THE TRADES.
A/V CONDUIT NOTES
A (1) 3/4"C.
B (3) 1"C.
C (1) 1"C.
D (1) 2"C.
E (1) 1-1/2"C.
F (3) 1-1/2"C.
G (2) 1"C.
H (2) 2"C.
J (2) 4"C.
K (3) 4"C.
L (3) 2"C.
M (1) 1/2"C.
N (2) 1-1/4"C.
O (2) 1-1/2"C.
A1 TO VBB.
B1 TO A/V RACKS 023.
C1 TO A/V RACKS AT STAGE LOCATION.
D1 TO SBB.
E1 TO A/V RACKS 023 COMPUTER FLOOR.
F1 TO VDB-501.
G1 TO ADB-501.
H1 TO CPB.
200 BALCONY-1
201 VESTIBULE
202 CRYING ROOM
203 MACHINE ROOM
204 MEZZANINE
221 PROJECTION ROOM
S-21 STAIR-1
S-22 STAIR-2
S-23 STAIR-3
S-24 STAIR-4
ROOM INDEX
L
L
SC
L
DN
UP
UP
DN
UP
UP
UP
F.E.C.
F.E.C.
F.E.C.
F.E.C.
DN
UP
DN
A3
A4
A5 A6 A7 A8 A9 A10 A11 A12
A
AA
AB
AD
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
H4
P
4.3
H5
4.8
M
L
C
L4
Q
S
T
ND
U
H1.5
1.5
H3.2
X
2.0
3.8
H1
2.6
3.6
0.8
G Y2
Z
L2
L3
P12
P15
X10
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E
F
B
Z2
Z3
Z1
Z4
P4 P5
P3
P2
P6
P7
P10
N1
N2
N3
M1
M2
M3
N
1.3 2.1
W
W3
W2
W1
P8
P9
2.2
4.2
N4 M4
4.1
P1
T4
T1
T2
T3
T5
S1
S2
S3
S4
S5
A1 A2
J
J1
J2
3.1
A.
GF
GF
AV
AV
AV
AV
AV
AV
AV
AV
AV
TL1
AV
TL1
CAM
6
6
6
TL1
AV
CAM CAM
CAM
CAM
6
6
6
AV
AV
TL1
TL1
AV
AV
TL1
110 110
110
110
110
110
R
WP/GF
GF
GF
GF
AV
AV AV
AV
CAM
AV
CAM
AV
AV
CAM
AV
RPAV1 - 34
RPAV1 - 37
F E1
B
K L C1
L E1
G E1
G E1
RPAV1 - 12
RPAV1 - 13
G E1
G E1
RPAV1 - 14
RPAV1 - 15
B
F E1
G H J E1
RPAV1 - 16
- <unnamed>
RPAV1 - 18
RPAV1 - 19
G E1 G E1
G E1 G E1
RPAV1 - 20,22
VDB
RPAV1 - 21,23 RPAV1 - 24,26
E E E L E1
A
C C1
7
7
7
AV
AV
7
7
A
A
A
A
A C1
A
C1 C
PRJ PRJ
RPAV1 - 30
RPAV1 - 31
RPAV5-1-5
RPAV5-6-10
RPAV5-11-15
RPAV5-16-20
RPAV5-21-25
RPAV5 - 28
RPAV5 - 27
RPAV5 - 26
RPAV5 - 29 RPAV5 - 30
S5
AV
S5
AV
RPAV6 - 2
S5
AV
S5
AV
S5
AV
RPAV6 - 1
A
A
A
A
A C1
FB1
AV
RPAV6 - 6
FB1
AV
RPAV6 - 7
FB1
AV
RPAV6 - 8 FB1
AV
RPAV6 - 9
N C1
N C1 N C1
N C1
RPAV6 - 10,12
AV
C C1
RPAV6 - 11,13
AV
C C1
RPAV6 - 15,17
AV
C C1
RPAV6 - 14,16
C C1 AV
S4
S4
S4
S4
RPAV1 - 10
AV
6
RPAV1 - 25
RPAV1 - 11
AV
A A
RPAV1 - 29
RP2 - 15
RP2 - 16
RP2 - 18
RP2 - 20
RP2 - 21
RP2 - 22
RP2 - 23
RP2 - 24
RP2 - 25
RP2 - 26
GF
RP2 - 27
RAP
REMOTE
ANNUNCIATOR
PANEL
RPAV1 - 39,41
AV
4
4 4
RPAV1 - 40,42
AV
4
RPAV1 - 40,42
6
EF-1
RP5 - 10
6
EF-2
RP5 - 9
RP4 - 18,20,22
RP2 - 1
UH-1
11
RP1 - 40
EF-5
6
RP2 - 2
RP2 - 28 RP2 - 3
6
9
9
RTU-4
RTU-3
A A
A
A
A
A C1
C1 A
A
A
A
1 1 1
PRJ
3
6
3
3
2
5
5
EF-6
12
12
13
13
13
7
8
S-11
S-12
119
120
118
117
116
115
106
107
113
111
102
105
108
109
101
S-13
S-14
104
C-101
103
14
14
14 14
15
15
GF
GF
16
16
16
16
16
17
18
DWH-2
UH-3
UH-3
11
11
FB1
AV
RPAV6 - 3
N C1
MDP3-7
MDP3-6
RP7-14
RP7-31
RP7-8
GF
RP2 - 19
RP2 - 17
A
112
110A
5
5
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
2/3/2009 5:18:57 PM
C:\Drawings\Northview
Church\2007-06019-Electrical-Central-Local.rvt
E301
FIRST FLOOR -
POWER PLAN
New Worship
Center
Checker
Author
05-22-08
2007-06019
1/8" = 1'-0"
1
POWER & SYSTEMS - LEVEL-1 - NEW
WORK
GENERAL NOTES
A E.C. TO COORDINATE WITH A/V DRAWINGS:
AV201, AV211, AV202, AV212, AV203, AV213, AV204, AV205, AV215, AV251, AV252, AV253,
AV301, AV302
FOR BOX TYPE, MOUNTING HEIGHT, EXACT LOCATION FOR A/V DEVICES AND A/V
EQUIPMENT AND ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
A/V CONSULTANT: CRAIG COMPTON
PRO-SOUND
PH: 407-816-9400
E-MAIL: CCOMPTON@PROSOUND.NET
PLAN NOTES
1 PROVIDE RECEPTACLE WITH NEMA CONFIGURATION - 6-20R. COORDINATE EXACT
REQUIREMENTS WITH A/V CONSULTANT PRIOR TO ROUGH-IN.
2 CABLE TRAY - 24" WIDTH x 4" DEPTH - CABLOFIL OR EQUAL. COORDINATE MOUNTING
HEIGHT AND OTHER REQUIREMENTS WITH A/V CONSULTANT PRIOR TO ROUGH-IN.
3 WIREMOLD TRENCH DUCT - 12" WIDTH x 4" DEPTH. LID TO BE CUSTOM MADE.
COORDINATE WITH ARCHITECT / A/V CONSULTANT FOR REQUIREMENTS.
4 PROVIDE SINGLE GANG BOX WITH 3/4" CONDUIT TO "CONTROL EQUIPMENT RACK" IN
BOOTH. PROVIDE BLANK COVERPLATE. DATA OUTLET AND CABLING BY OTHERS.
COORDINATE EXACT LOCATION AND MOUNTING HEIGHT WITH LIGHTING CONSULTANT /
SYSTEM INTEGRATOR PRIOR TO ROUGH-IN.
5 PROVIDE DUCT MOUNTED SMOKE DETECTORS ON THE RETURN DUCT FOR ROOFTOP
UNITS AND INTERFACE WITH FACP TO SHUT-DOWN UNITS UPON ALARM. COORDINATE
LOCATION WITH HVAC DRAWINGS.
6 EXHAUST FAN. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
LOCATION, CONTROL, AND OTHER ELECTRICAL REQUIREMENTS WITH HVAC DRAWINGS
WITH HVAC DRAWINGS.
7 ELECTRICAL WATER HEATER. PROVIDE FUSED DISCONNECT. PROVIDE ELECTRICAL ROUGH-IN
AND FINAL CONNECTIONS PER REQUIREMENTS. COORDINATE LOCATION WITH PLUMBING
DRAWINGS.
8 DEDICATED OUTLET WITH 120V, 20A CIRCUIT FOR RECIRCULATING PUMP FOR WATER HEATER.
COORDINATE LOCATION WITH PLUMBING DRAWINGS.
9 PROVIDE GFI/WP RECEPTACLE AND VAPORPROOF APPLETON LIGHT FIXTURE FOR ROOFTOP
UNITS. COORDINATE LOCATION WITH UNIT. PROVIDE WEATHERPROOF LIGHT SWITCH FOR
LIGHT FIXTURE.
10 COIL PUMP. PROVIDE COMBINATION STARTER AND SIZE PER REQUIREMENTS.
COORDINATE OTHER ELECTRICAL REQUIREMENTS WITH HVAC DRAWINGS.
11 UNIT HEATER. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
LOCATION, MOUNTING HEIGHT, AND OTHER ELECTRICAL REQUIREMENTS WITH HVAC
DRAWINGS.
12 CIRCUIT # RPAV6-2 FEEDS POWER OUTLETS IN THESE BOXES.
13 CIRCUIT # RPAV6-1 FEEDS POWER OUTLETS IN THESE BOXES.
14 PROVIDE SINGLE GANG BOX WITH 3/4" CONDUIT TO THE SERVER ROOM. PROVIDE A BLANK
COVER PLATE. RJ45 OUTLET AND CAT5 CABLING BY OTHERS. OVERALL LENGTH SHOULD
NOT EXCEED 285'.
15 PROVIDE FUSED DISCONNECT TYPE NEMA 3R FOR ROOF TOP UNIT AND WIRE PER
REQUIREMENTS.
16 CONDUITS FROM MAIN LEVEL, BOOTH, 1ST BALCONY, AND 2ND BALCONY ARE TO BE ROUTED
THRU THE CHASE SPACE AVAILABLE AT THE BACK OF THE NEW WORSHIP CENTER NEAR THE
REST ROOMS, STAIRS, ETC., DOWN BELOW THE UNDERFLOOR DUCT WORK BELOW THE
SEATING IN THE MAIN LEVEL TO THE STAGE RACK LOCATION, RACK LOCATION IN THE PIT
LEVEL, ELECTRICAL PANELS, SWITCHBOARD "MDP3", ETC. E.C. TO COORDINATE WITH
PLUMBING AND HVAC CONTRACTORS PRIOR TO INSTALLING THE CONDUITS TO PREVENT
CONFLICTS BETWEEN THE TRADES.
17 PROVIDE (3) SPARE 3" CONDUITS FROM GATHERING CENTER TO THE STAGE RACK LOCATION
FOR FUTURE A/V REQUIREMENTS. COORDINATE WITH A/V CONSULTANT.
18 STAGE RIGGING SYSTEM - PROVIDE REQUIREMENTS PER PANEL SCHEDULE "RP3".
COORDINATE ALL REQUIREMENTS WITH SHEETS TR1.0 AND TR2.0 PRIOR TO ROUGH-IN.
A/V CONDUIT NOTES
A (1) 3/4"C.
B (3) 1"C.
C (1) 1"C.
D (1) 2"C.
E (1) 1-1/2"C.
F (3) 1-1/2"C.
G (2) 1"C.
H (2) 2"C.
J (2) 4"C.
K (3) 4"C.
L (3) 2"C.
M (1) 1/2"C.
N (2) 1-1/4"C.
O (2) 1-1/2"C.
A1 TO VBB.
B1 TO A/V RACKS 023.
C1 TO A/V RACKS AT STAGE LOCATION.
D1 TO SBB.
E1 TO A/V RACKS 023 COMPUTER FLOOR.
F1 TO VDB-501.
G1 TO ADB-501.
H1 TO CPB.
101 ENTRANCE LOBBY
102 VESTIBULE
103 WORSHIP CENTER
104 SOUND BOOTH
105 CHAIR STORAGE/CATERING
106 VESTIBULE
107 VESTIBULE
108 MEN'S RESTROOM
109 JANITOR ROOM
110 WOMEN'S RESTROOM
111 WOMEN'S RESTROOM
112 VESTIBULE
113 VESTIBULE
115 STORAGE
116 WORKSHOP
117 SIDE PLATFORM
118 DELIVERY
119 PLATFORM
120 SIDE PLATFORM
124 JANITOR ROOM
C-101 CORRIDOR
S-11 STAIR-1
S-12 STAIR-2
S-13 STAIR-3
S-14 STAIR-4
ROOM INDEX
J
J
J
J
J
J
J
L
L
J
J
J J
V
V
V
S H
S
F
F
F
L
L L
H
F
V
V
V
W
L
L
L
L
F
F
L
L
F
L
L
F
V V V
V V V V
L
UP
UP UP
F.E.C.
F.E.C.
F.E.C.
DN
UP
LP1 LP2 RP1 RP2
MDP3
WP/GF
WP/GF
TL2
TL2
TL2
TL2
TL2
AV
AV
AV
AV
AV
C1
VBB C1
SBB
GF
TV1
AV
C1 TL1
TV1
C1
RF
RF
GF
GF
2
1
GF
GF
C1
AV RF
AVRF
RF
RF
AV
AV
AV AV
RF
RF
AV
RF
AV
AV
C1
AV
CP
AV
RPAV1
RPAV2
S-02
RPAV1 - 1
RPAV1 - 2
RPAV1 - 3
RPAV1 - 4
RPAV1 - 5
RPAV1 - 6 RPAV1 - 7
RPAV1 - 8
A1
A
A A1
A
A
A B1
A
A A1
A
A A1
A
A A1
A A1
A A1
C B1
A B1
B B1
C B1
A A1
H
O
A B1
B
A D1
A D1
A
A
A
A
A
RPAV3
RPAV4
RPAV5
RPAV4-1-6
RPAV4-7-12
RPAV4-13-18
RPAV4-19-24
TL2
SBX
JB-102
F
F
G
FB1
AV
RPAV4 - 30
AV
AV
RPAV4 - 32
G
RPAV4-33-36
RPAV4-37-40
AV
AV
AV
RPAV1 - 36
EP
FACP
RPAV6
RP1 - 10
RP1 - 11
RPAV1 - 35
4
5
7
6
8
STAGE LIFT
RP1 - 12
RP1 - 13
RP1 - 14
RP1 - 15
RP1 - 16
RP1 - 17
RP1 - 18
RP1 - 19
RP1 - 20
RP1 - 21
RP1 - 22
RP1 - 23
RP1 - 24
RP1 - 25
RP1 - 26
RP1 - 27
RP1 - 29
RP1 - 30
RP1 - 31
RP1 - 32
RP1 - 33
RP1 - 34
RP1 - 35
RP1 - 36
RP1 - 37
RP1 - 38
SUMP PUMP
MDP3-13
MCP-1
MCP-2
RP3
RP4
3
VFD
13
CUH-1
RP2 - 4
RP2 - 5
RP2 - 6
RP2 - 7
RP2 - 8
RP2 - 9
RP2 - 10
GF
GF
RP2 - 11
RP2 - 13
R R R
RP5
CUH-2
13
RP2 - 12
CUH-3
13
CUH-4 13
GF
22
16
UH-2
RP5 - 8
17
AC-3
14
AC-4
14
RP4 - 7,9
RP4 - 8,10,12
RP4 - 11,13
12 CU-3
RP4 - 14,16
CU-4
12
RP4 - 15,17
DP3
A
A
GROUND
BAR
C1
AV
19
19
B
B
RPAV1 - 9
RPAV4 - 25
RPAV4 - 26
AV AV
AV
AV
AV
AV
RPAV4 - 27
AV
AV
RPAV4 - 28
AV
AV
RPAV4 - 29
AV
AV
18
23
20
21
RP5 - 15
DPL-1
033
S-01
001
019
020
021
022
024
C-005
027
025
029
S-03
C-007
003
002
C-001
004
005
006
007
008 009
010
011
015
016
018
014A
014
013
C-004
034
023
026
032
031
030
028
C-009
C-003
019A
017
018A
018
TELEPHONE
BACKBOARD
RP2 - 30
RP2 - 29
48"
48"
24
24
24
24
24 24
24
24
24
48"
48"
48"
48"
24
24
24
24
24
24
24
24
24 24
24
24
24
24
24
24
24
24
24
GF
RP2 - 31
GF
GF
GF
RP2 - 14
25
25
EP - 23,25,27
ATS #1
GENERATOR
REMOTE
ANNUNCIATOR
EF-7
CU-1
12
CU-2
12
RP4 - 19,21,23
RP4 - 24,26,28
DWH-1
26
RP6
RP7
RP6-8
VAV-5
VAV-4
RP6-13
RP6-7
RP6-2
VAV-2
VAV-3
RP6-1
VAV-1
RP6-14
RP6-19 VAV-6
VAV-7
RP6-20
VAV-8
RP6-25
VAV-9
RP6-26
VAV-10
VAV-11
RP6-31
VAV-12
RP6-32
VAV-13
RP7-1
VAV-14
RP7-2
VAV-15
RP7-7
RP7-20
RP-13
RP7-19
RP7-26
RP7-25
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
2/3/2009 4:29:12 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E300
PIT LEVEL - POWER
PLAN
New Worship
Center
Checker
Author
05-22-08
2007-06019
1/8" = 1'-0"
1
POWER & SYSTEMS - PIT LEVEL
GENERAL NOTES
A E.C. TO COORDINATE WITH A/V DRAWINGS:
AV201, AV211, AV202, AV212, AV203, AV213, AV204, AV205, AV215, AV251, AV252, AV253,
AV301, AV302
FOR BOX TYPE, MOUNTING HEIGHT, EXACT LOCATION FOR A/V DEVICES AND A/V
EQUIPMENT AND ANY ADDITIONAL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
A/V CONSULTANT: CRAIG COMPTON
PRO-SOUND
PH: 407-816-9400
E-MAIL: CCOMPTON@PROSOUND.NET
B PROVIDE 3/4"C. FROM EACH VOLUME CONTROL BOX ON PIT LEVEL TO ABOVE LAY-IN
CEILING. PROVIDE NYLON BUSHING AT CEILING END OF CONDUIT.
PLAN NOTES
1 DEDICATED RECEPTACLE FOR SUMP PUMP AT ELEVATOR PIT. COORDINATE LOCATION
WITH PUMP PRIOR TO ROUGH-IN.
2 PROVIDE GFCI RECEPTACLE, VAPOR-PROOF LIGHT FIXTURE WITH WIRE GUARD AND LIGHT
SWITCH PER CODE REQUIREMENTS NEARS STOP SWITCH. PROVIDE 26W 'PL' LAMP FOR THE
LIGHT FIXTURE.
3 STAGE LIFT - 208V, 3PH, 60HZ, 10HP DRIVE MOTOR. PROVIDE 240V, 3 POLE, 60A FUSED
DISCONNECT WITH 40A FUSES. PROVIDE ALSO (2) 120V, 20A DEDICATED CIRCUITS FOR LIFT
PLATFORM (MCP-2) AND STAGE LIFT (MCP-1). COORDINATE ALL ELECTRICAL REQUIREMENTS
WITH STAGE LIFT SUPPLIER PRIOR TO ROUGH-IN. SEE SHEET TP1.0 FOR STAGE LIFT
DETAILS AND ONE LINE DIAGRAM.
4 FIRE PUMP CONTROLLER.
5 FIRE PUMP AUTOMATIC TRANSFER SWITCH.
6 FIRE PUMP. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
REQUIREMENTS WITH PLUMBING DRAWINGS PRIOR TO ROUGH-IN. SEE DETAILS IN
SINGLE-LINE DIAGRAM ON SHEET E400. CONDUCTORS FOR THE FIRE PUMP INSIDE THE
BUILDING TO BE ENCASED IN MINIMUM 2" CONCRETE AND BE PROTECTED BY FIRE RATED
ASSEMBLY TO ACHIEVE MINIMUM FIRE RATING OF 2 HOURS DEDICATED TO FIRE PUMP
CIRCUITS. FIRE PUMP NEEDS TO BE INSTALLED PER NEC 695 REQUIREMENTS.
7 JOCKEY PUMP CONTROLLER.
8 JOCKEY PUMP. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
REQUIREMENTS WITH PLUMBING DRAWINGS.
9 NOTE OMITTED.
10 NOTE OMITTED.
11 NOTE OMITTED.
12 CONDENSING UNIT. PROVIDE NEMA 3R FUSED DISCONNECT. PROVIDE ELECTRICAL ROUGH-
IN AND FINAL CONNECTIONS. COORDINATE LOCATION AND OTHER ELECTRICAL
REQUIREMENTS WITH HVACDRAWINGS.
13 CABINET HEATER. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
LOCATION, MOUNTING ARRANGEMENT, AND OTHER ELECTRICAL REQUIREMENTS WITH HVAC
DRAWINGS PRIOR TO ROUGH-IN.
14 A/C UNIT. PROVIDE FUSED DISCONNECT ON UNIT. PROVIDE ELECTRICAL ROUGH-IN AND
HVAC DRAWINGS.
15 NOTE OMITTED.
16 UNIT HEATER. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
LOCATION, CONTROLS, AND OTHER ELECTRICAL REQUIREMENTS WITH HVAC DRAWINGS.
17 EXHAUST FAN. PROVIDE ELECTRICAL ROUGH-IN AND FINAL CONNECTIONS. COORDINATE
LOCATION, CONTROLS, AND OTHER ELECTRICAL REQUIREMENTS WITH HVAC DRAWINGS.
18 SUMP PUMP FOR STAGE LIFT. PROVIDE OUTLET AND DEDICATED 120V, 20A CIRCUIT.
COORDINATE LOCATION AND MOUNTING REQUIREMENTS WITH PLUMBING DRAWINGS.
19 PROVIDE WIREMOLD "RFB4" STEEL RECESSED FLOOR BOX WITH (2) RFB-DR INTERNAL
DUPLEX OUTLET BRACKETS AND (2) DTB-2-4TKO COMMUNICATION BRACKETS WITH
S38PPTCAL FLANGED PARTITION FEED COVER ASSEMBLIES. PROVIDE ALL NECESSARY
ACCESSORIES AND FITTINGS TO MAKE A COMPLETE UNIT.
20 ELECTRICAL WATER HEATER. PROVIDE FUSED DISCONNECT. PROVIDE ELECTRICAL
ROUGH-IN AND FINAL CONNECTIONS PER REQUIREMENTS. COORDINATE LOCATION WITH
PLUMBING DRAWINGS.
21 DEDICATED OUTLET WITH 120V, 20A CIRCUIT FOR RECIRCULATING PUMP FOR
WATER HEATER. COORDINATE LOCATION WITH PLUMBING DRAWINGS.
22 RECEPTACLE FOR WATER COOLER. COORDINATE OUTLET LOCATION WITH UNIT.
23 ISOLATION TRANSFORMER - 225KVA - 230V/3PH PRIMARY - 230V/3PH/4WIRE SECONDARY.
24 PROVIDE SINGLE GANG BOX WITH 3/4" CONDUIT TO THE SERVER ROOM. PROVIDE A BLANK
COVER PLATE. RJ45 OUTLET AND CAT5 CABLING BY OTHERS. OVERALL LENGTH
SHOULD NOT EXCEED 285'.
25 LIGHTING CONTROL PANELS - "LP1", "LP2", AND "EP" - LIGHTOLIER CONTROLS - LOW
VOLTAGE LIGHTING CONTROL PANEL - 48 CIRCUITS.
26 DISCONNECT SWITCH FOR FIRE PUMP. SEE SINGLE-LINE DIAGRAM ON SHEET E400 FOR MORE
INFORMATION.
A/V CONDUIT NOTES
A (1) 3/4"C.
B (3) 1"C.
C (1) 1"C.
D (1) 2"C.
E (1) 1-1/2"C.
F (3) 1-1/2"C.
G (2) 1"C.
H (2) 2"C.
J (2) 4"C.
K (3) 4"C.
L (3) 2"C.
M (1) 1/2"C.
N (2) 1-1/4"C.
O (2) 1-1/2"C.
A1 TO VBB.
B1 TO A/V RACKS 023.
C1 TO A/V RACKS AT STAGE LOCATION.
D1 TO SBB.
E1 TO A/V RACKS 023 COMPUTER FLOOR.
F1 TO VDB-501.
G1 TO ADB-501.
H1 TO CPB.
001 STORAGE ROOM
002 SERVER ROOM
003 CONFERENCE ROOM
004 OFFICE
005 BLUE SKY ROOM
006 OFFICE
007 OFFICE
008 OFFICE
009 OFFICE
010 OFFICE
011 OFFICE
013 RECEPTIONIST
014 WAIT/LOBBY
014A SUITE ENTRY
015 WORK STATIONS
016 WORK ROOM
017 CHANGING ROOM WAITING AREA
018 MEN'S CHANGING ROOM
018A MEN'S TOILET
019 WOMEN'S CHANGING ROOM
019A WOMEN'S TOILET
020 MECHANICAL ROOM
021 GREEN ROOM
022 VIDEO CONTROL
023 PRODUCTION RACKS
024 TAPE STORAGE
025 VESTIBULE
026 AUDIO CONTROL
027 VIDEO EDIT
028 STORAGE
029 RECORDING STUDIO
030 VOICE
031 DRUM
032 VESTIBULE
033 TRAP ROOM
034 FIRE PUMP ROOM
C-001 CORRIDOR
C-003 CORRIDOR
C-004 CORRIDOR
C-005 CORRIDOR
C-007 CORRIDOR
C-009 CORRIDOR
S-01 STAIR-1
S-02 STAIR-2
S-03 STAIR-3
ROOM INDEX
VERTICAL MOUNT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R. (46" M.H.).
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" M.H.) TWO-GANG
ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" M.H.).
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" M.H.).
JUNCTION BOX.
WIRE & CONDUIT IN OR BELOW FLOOR SLAB OR BELOW GRADE.
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; CAPITAL LETTER
DENOTES PANEL; NUMBER DENOTES CIRCUIT.
A-1&2
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.
H1
B1
V VALVE SUPERVISORY SWITCH.
W WATER FLOW SWITCH.
S DUCT MOUNTED SMOKE DETECTOR (S/SUPPLY, R/RETURN).
S/R
H CEILING MOUNTED HEAT DETECTOR.
S CEILING MOUNTED SMOKE DETECTOR.
F FIRE ALARM SENDING STATION (46" M.H.).
FIRE ALARM SIGNALING LIGHT (80" A.F.F.), (# WHEN SHOWN INDICATES CANDELA
RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED
15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
L
15
BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL
F FIRE ALARM HORN & SIGNAL LIGHT (80" A.F.F.), (# WHEN SHOWN INDICATES
15
BUSHED CONDUIT OUT ABOVE ACCESSIBLE CEILING.
"W" INDICATES 48" M.H., "P" INDICATES 48" M.H.). STUB AN EMPTY 3/4"
W TELEPHONE OUTLET (18" M.H. EXCEPT WHEN SUBSCRIPT LETTER IS SHOWN,
48" M.H.). SINGLE GANG OUTLET BOX WITH BLANK COVERPLATE. STUB AN
EMPTY 3/4" BUSHED CONDUIT OUT ABOVE ACCESSIBLE CEILING.
DATA OUTLET (18"M.H. EXCEPT WHEN SUBSCRIPT "W" IS SHOWN, MOUNT AT
CIRCUIT BREAKER PANEL, SURFACE MOUNTED.
CIRCUIT BREAKER PANEL, FLUSH MOUNTED.
ELECTRIC MOTOR.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
SCHEDULE NOTES:
1
2
3
4
PROVIDE MOUNTING AND DIRECTIONAL ARROWS PER PLAN. COORDINATE EGRESS PATH WITH ARCHITECTURAL DRAWINGS PRIOR TO ORDERING ANY FIXTURES.
MOUNTING HEIGHT 24'-0".
MOUNTING HEIGHT 12'-0".
SEE ALSO "GALLEGOS" LIGHTING SHEETS FOR LIGHT FIXTURE SCHEDULES.
SCHEDULE NOTES:
1 BUSSMANN POWER MODULE SWITCH. SIZE PER MANUFACTURER'S RECOMMENDATIONS.
2 FUSED DISCONNECT TO BE INSTALLED PER NEC-695 REQUIREMENTS.
3 CONTROL PANEL BY STAGE LIFT SUPPLIER. E.C. TO COORDINATE WITH SUPPLIER FOR ALL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
PROVIDE (2) DEDICATED 120V, 20A CKTS TO MCP-1 AND MCP-2. SEE SINGLE-LINE DIAGRAM IN SHEET # TP1.0 FOR DETAILS.
4 CONTROL PANEL FOR RIGGING SYSTEM BY SYSTEM SUPPLIER. E.C. TO COORDINATE FOR ALL ELECTRICAL REQUIREMENTS WITH RIGGING
SYSTEM SUPPLIER PRIOR TO ROUGH-IN. PROVIDE (10) 120V, 20A CIRCUITS PER MANUFACTURER'S REQUIREMENTS. SEE SINGLE-LINE
DIAGRAM IN SHEET # TR1.0 FOR DETAILS.
5 WEATHER PROOF DISCONNECT REQUIRED.
6 EC SHALL WIRE FAN THROUGH LINE VOLTAGE THERMOSTAT. HC SHALL FURNISH THERMOSTAT TO E.C.
A CONVEYANCE / CONDUIT INSTALLATION - SHALL MEET ALL ANSI/NFPA 70 (NATIONAL ELECTRICAL CODE) REQUIREMENTS.
B ALL CONDUCTORS WILL BE COPPER IN CONDUIT. INSULATION SHALL BE RATED FOR 600V.
C ALL WORK WILL BE DONE IN ACCORDANCE WITH THE NEC.
D ALL 20 AMP. 120 VOLT POWER CIRCUITS SHALL CONSIST OF #12 AWG CONDUCTORS UNLESS INDICATED OTHERWISE.
E CONDUITS OF DIFFERENT MATERIALS SHALL NOT BE MIXED INDISCRIMINATELY IN THE SAME SYSTEM.
F MAINTAIN 16" SPACING BETWEEN RECEPTACLES AND OTHER RECESSED OUTLETS EVEN WHEN
LOCATED ON OPPOSITE SIDES OF PARTITION TO ELIMINATE SOUND TRANSMISSION FROM ONE SPACE
TO THE OTHER. CENTER DEVICES WHERE APPLICABLE IN EACH WALL SECTION.
G NO SECTION OF A TELECOMMUNICATION CONDUIT SYSTEM SHALL BE LONGER THAN 100' OR CONTAIN
MORE THAN TWO 90° BENDS, OR 180° TOTAL OF BENDS AND ELEVATION CHANGES, BETWEEN PULL
POINTS OR PULL BOXES. FOR CONDUIT RUNS THAT TOTAL MORE THAN 100' IN LENGTH, INSERT PULL
BOXES SO THAT NO SEGMENT EXCEEDS THE 100' LIMIT.
H BENDS IN TELECOMMUNICATIONS CONDUITS SHALL BE LONG SWEEPS WITH A RADIUS OF 10 TIMES THE
INSIDE DIAMETER OF THE CONDUIT.
I ALL METALLIC RACEWAYS (I.E., CONDUITS AND CABLE TRAY SYSTEMS) SHALL BE CONNECTED TO THE
EXPANDED BUILDING GROUND LOOP, DIRECTLY TO THE COMMUNICATIONS RESOURCE ROOMS BUSBAR
OR VIA INTERCONNECTION OF CONVEYANCE ALREADY CONNECTED TO BUSBAR.
J FIRE STOPPING OF CONVEYANCE MUST MEET ALL APPLICABLE BUILDING CODE REQUIREMENTS.
K CONFIRM DATA AND COMMUNICATION DEVICE LOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.
L REFER TO ARCHITECTURAL SHEETS FOR EXACT LOCATION OF TACKBOARDS, MARKER BOARDS,
CASEWORK, DESKS, ETC.- CONFIRM LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR
TO ROUGH-IN.
M ALL EXIT SIGNAGE SHALL BE WIRED AHEAD OF LOCAL SWITCHING.
N REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LIGHTS, DIFFUSERS, ETC.
O ALL THEATRICAL LIGHITNG REQUIREMENTS SHALL BE COORDINATED WITH THE THEATRICAL LIGHTING
CONSULTANT PRIOR TO ANY WORK BEING PERFORMED.
P VERIFY EXACT LOCATION OF ALL LIGHTING FIXTURES WITH MECHANICAL DUCTS AND SPRINKLER PIPES
AND HEADS BEFORE ROUGH-IN TO PREVENT CONFLICTS.
Q EXACT LOCATION OF ALL DEVICES SERVING EQUIPMENT TO BE VERIFIED AT SITE WITH
ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.
R ALL EMPTY CONDUITS SHALL BE INSTALLED WITH PULL WIRE PER SPECIFICATIONS.
S ALL AUDIO / VIDEO DEVICES AND EQUIPMENT LOCATIONS AND REQUIREMENTS SHALL BE
COORDINATED WITH THE AUDIO / VIDEO CONTRACTOR PRIOR TO ANY WORKING BEING PERFORMED.
T ALL DEVICES INSTALLED IN / ON WALLS, SHALL BE DONE SO THAT THEY ARE AT EQUAL ELEVATIONS.
(I.E. DEVICES INSTALLED AT 18" M.H. SHALL ALL BE AT 18" M.H., ALL DEVICES INSTALLED AT 46" M.H.
SHALL BE INSTALLED AT 46" M.H.)
MOTOR
120V-1PH
CHARACTERISTICS
NAMEPLATE
CIRCUIT NO.
NUMBER
FLA
407/450
HP
KVA
OR
MOTOR
LOCATION
-
208V-3PH
208V-1PH
-
MAGNETIC
MANUAL
NEMA SIZE
LOCATION TYPE
AC DRIVES (VFD)
MOTOR O/L
BUILT-IN
2-SPEED
2-WINDING
MOTOR CONT.
NEAR MOTOR
SEE NOTE
TYPE
STARTER
FURNISHED BY
ROOM NUMBER
SEE NOTE
PANEL
EQUIP. CONT.
CENTER
STARTER
MANUAL
DISC. SWITCH
NEAR MOTOR
OR BREAKER
FEEDER SW.
RECEPTACLE
PANELBOARD
PANEL
EQUIP. CONT.
CENTER
MOTOR CONT.
DISCONNECT MEANS
LOCATION
FURNISHED BY
INTEGRAL WITH
MOTOR NO. BY E.C.
INTERLOCK WITH
FURNISHED BY
SEE NOTE
EQUIPMENT
STARTER
MANUAL AT
CONTROL
GRD. SIZE
WIRE SIZE
CONDUCTORS
NUMBER OF
SEE NOTE
SEE NOTE
CONDUIT SIZE
FEEDER
FIXTURE SYMBOL
CAT. NO.
G.E. LAMP
WATTS/LAMP
INCAN.
FLUOR.
FIXTURE VOLTAGE
H.I.D.
QUANTITY
LAMPS
CS-CEIL. SURFACE
BRONZE
C--CHAIN MTD.
STANDARD
SEE NOTE
ALUMINUM
BLACK
WHITE
UC-UNDER CAB.
TRIM COLOR
WM-WALL MTD.
SM-STEM MTD.
R--RECESSED
S--SURFACE
MOUNTING
SEE NOTE
DEPTH
LENGTH
WIDTH
DIAMETER OR
SIZE (IN.)
MANUFACTURER
& CATALOG NO.
OTHER ACCEPTABLE
MANUCATURES MEDIA
DIFFUSING
X1 LED INCLUDED 120 DUAL-LITE # LES SERIES MCPHILBEN, SURE-LITE
CLEAR MIRROR FACE W/RED
STENCIL LETTERS
4 PER PLAN 14.38 9.88 1.38 1
X2 LED 7 INCLUDED 120 DUAL-LITE # LT SERIES MCPHILBEN, SURE-LITE PER PLAN 14.38 9.88 1.38 1
RTU-1 MDP3-4 ROOF TOP UNIT #1
RTU-2 MDP3-5
RTU-3 MDP3-6 231/250
RTU-4 MDP3-7 204/250
ROOF
AC-1 (15A MOCP) AIR CONDITIONER 1 37KW
HC SEE MAIN
SWBD. "MDP3"
-
AC-2 (15A MOCP) AIR CONDITIONER 2 37KW -
CU-1 (40A MOCP) CONDENSING UNIT 1 20FLA 5
CU-2 (40A MOCP) CONDENSING UNIT 2 20FLA
EF-1 - EXHAUST FAN 1 (1/4HP) -
EF-2 - EXHAUST FAN 2 (1/4HP) -
EF-3 - EXHAUST FAN 3 (1/4HP) EC -
EF-4 - EXHAUST FAN 4 (1/6HP) EC -
EF-5 - EXHAUST FAN 5 (1/4HP) -
ELEV ELEVATOR 30HP EC
FP FIRE PUMP 30HP EC
1
2
SL STAGE LIFT 10HP 3
AC-3
AC-4
(45A MOCP)
(45A MOCP)
AIR CONDITIONER 3
AIR CONDITIONER 4
33.5FLA
33.5FLA
CU-3
CU-4
CONDENSING UNIT 3
CONDENSING UNIT 4
19.3FLA
19.3FLA
(40A MOCP)
(40A MOCP)
EF-6
EF-7
EXHAUST FAN 6
EXHAUST FAN 7
(1/4HP)
(1/6HP)
ROOF TOP UNIT #2
ROOF TOP UNIT #3
ROOF TOP UNIT #4
204/250
231/250
JP JOCKEY PUMP 3/4HP
AV
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" M.H.).
H1 1 250 T4 LAMP 120 GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL COOPER, KIRLIN
H2 1 500 T4 LAMP 120 COOPER, KIRLIN
H3 1 400 T4 LAMP 120 COOPER, KIRLIN
A 1 400 HPS 120 LSI # HFR5400HPS-120-F 2
B 1 125 MH 120 LSI # HFSH3175MH-120-F 3
GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL
GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL
DP2-1
DP2-2
DP2-4
DP2-8
DP2-9
DP2-19
DP2-21
DP2-22
DP2-23
EP-34
EP-35
EP-36
EP-37
EP-38
EP-39
EP-40
EP-41
EP-42
C 1 100 MH 120 GOTHAM # LAH-100M-12FW-FFL-120 COOPER, KIRLIN
WHITE FACE W/RED
STENCIL LETTERS
4
GENERAL LEGEND NOTES:
A
B
SEE A/V DRAWINGS FOR LEGEND ON A/V DEVICES.
SEE THEATRICAL LIGHTING DRAWINGS FOR LEGEND ON THEATRICAL LIGHTING FIXTURES.
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
EC
EC
PC
PC
HC
HC
HC
HC
EC
EC
EC
EC
EC
EC
EC
EC
HC
HC
HC
HC
HC
EC
EC
EC
EC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
EC
EC
EC
EC
EC
EC
EC
ROOF
ROOF
ROOF
PROJECTION ROOM
PROJECTION ROOM
A/V RACK
SERVER ROOM
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ELEV. EQUIP. ROOM
FIRE PUMP ROOM
MECHANICAL ROOM
JAN. CLOSET 109
6KW
6KW
DWH1
DWH2
DOM. WATER HEATER 1
DOM. WATER HEATER 2
3 12 12 .75
3 12 12 .75
2 6 8 1
2 6 8 1
3 10 10 .75
3 10 10 .75
3 8 10 .75
3 8 10 .75
5
5
5
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
3 1 6 1.5
3 1 6 1.5
3 12 12 .75
3 8 10 1.5
3 10 10 .75
3 10 10 .75
6
6
6
6
RTU-5 MDP3-8 ROOF TOP UNIT #5 231/250 ROOF HC HC HC
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
2/3/2009 4:29:02 PM
\\DAYDATA1\TEAMDATA\l600\2007-06019\DRAWINGS\2007-06019-Central.rvt
E001
LIGHTING FIXTURE
SCHEDULE, LEGEND &
INDEX OF DRAWINGS
New Worship
Center
Checker
Author
05-22-08
2007-06019
ELECTRICAL DRAWING INDEX
SHEET DESCRIPTION
E001 LIGHTING FIXTURE SCHEDULE, LEGEND & INDEX OF DRAWINGS
E002 SITE LIGHTING AND UTILITY PLAN
E003 ELECTRICAL DETAILS
E100 GATHERING CENTER - DEMO
E200 PIT LEVEL - LIGHTING PLAN
E201 FIRST FLOOR - LIGHTING PLAN
E202 BALCONY ONE - LIGHTING PLAN
E203 BALCONY TWO - LIGHTING PLAN
E205 CATWALK - NEW WORK - LIGHTING
E206 ROOF LIGHTING
E300 PIT LEVEL - POWER PLAN
E301 FIRST FLOOR - POWER PLAN
E301-A FIRST FLOOR - POWER PLAN
E302 BALCONY ONE - POWER PLAN
E302-A BALCONY ONE - POWER PLAN
E303 BALCONY TWO - POWER PLAN
E305 CATWALK-POWER PLAN
E400 SINGLE-LINE DISTRIBUTION DIAGRAM
E401 PANELBOARD SCHEDULES
E402 PANELBOARD SCHEDULES
E403 PANELBOARD SCHEDULES
SKE-1 FIRST FLOOR - POWER PLAN
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/29/2009 9:55:46 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H301
ROOFTOP EQUIPMENT
SECTIONS
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
F
B
Z1
P4 P5
P3
P2
P6 P7
P10
N1
N2
N3
M1
M2
M3
N 1.3 2.1
W
W3
W2
W1
P8
P9
2.2
4.2
4.1
P1
T4
T1
T2
T3
T5
S1
S2
S3
S4
S5
A1 A2
J
J1
J2
3.1
A.
ELEV.
S-33
301
S-33
300
S-33
S-34
T
RTU-1
32"D
32"D
32"D
32"D
G1 - 46 x 34
3130 CFM
(2)
16"D
16"D
16"D
16"D
16"D
16"D
16"D
16"D
16"D
16"D
16"D
16"D
14/14
14/14
18/30
18/20
30/18 DN
30/18 DN
28"D
28"D DN
3 32"D DN
2
C-D S
C-S
C-S
B-S
A-S
C-S
1 1705 CFM
1 1705 CFM
1 1705 CFM
1705 CFM 1
1705 CFM 1
1705 CFM 1
6120 CFM 1
6260 CFM 1
4
4
4
4 4
4
4
4
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/29/2009 9:55:45 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H231
SECOND BALCONY
LEVEL FLOOR PLAN -
HVAC
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
1/8" = 1'-0"
1
SECOND BALCONY LEVEL FLOOR PLAN -
HVAC
1 DUCTSOX LOCATED HIGH ABOVE WORSHIP CENTER AND BALCONY. CFM IS
INDICATED.
2 RETURN AIR DUCT OPEN TO CHASE.
3 SUPPLY AIR DUCT RISER IN CHASE SERVED BY RTU-1.
4 START DUCT SOX FABRIC DUCTWORK.
5 NOT USED.
NOTES
300 BALCONY-2
301 ELEVATOR VESTIBULE
S-33 STAIR-3
S-34 STAIR-4
ROOM INDEX
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E
F
B
Z2
Z3
Z1
Z4
P4 P5
P3
P2
P6
P7
P10
N1
N2
N3
M1
M2
M3
N
1.3 2.1
W
W3
W2
W1
P8
P9
2.2
4.2
N4 M4
4.1
P1
T4
T1
T2
T3
T5
S1
S2
S3
S4
S5
A1 A2
J
J1
J2
3.1
A.
EF-1
RTU-2
EF-3
EF-2
T
G1 - 36 x 8
A-D
AC-1 AC-2
U/C
EF-4
1
ELEV.
2
2
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
S-24
221
S-21 S-22
S-23
203
200
201
204
202
S-24
5
5
5
TYP.
6
7 7
8
A-D
G1 - 44 x 44
3780 CFM
(2)
1
H003
32"D UP
54/32 DN
28"D UP
S3 -
105 CFM
6"
(70)
30/18 UP
40/26 DN
30/18 UP
40/26 DN
RTU-5
RTU-1
50/34 DN
24"D
24"D
24"D
24"D
24"D
24"D
24"D
F1 - x
1500 CFM
36 12 F1 - x
1500 CFM
36 12
24/18
30/16
F1 - x
1500 CFM
F1 - x 36 12
1500 CFM
36 12
24/18
30/16
A2 - 6"
150 CFM
C-D S
3
2
A-D S
S1 -
135 CFM
8"
U/C U/C
U/C
U/C
4
4
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/29/2009 9:55:43 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H221
FIRST BALCONY
LEVEL FLOOR PLAN -
HVAC
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
1/8" = 1'-0"
1
FIRST BALCONY LEVEL FLOOR PLAN -
HVAC
1 SUPPLY DUCT FROM RTU-1 TO RISE IN CHASE TO SERVE BALCONY 1 AND
BALCONY 2.
2 SUPPLY MAIN TO RUN ABOVE FIRST BALCONY CEILING TO SERVE BALCONY 1 AND
ADJACENT ROOMS.
3 RETURN AIR DUCT SERVES RTU-1 - OPEN TO CHASE PLENUM.
4 SMOKE DETECTOR BY E.C.
5 LOCATE ANGULAR JOINTS IN THE CENTER SPACE BETWEEN THE BALCONY
STRUCTURAL BEAMS. COORDINATE WITH ARCHITECT PRIOR TO LAYOUT OF DUCT.
6 WALL LOUVER - REFER TO FAN SCHEDULE, DRAWING H001.
7 ROUTE REFRIGERANT PIPING TO CONDENSING UNIT ON ROOF. PROVIDE
INSULATION AND SUPPORTS PER MANUFACTURER RECOMMENDATIONS.
8 PROVIDE LINED SHEET METAL TRANSFER DUCT WITH A MINIMU OF 2 - 90 DEG.
ELBOWS. DUCT TO BE OPEN TO ELEVATOR MACHINE ROOM.
NOTES
200 BALCONY-1
201 VESTIBULE
202 CRYING ROOM
203 MACHINE ROOM
204 MEZZANINE
221 PROJECTION ROOM
S-21 STAIR-1
S-22 STAIR-2
S-23 STAIR-3
S-24 STAIR-4
ROOM INDEX
L3
P12
P15
X10
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E
F
B
Z2
Z3
Z1
Z4
P4 P5
P3
P2
P6
P7
P10
N1
N2
N3
M1
M2
M3
N
1.3 2.1
W
W3
W2
W1
P8
P9
2.2
4.2
N4 M4
4.1
P1
T4
T1
T2
T3
T5
S1
S2
S3
S4
S5
A1 A2
J
J1
J2
3.1
A.
50/24
ELEV.
UH-1
EF-5
EF-6
U/C
U/C
U/C
K1 - 24 x 12
300 CFM
(2)
J2 - 12 x 24
J1 - 12 x 24
J2 - 12 x 24
J1 - 12 x 24
K2 - 24 x 12
125 CFM
K2 - 24 x 12
235 CFM
K2 - 24 x 12
235 CFM
K2 - 24 x 12
225 CFM
RTU-4
H1 - 12 x 8
100 CFM
L
S
D
CU-1
AC-1
L
S
D
CU-2
AC-2
F2 - x
800 CFM
24 10
F2 - x
300 CFM
12 8
(2)
T
T
RTU-2
16"D
F2 - x
330 CFM
18 10
(3)
F2 - x
125 CFM
12 6
(2)
G1 - 12 x 6
(2)
K1 - 24 x 12
1000 CFM
CU-4
CU-3
EF-3
EF-2
EF-1
U/C
U/C
T
EF-3
A1 - 8"
200 CFM
S2 -
100 CFM
6"
S2 -
100 CFM
6"
S1 -
150 CFM
8" S1 -
150 CFM
8"
S1 -
200 CFM
8"
S1 -
200 CFM
8"
10"D
12/12 12/6
12/6
12/6
20/8 20/8
12/6
12/12
12/6
12
12
14 14
12
6
RTU-3
1
1
11
RTU-2
1
2
3
9 9
11
10 10
105
106
108
109
102
110
112
113
116
101
S-11
S-12
3
H003
4
H003
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
106
108
109
102
110
112
113
116
101
S-11
S-12
105
108
109
102
110
112
113
116
101
S-11
S-12
105
108
109
102
110
112
113
116
101
S-11
S-12
105
108
109
102
110
112
113
116
101
S-11
S-12
105
108
109
102
110
112
113
116
101
120
S-11
S-12
105
107
108
109
102
110
112
111
115
116
117
101
S-13
S-14
104
C-101
119
118
S-11
S-12
103
12
12
15
15
TYP.
T
RTU-3
16
14' - 8"
UH-3
T
UH-3
T
C-D
40/24
A-D
14' - 8"
A1 - 6"
75 CFM
12"D
G1 - 48 x 46
4450 CFM
(2)
G1 - 40 x 40
3750 CFM
(2)
G1 - 36 x 12
1315 CFM
40/24
48/24
28"D
44/28
40/26
G1 - 48 x 46
4450 CFM
(2)
20/34
30/18 UP
S3 -
105 CFM
6"
(72)
A-S
A-S
40/26
24"D
SA-3
16
7
2
3
2
3
RTU-1
RTU-5
1
1
16
SA-5
SA-6
SA-7
SA-8
4
5
U/C U/C
12/6
8/6
U/C
U/C
U/C
U/C
U/C
K2 - 24 x 12
125 CFM
B-D
B-D
B-D
B-D
T
RTU-5
1'-10"AFF
1'-10"AFF
J1 - 12 x 24
20/8
B-D
C-D
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/29/2009 11:44:49 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H211
FIRST LEVEL FLOOR
PLAN - HVAC
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
1/8" = 1'-0"
1
FIRST LEVEL FLOOR PLAN - HVAC
1 ROOFTOP UNIT WITH ROOF CURB ON ROOF. COORDINATE EXACT LOCATION
WITH STRUCTURE.
2 SUPPLY AIR DUCT RISES TO SERVE ROOFTOP UNIT ABOVE. COORDINATE RISER
LOCATION WITH STRUCTURE.
3 RETURN AIR DUCT RISES TO SERVE ROOFTOP UNIT ABOVE. COORDINATE
RISER LOCATION WITH STRUCTURE.
4 RETURN DUCT DROPS TO SERVE WORSHIP CENTER.
5 28"D SUPPLY DUCT RISES TO SERVE STAGE. REFER TO H221 AND H231 FOR
CONTINUATION.
6 SUPPLY DUCT TO RISE IN CHASE TO SERVE BALCONY 1 AND BALCONY 2.
7 RETURN DUCT RISES INTO CHASE ABOVE AND TERMINATE APPROX. 12" ABOVE
CHASE FLOOR AND TRANSITION TO SOUND ATTENUATOR (SA-4) - OPEN TO
CHASE PLENUM.
8 NOT USED.
9 HORIZONTAL INDOOR A/C UNIT - SUPPORT UNIT FROM WALL AND ROOF
STRUCTURE WITH TYPE J1 ISOLATORS. LOCATE IN CORNER OF PROJECTION
ROOM AT APPROX. 16'-0" A.F.F.
10 EXTEND 1" DRAIN LINE THRU WALL AND TURN DOWN TO ABOVE ROOF AND
TERMINATE WITH SPLASH BLOCK.
11 PROVIDE PITCH BOX THRU ROOF FOR REFRIGERANT PIPING TO DROP THRU
ROOF TO ABOVE PIT LEVEL CEILING. REFER TO DRAWING H201 FOR
CONTINUATION.
12 EXHAUST FAN ON ROOF WITH ROOF CURB. COORDINATE ROOF OPENING WITH
STRUCTURE.
13 PROVIDE RETURN AIR SOUND BOOT. REFER TO DETAIL, DRAWING H002.
14 EXISTING HOT WATER CABINET HEATER AND ASSOCIATED PIPING TO REMAIN.
15 LOCATE ANGULAR JOINTS IN THE CENTER SPACE BETWEEN THE BALCONY
STRUCTURAL BEAMS. COORDINATE WITH ARCHITECT PRIOR TO LAYOUT OF
DUCT.
16 SMOKE DETECTOR BY E.C.
NOTES
101 ENTRANCE LOBBY
102 VESTIBULE
103 WORSHIP CENTER
104 SOUND BOOTH
105 CHAIR STORAGE/CATERING
106 VESTIBULE
107 VESTIBULE
108 MEN'S RESTROOM
109 JANITOR ROOM
110 WOMEN'S RESTROOM
111 WOMEN'S RESTROOM
112 VESTIBULE
113 VESTIBULE
115 STORAGE
116 WORKSHOP
117 SIDE PLATFORM
118 DELIVERY
119 PLATFORM
120 SIDE PLATFORM
124 JANITOR
C-101 CORRIDOR
S-11 STAIR-1
S-12 STAIR-2
S-13 STAIR-3
S-14 STAIR-4
ROOM INDEX
275 CFM
A1 - 8"
200 CFM
(2)
F1 - x
50 CFM
10 6
A1 - 6"
75 CFM
A1 - 10"
300 CFM
(2)
A1 - 8"
200 CFM
A1 - 8"
180 CFM
A1 - 8"
180 CFM
A1 - 8"
180 CFM
A1 - 8"
180 CFM
CUH-3
CUH-4
4-1
4-3
4-2
4-4
4-5
4-6
4-11
4-14
4-15
10"D
18/14
16"D 14"D
14"D
14"D
24/16
48/20
38/16
28/16
10/10
10/10
10/10
8/8
8/8
12/10
K2 - 8 x 8
150 CFM
10/6
10/6
10/8
K2 - 8 x 8
150 CFM
4-7
8/8 12/10
AC-4
CU-4
L
S
CU-3
AC-3
S
L
D
4-9
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
9
ELEV.
T 4
U/C
A1 - 12"
425 CFM
(4)
A1 - 6"
70 CFM
T 2
T 3
T
1
T 6
U/C U/C
F1 - x
50 CFM
10 6
T
8
7 T
T 10
J1 - 12 x 24
4-8
F1 - x
330 CFM
24 8
(3)
18/12
12/12
T
12
T
13
T 11
T
14
T
15
T
T
T
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
J1 - 12 x 24
10"D
A1 - 8"
160 CFM
A1 - 8"
A1 - 6" 250 CFM
125 CFM
G1 - 24 x 12
(2)
UH-2
G1 - 24 x 12
(2)
T
1
1
1
1
1
1
1
1
1
1
1
1
1
11
7
8
9
10
SA-2
13
12
15
EF-6
17
T
EF-6
18
CU-2
EF-5
CU-1
22
22
23
24
EF-7
EP EP EP EP
26
25
A-D
003
002
C-001
004
005
006
007
008
009
010
011
015
016
018
S-02
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
031
030
028
C-009
C-003
019A
017
018A
003
002
C-001
004
006
007
008
009
010
011
015
016
018
S-02
014A
014
013
C-004
034
023
026
032
031
030
028
C-009
C-003
019A
017
018A
10"D
8"D
U/C
5
H003
27
5 T
A-D
7' - 0"
6' - 5 3/4"
7' - 0"
A-D
7' - 0"
27
A-D
U/C
10/10
18/16
14/14
31
31
16/12
31
12/12
31
12/12
31
12/12
31
12/12
31
30/14
J1 - 12 x 24
1
SA-1
B-S
J1 - 12 x 24
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/29/2009 9:55:30 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H201
PIT LEVEL FLOOR
PLAN - HVAC
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
1/8" = 1'-0"
1
PIT LEVEL FLOOR PLAN - HVAC
1 PROVIDE RETURN AIR SOUND BOOT. REFER TO DETAIL, DRAWING H002.
2 NOT USED.
3 NOT USED.
4 NOT USED.
5 NOT USED.
6 NOT USED.
7 40x26 SUPPLY DUCT RISES IN CHASE TO SERVE WORSHIP CENTER.
8 44x28 RETURN DUCT DROPS IN CHASE TO SERVE WORSHIP CENTER AND
TERMINATES WITH SOUND ATTENTUATOR SA-2 IN VERTICAL OPEN IN CHASE.
CHASE SERVES AS RETURN AIR PLENUM.
9 RETURN AIR DUCT RISES TO SERVE ROOFTOP UNIT (RTU-3) ABOVE.
COORDINATE RISER LOCATION WITH STRUCTURE.
10 SUPPLY AIR DUCT RISES TO SERVE ROOFTOP UNIT (RTU-3) ABOVE.
COORDINATE RISER LOCATION WITH STRUCTURE.
11 CONDENSING UNIT LOCATED ON ROOF TO SERVE INDOOR UNIT AC-3. ROUTE
REFRIGERANT PIPING ABOVE CEILING PER MANUFACTURER'S
RECOMMENDATIONS.
12 RETURN AIR DUCT RISES TO SERVE ROOFTOP UNIT (RTU-4) ABOVE.
COORDINATE RISER LOCATION WITH STRUCTURE.
13 SUPPLY AIR DUCT RISES TO SERVE ROOFTOP UNIT (RTU-4) ABOVE.
COORDINATE RISER LOCATION WITH STRUCTURE.
14 NOT USED.
15 RETURN AIR DUCT EXTENDED TO ABOVE CORRIDOR CEILING - OPEN TO PLENUM.
16 NOT USED.
17 EXHAUST FAN (EF-6) ON ROOF WITH ROOF CURB. COORDINATE ROOF OPENING
WITH STRUCTURE. TERMINATE DUCT WITH 0.25" MESH SCREEN AT 8" BELOW
ROOF DECK OPEN TO MECH. ROOM.
18 DDC PANEL.
19 NOT USED.
20 NOT USED.
21 NOT USED.
22 CONDENSING UNIT ON ROOF TO SERVE INDOOR A/C UNIT. ROUTE REFRIGERANT
PIPING PER MANUFACTURER'S RECOMMENDATIONS.
23 EXHAUST FAN (EF-5) ON ROOF WITH ROOF CURB. COORDINATE ROOF OPENING
WITH STRUCTURE FOR EXHAUST LOCATION.
24 CONDENSING UNIT LOCATED ON ROOF TO SERVE INDOOR UNIT AC-4. ROUTE
REFRIGERANT PIPING ABOVE CEILING PER MANUFACTURER'S
RECOMMENDATIONS.
25 0.75" DRAIN LINE DROPS IN WALL TO HUB DRAIN BELOW SINK.
26 0.75" DRAIN LINE EXTENDS INTO MECH. ROOM AND DROPS ALONG WALL TO
NEAREST FLOOR DRAIN.
27 SMOKE DETECTOR BY E.C.
28 NOT USED.
29 NOT USED.
30 NOT USED.
31 TRANSFER AIR DUCT ABOVE CEILING - SIZE LISTED - PROVIDE 90 DEG. ELBOW
AND TERMINATE WITH 90 DEG. ELBOW TURNED UP.
NOTES
001 STORAGE ROOM
002 SERVER ROOM
003 CONFERENCE ROOM
004 OFFICE
005 BLUE SKY ROOM
006 OFFICE
007 OFFICE
008 OFFICE
009 OFFICE
010 OFFICE
011 OFFICE
013 RECEPTIONIST
014 WAIT/LOBBY
014A SUITE ENTRY
015 WORK STATIONS
016 WORK ROOM
017 CHANGING ROOM WAITING AREA
018 MEN'S CHANGING ROOM
018A MEN'S TOILET
019 WOMEN'S CHANGING ROOM
019A WOMEN'S TOILET
020 MECHANICAL ROOM
021 GREEN ROOM
022 VIDEO CONTROL
023 PRODUCTION RACKS
024 TAPE STORAGE
025 VESTIBULE
026 AUDIO CONTROL
027 VIDEO EDIT
028 STORAGE
029 RECORDING STUDIO
030 VOICE
031 DRUM
032 VESTIBULE
033 TRAP ROOM
034 FIRE PUMP ROOM
C-001 CORRIDOR
C-003 CORRIDOR
C-004 CORRIDOR
C-005 CORRIDOR
C-007 CORRIDOR
C-009 CORRIDOR
S-01 STAIR-1
S-02 STAIR-2
S-03 STAIR-3
ROOM INDEX
S3 -
105 CFM
6"
(3)
24" D
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/4" = 1'-0"
1/29/2009 9:55:26 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H003
DETAILS
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
1/4" = 1'-0"
3
SECTION
1/4" = 1'-0"
4
SECTION
1/4" = 1'-0"
5
SECTION
1/4" = 1'-0"
1
SECTION
1/4" = 1'-0"
2
SECTION
SHUTOFF AND BALANCING VALVE
CHECK VALVE
D DRAIN PIPE.
DIRECTION OF FLOW
PITCH DOWN
EP EXPANSION TANK PIPE.
GENERAL NOTES
FANS
DUCT CONSTRUCTION & SEALING
INDEX OF DRAWINGS
AIR DISTRIBUTION DEVICES
AIR SUPPLY ROOFTOP UNITS
ROOM HEATING UNITS-ELECTRIC
COOLING SPLIT SYSTEM
COOLING-HEATING SPLIT SYSTEMS
SOUND ATTENUATORS
AIR CONTROL UNITS - ELECTRIC
SHEET DESCRIPTION
OUTDOOR UNIT INDOOR UNIT
GENERAL CONTRACTOR.
WALL LINTEL FOR WALL OPENING BY
WHERE REQUIRED FOR DECK SUPPORT AND
STEEL FRAMING AROUND ROOF OPENING.
PHASE
CONSIDERED MINIMUM.
MOTOR HORSEPOWERS LISTED ARE TO BE
300 & 301 MEASURED AT 5 FT. FOR P.R.V.'S.
SONES VALUES BASED ON A.M.C.A. BULLETINS
DESCRIPTION
UNIT
GENERAL NOTES
CONTRACTOR.
VERIFY SIZE & COORDINATE WITH GENERAL
ROOF & WALL OPENINGS ARE APPROXIMATE.
SERVICE
SONES
STATIC WHEEL MAX.
PRESS
CFM
DIA.
MOTOR
H.P. VOLT
REMARKS
APPROX. ROOF/
WALL OPG.
CLASS CLASS
STRUCT.
S.P. CON-
SHEET METAL DUCT; INTERIOR LINING; EXTERIOR INSULATION; ETC.
REFER TO SPECIFICATIONS FOR DUCT CONSTRUCTION OPTIONS:
DUCT SYSTEM
LEAKAGE CLASS FOR RECTANGULAR/ROUND METAL DUCT.
GENERAL NOTES
LEAKAGE
S.M.A.C.N.A. CLASS.
SEAL REMARKS
O.W.B.E.
FINISH KEY: "O.W.B.E."-OFF WHITE BAKED ENAMEL,
"E.C.L."-ETCHED CLEAR LACQUER OR ANODIZED.
SUPPLY AIR DIFFUSERS SHALL BE 4-WAY
BLOW UNLESS OTHERWISE NOTED ON DWGS.
DESCRIPTION
REFER TO SPECIFICATIONS FOR OTHER
ALL LAY-IN AIR DEVICES SHALL FIT IN
24"X24" LAY-IN CEILING SYSTEM.
SYMBOL
GENERAL NOTES
MANUFACTURERS.
TYPE MOUNTING MATERIAL
LAY-IN SURFACE STEEL
PROVIDE AUX. FRAMES FOR AIR DEVICES IN
PLASTER, GYPSUM BOARD, GLAZED TILE OR
CERAMIC TILE SURFACES.
FINISH CATALOG NUMBER SEE
ACCESSORIES NOTE
A1
A2
F1
G1
H1
J1
J2
K1
K2
S1
SUPPLY CLG. SQ. DIFFUSER
SUPPLY CLG. SQ. DIFFUSER
DOUBLE DEFLECTION SUPPLY REGISTER
RETURN GRILLE
RETURN/EXHAUST REGISTER
RETURN CLG. GRILLE
RETURN CLG. GRILLE
RETURN CLG. REGISTER
RETURN CLG. REGISTER
ALUM. PRICE
SCDA
SCDA
5200
90
530D
80
80
80D
80D
---
---
O.B.D.
---
O.B.D.
---
---
O.B.D.
O.B.D.
-
-
-
-
-
-
-
-
-
SUPPLY DUCT DOWNSTREAM OF
ROOFTOP UNITS (RTU-1,2,3,4,5)
SUPPLY DUCT DOWNSTREAM OF VAV
REHEAT BOXES
RETURN AIR DUCTWORK
TRANSFER AIR DUCTWORK
GENERAL/TOILET EXHAUST
ANY DUCTWORK NOT LISTED ABOVE
+3.0"
+1.0"
-1.0"
-1.0"
-1.0"
+1.0"
B
C
12/6
24/12
-
-
-
-
-
-
EF-1
EF-2
EF-3
EF-4
AUTOMATIC TEMP. CONTROLS SUBCONTRACTOR
A.T.C.
H HOT WATER SUPPLY PIPE
H HOT WATER RETURN PIPE
WATER MAKE-UP PIPE
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
L REFRIGERANT - LIQUID
S REFRIGERANT - SUCTION
HG REFRIGERANT - HOT GAS
"CONNECT TO EXISTING" SYMBOL - DUCTS OR PIPES
A ALL DUCTS AND PIPES TO BE RUN ABOVE CEILING. WHERE NO CEILINGS ARE
INSTALLED HOLD TIGHT TO STRUCTURE OR AS NOTED.
B THIS CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL THE PIPES, DUCTS,
UNITS, ETC. WITH ALL OTHER TRADES. PROVIDE ADJUSTMENTS OR OFF-SETS WHERE NECESSARY.
C COORDINATE THE LOCATION OF ALL AIR DEVICES LOCATED IN THE CEILING WITH THE
ARCHITECTS REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING PLAN.
D SPACE ABOVE CEILING SHALL BE USED AS A RETURN AIR PLENUM. (RTU-4)
E ALL EXPOSED DUCTWORK, PIPING, (VAV-REHEAT BOXES, AIR DEVICES SHALL BE
GALVANNEALED OR BONDERIZED COATING (PAINT GRIP) IN ORDER TO ACCEPT PAINT.
FINISH PAINTING WILL BE DONE BY OTHERS.
F BRANCH DUCTS FROM VAV-REHEAT BOXES AND AIR DEVICES SHALL BE SAME SIZE
INLET OF UNIT OR DEVICE UNLESS NOTED OTHERWISE.
G BRANCH PIPING TO VAV-REHEAT BOXES SHALL BE SAME SIZE INDICATED ON AIR
CONTROL UINIT SCHEDULE.
H COORDINATE EXPOSED DUCT LOCATIONS WITH ARCHITECTURAL DRAWINGS IN
ADDITION TO SPECIFIC HVAC PLAN NOTES.
I ALL SQUARE CORNER DUCT FITTINGS, EXCEPT RETURN AIR TRANSFER BOOTS SHALL
BE EQUIPPED WITH AIRFOIL TYPE TURNING VANES.
J ALL PENETRATIONS FOR ATC DEVICES SHALL BE REPAIRED AND REINSULATED.
K ATC COMPONENTS, POINTS, OR HARDWARE NOT SHOWN BUT REQUIRED TO ACHIEVE
THE SPECIFIED SEQUENCE OF CONTROL SHALL BE INCLUDED.
L THIS CONTRACTOR SHALL COORDINATE WITH AUDIO/VISUAL TECHNOLOGY DRAWINGS
FOR ALL CABLE TRAY, CONDUITS, PROJECTORS, ETC. LOCATED ABOVE CEILINGS
REQUIRING ACCESS SPACE.
M THIS CONTRACTOR SHALL COORDINATE WITH ALL TRADES PRIOR TO TRENCHING,
INSTALLATION OF UNDERFLOOR DUCTWORK, BACKFILL AND ALL RISERS THRU FLOOR
SLAB. REFER TO DETAILS AND SPECIFICATIONS.
N INSTALLATION OF DUCT SOX IN WORSHIP CENTER SHALL BE COORDINATED WITH ALL
TRADES AND DUCT SUPPORTS SHALL MEET MF'RS. RECOMMENDATIONS.
LEAV. AIR TEMP. (DB/WB)
ENT. AIR TEMP. (DB/WB)
DX-COOLING
TOTAL (MBH)
COOLANT
SENSIBLE (MBH)
ENTERING AIR TEMP.
STAGES
HEATING
COOLING CAPACITIES BASED ON 95 DEG. AMBIENT TEMP.
TOTAL S.P.- INCHES W.G.
TYPE
MOTOR (MIN. H.P.)
UNIT CONFIGURATION
SUPPLY FAN
GAS (CFH)
WHEEL TYPE
WHEEL DIA.
CFM (TOTAL)
UNIT NUMBER
AREA SERVED
UNIT LOCATION
GENERAL NOTES MOTOR - 208V - 3 PHASE UNLESS NOTED
OTHERWISE.
RTU-2
STAGE AREA
ROOF
SINGLE ZONE-VAV
8,750
4.9"/3.0"
27"
PLENUM
15 HP
YES
BALCONIES
ROOF
SINGLE ZONE-VAV
4.9"/3.0"
2 @ 27"
PLENUM
2 @ 15 HP
YES
RTU-1
PIT LEVEL ROOMS
ROOF
DISTRIBUTED-VAV
8,750
4.9"/3.0"
27"
PLENUM
15 HP
YES
RTU-4
427.0 196.0
60.0
128.0
362.0
490.0
80.0 / 67.0
56.1 / 55.7
TOTAL S.P.- INCHES W.G./E.S.P.
MOTOR (MIN. H.P.)
CFM (MIN./MAX.)
3 NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH NOTE IS SHOWN.
MINIMUM OUTSIDE AIR CFM
ISOLATOR ROOF CURB
4,000
POWER EXHAUST
4,000 / 14,000
2.5" / 1.5"
7.5
APPROX. CABINET DIMENSIONS
DESCRIPTION
NO.
UNIT
GENERAL NOTES
CFM
STAIRS
SERVICE
LENGTH
66"
DEPTH
9" 1,2
RECESS
-
HEIGHT
750 15 25"
NOTES
CUH-1
UH-1 UNIT HEATER - HORIZONTAL
CABINET UNIT HEATER
COST FOR INCREASE OR CHANGE OF ELECTRICAL SERVICE
MODEL NO. (OUTDOOR UNIT)
BASIS OF DESIGN (MFR. & NO.)
MOUNTING
VOLTAGE & PHASE
DESCRIPTION
UNIT NUMBER
MAX. FUSE SIZE (FLA / MOP)
CAPACITY
ENTERING AIR DB
REFRIGERANT (LIQUID & SUCTION)
REFRIGERANT LIQUID TYPE
KW / VOLTAGE
HUMIDIFIER
TYPE
SENSIBLE (MBH)
COOLING
REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE
DISCRIPTION
FAN
MOTOR HP
TOTAL (MBH)
UNIT CONFIGURATION
EXTERNAL S.P.
CFM
INDOOR UNIT NUMBER
AREA SERVED
GENERAL NOTES:
FOR EQUIPMENT SELECTED SHALL BE BORNE BY H.C.
BE VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER.
CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST
SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL.
ELECTRIC SERVICES FOR OUTDOOR AND INDOOR UNIT -
AC-3
SIZES, NUMBER OF PIPES AND CIRCUITS, ARRANGEMENT,
ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
INDOOR UNIT
ENTERING AIR WB
HTG.
KW / VOLTAGE
ELECTRIC REHEAT - (MBH)
MODEL NO. (INDOOR UNIT)
MAX. FUSE SIZE (FLA / MOP)
NOMINAL TONS
(APPROX. SIZES)
OUTDOOR UNIT
VOLTAGE
33.5 FLA / 45.0
MMD36E-A
CU-3
CONDENSING UNIT
3.0
19.3 FLA / 40.0
208 / 1
ROOF
PFC037A
3/8" & 7/8"
R134A
LIEBERT
37.2
28.5
80.0
67.0
16.0
4.7 / 208-1
208 / 1
AIR-COOLED
HORIZ. CONCEALED
1200
0.4"
SPLIT SYSTEM
1/2
A/V RACK
EF-5
POWER ROOF VENTILATOR TOILET ROOMS 1095
POWER ROOF VENTILATOR TOILET ROOMS 700
POWER ROOF VENTILATOR STORAGE ROOM
SIDEWALL EXHAUSTER
POWER ROOF VENTILATOR TOILET ROOMS
ELEVATOR EQUIP. ROOM
300
EF-6 POWER ROOF VENTILATOR MECHANICAL ROOM
ALUM. E.C.L.
0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,3
0.5 10" 10.0 1/4 115 1 14.5"x14.5" 1,3
0.375 12" 10.0 1/4 115 1 14.5"x14.5" 1,4
0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4
0.5 9" 8.0 1/4 115 1 14.5"x14.5" 1,3
0.5 12" 10.0 1/4 115 1 14.5"x14.5" 1,4
500
1000
1000
STAIRS
500 10 46" 9" 25" -
CUH-2 CABINET UNIT HEATER
CORRIDOR
CUH-3 CABINET UNIT HEATER -
UH-2 UNIT HEATER - HORIZONTAL
DELIVERY
FIRE PUMP ROOM
700 10 27.7 21" 6" 24" - -
700 7.5 20.8 - -
TONS - COOLING 40 30 30
14,000
VFD
MODULATING GAS HEAT
2
R-410A
MISC.
UNIT MOUNTED
YES
DISCONNECT SWITCH YES
CONTROL PANEL WITH
LON INTERFACE YES
ELECTRICAL - (MCA / MOP)
UNIT WEIGHTS
BASIS OF DESIGN
231.0/250.0
8,000 LBS.
YORK "SERIES 40"
ELECTRIC SERVICES FOR OUTDOOR UNIT AND INDOOR UNIT -
VERIFIED BY HVAC CONTRACTOR AND UNIT SUPPLIER. COST FOR
DX-COOLING
POWER CCT. (A.)
ENTERING AIR TEMP. (WB)
BASIS OF DESIGN (MFR.)
HOT GAS BY-PASS
(APPROXIMATE SIZES)
REFRIG. LIQUID & SUCTION
VOLTAGE & PHASE
POWER CIRCUIT (FLA / MOP)
ENTERING AIR TEMP.
HEATING OUTPUT (MBH)
KW
VOLT.
PIPE
RUNOUT
GPM
ENTERING AIR TEMP. (DB)
MOUNTING
NOMINAL TONS
DESCRIPTION
OUTSIDE AIR
LEAVING AIR TEMP.
HEATING
ELECTRIC
COIL
COIL
WATER
HOT
WATER
PHASE
STAGES
(MIN.)
AUTO
VALVE
ENTERING
IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
OF PIPES AND CIRCUITS, ARRANGEMENT, ETC. SHALL BE
AND ARE BASED ON SINGLE CIRCUITING. SIZING, NUMBER
REFRIGERANT PIPING - SIZES LISTED ARE APPROXIMATE
SENSIBLE (MBH)
VOLTAGE & PHASE
EXTERNAL S.P./TOTAL
UNIT CONFIGURATION
DESCRIPTION
FAN
TOTAL (MBH)
MOTOR HP
CFM
AREA SERVED
SYSTEM NUMBER
GENERAL NOTES:
SINGLE POWER SERVICE TO EACH UNIT BY ELECTRICAL
CONTRACTOR. ADEQUACY OF LISTED CIRCUIT SIZES MUST BE
INCREASE OR CHANGE OF ELECTRICAL SERVICE FOR
MENT SELECTED SHALL BE BORNE BY HVAC CONTRACTOR.
EQUIP-
AC-1
PROJECTION ROOM
CABINET C
7.5
AIR HANDLING
DRAW-THRU
HORIZONTAL
TONS - COOLING
AC-2
PROJECTION ROOM
CABINET C
7.5
AIR HANDLING
DRAW-THRU
HORIZONTAL
3,000
0.75" / 2.0"
2 HP
208/3
81.5
69.9
75.0
62.0
3,000
0.75" / 2.0"
2 HP
208/3
81.5
69.9
75.0
62.0
105.3
103 F
INDOOR UNIT FAN-ELECTRIC
8.0 FLA / 15.0 MOP / 208-3
0
105.3
103 F
0
CU-1 CU-2
7.5
20.0 / 40.0
208/3
ROOF
7/8" & 3/8"
YES
AAON
7/8" & 3/8"
YES
AAON
7.5
20.0 / 40.0
208/3
ROOF
208 3
208 3
AC-4
33.5 FLA / 45.0
MMD36E-A
CU-4
CONDENSING UNIT
3.0
19.3 FLA / 40.0
208 / 1
ROOF
PFC037A
3/8" & 7/8"
R134A
LIEBERT
37.2
28.5
80.0
67.0
16.0
4.7 / 208-1
208 / 1
AIR-COOLED
HORIZ. CONCEALED
1200
0.4"
SPLIT SYSTEM
1/2
SERVER ROOM
REFRIGERANT
R-410A R-410A
STAIRS/CORRIDOR
CUH-4 CABINET UNIT HEATER -
RTU-3
WORSHIP CENTER
ROOF
SINGLE ZONE-VAV
14,000
40
NO. SERVICE
UNIT
REMARKS
L W H
SIZE
CFM
S.P.
MAX
SA-1 RTU-3 SUPPLY
CEILING SLOT DIFFUSER-48" LONG-1 SLOT
S2 CEILING SLOT DIFFUSER-24" LONG-1 SLOT
60 40 26 8,900 0.25"
SA-2 RTU-3 RETURN 60 44 28 8,900 0.25"
70 F 70 F
LEAVING AIR TEMP. (DB / WB)
52.7 / 52.1 52.7 / 52.1
8.0 FLA / 15.0 MOP / 208-3
F2 SPIRAL DUCT GRILLE SDGE ---
TBDI-2100 INSUL. PLENUM
TBDI-2100 INSUL. PLENUM
-
-
EF-7 SIDEWALL EXHAUSTER FIRE PUMP ROOM 500 0.25 12" 8.0 1/6 115 1 14.5"x14.5" 2,4
REMARKS
1 PROVIDE FAN WITH 12" HIGH ROOF CURB AND DISCONNECT SWITCH.
2 PROVIDE FAN WITH WALL COLLAR, MOTOR SIDE GUARD, DAMPER AND TERMINATE WITH WALL LOUVER. LOUVER EQUAL TO GREENHECK MODEL "EDJ-430".
3 FAN SHALL BE CONTROLLED BY DDC. PROVIDE OCCUPIED/UNOCCUPIED SCHEDULE.
4 FAN SHALL BE CONTROLLED BY LINE VOLTAGE THERMOSTAT, FURNISHED BY H.C. AND INSTALLED BY E.C.
--
--
SA-3 RTU-1 SUPPLY 60 54 32 14,000 0.25"
--
--
SA-4 RTU-1 RETURN 60 50 34 14,000 0.25"
--
--
SA-5 RTU-2 SUPPLY 60 50 24 8,900 0.25"
SA-6 RTU-2 RETURN 60 48 24 8,900 0.25"
VFD'S FOR FANS ARE UNIT MOUNTED.
TOTAL (MBH) 427.0
T
THERMOMETER WITH THERMOWELL.
GAS DELIVERY PRESSURE - 7" W.C.
UH-3 UNIT HEATER - HORIZONTAL STORAGE AREA
700 10 27.7 208 3 - -
INLET
"C.V.R." CONSTANT VOLUME REHEAT.
"V.V.R." VARIABLE VOLUME REHEAT;
TYPES - "V.V." VARIABLE VOLUME;
UNIT
NO.
TYPE
DIA.
GENERAL NOTES
PHASE
REHEAT COILS CAPACITY BASED
ON WINTER MIN. CFM
KW
CFM
MIN.
WINTER
MAX. MIN.
SUMMER
REHEAT COIL
STAGES VOLT.
SEE
NOTE
ELEC. SERVICE TO THREE-PHASE UNITS TO
BE THREE-WIRE UNLESS NOTED
VERIFY/COORDINATE CABINET DIMENSIONS, MOUNTING
AND RECESS REQUIREMENTS WITH ARCHITECTURAL
DWGS. PRIOR TO ORDERING.
RECESSED UNITS TO HAVE FOUR(4) SIDE OVER
LAP UNLESS OTHERWISE NOTED
BY GEN. CONT'R.
LINTELS IN MASONRY WALLS FOR FULL &
SEMI-RECESSED UNIT WALL OPENING PROVIDED
THREE(3) PHASE COIL LOADS SHALL BE DIVIDED
EVENLY ACROSS EACH PHASE.
KW
ELEC. SERVICE
AMP VOLT PHASE
21" 6" 24"
21" 6" 24"
52.6 208 3
NOTES
1 TOP SUPPLY GRILLE; FRONT BOTTOM RETURN GRILLE
1,2
1,2
1,2
35.1 208 3
750 15 52.6 208 3 66" 9" 25"
750 15 52.6 208 3 66" 9" 25"
C 24/12
C 24/12
C 24/12
C 24/12
34.0 / SCR
208 / 3
34.0 / SCR
208 / 3
95.0 A. 95.0 A.
SA-7 RTU-5 SUPPLY 60 40 26 10,100 0.25"
SA-8 RTU-5 RETURN 60 44 28 10,100 0.25"
RTU-5
WORSHIP CENTER
ROOF
SINGLE ZONE-VAV
14,000
40
S3 CEILING SLOT DIFFUSER-24" LONG, TBDI-2100
INSUL. PLENUM -
2-SLOT, 1.5" SLOT WIDTH
--
--
4.9"/3.0"
2 @ 27"
PLENUM
2 @ 15 HP
YES
4.9"/3.0"
2 @ 27"
PLENUM
2 @ 15 HP
YES
UNIT DIMENSIONS 255"L x 92"W x 64"H
DEMAND VENTILATION ON SPACE
OR RET. AIR C02 LEVELS YES
UNIT
60.0
MODULATING GAS HEAT
2
60.0
MODULATING GAS HEAT
2
60.0
MODULATING GAS HEAT
2
60.0
MODULATING GAS HEAT
2
196.0 128.0
427.0
427.0
427.0
427.0
362.0
490.0
80.0 / 67.0
56.1 / 55.7
R-410A
362.0
490.0
80.0 / 67.0
56.1 / 55.7
R-410A
80.0 / 67.0
56.1 / 55.7
R-410A
80.0 / 67.0
56.1 / 55.7
R-410A
285.0
350.0
285.0
350.0
2,200 / 8,750
2.2" / 1.5"
7.5
4,000 / 14,000
2.5" / 1.5"
7.5
2,200 / 8,750
2.2" / 1.5"
7.5
4,000 / 14,000
2.5" / 1.5"
7.5
2,200
YES
YES
YES
204.0/250.0
6,000 LBS.
YORK "SERIES 40"
YES
4,000
YES
YES
YES
231.0/250.0
8,000 LBS.
YORK "SERIES 40"
255"L x 92"W x 64"H
YES
2,200
YES
YES
YES
204.0/250.0
6,000 LBS.
YORK "SERIES 40"
YES
4,000
YES
YES
YES
231.0/250.0
8,000 LBS.
YORK "SERIES 40"
255"L x 92"W x 64"H
YES
2 INTEGRAL THERMOSTAT. H001 LEGEND, GENERAL NOTES, AND SCHEDULES
DETAILS
H201 PIT LEVEL FLOOR PLAN
H211 FIRST LEVEL FLOOR PLAN
H221 FIRST LEVEL BALCONY FLOOR PLAN
H231 SECOND LEVEL BALCONY FLOOR PLAN
H301 ROOFTOP EQUIPMENT SECTIONS
H002 DETAILS
H003 DETAILS
H101 EXISTING FIRST LEVEL PLAN-DEMOLITION
4-1 V.V.R.
4-2
4-3
4-4
4-5
4-6
4-7
4-8
4-9
4-10
4-11
4-12
4-13
4-14
4-15
12" 1325 690 200 10 -
V.V.R. 12" 1275 640 195 10 -
V.V.R. 12" 1200 600 180 9 208 3 -
V.V.R. 14" 1770 885 270 13 208 3 -
V.V.R. 6" 350 175 55 3 3 -
V.V.R. 10" 915 460 140 7 3 -
V.V.R. 8" 450 300 70 6 3 -
V.V.R. 10" 1000 700 150 14 3 -
V.V.R. 6" 275 150 45 2 3 -
V.V.R. 8" 535 280 85 4 3 -
V.V.R. 6" 285 145 45 2 3 -
V.V.R. 200 100 30 1.5 3 -
V.V.R. 200 100 30 1.5 3 -
V.V.R. 380 190 60 3 3 -
V.V.R. 300 250 45 4 3 -
6"
6"
6"
6"
208
208
208
208
208
208
208
208
208
208
208
208 3
SCR 208 3
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
SCR
DATA PENDING RESUBMITTAL OF ROOFTOP SHOP DWGS
RETURN TRANSFER DUCTWORK/SOUND BOOTS
RETURN DUCT UPSTREAM OF ROOFTOP UNITS (RTU-1,2,3,4 & 5)
INTERIOR DESIGN AREA
SUPPLY DUCT DOWNSTREAM OF ROOFTOP UNITS (RTU-1,2,3,4 & 5)
LINED EXTERNAL
NOTES
INSULATION
SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-RECTANGULAR
DUCT
GENERAL/TOILET EXHAUST
SUPPLY DUCT DOWNSTREAM OF VAV REHEAT BOXES-ROUND
RETURN DUCTWORK
NOTES
1 REFER TO SPECIFICATIONS. 23 07 13
1
1
1
1
1
1
-3 DEG. DB WINTER
75 DEG. WB SUMMER
91 DEG. DB SUMMER
OUTSIDE DESIGN TEMPERATURES DESIGN ALTITUDE 792 FT.
ALL AREAS EXCEPT LISTED BELOW
INTERIOR DESIGN AREA
WINTER
DB % HUMIDITY DB
75 50
SUMMER
% HUMIDITY
N/A
ELEC./TECH. RM./IT CLOSETS 80 50 N/A N/A
WORSHIP CENTER
75 50 N/A
RECORDING STUDIO
75 50 N/A
VIDEO/AUDIO CONTROL
75 50 N/A
BALCONY 1&2
75 50 72 N/A
72
72
72
72
1
SUPPLY DUCTSOX 2
2 INSULATION FOR DUCTSOX TO MEET APPLICATION AND PER MF'R. RECOMMENDATION.
LEGEND
DUCT INSULATION SCHEDULE
HVAC DESIGN DATA
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/29/2009 11:44:41 AM
C:\Drawings\revit\Northview\2007-06019-Central-local.rvt
H001
LEGEND, GENERAL
NOTES, AND
SCHEDULES
New Worship
Center
ARC
CSR/GSS
05-22-08
2007-06019
B1
1.5"
1.5"
3"
1.5"
1.5"
2"
2"
3"
2"
1.5"
4"
4"
4"
4"
4"
4"
4"
4"
B2
PIT
WALL
BUILDING
CO
4"
4"
4"
F2
FD2
FD2
D1
4"
4"
3"
PIT
PIT
2"
2"
2"
1.5"
2"
MATCHLINE "A"
MATCHLINE "A"
4"
4"
4"
2"
PIT
PIT
PIT
PIT
PIT
PIT
PIT
2" HUB DRAIN
B1
CO
B2
A3
A4
B2
G1
F1
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
1.5"
2"
2"
3"
2"
3"
2"
2"
2"
3"
3"
3"
3"
2"
2"
2"
3"
4"
4"
2"
PIT
NOTE: PROVIDE P-TRAPS ON FIXTURES AND DRAINS AS
SPECIFIED ON DRAWINGS AND AS REQUIRED BY CODE.
4"
4"
CO
3" VTR
FD2
4"
4"
4"
2"
2"
1ST
CO
CO
CO
FD2
FD2
FD2
4"
4"
4"
4"
4"
FD1
3"
FD1
3"
C1
2"
1ST
1.5"
G1
CO
B2
B2
2"
2"
2"
2"
2"
FD1
FD1
4"
4"
4"
A1
A1 1.5"
1.5"
1.5"
1.5"
3"
3"
1ST
1ST
CO
4"
BUILDING
WALL
4"
3"
2"
2"
2"
4"
4"
4"
4"
4"
A2
A2
A2
A2
A2
A2
A2 4"
4"
4"
4"
1.5"
1.5"
2"
1.5"
1.5"
1.5"
1.5"
2"
2"
A1
B1
B1
B1
B1
B1
1ST
3"
2"
FD1
FD1
3"
3"
4"
4"
A2
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/28/2009 8:40:12 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P300
SOIL, WASTE AND
VENT DIAGRAM
New Worship
Center
TWN
ATM
05-22-08
2007-06019
F.E.C.
RD3
2,560 SQ.FT.
RD2
1,790 SQ.FT.
RD3
2,660 SQ.FT.
RD3
3,075 SQ.FT.
RD3
3,340 SQ.FT.
RD1
1,030 SQ.FT.
RD2
2,140 SQ.FT.
RD2
2,190 SQ.FT.
RD3
3,170 SQ.FT.
RD4
4,615 SQ.FT.
RD2
1,360 SQ.FT.
RD2
1,530 SQ.FT.
RD5
9,550 SQ.FT.
RD5
8,965 SQ.FT.
VTR
VTR
VTR
VTR
VTR
VTR
SCUPPER
SCUPPER
RD1
400 SQ.FT.
RD1
500 SQ.FT.
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/29/2009 10:58:15 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P206
ROOF PLAN
New Worship
Center
TWN
ATM
05-22-08
2007-06019
GENERAL NOTES
A REFER TO DETAILS, DIAGRAMS AND SCHEDULES FOR PIPING AND PIPE
SIZES NOT SHOWN.
B PC SHALL COORDINATE INSTALLATION CAREFULLY WITH ALL OTHER
TRADES.
NOTES
1 EXHAUST FAN BY HC.
2 ROOFTOP UNIT BY HC.
3 FLUES BY HC.
4 CONDENSING UNIT BY HC.
5 PROVIDE ROOF PENETRATION PIPE CURB.
6 PROVIDE VALVE, DIRT LEG, REGULATOR, UNION AND CONNECT TO UNIT.
REGULATOR SHALL BE SIZED FOR 2 PSI INLET PRESSURE AND 7" W.C.
DELIVERY.
1 ,035 S Q .TF .
R 5D
9 ,055 S Q .TF .
R 5D
8 ,569 S Q .TF .
V RT
V RT
V RT
V RT
V RT
V RT
S UC PP RE
S UC PP RE
R 1D
4 00 QS .TF .
R 1D
5 00 QS .TF .
DN
DN
UP
UP
DN
UP
UP
DN
F.E.C.
F.E.C.
F.E.C.
F.E.C.
DN
UP
DN
D N
R O F
R D
A C EC SS H TA HC
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
S UC PP RE
A C EC SS H TA HC
S M O K H E CTA SEH
S UC PP RE
1
1
1
2
2
1
4
4 1
1
2
2
3
4
R UT 53 2 HFC
R UT 2
5 33 HFC
2 R UT
5 33 HFC
2 R UT 22 35 HFC
F
.E .C
R 2 ,065 S 3D Q .TF .
R 2D
1 ,097 S Q .TF .
R 2 ,066 S 3D Q .TF .
R 3D
3 ,570 S Q .TF .
R 3D
3 ,043 S Q .TF .
R 1D
1 ,030 S Q .TF .
R 2D
2 ,041 S Q .TF .
R 2D
2 ,091 S Q .TF .
R 3D
3 ,071 S Q .TF .
R 4D
4 ,516 S Q .TF .
R 1 ,063 S 2D Q .TF .
R 2D
1 ,035 S Q .TF .
R 5D
9 ,055 S Q .TF .
R 5D
8 ,569 S Q .TF .
V RT
V RT
V RT
V RT
V RT
V RT
S UC PP RE
S UC PP RE
R 1D
4 00 QS .TF .
R 1D
5 00 QS .TF .
FDV FDV
4" FR 4" FR
FCE1
4" FR UP
2.5" FR DN
A2
A2
A2
A2
A2
A2
A2
B1
B1
B1
B2
B2 A1 A1
D1
B1
A2
B1
B1
C1
C2
C2
A2
4" FIRE
6" FR
FCE2
FCE2
FCE1
4" FR
VTR
D2
C2
FD1
VR
VR
VR
VR
FD1
3" STORM
6" DS
7,945 SQ.FT.
2" GAS UP
THRU ROOF
FD1 A1
5" STORM
VTR
VR
FIRE PUMP
TEST HEADER
FROM FDC
CHECK VALVE
4" FDC
RD1
1,030 SQ.FT.
8" DS
8" DS 11,735 SQ.FT.
11,105 SQ.FT.
FD2
1
2 7
WH
3,075 SQ.FT.
6" STORM
3" STORM
0.75" DCW
6" FIRE
0.75" DCW
3,340 SQ.FT.
0.5" DCW & DHW
1" DCW
0.75" DHWR
0.75" DHW
1" DCW
6" FIRE
2" SPRINKLER DRAIN
5
WH
5" DS
4,350 SQ.FT.
0.75" DCW
4" FIRE
0.75" DHWR
0.75" DHW
1" DCW
6" FIRE
4" DS
1,790 SQ.FT.
2.5" DCW FROM BELOW
4
4" STORM
RD3
5" STORM
5" DS
2,260 SQ.FT.
RD3
2,660 SQ.FT.
5" STORM
1.25" 4
1"
3 1.5"
9
8
6
1.25" DCW
1.5" DCW
1.25" DHW
0.75" DHWR
4" FIRE
1.5" DCW
10
10
10
VTR
VTR
13
2" 3
6
0.75" DCW
WH
2.5" DCW
1" DHW
0.75" DHWR
4" FIRE
1.5" DCW
2.5" DCW
1.25" DHW
0.75" DHWR
2,560 SQ.FT.
11
S
S
11
2" SD
G1
C2
RD1
500 SQ.FT.
3" STORM
B1
B1
FD1
CO
RD3
RD3
5" STORM
2" GAS
FROM BELOW
13
FD1 A1
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/28/2009 8:39:36 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P203
FIRST LEVEL - NEW
WORK
New Worship
Center
TWN
ATM
05-22-08
2007-06019
GENERAL NOTES
A ALL PIPING SHOWN IS LOCATED ABOVE SUSPENDED CEILINGS
(AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURAL
AREAS) UNLESS INDICATED OTHERWISE.
B REFER TO DETAILS, DIAGRAMS AND SCHEDULES FOR PIPING AND
PIPE SIZES NOT SHOWN.
C PC SHALL COORDINATE INSTALLATION CAREFULLY WITH ALL OTHER
TRADES.
D ANNULAR SPACE OF PIPE, CONDUIT AND OTHER SIMILAR
PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE
FIRESTOPPED. IN ADDITION,PENETRATIONS THRU 0-HOUR RATED
FLOORS SHALL ALSO BE FIRESTOPPED TO RETARD PASSAGE OF
FIRE AND SMOKE. REFER TO ARCHITECTURAL DRAWINGS FOR
CONSTRUCTION, LAYOUT AND FIRE RATINGS OF FLOORS, WALLS,
PARTITIONS AND OTHER BUILDING ELEMENTS.
E FINISHED FLOOR ELEVATION:
FIRST LEVEL - 817.64'
F PROVIDE INDIVIDUAL SHUT-OFF VALVES FOR EACH FIXTURE AND/OR
FOR EACH PIPE DROPPING TO EACH GROUP OF FIXTURES AS
REQURED.
NOTES
1 SPRINKLER FLOOR CONTROL VALVE BY FSC. SEE DETAIL A ON SHEET
P001.
2 TO SPRINKLERS SERVING FIRST FLOOR. COORDINATE LOCATIONS OF
ALL SPRINKLER PIPING AND DEVICES CAREFULLY WITH ALL OTHER
TRADES.
3 DCW PIPING TO DROP IN CHASE. PROVIDE FULL SIZE MANIFOLD AND
SERVE EACH WATER CLOSET FLUSH VALVE INDIVIDUALLY FROM
MANIFOLD.
4 DCW PIPING TO DROP IN CHASE. PROVIDE FULL SIZE MANIFOLD AND
SERVE EACH URINAL FLUSH VALVE INDIVIDUALLY FROM MANIFOLD.
5 SPRINKLER DRAIN PIPING TO DROP TO NEAR FLOOR LEVEL. PIPING
SHALL EXIT BUILDING 6" A.F.F. AND ELBOW DOWN. PROVIDE
CONCRETE SPLASHBLOCK BELOW OUTLET.
6 0.75" DCW AND DHW TO DROP IN CHASE AND SERVE LAVATORIES.
7 PIPING TO DROP IN CHASE AND SERVE HOSE BIBB MOUNTED 36" A.F.F.
PROVIDE TRAP PRIMER NEAR CEILING. DISCHARGE PIPING TO DROP IN
CHASE TO BELOW FLOOR AND SERVE ADJACENT FLOOR DRAIN.
8 PROVIDE FLOW CONTROLLER IN PLUMBING HOT WATER RETURN PIPING.
EACH FLOW CONTROLLER SHALL BE 0.75" SIZE AND FLOW 1 GPM EACH.
9 FIRST LEVEL DOMESTIC WATER HEATER. SEE DETAIL ON SHEET P002.
10 PROVIDE TRAP PRIMER FLUSH TUBE AS MANUFACTURED BY FLUSH VALVE
MANUFACTURER. DISCHARGE PIPING SHALL DROP IN CHASE TO BELOW
FLOOR AND SERVE ADJACENT FLOOR DRAIN.
11 RISER ISOLATION VALVE WITH SUPERVISORY ATTACHMENT BY FSC.
12 2" PUMPED DISCHAGE FROM ELEVATOR PIT SUMP PUMP TO RISE UP
TIGHT TO WALL AND DISCHARGE OVER MOP BASIN.
13 1.25" DCW AND 0.5" DHW TO DROP IN CHASE AND SERVE WATER CLOSET
AND LAVATORY.
0.5" DHW
1.5" DCW, 1" DHW
& 0.75" DHWR FROM BELOW
0.5" DHW
0.5" DCW
WH
0.75" DCW
0.75" DCW
1" DCW
1.25" DCW
1.5" DCW
0.75" DHW
0.75" DHWR 0.75" DHW
1" DHW
8" DS
11,105 SQ.FT.
8" STORM
VTR
1,530 SQ.FT. RD2
4" STORM 4" STORM
8"DS
25,735 SQ.FT.
8" DS
11,735 SQ.FT.
RD2 1,360 SQ.FT.
8" STORM
9
9
11
12
13
D3
13
8
FD2
FD2
FD2
6" FIRE
4" FIRE
6
7
S
FS
S
FD1 FD1
14
RD1
400 SQ.FT.
3" STORM
3" DS
400 SQ.FT.
2" GAS UP
2" GAS
1.5" GAS UP
THRU ROOF
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/28/2009 8:39:10 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P202
PIT LEVEL - NEW
WORK
New Worship
Center
TWN
ATM
05-22-08
2007-06019
1/8" = 1'-0"
1
PIT LEVEL - NEW WORK
GENERAL NOTES
A ALL PIPING SHOWN IS LOCATED ABOVE SUSPENDED CEILINGS
(AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURAL
AREAS) UNLESS INDICATED OTHERWISE.
B REFER TO DETAILS, DIAGRAMS AND SCHEDULES FOR PIPING AND PIPE
SIZES NOT SHOWN.
C PC SHALL COORDINATE INSTALLATION CAREFULLY WITH ALL OTHER
TRADES.
D ANNULAR SPACE OF PIPE, CONDUIT AND OTHER SIMILAR PENETRATIONS
OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION,
PENETRATIONS THRU 0-HOUR RATED FLOORS SHALL ALSO BE
FIRESTOPPED TO RETARD PASSAGE OF FIRE AND SMOKE. REFER TO
ARCHITECTURAL DRAWINGS FOR CONSTRUCTION, LAYOUT AND FIRE
RATINGS OF FLOORS, WALLS, PARTITIONS AND OTHER BUILDING
ELEMENTS.
E FINISHED FLOOR ELEVATION:
PIT LEVEL - 808.64'
F PROVIDE INDIVIDUAL SHUT-OFF VALVES FOR ALL BASEMENT FIXTURES.
NOTES
1 DOMESTIC WATER SERVICE. SEE DETAIL B ON SHEET P002
2 NOTE DELETED
3 PIT LEVEL DOMESTIC WATER HEATER. SEE DETAIL E ON SHEET
P002 FOR EQUIPMENT, DEVICES AND PIPE SIZING.
4 PROVIDE OVERSIZED SLEEVE THRU WALL FOR GAS PIPING
ENTERING BUILDING AND CAULK WEATHERTIGHT. SEE DETAIL B
ON SHEET P001.
5 PROVIDE ISOLATION VALVE FOR SPRINKLER AT BOTTOM OF
ELEVATOR PIT.
6 SPRINKLER FLOOR CONTROL VALVE BY FSC. SEE DETAIL A ON
SHEET P001.
7 TO SPRINKLERS SERVING PIT LEVEL. COORDINATE LOCATIONS
OF ALL SPRINKLER PIPING AND DEVICES CAREFULLY WITH ALL
OTHER TRADES.
8 30 HP, 750 GPM VERTICAL INLINE FIRE PUMP PACKAGE. SEE
DETAIL A ON SHEET P002.
9 RISER ISOLATION VALVE WITH SUPERVISORY SWITCH BY FSC.
10 PROVIDE VALVE, DIRT LEG, REGULATOR, UNION AND CONNECT TO
HVAC BOILER PROVIDED BY HC. REGULATOR SHALL BE SIZED
CAPABLE OF FLOWING 1,800 CFH WITH 2 PSI INLET PRESSURE
AND 7" W.C. OUTLET PRESSURE. GAS REGULATORS TO VENT TO
OUTSIDE.
11 PROVIDE STANDPIPE WITH 1.5" P-TRAP AND 6" OF 2" PIPING
UNDER COUNTER FOR HVAC CONDENSATE PIPING.
12 2" PUMPED DISCHARGE FROM SUMP PUMP AT BOTTOM OF LIFT
PIT TO RISE UP TIGHT TO WALL AND DISCHARGE OVER MOP
BASIN.
13 PROVIDE TRAP PRIMER WITH DISTRIBUTION UNIT. DISCHAGE PIPING
TO DROP TIGHT TO WALL TO UNDER FLOOR TO SERVE FLOOR
DRAINS.
14 PROVIDE TRAP PRIMER WITH DISTRIBUTION UNIT ABOVE CEILING.
DISCHARGE PIPIGN SHALL DROP CONCEALED IN WALL TO BELOW
FLOOR AND SERVE TOIELT ROOM FLOOR DRAINS.
1
4" WATER SERVICE
6" FIRE SERVICE
VR
1
CO
4" SANITARY
INV. 805.14'
VR
4
4" TO FDC
6" DS
4,615 SQ.FT.
6" ST
1
CO
8" ST
8,185 SQ.FT.
INV. 806.97'
8" ST
1.5" DCW
1" DHW
1.DHWR5" DCW 0.75"
1.5" DCW UP
4" DOMESTIC WATER
SERVICE UP
2.5" DCW
6" FIRE SERVICE UP
6" FROM FIRE PUMP
TEST
6" DS
1
CO
8" STORM
7,945 SQ.FT.
INV. 811.00'
1
CO 10" STORM
25,735 SQ.FT.
INV. 806.64'
INV. 815.00'
FD2
VR
4" SS
8" DS
10" STORM
VR
UP TO FPTH
CO
CO
CO CO
1.5" DCW
6
5
7
2" PUMPED
DISCHARGE
2" PUMPED
DISCHARGE
FD2
G1
HD B1
CO
FD2
FD2
D2
3" DS
400 SQ.FT.
3" STORM
FD1 FD1
B1
C1
B2
A1
G1
A1 FD1
B2 A1
FD1
4" SS
2" PUMPED
DISCHARGE
UP TO
MOP BASIN
C2
C2
FD1
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/8" = 1'-0"
1/28/2009 8:38:46 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P201
UNDERFLOOR PLAN
New Worship
Center
TWN
ATM
05-22-08
2007-06019
1/8" = 1'-0"
1
UNDERFLOOR PLAN
GENERAL NOTES
A ALL PIPING SHOWN IS LOCATED IN GRADE, BELOW FINISHED FLOOR
UNLESS INDICATED OTHERWISE.
B REFER TO DETAILS, DIAGRAMS AND SCHEDULES FOR PIPING AND PIPE
SIZES NOT SHOWN.
C PC SHALL COORDINATE INSTALLATION CAREFULLY WITH ALL OTHER
TRADES.
D FINSHED FLOOR ELEVATIONS:
PIT LEVEL - 808.64'
FIRST FLOOR - 817.64'
NOTES
1 PIPING CONTINUED BY SITE UTILITY CONTRACTOR.
2 PIPING TO DROP IN THIS AREA.
3 COORDINATE CLOSELY WITH HC LOCATIONS AND ELEVATIONS OF BELOW
FLOOR DUCTWORK AND PIPING. SANITARY AND DOMESTIC WATER PIPING
TO BE LOCATED BELOW DUCTWORK.
4 PIPING CONTINUED ON SITE PLAN, SHEET P003.
5 LIFT PIT SUMP PUMP. SEE DETAIL D, SHEET P002.
6 SUMP PUMP DISCHARGE TO RISE UP TIGHT TO WALL NEXT TO MOP BASIN,
ELBOW DOWN AND DISCHARGE INTO MOP BASIN.
7 ELEVATOR PIT SUMP PUMP. SEE DETAIL C, SHEET P002
WATER HEATER - 1ST LEVEL
NOTES
SCALE: NONE
D
P002
1
4
2
6
CO
2"
MOTOR - 0.33 HP., 115V., 1-PHASE.
3
PD
HEAVY DUTY STEEL COVER.
TO RECEPTACLE PROVIDED BY E.C.
SLEEVE PIPE THRU WALL AND PROVIDE
EXTEND PUMPED DISCHARGE OVER MOP BASIN.
INSTALL PIPING AS LOW AS POSSIBLE IN A MANNER
TO NOT INTERFERE WITH LIFT EQUIPMENT
CORD AND PLUG WITH UNIT. CONNECT
BASIN - 18"x22" POLYETHYLENE WITH PERFORATED
WATERTIGHT SEAL.
UNIT - ZOELLER NO M57.
LIFT PIT WALL.
5
4
2
3
PIT LEVEL
SUBMERSIBLE SUMP PUMP PACKAGE
CAPACITY - 34 GPM @ 10 FT. HD.
1
FS
FPTH
6"
6"
6"
F
WS
FLOOR DRAIN
0.75"
4"
1 4" WATER SERVICE.
2 STRAINER, WATTS #77F-D-FDA. PROVIDE BLOW-OFF
PIPING WITH VALVE. RUN TO FLOOR DRAIN.
3 CHECK VALVE.
4 RP TYPE BACKFLOW PREVENTER, WATTS #009 SERIES
1
P
5 DRAIN VALVE
5
6
3"
P
4"
2 4
3"
3
6 DOMESTIC WATER METER.
SCALE: NONE
1
3
SUBMERSIBLE SUMP PUMP PACKAGE WITH OIL SENSOR
HEAVY DUTY STEEL COVER.
2
3
MOTOR - 0.33 HP., 115V., 1-PHASE.
CAPACITY - 30 GPM @ 10 FT. HD.
TO RECEPTACLE PROVIDED BY EC.
CORD AND PLUG WITH UNIT. CONNECT
BASIN - 18" DIA x 30" DEEP POLYETHYLENE WITH PERFORATED
UNIT - ZOELLER NO N57 OR EQUAL BY WEIL OR HYDR-O-MATIC
6
5
SLEEVE PIPE THRU WALL AND PROVIDE
ELEVATOR PIT WALL.
2" TO MOP BASIN ON FIRST LEVEL.
4
1
6
4
WATERTIGHT SEAL.
INSTALL PIPING IN A MANNER TO NOT INTERFERE
WITH ELEVATOR CAR, RAILS, ETC.
2"
1.5"
CO PD
OIL SENSOR - ZOELLER NO 10-1527 PUMP SWITCH.
2
7 LOAD RELAY PROVIDED WITH OIL SENSOR.
7
5
5 6
B
P002
A
P002
C
P002
5
1
FLOOR DRAIN
8
2
FLOOR DRAIN
8 THERMAL EXPANSION TANK
5 4" HIGH CONCRETE BASE BY P.C.
AMTROL MODEL ST-5V
3 NOTE DELTED
6 VACUUM RELIEF VALVE.
7 ELECTRICAL CONNECTION BY E.C.
RECOVERY: 27 GPH AT 90 DEGREES F.
1 ELECTRIC WATER HEATER
6 KW, 208V, 3 PH
A.O. SMITH MODEL DSE-40 WITH GOLDENROD ELEMENTS, OR EQUAL
2 COMBINATION PRESSURE-TEMPERATURE
STORAGE: 40 GALLONS
RELIEF VALVE, AIR GAP DISCHARGE OVER
TEMPERATURE RISE
4 DRAIN VALVE . EXTEND TO FLOOR DRAIN.
7
E
SET THERMOSTAT AT 125 DEGREES.
DCW
DHWR
DHW
DCW
4
6
9 RECIRCULATION PUMP
CAPACITY: 2 GPM @ 5 FT HD
MOTOR: 0.4 AMP - 120 VOLT - 1 PHASE
BASIS OF DESIGN: B&G BRONZE FOX NBF9U/LW WITH AQ-3/4 AQUASTAT.
PROVIDE CORD AND PLUG AND PLUG INTO EC PROVIDED RECEPTACLE.
1.5" FROM WATER SERVICE
0.75"
1.5" 1"
0.75"
9
DCW
DHW
E
P002
5
1
8
2
8 THERMAL EXPANSION TANK
5 4" HIGH CONCRETE BASE BY P.C.
AMTROL MODEL ST-5V
6 VACUUM RELIEF VALVE.
7 ELECTRICAL CONNECTION BY E.C.
4 DRAIN VALVE . EXTEND TO MOP BASIN.
7
E
4
6
3
F
P002
DCW
DHW
DHWR
2.5"
0.75" 1.25"
DHW
DCW
DHWR
DHWR
DHWR
FPTH
FPTH
10 TRAP PRIMER WITH DISTRIBUTION UNIT. DISCHARGE PIPING TO DROP
TIGHT TO WALL, UNDER FLOOR TO SERVE FLOOR DRAINS.
10
7 TRAP PRIMER WITH DISTRIBUTION UNIT. DISCHARGE PIPING TO DROP
TIGHT TO WALL, UNDER FLOOR TO SERVE FLOOR DRAINS.
7
4"
T
T P
WATER DEPARTMENT TO PROVIDE AND INSTALL WATER METER.
PC TO PROVIDE WATER METER SPREAD. COORDINATE CLOSELY
ALL RULES AND REGULATIONS WITH WATER DEPARTMENT.
T
T P
MOP BASIN
RECOVERY: 27 GPH AT 90 DEGREES F.
1 ELECTRIC WATER HEATER
6 KW, 208V, 3 PH
A.O. SMITH MODEL DSE-40 WITH GOLDENROD ELEMENTS, OR EQUAL
2 COMBINATION PRESSURE-TEMPERATURE
STORAGE: 40 GALLONS
RELIEF VALVE, AIR GAP DISCHARGE OVER
TEMPERATURE RISE
SET THERMOSTAT AT 125 DEGREES.
3 RECIRCULATION PUMP
CAPACITY: 2 GPM @ 5 FT HD
MOTOR: 0.4 AMP - 120 VOLT - 1 PHASE
BASIS OF DESIGN: B&G BRONZE FOX NBF9U/LW WITH AQ-3/4 AQUASTAT.
PROVIDE CORD AND PLUG AND PLUG INTO EC PROVIDED RECEPTACLE.
9 FLOW CONTROLLER: PROVIDE UNIT SIZED FOR 1 GPM FLOW.
9
9
DCW
DCW
DHW
DHW
DCW
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
10.18.07
No. Description Date
1 SCHEMATIC DESIGN
2
3
4
5
6
7
8
11
DESIGN DEVELOPMENT 01.18.08
CD 50% 03.14.08
PERMIT SET 04.25.08
ADDENDUM #2 05.16.08
ADDENDUM #3 05.22.08
ADDENDUM #5 06.04.08
PERMIT SET 06.10.08
CONSTRUCTION SET 08.01.08
12 ASI6 12.23.08
13 PERMIT RE-SUBMISSION 1.28.09
1/28/2009 8:38:35 AM
C:\Drawings\revit\Northivew
Church\2007-06019-Central-LOCAL.rvt
P002
DETAILS
New Worship
Center
TWN
ATM
05-22-08
2007-06019
8"
GROUT GUARDRAIL POST 4'-0" DEEP
MINIMUM FROM TOP OF RETAINING WALL,
TYPICAL. FILL GAP BETWEEN POST AND
FINISH TOP FINISH BLOCK OF WALL WITH
COMPRESSIBLE FILLER AND SEALANT.
RETAINING WALL EDGE
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
As indicated
2/9/2009 11:22:38 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A508
STAIR DETAILS
NEW WORSHIP
CENTER
Checker
Author
01-21-2009
535-3581
A508 3/4" = 1'-0"
4 ALTERNATING TREAD DEVICE
4 PERMIT SET 04.25.08
A508 1/2" = 1'-0"
1 PIT ROOF ACCESS LADDER
7 ADDENDUM #4 05.30.08
9 ADDENDUM # 6 06.10.08
10 PERMIT SET 06.10.08
11 CONSTRUCTION SET 08.01.08
A508 1/2" = 1'-0"
2 PIT LEVEL ENTRY GUARDRAIL ELEVATION
18 ASI 007 01.21.09
18
P9
1
A504
SECOND
BALCONY
LEVEL
BELOW
CATWALK
LEVEL
ALTERNATING
TREAD DEVICE
TO ROOF
F4
F4
A3
1' - 11"
1' - 0"
7' - 0 1/16"
4' - 4"
1' - 2 3/4"
17 TREADS DN @ 11" = 14' - 8"
A523
20
18
A523
19
1' - 11"
1' - 0"
P
M
L
C
L4
L3
P12
P10
P9
1
A504
STAIR-3
S-23
F4
F4
A3
LEVEL 1
BELOW
INTERMEDIATE
LANDING ONE
FIRST
BALCONY
LEVEL
15 TREADS UP @ 11" = 13' - 9"
1' - 0"
1' - 0"
1' - 11"
9' - 0"
14 TREADS UP @ 11" = 12' - 10"
15 TREADS DN @ 11" = 13' - 9"
4' - 6" 4" 4' - 6"
A521
13
A12
P M
L
C
L4
ND
L3
P12
P10
M1
M2
P9
1
A504
STAIR-3
S-13
WOMENS'
REST RM.
111
F4
F4
F6
A3
PIT
LEVEL
BELOW
LEVEL 1
1' - 11"
1' - 0"
15 TREADS UP @ 11" = 13' - 9"
15 TREADS DN @ 11" = 13' - 9"
4' - 6" 4"
M
L
C
L4
ND
P12
A302
4
P10
M1
M2
P9
1
A504
?
?
S03
4' - 4"
PIT
LEVEL
15 TREADS UP @ 11" = 13' - 9"
C008
SEE C-SERIES
DRWGS. FOR
STAIR AND
WALL
1' - 11"
1' - 0"
1' - 0"
1' - 0"
5' - 0"
9 TREADS @ 1'-8" = 15' - 0"
1' - 5 1/8"
1' - 0"
1' - 0 1/2"
A508
2
AS-8
1
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
1/4" = 1'-0"
2/9/2009 11:21:27 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A503
STAIR PLANS AND
SECTIONS-STAIR 3
NEW WORSHIP
CENTER
Checker
Author
01-21-2009
535-3581
A503 1/4" = 1'-0"
4 STAIR-3 SECOND BALCONY LEVEL
A503 1/4" = 1'-0"
5 STAIR-3 CATWALK LEVEL
A503 1/4" = 1'-0"
3 STAIR-3 FIRST BALCONY LEVEL
A503 1/4" = 1'-0"
2 STAIR-3 LEVEL 1
A503 1/4" = 1'-0"
1 STAIR-3 PIT LEVEL
4 PERMIT SET 04.25.08
6 ADDENDUM #3 05.23.08
10 PERMIT SET 06.10.08
11 CONSTRUCTION SET 08.01.08
18
18 ASI 007 01.21.09
110A
PLATFORM
119
SIDE
PLATFORM
117
SIDE
PLATFORM
120
PROJECTION ROOM
STAIR-2
S-12
PIT
LIFT
Alternate A-1
CAPSTONE
OFF.
121 A
2
A412
MAIN LEVEL - 21 ROWS - 1100 SEATS
FIRST BALCONY - 8 ROWS - 530 SEATS
SECOND BALCONY - 6 ROWS - 400 SEATS
R 40' - 0"
1
A412
C101
1 5
H3
4
2.3 4
R 113' - 8 1/4"
R 123' - 0"
X9
X2
X3
X6
X7
X8
H2
4.6
4.6
H4
P
4.3
H5
4.8
M
L
L
L4
S
T
ND
U
H1.5
1.5
9' - 9 1/4"
MATCH LINE
2
3
S01C
S101E
S101F
S11A S12A
MATCH LINE
2
A413
2
A421
1
A421
8' - 3 3/4"
13' - 6 3/4" 11' - 8 3/8"
R 123' - 0"
4' - 8 1/4"
31.01
R 105' - 0 1/4"
124.49
15' - 0"
3
A421
2
A423
1
A422
H3.2
CHAIR
STORAGE/
CATERING
105
MENS'
RESTROOM
108
ENTRANCE
LOBBY
101
DIAPER
CHANGE
DIAPER
CHANGE
JAN. RM.
109
105
108
109
110A
111
X
2.0
3.8
3.8
H1
2.6
3.6
3.6
0.8
Y2
G
Z
67' - 8 3/4"
48' - 2 3/4"
L2
P12
R 112' - 9"
P15
X10
X4
X5
CAPSTONE
114
A521
1
A521
2
A521
3
A302 2
3
A302
6
A302
4
A302
1
A302
7
X1
0.4 2.4 2.8 3.3 4.4
Y
E F
B
Z2
Z3
Z1
Z4
P4 P5
P3
P2
P6
P7
P10
A502
2
A501
2
A511
4
STAIR-4
S-14 STAIR-3
S-13
N1
N2
N3
M1
M2
M3
N
1.3 2.1
W
W3
W2
W1
P8
P9
SOUND BOOTH
104
CORR.
C-101
116A
118C
A532
2
A532
1
STAIR-5
S-15
2.2 4.2
N4 M4
A505
1
A503
2
4.1
4.1
P1
T4
T2
T3
T5
S1
S2
S3
S4
S5
S11B
1
A426
1
A423
3
A423
2
A427
118B
CAPSTONE
STO.
121 B
121B
J
J1
J2
LEVEL-1
103
115A
115B
3.1
R 49' - 9"
3
A424
2
A422
1
A424
4
A424
2
A424
2
A426
9 12
11
11
9 12 9 12
12 9
12 9
11
11
11
10
2
20
ROOF AREA
SEE A251
21
17
22
TYP.
21 TYP.
21
11
21 TYP.
5
16
21
40' - 0"
13' - 2" 5' - 3 1/2"
3
1
12
4
1
21
TYP.
19
R 114' - 0 1/2"
R 123' - 0"
16
20 20
10
3 A111
A111 4
3
A426
F6
F4
UP
SLOPE 1:12
UP
SLOPE 1:12
UP
SLOPE 1:12
UP
SLOPE 1:12
UP
SLOPE 1:12
UP
SLOPE 1:12
-3' - 0"
-3' - 0"
0"
3' - 6"
0"
0"
-3' - 0"
0"
F4
F6
A3
F7
A3
A2
A3
A3
F3
F7
F3
F7
F3
F7
B2
F6
D1
F7
A3
A3
F6
A3
A2
D1
F6
F6
F6
A2
A1
F7 F7
F6
A3
F6
A3
A2
A3
A3
B2
F6
F4
F4
F2
B1
F2
F2
F4
F4
B1
B1
A1 F1 A2
F1
F1
A3
F1
F1 F1
F1
A2
B1
A3
A2
A2
A2
A2
D1
A1
A3
B1
A3
F3
DN
SLOPE 1:12
DN
SLOPE 1:12
DN
SLOPE 1:12
DN
SLOPE 1:12
DN
SLOPE 1:12
DN
SLOPE 1:12
17 17
82' - 5 13/16"
3' - 6"
8
15
A1
A3
F6
A2
A2
A2
TOILET
TOILET
F7 A3
A3
F6
9
A702
20
D1
F6
F6
F6 F6
6
Elevator
Alternate A-2
LOBBY RENOVATION
Alternate A-6
CAMERA
PLATFORM
3
A427
817' - 7 5/8"
23
1' - 8 1/2"
8' - 0" 4"
28' - 10"
5' - 5"
4' - 9"
19' - 5"
18' - 9"
13 13
A533
8
1
A508
24
24
24
24
24
A611
11
A612
1
A612
2
A.
A612
3
A612
8
16
A603
HOSE
CABINET
HOSE
CABINET
5' - 0"
5' - 0"
5' - 0"
5' - 0"
5' - 3"
DIAPER
CHANGE
DIAPER
CHANGE
SHELVES
BENCH
110B
WOMENS'
REST RM.
110B
26
14
14
F4
F4
F3
A508
2
AS-8
1
5' - 8"
9' - 10"
4' - 0"
ALIGN
11' - 0"
27
27
25
25
28
AS-10
1
1' - 5 1/16"
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
1/8" = 1'-0"
2/9/2009 11:20:36 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A211-A
FIRST FLOOR PLAN
NEW WORSHIP
CENTER
Checker
Author
01-21-2009
535-3581
1 SCHEMATIC DESIGN 10.18.07
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
GENERAL NOTES
KEYNOTES
A. ALL DIMENSIONS ARE TO FINISH FACE OF
CONSTRUCTION UNLESS NOTED OTHERWISE.
B. SEE PARTITION SCHEDULE ON SHEET A702 FOR
GRAPHIC AND NARRATIVE DESCRIPTION OF
THE PARTITION TAGGED AND
KEYNOTED ON THESE PLAN DRAWINGS.
C. SEE SHEET A000 FOR ADDITIONAL GENERAL
NOTES AND ABBREVIATED NOTES WHICH
MAY APPEAR ON ALL CONSTRUCTION PLANS
AND DRAWINGS.
D. PARTITION TYPES INDICATED ARE
CONTINUOUS TO A CORNER OR AN
INTERSECTING PARTITION, UNLESS
INDICATED OTHERWISE. WHERE
PARTITIONS OF DIFFERENT
THICKNESSES MEET, MAINTAIN A
FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS,
UNLESS NOTED OTHERWISE.
E. METAL STUD GAUGES SCHEDULED
ARE THE MINIMUM REQUIRED,
AND MAY BE INCREASED BY
SPECIFICATIONS TO ACCOMMODATE
LOADS, FINISHES, OR UNBRACED
CEILING HEIGHT LIMITS. DO NOT
CONSIDER CEILING SYSTEM(S) AS
A PARTITION BRACING ELEMENT.
F. EDGES OF GYPSUM BOARD LEFT
EXPOSED TO VIEW, OR ABUTTING
DISSIMILAR MATERIAL, IS TO BE
FINISHED WITH METAL "J" BEAD
TRIM AND COMPOUND UNLESS
NOTED OTHERWISE.
G. PARTITION SCHEDULE IS BASED ON
THE USE OF GYPSUM BOARD, BUT
FACING BOARD MAY VARY,
DEPENDENT ON FINAL FINISH
SCHEDULED FOR THAT PARTITION:
USE MOISTURE AND MOLD RESISTANT
BOARD WHERE SINKS OR
CERAMIC TILE ARE SCHEDULED.
H. ALL DOOR OPENINGS SHALL BE
6" FROM A PERPENDICULAR
PARTITION TO OUTSIDE FACE OF FRAME,
UNLESS NOTED OR
DETAILED OTHERWISE.
PLATFORM. CONSTRUCTION: 1/2" x 4'-0" x 8'-0" PAINTED
PLYRON FINISH FLOORING (STAGGERED JOINTS), SCREW
ATTACHED OVER 1" T&G PLYWOOD OR OSB SUBSTRATE,
GLUE ADHERE TO POURED CONCRETE DECK.
FACE OF PLATFORM (36” ABOVE SEATING FLOOR) REF. #
9/A7.02 FOR SECTION DETAIL OF FACE OF STAGE.
LIFT. ALTERNATE A-1. BASE BID WORK EXCLUDES
THE MECHANICAL LIFT. THE LIFT PLAFORM AREA WILL BE
FILLED WITH A PIT PLATFORM INFILL SYSTEM. SEE SHEET
TP1.1 FOR SCOPE OF BASE BID WORK. ALTERNATE A-1 BID TO
INCLUDE THE MECHANICAL LIFT IN LIEU OF THE INFILL
SYSTEM. SEE SHEET TP1.0 FOR THE SCOPE OF THIS WORK.
REAR PROJECTION SCREEN/CYC.
SLAB ON GRADE CONCRETE. ACID STAIN BLACK.
CAMERA PLATFORM. 1’ HIGH WOOD PLATFORM WITH
INTEGRAL STEP. FULLY CARPETED.
AISLE WAY, CARPETED. EDGE OF AISLEWAY INDICATED
WITH SOLID LINE. THEATER SEATING SHALL NOT
ENCROACH UPON THIS BOUNDARY LINE. AISLEWAY
EGRESS LIGHTING PROVIDED BY DOWNLIGHTING
INTEGRAL WITH THEATER SEATS.
NOT USED
FIXED SEATING AREA FLOORING FINISH: ACID STAINED
CONCRETE. REFER TO FINISH LEGEND AND
SPECIFICATIONS.
REAR AND FRONT CROSSAISLES. CARPETED.
EDGE OF CARPETING EXTENDED INTO SEATING ZONE
BY 2’-0". PROVIDE RUBBER TRANSITION STRIP, COLOR AS
SELECTED BY ARCHITECT.
FIXED AUDITORIUM SEATING. SEATING
MANUFACTURER TO PROVIDE LAYOUT WITH AVERAGE
CHAIR WIDTH OF 22” AND ROW SPACING OF 36”.
LAYOUT TO ACCOUNT FOR GOAL STATED ON
DRAWINGS FOR EACH LEVEL FOR A TOTAL PROJECTED
WORSHIP CENTER SEAT COUNT OF 2000 MIN. SEATING
LAYOUT SHOWN IS FOR INFORMATIONAL AND
CONCEPTUAL PURPOSES ONLY AND IS NOT INTENDED
AS THE FINAL LAYOUT. SEATING SUPPLIER AND
INSTALLERS SHALL COORDINATE EARLY IN THE
PROJECT WITH THE MECHANICAL CONTRACTOR TO
LOCATE THE UNDERFLOOR AIR DISTRIBUTION DEVICES.
HANDRAILING. 1 1/2:” DIA. WOOD ON WALL BRACKETS.
INSTALLED HEIGHT 36”.
MAIN CURTAIN, SEE THEATER DRAWINGS TR1.0.
OPENING IN PLATFORM TO PIT LEVEL BELOW.
PROVIDE SAFETY NETTING FOR FALL PROTECTION TO
FILL OPENING. NETTING TO BE INSTALLED IN MULTIPLE
(4 TO 6) SECTIONS WITH MEANS FOR ATTACHMENT AT
FULL PERIMETER OF OPENING. SUPPLIER TO
ENGINEER NETTING TO MEET LOADING
REQUIREMENTS. ANY STAIR DEVICES SHOWN ON ANY
DRAWINGS IN THIS AREA ARE NOT TO BE INCLUDED IN
THIS PROJECT AND WILL BE PORTABLE DEVICES
PROVIDED BY THE OWNER.
UTILITY SINK, SEE PLUMBING DRAWINGS. FLOOR
SINKS IN JANITOR CLOSETS TO RECEIVE CERAMIC TILE
ON TWO WALLS WITH S.S. MOP HOLDER.
PROJECTOR SHELVING FOR REAR PROJECTORS. SEE
STRUCTURAL DWGS.
NOT USED.
SIDE STAGE MONITOR POSITION. REFERENCE SHEET
AV253 FOR ADDITIONAL INFORMATION.
SYMBOL INDICATES ADA WHEELCHAIR ACCESSIBLE
SEATING, TYP. FACILITY WILL COMPLY WITH 1%
DESIGNATED SEATING TO COMPLY WITH IBC 1108.2.2.
21 SPACES FOR PROJECTED COUNT OF 2,030.
STRUCTURAL TUBE STEEL MEMBERS, TYP. SEE
STRUCTURAL DRAWINGS. STRUCTURAL MEMBERS
(COLUMNS, BEAMS, TRUSSES AND BRACING) SHOWN
EXPOSED TO VIEW ON PLANS TO BE PAINTED, FULL
HEIGHT UNLESS OTHERWISE INDICATED.
ALL WALLS, CEILINGS, STAIRS, STRUCTURE, CONDUITS,
AND HVAC DEVICES IN THIS AREA TO BE PAINTED
BLACK. FLOORS TO BE SEALED CONCRETE.
SOUND MIXING BOOTH WITH LOW GYPSUM BOARD
PARTITIONS. REF. SECTION 3/A5.10 AND AV253 FOR
ADDITIONAL INFORMATION. AREA TO BE FULLY
CARPETED. FINISH FLOOR ELEVATION = 2'-4" BELOW
MAIN LEVEL. PROVIDE 1:12 RAMPED CONCRETE
FLOOR TRANSITION AT BOOTH ENTRANCE FROM
AISLE TO WEST OF BOOTH.
3/4" PAINTED PLYWOOD OVER GYB. BD., 4'-0" HIGH FROM
FINISH FLOOR.
TRAFFIC BOLLARDS, REFERENCE 15/A6.03 FOR DETAIL.
FUTURE PODIUM OPENING.
SEGMENTED BUMPER RAIL.
42" HIGH GUARDRAIL WITH 1-1/2" DIA PAINTED STEEL TUBE.
MAXIMUM 21" BETWEEN HORIZONTAL AND VERTICAL TUBES.
1-1/2" DIA PAINTED STEEL TUBE HANDRAIL AT STAIR WITH 1'-0"
EXTENSION AT TOP AND BOTTOM OF STAIR.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
ADD STAGE LIFT. STAGE PLATFORM TO FILL IN AREA OF THE STAGE
LIFT IN BASE BID.
ADD ELEVATOR SYSTEM (CAB, MACHINE, CONTROLS, RAILS, PISTON).
HOISTWAY SHAFT, PIT, LOCKED HOISTWAY DOORS, CONDUITS AND
PATHWAYS AND ALL ROUGH-IN AND BACK-BOXES TO INSTALL
ELEVATOR AND HALL STATIONS AT A LATER DATE TO BE BASE BID.
DEDUCT ALL WORK IN EXISTING WORSHIP SPACE BELOW MATCH LINE
EXCEPT STAIR S-5 AND ANY CUTTING AND PATCHING REQUIRED FOR
NEW ADDITION.
Alternate A-2
Alternate A-6
Alternate A-1
5 ADDENDUM #2 05.16.08
23
6 ADDENDUM #3 05.23.08
A211-A 1/8" = 1'-0"
1 LEVEL-1 MAIN LEVEL-A
24
8 ADDENDUM #5 06.04.08
10 PERMIT SET 06.10.08
11 CONSTRUCTION SET 08.01.08
19
19
19
19
19
19
19
19
19
19
19
19
19
25
26
19
19
19
27
19
19
19
19
19
19
19
19
19 ASI 008 02.02.09
19
28
18
J
J1
J2
7 (12)
5 (98)
STAIR-1
S-01
CONF. RM.
003
STO. RM.
001
SERVER ROOM
002
WOMEN'S C.R.
019
BLUE SKY RM.
005
OFFICE
006
OFFICE
007
OFFICE
008
OFFICE
009 OFFICE
010 OFFICE
011
WORK
STATIONS
015 WORK RM.
016
WAIT/LOBBY
014
RECE.
013
GREEN ROOM
021
VIDEO
CONTROL
022
MECH. ROOM
020
FIRE PUMP
ROOM
034
TRAP ROOM
033 AUDIO
CONTROL
026
VIDEO EDIT
027
RECORDING
STUDIO
029
DRUM
031
VOICE
030
VESTIBULE
C008
OFFICE
004
CORR.
C-001
C.R. WAITING
AREA
017
MEN'S C.R.
018
GREEN RM.
ENTRY
021A
CORR.
C-007
CORR.
C-005
VEST.
025
CORR.
C-009
?
?
3.1
A.
NUMBER OF CALCULATED OCCUPANTS
PATH OF EGRESS
RECESSED FEC
HANDICAPPED ENTRY
1 HOUR RATED WALL
2 HOUR RATED WALL
APPLIED FIREPROOFING MATERIAL ON STEEL STRUCTURE IN
SHADED AREA
UL#X772 (1 HR. FIRE RATING FOR WIDE FLANGE COLUMNS)
UL#X771 (1 HR. FIRE RATING FOR TUBE COLUMNS)
UL#N782 (1 HR. FIRE RATING FOR BEAMS & MISC. STEEL)
100
BD
C2 CB
1 3 5
H3
2.3 4
X9
X2
X3
X6
X7
X8
H2
4.6
H4
P
4.3
H5
4.8
M
L
C
L4
Q
S
ND
U
H1.5
1.5
H3.2
X
2.0
3.8
H1
0.8 2.6 3.6
Y2
G
Z
L2
L3
P12
P15
X10
X4
X5
X1
0.4 2.4 2.8 3.3 4.4
Y
E F
B
Z2
Z3
Z1
Z4
P4 P5
P3
P2
P6 P7
P10
N1
N2
N3
M1
M2
M3
N
1.3 2.1
W
W3
W2
W1
P8
P9
2.2 4.2
N4
4.1
P1
T4
T1
T2
T3
T5
S1
S2
S3
S4
S5
WORKSHOP
116
STORAGE
115
SIDE
PLATFORM
117
DELIVERY
118
STAIR-1
S-11
CHAIR
STORAGE/
CATERING
105
VEST.
107
CORR.
C-101
SOUND BOOTH
104
VESTIBULE
102
VEST.
112
VEST.
113
VESTIBULE
106
J
J1
J2
1 (1100)
6 (2) 4 (97)
5 (2)
4 (162)
2 (325) 2 (525)
3 (96)
2 (346)
6 (2)
5 (3) 2 (105)
7 (1)
6 (3)
7 (7)
4 (284)
7 (1)
TWO HOUR SEPARATION
BETWEEN EXISTING ASSEMBLY
USE AND NEW A-3 ASSEMBLY USE
PLATFORM
119
LEVEL-1
103
3.1
A.
2/9/2009 11:18:01 AM
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
No. Description Date
As indicated
2/9/2009 11:18:13 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A001
LIFE SAFETY PIT
LEVEL AND MAIN
LEVEL
NEW WORSHIP
CENTER
Checker
Author
01-21-2009
535-3581
A. APPLICABLE CODES
1. INDIANA BUILDING CODE - 2003 (REFERENCES IBC 2000)
B. BUILDING CLASSIFICATIONS
1. USE GROUP: (IBC 303.1) - ASSEMBLY GROUP, A-3
2. SEPARATION OF OCCUPANCIES: (IBC T302.3.3) - 2 HOURS BETWEEN NEW A-3, ASSEMBLY AND EXISTING A-3, ASSEMBLY
3. CONSTRUCTION CLASSIFICATION: (IBC 603) - 2B, NON-COMBUSTIBLE, UNPROTECTED
C. HEIGHT AND AREA LIMITATIONS
1. ALLOWABLE HEIGHT: (IBC T503) - 2 STORIES/55'-0"
2. HEIGHT MODIFICATIONS: (IBC 504.2) - +2 STORIES/55'-0"
+1 STORY/20'-0" (WITH AUTOMATIC SPRINKLERS)
+3 STORIES/75'-0"
3. ALLOWABLE AREA: (IBC T503) - 9,500 GSF/STORY
4. AREA MODIFICATIONS (IBC 506) - +9,500 GSF ALLOWABLE AREA
+23,000 GSF (WITH AUTOMATIC SPRINKLERS)
+46,000 GSF/STORY
5. a. ACTUAL HEIGHT: 2 STORIES/65'-4"
b. ACTUAL GSF: 25,600 SF MAIN LEVEL/ 13,200 SF PIT LEVEL
D. FIRE RESISTANT RATINGS
1. STRUCTURAL FRAMING INCLUDING COLUMNS, GIRDERS, TRUSSES
SUPPORTING MORE THAN 1 FLOOR - 0 HR. (T601)
SUPPORTING ROOF ONLY - 0 HR. (T601)
2. EXTERIOR WALLS (LOADBEARING) - 0 HR. (T601)
(NONLOADBEARING) - 0 HR. (T601)
3. INTERIOR WALLS (LOADBEARING) - 0 HR. (T601)
(NONLOADBEARING) - 0 HR. (T601)
4. FLOORS - 0 HR. (T601)
5. ROOF - 0 HR. (T601)
6. SHAFTS/ELEVATOR HOISTWAY - 1 HR.< 4 STORIES (707.4)
(INCLUDING STRUCTURE)
UL NUMBERS FOR APPLIED FIREPROOFING
UL#X772 (1 HR. FIRE RATING FOR WIDE FLANGE COLUMNS)
UL#X771 (1 HR. FIRE RATING FOR TUBE COLUMNS)
UL#N782 (1 HR. FIRE RATING FOR BEAMS & MISC. STEEL)
- CLOSE OFF BOTTOM OF SHAFTS TO MAINTAIN SAME RATING AS WALLS
AND SUPPORTING STRUCTURE
7. CORRIDORS - 0 HR. (T1004.3.2.1)
8. EXIT PASSAGEWAY - 1 HR. (1005.3.3.2)
9. PERIMETER FIRE SEPARATION - 10" GAP MAXIMUM, UL #CW-D-2001
- 2.5" GAP MAXIMUM, UL #CW-S-1001
CALCULATION OF OCCUPANT LOAD DETERMINED PER OBC 1003.2.2.2 (THE NUMBER IN "()" IDENTIFIES THE NUMBER OF OCCUPANTS):
ACTUAL FIXED SEATING LAYOUT
ROOM AREA (NET S.F.) DIVIDED BY 5 (ASSEMBLY STANDING)
ROOM AREA (NET S.F.) DIVIDED BY 7 (ASSEMBLY CHAIRS)
ROOM AREA (NET S.F.) DIVIDED BY 15 (ASSEMBLY WITH TABLES AND CHAIRS AND STAGES/PLATFORM AREAS)
ROOM AREA (GROSS S.F.) DIVIDED BY 100 (BUSINESS AREA)
ROOM AREA (GROSS S.F.) DIVIDED BY 200 (KITCHEN)
ROOM AREA (GROSS S.F.) DIVIDED BY 300 (STORAGE AREA/MECHANICAL AREA)
A001 1/16" = 1'-0"
2 LIFE SAFETY LEVEL-0 PIT LEVEL
1
2
3
4
5
6
7
E. MEANS OF EGRESS
1. OCCUPANT LOAD:
PIT LEVEL - 110 OCCUPANTS (IBC T1003.2.2.2)
MAIN LEVEL - 3,061 OCCUPANTS (IBC T1003.2.2.2)
FIRST BALCONY - 543 OCCUPANTS (IBC T1003.2.2.2)
SECOND BALCONY - 400 OCCUPANTS (IBC T1003.2.2.2)
TOTAL - 4,114 OCCUPANTS
2. CAPACITY OF COMPONENTS:
a. NUMBER OF PEOPLE PER STAIR: 543 PEOPLE (FIRST BALCONY OCCUPANTS)/ 3 STAIRS = 181 PEOPLE / STAIR
b. REQUIRED WIDTH OF STAIR (44" MIN REQUIRED - IBC 1003.3.3.1): .2" x 181 (FIRST BALCONY OCCUPANTS) = 37"
c. REQUIRED WIDTH OF DOORS (32" MIN REQUIRED - IBC 1003.3.1.1):
.15" x 1,396 (NEW WORSHIP CENTER OCCUPANTS) = 210" (16 DOORS X 36" WIDE = 576" OUT OF WORSHIP CENTER)
.15" x 1,665 (EXISTING SANCTUARY OCCUPANTS) = 250"
.15" x 4,114 (TOTAL MAIN LEVEL OCCUPANTS) = 618" (19 DOORS X 36" WIDE = 684" OUT OF BUILDING)
3. LENGTH OF EXIT ACCESS TRAVEL: 250 L.F.. (IBC T1004.2.4) - FULLY SPRINKLERED
4. COMMON PATH OF TRAVEL: 75'-0" MAX. (IBC 1004.2.5) - FULLY SPRINKLERED
5. DEAD END LENGTH: 20'-0" MAX. (IBC 1004.3.2.3) - FULLY SPRINKLERED
F. PLUMBING FIXTURES REQUIREMENTS (IBC T2902.1)
1. OCCUPANT LOAD (NEW WORSHIP CENTER & ALL EXISTING LEVELS):
2,909 MALE OCCUPANTS
2,909 FEMALE OCCUPANTS
2. WATER CLOSETS:
2,909/150 = 20 WATER CLOSETS, MALE REQUIRED (36 WATER CLOSETS PROVIDED)
2,909/75 = 39 WATER CLOSETS, FEMALE REQUIRED (39 WATER CLOSETS PROVIDED)
3. LAVATORIES:
2,909/200 = 15 LAVATORIES, MALE REQUIRED (20 LAVATORIES PROVIDED)
2,909/200 = 15 LAVATORIES, FEMALE REQUIRED (24 LAVATORIES PROVIDED)
4. DRINKING FOUNTAINS:
5,818/1000 = 6 DRINKING FOUNTAINS (6 DRINKING FOUNTAINS PROVIDED)
4 PERMIT SET 04.25.08
A001 1/16" = 1'-0"
1 LIFE SAFETY LEVEL-1 MAIN LEVEL
5 ADDENDUM #2 05.16.08
6 ADDENDUM #3 05.23.08
10 PERMIT SET 06.10.08