HomeMy WebLinkAboutCorrespondenceNovember l2, 2003 Mr. Roger Ward Roger Ward Engineering, Inc. G2S5 North College Avenue, Suite 2 Indianapolis, IN 46220 RE: Project Review 2/1TumJY,QOd Jagua~r;~'~e_t~c.g~96?" Street Auto Park Dear Mr. Ward: W t ~. ~~7/rR~C~~~FO Opps a~~3 The City Engineer has reviewed the revised plans submitted for this project. We offer the following comments based upon her review: Sheet C101 -Title Sheet 1. Plans that contain the following on the Title Page will not be approved: "THESE DOCUMENTS ARE SUBJECT TO PERIODIC REVfSIONS BY ROGER WARD ENGINEERING. THE HOLDER IS RESPONSIBLE FOR VERIFYING THAT THESE DOCUMENTS ARE THE MOST CURRENT PR[OR TO USE." While this statement may apply to the contractor and his subs, this would not apply to the City of Carmel and we therefore require that you remove it from the plans. Sheet C101 -Site and Utility Plan 2. We require clarification/certification that the Floodway li mits and 100 Base Year Flood Elevation were actually revised (reference: "Floodway Per IDNR 1996 Study" and "Gripe's Floodway Limit" as noted on Sheet C101). We were made aware that during the designing of the CarMax site adjacent to the 96th S[ree[ Auto Park, it was discovered that work originally planned for the HH Gregg site on the south side of 96`" Street that would have caused modifications to the Floodway limits/zones was not done, and therefore, the floodway limits remained unchanged. As I understand it, one or more of the existing buildings within the Auto Park are at finished flood elevations that could be at risk of flooding. Certainly, during the flooding event of September I of this year, it became obvious that flood limits should accurately and clearly be defined for all future construction/projects. Although details of whether the floodway has or has not been formally and officially revised remain unclear, we would like to avoid any furtherance of this potential incorrect assumption, which directly affects the finished floor elevations of any buildings. 3. This office will not approve plans containing the Roger Ward Engineering, Inc. "disclaimer", as the plans as submitted should represent the design plans for a new project, and are required to be certifying to all information on such drawings. If certain information that was collected from previous surveys or plans cannot be checked, verified and/or certified, it should not be shown on these plans. 4. The slope of the storm sewer from structure 725 to end section 722 (calculated by this office at 0.15°l0) is very flat and long, making the pipe very difficult to clean, especially due to it's longer length. We anticipate problems with sedimentation building up within this segment of pipe potentially after every storm event for which the end section is submerged when the creek elevations rise. Can this slope be made steeper or the outlet pulled further from the flowline of the creek? (Although this pipe will be the development's responsibility, we do want to see that the drainage will function properly for the site.) 5. We require verification [hat the drainage plan for this portion of the 96`" Street Auto Park is in conformance with the original drainage plan prepared by Paul I Gripe Engineers and that this site does not require onsite detention. The city has been able to allow certain developments adjacent to the creek to utilize the `beat the peak" methodology, but we are not certain of the extent of developed area of this portion of the site with respect to [he drainage calculations and hydrographs peaks on the original submittal. ller:v:r~u:~r Or I:NGIyIi11ItlyG O~~e Civic S~uner, CAewtt. IV' 46032 Orr[cc 317571.2441 Fns 377.>77.2439 l]4,111. k~ccc,e~ci.uirmcl.in.us JAA'IES )3RAI\'ARD, MAPOR Mr. Roger Ward, P.E. November 12, 2003 Page 2 If you have questions, please contact Kate Weese, Mike McBride or me at 571-2441. Sincere/~ 'C'~ Dick Hill, Assistant Director Department of Engineering cc: M. Kate Weese, City Engineer Mike nt Cit En ineer ervtces John Duffy, Carmel Utilities Larry Heid, Tom Wood, Inc. S:\PROJREV03\TOM WOODIAGUAR#2Revised EROSION AND SEDIMENT CONTROL PLAN TECHNICAL REVIEW AND COMMENT Hamilton County Soil and Water Conservation District 1108 South 9t" Street, Noblesville IN 46060 Ph- 317-773-1432 or Email at PROJECT NAME: Tom-Wood Jaguar-L~aidxRovee Uo'lvo SUBMITTED BY: Mr. Larry Heid Tom Wood Inc 3003 E. 96th Street, Suite 201 Indianapolis, IN 46280 317-574-0143 REVIEWED BY: John B. South P.E. ~ ~-a 3 ~ P~~~s Mr. Roger Ward Roger Ward Engineering 6285 North college Avenue, Suite 2 Indianapolis, IN 46220 Certified Professional in Erosion and Sediment Control PLAN REVIEW DATE: Juue 17, 2003 Acreage: 12 ac LOCATION: West of Gray Road on the north side of 96th Street LEGAL DESCRIPTION: Sec. 8 TOWNSHIP: 17N RANGE: 4E CIVIL TOWNSHIP: Clay SOIL SURVEY MAP SHEET: 57 The technical review and comments are intended to evaluate the completeness of the erosion and sediment control plan for the The erosion and sediment control plan submitted was not reviewed for the adequacy of the engineering design. All included in the plan, as well as those recommended to the comments should be evaluated as to their feasibility by a qualified individual with structural practices designed by a qualified engineer. The plan has not been reviewed for local, state, or federal permits that may be required to proceed with this project. Additional information, including design calculations may be requested to.further evaluate the erosion and sediment control plan. The erosion and sediment control plan has been reviewed and it has been determined that the plan: X Satisfies the minimum requirements and intent of 3271AC 15-5 (Rule 5). Notification will be forwarded to the Indiana Department of Environmental Management. Proper implementation of the erosion and sediment control plan and inspections of the construction site by [he developer or a representative are necessary to minimize off-site sedimentation. The developer should be aware that unforeseen construction activities and weather conditions might affect the performance of a practice or the erosion and sediment control plan. The plan must be a flexible document, with provisions to modify or substitute practices as necessary. Revised 4 / 97 Cc: Carmel DOCS Ha. Co. Surveyor IDEM File a EROSION AND SEDIMENT CONTROL PLAN TECHNICAL REVIEW AND COMMENT Hamilton County Soil and Water Conservation District 1108 South 9`h Street, Noblesville IN 46060 Ph- 317-773-1432 or Email at .john-south(a,iaswcd.org PROJECT NAME: Tom Wood Jaguar Land Rover Volvo SUBMITTED BY: Mr. Larry Heid Tom Wood Inc 3003 E. 96`~ Street, Suite 201 Indianapolis, IN 46280 317-574-0143 REVIEWED BY: John B. South P.E. Mr. Roger Ward Roger Ward Engineering 6285 North college Avenue, Suite 2 Indianapolis, IN 46220 Certified Professional in Erosion and Sediment Control PLAN REVIEW DATE: June 17, 2003 Acreage: 12 ac LOCATION: West of Gray Road on the north side of 96`h Street LEGAL DESCRIPTION: Sec. 8 TOWNSHIP: 17N RANGE: 4E CIVIL TOWNSHIP: Clay SOIL SURVEY MAP SHEET: 57 The technical review and comments are intended to evaluate the completeness of the erosion and sediment contro/plan for the project. The erosion and sediment control plan submitted was not reviewed for the adequacy of the engineering design. All practices included in the plan, as well as those recommended in the comments should be evaluated as to their feasibility by a qualified individual with structural practices designed by a qualified engineer. The plan has not been reviewed for local, state, or federal permits that may be required to proceed with /his project. Additional information, including design calculations may be requested to further evaluate the erosion and sediment control plan. The erosion and sediment control plan has been reviewed and it has been determined that the plan: Satisfies the minimum requirements and intent of 327IAC IS-5 (Rule 5). Notification will be forwarded to the Indiana Department of Environmental Management. X Does not satisfy the minimum requirements and intent of 327IAC t5-5 (Rule 5); deficiencies are noted in the checklist and in the comments section. Deficiencies constitute potential violations of the rule and must be adequately addressed for compliance. The information necessary to satisfy the deficiencies must be submitted: Proper implementation of the erosion and sediment control plan and inspections of the construction site by the developer or a representative are necessary to minimize off-site sedimentation. The developer should be aware that unforeseen construction activities and weather conditions might affect the performance of a practice or the erosion and sediment control plan. The plan must be a flexible document, with provisions to mods or substitute practices as necessary. Revised 4 / 97 PROJECT: Tom Wood Jaguar Land Rover Volvo Page 2 of 3 ARE THE FOLLOWING ITEMS ADEQUATELY ADDRESSED ON THE PLANS ? (All Pans Must Include Appropriate Legends, Scales, and North Arrow) (items drat are Not Applicable to this Projec! are designated by NA) Yes No PROJECT INFORMATION X 1 A Project Location Map (Show project in relation to other areas of the county) x 1B Narrative Describing the Nature and Purpose of the Project x IC Location of Planned and/or Existing Roads, Utilities, Structures, Highways, etc. X ID Lot and/or Building Locations x I E Landuse of Adjacent Areas (Show the Entire Upstream Watershed and Adjacent Areas Within 500 Feet of the Property Lines) Yes No TOPOGRAPHIC, DRAINAGE, AND GENERAL SITE FEATURES X 2A Existing Vegetation (Identify and Delineate ) x 2B Location and Name of All Wetlands, Lakes and Water Courses On and Adjacent to the Site X 2C 100 Year Floodplains, Floodway Fringes, and Floodways (Note if None) X 2D Soils Information (/jhydric soils are present, it is the responsibility ojthe owner/developer to investigate the existence of wetlands and to obtain permits from the appropriate government agencies.) x 2E Existing and Planned Contours at an Interval Appropriate to Indicate Drainage Patterns X 2F Locations of Specific Points Where Stormwater Discharge Will Leave the Site x 2G Identify All Receiving Waters (/j Discharge is ro a Separate Municipal Storm Sewer, Identify the Name ojthe Municipal Operator and the Ultimate Receiving Water) x 2H Potential Areas Where Storm water May Enter Groundwater (Note if None) x 21 Location of Stormwater System (include Culverts, Storm Sewers, Channels, and Swoles) Yes No LAND DISTURBING ACTIVITIES x 3A Location and Approximate Dimensions of All Disturbed Areas [i. e., Construction Limits) (Areas Where Vegetative Cover Will Be Preserved Should be Clearly Designated} X 36 Soil Stockpiles and or Borrow Areas (Show Locations or Note if None) Yes No EROSION AND SEDIMENT CONTROL MEASURES x 4A Sequence of When Each Measure Will Be Implemented (Relative to Earth Disturbing Activities) x 4B Monitoring and Maintenance Guidelines for Each Measure X Comment 4C Perimeter Sediment Control M¢asares (Location, Construction Detail, Dimensions, and Specifications) X 4D Temporary Seeding (Specifications; Including Seed Mix, Fertilizer, Lime, and Mulch Rates) x 4E Temporary Erosion and Sediment Control Measures (Location, Construction Detail, Dimensions, and Specifications) x 4F Permanent Erosion and Sediment Control Measures (Location, Construction Detaid, Dimensions, and Speciftcations) X 4G Storm Drain Inlet Protection (Location, Construction Detail, Dimensions, and Speciftcalions) X 4H Stormwater Outlet Protection (Location, Construction Derail, Dimensions, and Specifications) X 41 Stable Construction Entranee (Location, Construction Detail, Dimensions, and Specifications) N/A 4J Erosion and Sediment Control on Individual Building Lots (Specifications) x 4K Permanent Seeding (Specifications; Including Seed Mix, Fertilizer, Lime, and Mulch Rates) Revised 4 / 97 EROSION AND SEDINLENT CONTROL PLAN TECHNICAL REVIEW COMMENTS PROJECT: Tom Wood Jaguar Land Rover Volvo Page 3 of 3 Note: Al[ erosion and sediment control measures shown on tJte plans and referenced in this review must meet the design criteria, standards, and specifications outlined in the 'Indiana Handbook for Erosion Control in Developing Areas "from the Indiatta Department of Natural Resources, Division of Soi[ Conservation or similar Guidance Documents. 3A. Show construction limits o the plan. 4A. Erosion and sediment control construction sequence needs to be unique for this site and should include all the construction period. See the "sample below. Note, while the building is being constructed, all disturbed areas should be protected with gravel, paving or grass. Please consider this in your sequence. 4C. Ditch checks are recommended in the Swale along the north P/L. Place one check dam downstream of the last riprap channel, at the floodway line and one 100' upstream of the floodway line. How will gully erosion in the creek bank be prevented from the southern most riprap outlet Swale? Draft Erosion and Sediment Control Sequence for Typical Commercial Construction Site 1. Before construction, evaluate, mark, and protect important trees and associated rooting zones, unique areas (e.g., wetlands) to be preserved, and vegetation suitable for filter strips 2. Install construction entrance 3. Install perimeter BMPs- list those for your site. Provide earthmoving instructions that compliment erosion and sediment control plan 4. Start mass earthwork Establish stone entrance and staging area Start building construction Finish grade and seed basins, slopes, swales and mounds Temporary seed all disturbed areas Install storm and sanitary sewer and utilities Install inlet protection as storm inlets are completed 7. Complete parking lots, roadways and curbs 8. Temporary seed all disturbed areas 9. Complete building 10. Final grade and landscaping 11. Complete final seeding Maintain all erosion and sediment control practices until all disturbed areas are permanently stabilized. Note: IDEM will be notified when the plan is approved. Cc: Carmel DOCS Ha. Co. Surveyor File =4y: ~, ROGER WARS -, ENGINEERING 1NC ORPO RATED 6285 N. College Avenue, Suite 2 Intlianapolis, IN 46220 • 317-251-1738 • Fax: 251-1923 May 28, 2003 Mr. John Dobosiewicz Department of Community Development ~, c ~v~ City of CarmE~ 'V~ One Civic Square Carmel, IN 46032 RE: Tom Woods'Jaguar„L~andeRovernVolvo~~ Dear Mr. Dobosiewicz: • CNIL ENGINEERS SITE DESIGNERS DEVELOPMENT CONSULTANT'S n ^ ,, r c, c,. ~.U~ This letter is in response to the TAC meeting minutes dated April 16, 2003, regarding your department's comments for the above project. The following describes the action taken for each of your comments. Scott Brewer: 1. The species of Crab Apples that are not recommended for the site are trees that already exist on site per the Dan Young approved Landscaping Plan by Paul I. Cripe. Tom Wood will replace the six dead Colorado Spruce trees currently on site, but will not replace any live trees with a different type of tree or shrub. 2. The note about "the root flare should be planted at grade level" has been added to both planting details on sheet L101. 3. The existing trees that are located on the existing forcemain are scheduled to be relocated in the same areas, but approximately 5 feet south of their current location. 4. The east property line buffering requirement has been addressed. 5. The landscaping that Tom Wood Volkswagen has been continued around the access street as you have requested. 6. There is no landscaping around the proposed building at this time. Laurence Lillig: 7. The headlight concern along the parking lot edge on the north side was addressed at the meeting, but was not shown in the meeting minutes. We all agreed that there is no headlight issue because there are no backyards for them to shine into. 8. The lights on the lighting plan are fully cut off, fully shielded as you have requested. Mike Balay, Steve Kern (Jaguar property manager), Larry Lawhead, Jim Rago (Light Source), and Mike Hollibaugh discussed the lighting issue by telephone on April 24, 2003. The lights are being corrected on the Lexus and Volkswagen sites to the agreed lights and they are going to be used on the Jaguar, Land Rover, Volvo site too. 9. The sign package was delivered to the DOCS on Friday April 18, 2003. John Dobosiewicz: 10. The owner and designers are aware that the Plan Commission is the final arbiter on the Landscape Plan. We believe that this Landscape Plan meets your requirements. 11. I believe the 96`h Street proposed ground sign for Lexus, Volvo, Jaguar, and Land Rover has been submitted to you. 12. Larry Lawhead for Tom Wood is addressing the Jaguar statue issue. 13. Mike Balay has addressed the color elevation you needed. 14. A videotape of the Land Rover Nature Trail was shown at the Plan Commission meeting. I believe that the Nature Trail is not a problem at this time. 15. Attached you will find a copy of the cover letters to John South, Jim Haag, and Dick Hill addressing all of their concerns. I hope the above addresses your concerns, and we look forward to receiving plan approvals for this project. Thank you. Sincerely, ROGER WARD ENGINEERING, INC. Mike Hoff Associate S:yobs\twi\001 \docs\DOC5052803. doc MAY. 2.20037 9:53AM:: ~BARNES~RNBURG 317-231-7433 •N0.997 P. 2 OFFICIAL MINUTES CARMEL CLAY TECHNICAL ADVISORY COMMITTEE April 16, 2003 REPRESENTING THE CITY OF CARMEL: Bill Akers, CCC Gary Hoyt, CFD Scott Brewer, DOCS Laurence Lillig, DOGS Steve Broermann, FiCHD Jerry Liston, HCSO Jon Dobosiewicz, DOCS Chuck Shupperd, 'Vectren Energy John Du$y, CU John South, HCS~V Attachuxents: received bye-mail; Andy l{em, CTRWD Received by mail; S.J. Prater, Panhandle Eastern Pipeline Company Page: 2. THE TRAIIS AT HAYDEN RL1V (PR1I~IARY PLA17 Page: 4. LONG BRANCH ESTATES, SECTION 3 (SECONDARY PLAT AND CONSTRUCTION PLANS) Page: 6. C SPECIALTIES, INC. (STYE PLAN REVIEW) Page: 9. BRAVSON PROPERTIES, LLC (DEVELOPMENT PLAN) Page: 12. MERIDIAN NORTH MEDICAL (PRIlyARY AND SECONDARY PLaT) Page: 14. BALLANTRAE SUBDIVISION (PRiVi IARY PLAT) -REVISED PLAN Page: 16. SADDLE CREETC, SECTION 12 (SECONDARX PLAT A:~Ib CONSTRUCTION PLANS) Page: 17. TOM WOOD JAGUAR (DEVELOPMENT PLAN) Page: 20. ALEXANDRL4(DEVELOPMENTPLAN) Page: 25. CARMEL CEMHTERX (DEVELOPMF-NT PLAN) Page: 27, PROVIDENCE AT OI D MERIDIAN, pHASE IT {SECONDARY PLAT AND CONSTRUCTION PLANS) NAV. 2.2003 9:53AN~ BARN'ES~ORNBURG 311-231-1433 • NQ 991 P. 3 page 17 of 2 2cchnical Advisory Consmihee Miauces Apv716, 2003 BRXANT: J. Liston said they would want to keep this regulated. It is going to be their responsibility and not City? LISTON: We will share inspections. IIlI T,: The question I have is about the plat passing blister at your entrance is theright-of--way available? DOBOSIEWICZ: flas and offer been made to the adjoining property owner for the right-of--way passing blistez? BRY AN't: I am not sure if it has. DOBOSIEWICZ: The property owner will have to give it up no matter how the property is developed. But if you make an ofl'er on the pzoperty foz the improvements- They should not say no, for the sake of no. It is important to us that we get this constructed. Call me and we will tallc about it. PRAYER No Comments. KERN: The District has received the revised plans for this project. These plans have been reviewed and wiU be fozsvarded too IDEIvI for permit approval in the neaz future. Please reroittd all TAC applicants to provide plans directly to the District at our main office address in care of: Andy Kem, 10701 North College Avenue, Suite A, Indianapolis, IN46208-1098. SND. TOllx WOOA JAG'CJAR (DEVELOPMENT PLAN] The applicant seeks approval to construct an automobile dealership. The Site is located at 4620 East 96t° Street The site is coned B-3/busineas. Fled by Lawrence E. Lawhead for Tom Wood Jaguar, Tnc Representing the Petitioners: Mike Hoff, ROGER WARD ENGtNEERTNC Lawrence Lawhead, BARNS 8• THORNBURG LAW~AD: Proposed new dealership along 96`s Stxeet, part of the Carmel Auto Park. Comprisixag of Tom Wood Jaguaz, Range Rover and Volvo. Ahigh-end dealership. We have been approved for that and now come before the Plan Commission for ADLS approval. IIOFF: The project is located north o£Tom Wood VoUtswagen dealership and north of Tom O'Brien dealership. Dan Young had the property before. I3e did do some of the construction originally approved along the flood way. We aze going to do little or no work along that floodway other than to install an outlet storm pipe into the creek. SHUPPERD: Run service and small cartage load usage and size equipment accordingly a 1-800 number for busy times when you really need it. Call and get the approval to get into the system. MAY. 2.2003 9:§4AM BARNE~HORNBURG 311-231-7433 ~ N0.991 P. 4 page 18 of 2 TechaicalAdvisory Coma+ihee Mztutes Apa116, 2003 SOU"f'H: We have good seeding weather now. It is my recommendation that we seed that Aoodway/flood plain azea that you will not be doing any constzuction in. IIOYT: Sent letter to M. Hoff who kindly answered all bis questions. I would like to meet with owner and architect to discuss where the Fire Aepartment connection should be located. and fill out the Knox box application at that time. I would like to see a small detailed drawing of how the water system is coming in. Proposed water system on the wall or better suited in the yard. I like the hydrant layout. It would not have a full fire alarm. We will just monitor the sprinkler system, AKER4: No comment. H17.i.: Comments general information. Vi%ater is Indianapolis Water Company, Carmel sewer and sanitary sewer jurisdiction. Tom Wood Volkswagen had to get consent to encroach on existing easements. You may have to do that as well. Sanitary sewer availability accepted only after BZA approval. Twill need an estimate of water usage or use from another facility. We require a minimum of one yeaz's wo o water r s o es a lsh water usage. LAWIiEAD: We are moving from a facility down the street in Marion County this is going to be larger. Will those bills be ok? HILL: Yes. Some other comments. We would like you to designate all utilities, sanitary, storm as either existing or pr~osed~Identify and label the sewer laterals structure surface ow. p~azeas require to be curbed- I only see one structure serving that whole pazking azea. Is that right? HOFF: That is cozrect. Td7T,L: What will you do with surface water? 1IOFF: Most of it is going to the reaz, which is the existing drain Swale. HILL: I expect with Kate she will require Paul Cripe to meet the standards of the original site. BRER%Elt: A couple of points. First, your species for Crab Apples is not recommended and the graphic planting detail there should be a note that says root flare should be planted at grade level--The buffering to the north and to the west along the drainage Swale is that in place? LAWHEAA: No. They planted something there but we are not sure what is in there. Waiting to meet with the subdivision to the north. We may be buffering that area more. DOBOSIEWICZ: Ultimately the Plan Commission is the final arbiter. You will need to present it to the Plan Comtxtiission. MAY. 2.2003 9:§4AM BARNES~ORNBURG 317-231-7433 ~ N0.991 P. 5 Page 19of2 ~ ~iy'i% Technical tldvisory Committee Mfnures ~°t° Apv116, 2003 BREWER: Also there is a force main out there and on the plan you show buffering planting on top of that force main. It will have to be adjusted to show no plants on top of the main. They may ask you to specify in the landscape easement a utility easement for file main. 7. Dobosiewicz may want that on the plans. Also on the east side there is also a buffering requirement. Adjacent to Tom Wood they have some Iapi~t g that is not showing. I would like to see it continue around the curve, which you do not have. oT~lan landscaping around the building? BRYANT: No. LILLTG: I have some concerns about this ~a lid g lot edge on the north side. We aze going to have car headlights shining into people's backyazds. I think there should be some sort of hedgerow to block those lights. At least to the height of a Land Rover's headlamps. DOBOSIEWICZ: We need submitted the proposed ground sign at 96`s Street that is on the Tom Wood Lexus side. Flow that will be divided out. Will it be Lexus, Volvo, Jaguar; and Range Rover etc? 1 want you to copy me on how that will play out. You indicated that it would not include the Tom O'Brien sign. These signs will be permitted without a variance through ADLS. This thing on top of the building just is not going to happen. Xou can figure six different ways but you will be wasting your time. The color elevation we should have it now. So we can offer comments and review. If we do not get it until Plan Commission you may or may not find us arguing for a continuance based on that insufficient time to review the petition. Sit down with S. Brewer and review those areas. The Plan Commission is going to have questions about the band Rover Nature Trail. I would go as far as to say, that a videotape of an existing site where that is employed would be beneficial for the Plan Commission. LLLLIG: Specifically, regarding the lighting plan. The pictures need to be full cut off, fully shielded. All Lexus, Volkswagen and O'Brien are to be twenTy, (20) to thirty, (30) times what they are supposed to be. This needs to be done correctly this time around. What I understand from the lighting contractor at least one of those sites is going to be very expensive. Need your signpackagze by the end of the week. PRAYER: No comment. KERN: No comment. ENA. MA4. 28.2003 4; 22PM BARNES &TI t~RNBURG Lawrence ~, Lawbpd (317) 231.1262 . ateeil: llswhead®btlaa.com ViaVur F Jon C. Dobosiewicz, planning Administrator CITY OF CARMEL Department of Communitq Services One Civic Squaze Catmel, Indiana 46032 Re: 2"om Wood Jaguar/,Land Rover/)to[vo Special Studies Committee -June 3, 2003 Meeting Docket No. 68-03 DP/ADCs Deaz Mr. Dobosiewicz: ~~RtCi lUF~ 2~ ?~ ~~ ~UCS As we discussed yesterday, I would like to request that the Special Studies Committee hearing on the Tom Wood Jaguar Project be moved to June 12, 2003 from June 3, 2003. The reason for this request is that June 3, 2003 is graduation day for Carmel High School and I have a son who is a graduating senior. I understand that both the June Std and June 12d' hearing recomtnendationswdl then be heard at the June 7 2003 Plan Commission Hearing. Thank you for your assistance on this matter. Very truly yours, BARNES 8r; THORNBLTRG By. ~ LAWRENCE E. LAWHEAD LEL/dkh Enclosures INDSOI LEL N0. 6B1 P. 2 I l soerh ~rrd~n street Indianaptdis, lodiatu 46204.3535 U$A. (317) 736•/Sl3 Fan (317)231-7433 wwa.bdaw.eom May 28, 2003 _ _ %, Indianapolis Fort Wayne South Bend Elkhart Chic4go Washingcon, D.C. May 16, 2003 Mr. Mike Hoff Roger Ward Engineering, Inc. 6285 North College Avenue, Suite 2 Indianapolis, IN 46220 RE: Project Review #1 nom Wood Jaguar;etc" 96th'S[reet'Auto`Park Dear Mr. Hoff This office has reviewed the plans submitted for this project. We apologize for the delay in responding We offer the following comments: General Information 1. The project site is located within current City of Carmel Corporate Limits. 2. Jurisdictions: • Streets and Right of Way (96's Street) -City of Carmel. • Water -Indianapolis Water Company Service Area. • Sanitary Sewer and Storm Sewer- City of Carmel 3. Board of Public Works and Safely Approval Requirements: • Sanitary Sewer Availability (Connection). • Any permanent improvement, including irrigation systems, [o be installed in public right of way or dedicated easements. This requires a Consent to Encroach Agreement between the City and the Owner or Owners. I am enclosing a schedule of Board of Public Works and Safety meeting dates and agenda deadlines for your use. Please use the Engineering Department deadlines for submission to the Board. Any submission to the Board requires prior Etna! approva(by the Carme! Clay Plan Commission and/or the Board of Zoning Appeals and completion of review by the Technical Advisory Committee. All written requests to be placed on the Board's agenda m«st include the appropriate Docket Numbers and the date (or dates) ojapproval by the Plan Commission and/or BZA. 4. Sanitary Sewer Connection Fees: • Connection Fees are based upon the average user factor tables from Section 9-200 (sanitary) of our Utility Ordinance. The Connection Fees are $795.00 per E.D.U. for sanitary sewers. There are no classifications in our tables for auto dealerships other than the Retail classification, which is 1.0 E.D.U per 1000 square feet. You do have the option of requesting approval from our Board of Public Works and Safety to utilize actual usage from an existing similar facility as a base calculation for the proposed facility. Such requests must be accompanied by proof of a minimum of one years worth of actual water usage, recapped by total gallons per month, and must include the name, location and size in square feet of the facility being utilized as a base for calculation of fees. 5. T.A.C. Review/Drawings submitted for approval: We request that al] comments and comment letters generated by this office be answered in writing and be accompanied by a drawing reflecting requested revisions. Final drawings will not be approved for constmction until all issues have been resolved. All Carmel Utility issues must also be resolved. The design engineer must certify all drawings submitted for final approval. This office will require a DEPARTMENT OP ENGIKEERI: "G OvE Crnc SQcnae. Cnw~iEL, tN 46032 OFFICE 317.577.2441, Feix 317.571-2439 ERIAIt kweese rOci.carmel.in.us I41r. Mike Hoff May ] 6, 2003 Page 2 minimum of four-sets (maximum seven-sets) of approved drawings after all issues have been resolved. The drawings will be stamped approved and signed by both the City Engineer and Director Carmel Utilities. The Developer/Owner will receive one-set which is to be maintained on the constmction site at all times. Carmel Utilities will receive one-set. Our Public Works Inspector will receive one-set and one-set will be maintained in the Department of Engineering. If more than four-sets are requested to be approved, the additional sets must be submitted with the four-sets. 6. Please be advised [hat any installation of signs, walls, irrigation systems, etc. within dedicated right of way or easements will require a Consent to Encroach Agreement between [he Owner/Developer and the City of Carmel: This agreement requires review and approval by our Law Department and Board of Public Works and Safety approval. 7. Carmel Utilities does not subscribe to "Holey Moley" and should be contacted directly for all sanitary sewer locates. 8. Carmel Utilities will provide a separate review of this project for sanitary sewer issues. 9. I am including copies of the following items with [his correspondence: • Department of Engineering Commercial Project Approval Procedures. • Permit Data, Contacts, etc. • Commercial Permitting Procedures. I will send a copy of our Residential Subdivision and Commercial Irrigation System Requirements upon request. BONDING REQUIREMENTS ]0. Upon initial review, it appears that [here will be no bonding requirements for this project. PROJECT COMMENTS Sheet C101 -Site and Utility Plan 11. Designate all utilities {sanitary, storm and water) as either existing or proposed on this and on all appropriate sheets. 12. Identify and label the sanitary sewer lateral to serve the showroom. 13. This project will be subject to review by Carmel Utilities. CommeroiaUretail sanitary sewer laterals are usually required to discharge into a sanitary sewer structure. Carmel Utilities will advise you regarding this issue. 14. All parking areas are required to be curbed. 15. There is only one stmcture and one run of storm pipe identified within all of the paved parking areas. How do you proposed [o accommodate storm mnoff from all the other impervious surface areas? 16. Please provide drainage calculations or proof that this development adheres to the original approved drainage plan for [he 96'" Street Auto Park. 17. Identify and label the easement for the existing sanitary sewer along the west perimeter of [he development. Likewise, identify and label [he easement along the east perimeter. This is applicable to all appropriate sheets. 18. There is a drainage easement identified on the 96`h Street Auto Park plat that is on either side of Carmel Creek. Identify and label this easement on all applicable sheets. We reserve the right to provide additional comments upon receipt of drainage calculations and upon the City Engineer's review of [he plans for [his project. The above comments are based uposthe Engineering Department's initial review. Please provide our office with a follow up letter and revised plans, indicating all revisions. Second and subsequent reviews will focus only on revised items. It is critical that our office be made aware of all modifications made on the plans being re-submitted, particularly if any such changes are considered "new" or fall outside of our initial review. If you have questions, please contact Kate Weese, Mike McBride or me at 571-2441. Mr. Mike Hoff May 16, 2003 Page 3 If you have questions, contact Kate Weese, Mike McBride or me at 571-2441. Sin ely, Dick Hill, Assistant Director Department of Engineering Enclosures cc: M. Kate Weese, City Engineer (w/o encl.) Mike McBride, Assistant City Engineer (w/o encl.) Laurence Lillig, Department of Community Services (w/o encl.) Jon Dobosiewicz, Department of Community Services (w/o encl.) John Duffy, Carmel Utilities (w/o encl.) Larry Heid, Tom Wood, Inc. S:\PROIREV03\TOM WOOD]AGUAR -,_, BARNES &THOR~IBURG ] 1 South Meridian Scteet Indianapolis, Indiana 46204-3535 U.S.A. (317) 236-1313 Fax (317) 231-7433 www.bdaw.com May 14, 2003 - Via Hand Delivery Mr. Dick Hill CITY OF CARMEL Department of Engineering Carmel City Hall, First Floor One Civic Square Carmel, Indiana 46032 Re: Ton: Wood Jaguar/Lm:d Rover/Volvo 6/ADCs Dear Mr. Hill: `~FO~,e~ O ~~ /F 00~ ?GO Enclosed please find copies of Tom Wood Jaguar Volvo, Inc.'s January 30, 2002 thru December 3Q 2002 Indianapolis Water Monthly Statements. Please do not hesitate to contact my office if further information is needed Very truly yours, BARNES & THORNBURG By: LEL/dkh Enclosures cc: Mr. Jon Dobosiewicz (w/o encls.) IND501 LCL 587081 v1 Original Signed by Lawrence E.Lawhead LAWRENCE E. LAWHEAD Indianapolis For[ Wayne Soudt Bcnd Elkhart Chicago Washington, D. C. ., :. ~:. ., ~. _. _ O "~ ~GF OC,~ AGO , i` • ERrJOIIS INDIANAPOLIS WATER MONTHLY STATEMENT "'` m DEPARTMENT OF PUBLIC WORKS 1 0 /;.~tralme° aoa Customer number: 000326437 Site number: 000267612 ~aleeny~/S•~E~~~e Dec 30,2002 Billing date: Due date: JAN 16.2003 ~ Late payment date: JAN 16,2003 01818654 ;'~~ Lobby hours: Mon-Fri: R:00 - 4:30 ;' = TOM WOOD JAGUAR VOLVO INC Customer service hours: Mon-Fri: R:00 - 6:00 ~, 3455E 96TH ST Customer service: 1-317-631-1431 INDIANAPOLIS, IN 46240-1425 Toll free: 1-877-631-1431 ~J~u~J~~un~~~~~u~~~nn n~~~~u~~~~J~J~~~u~J~n~~~nJ~~~~ TDD: 1-317-263-6308 .e• •• s _ Las[ statement $100.37 Payment(s)received ~ $100.37 - i~ ~ Wa[ercharges $82.47 ~ Sewer charges ~ r $53:47 rJ ~ :J~ .~i ,sg ,,,~ Tax $4.12 ~Jd# J h - - il '` LL#~ ~ ~ .. _.wh 4. a $140.06 DETAIL OF CHARGES ON BACK ~ ~ • ~ ~ JAN 16,2003 Late fees if paid after JAN 16,2003 Water charges $2.68 Sewer charges $5.35 Consump~ion x 100 N FS 60 6s 30 JS 0 Jan Fcb Mar Apr May Jun 1W Aub Sep Oat Nov Dec Graph indicatesconsump[ion history . i, __ ~1 -_ _ ~. - „ _ 1NDIANAPOLIS WATER DEPARTMENT OF PUBLIC WORICTMi Serving Central Irbiana Operate0 by U9, ss~=a olelesrz TOM WOOD JAGUAR VOLVO INC __ 3455E 96TH ST __ INDIANAPOLIS, IN 46240-1425 ~~~u~~~~un~r~~~u~~~nnu~~~~n~n~~~~~~~n~~~~i~~~ur~~~~ Last statement $161.12 Payment(s)received $]61.12 - Wa[ercharges ,~ .. $60x8 Sewer charges e'~ ~36~''.r4$ Tax ` ~i :$3.04... ~. :. MONTHLY STATEMENT Customer number: 000326437 Site number: 000267612 Billing date: Nov 26,2002 Due date: DEC 13,2002 Late payment date: DEC 13,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: R:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-631-1431 TDDi 1-317-263-6308 • ~ ~ • - ~ • t, This statement reflects acorrection to m, ~he~s Ammer s,e~wer adjustment that was ~i'~spphedRto your l ~[ bd~ng~afement s ~~ ~ n /rl ~j~/ ~ ~ $100.37 DETAIL OF CHARGES ON BACK • ~ ~ DEC 13,2002 Late fees if paid after DEC 13,2002 Water charges $2.04 Sewer charges ~ $3.65 c~,~u~aoa = loo cu rr 60 a? 30 ~s 0 Da lan Fcb Mar Apr May l,m ]ul Aug Scp Oct Nov m Graph indicates consumption history v Detoch here and return bottom portion with payment v ~ _ _ _ _ , ,,,. ~.: `, Idianapo~is INDIANAPOLIS WATER ~ MONTHLY STATEMENT WATER DEPARTMENT OF PUBLIC WORKS ' - 'Serving Cent211ndiana - Customer number 000326437 i1 ,i :Y l Operated by VS`== ags ~ 01 BI8558 TOM WOOD JAGUAR VOLVO INC 3455E 96TH ST INDIANAPOLIS, IN 46240-1425 Itlttltllttt.I.Itltellltt t...Iltlttlttitltltlttltlttltltttltll Last statement $95.70 Payment(s)received ~$95.68 - Water charges S h 1~ 7 r" » $93 90 z 2` ewer c arges ~ ~ $6 30 ,t - Tax ~ ,~ $4.70......_ S` ~!! r~~r' °'~~, rx 3 ~~ Site number: 000267612 Billing date: Oct 28,2002 Due date: ~ NOV 14,2002 Late payment date: NOV 14,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: R:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-631-1431 TDD: 1-317-263-6308 '~' a •' • A New Partnership and A~New Look. Your bill~m~ay,~look a little different, but ourcommrtment to our consumers is still ng: Indianapolis Water and Ilter, working together to make every count! "1 ~ , fir' ~ t +.,f a~.: t ?.~E"h I S r C~ F I Ca $161.12 ~O• ~~ 8 7~ ~ O y8' [f0 ~ yo va~ DETAIL OF CHARGES ON BACK ~ NOV 14,2002 Late fees if paid after NOV 14,2002 Water charges $3.03 Sewer charges - $6.25 cokump0uo a too cu Fr 60 OS ao is 0 Nov Dec ]m Fcb Mae`Apr May by 1W Aug Sep Oct` ; / INDIANAPOLIS WATER COMPr1NY ~ MONTHLY STATEMENT DEPARTMENT OF PUBLI C WORKS Customernumber: 000326437 PO BOX 1220 Site number: 000267612 INDIANAPOLIS, IN 46206 Billing date: Sep 27,2002 Due date: OCT 14,2002 Late payment date: OCT 14,2002 -~ olaiezse TOM WOOD JAGUAR VOLVO INC Lobby hours: Mon-Fri: R:00 - 4:30 3455E 96TH ST Customer service hours: Mon-Fri: 8:00 - 6:00 BQDL4NAPOLIS, IN 46240-1425 Customer service: 1-317-631-1431 ~~~n ~~~~nu~~~~~1~~~~~nu~~~l~n ~u~l ~l~l~ n ~l~n ~l~u~~l~~ Toll free: 1-877-631-1431 TDD: 1-317-263-6308 Las[ statement $119.05 Payment(s)received $119.05 - You now have the availability of paying Water charges $58 34 Your bill at Union Federal Bank . locations for a minimal fee of $1.00 for Sewer charges -~ -~~ $34 44 bank account holders and $2.00 for Tax $2 92 non-bank accountholders. . If you have a disconnect notice and pay the bill on the disconnect date, you must contact the call center at 631-1431 q,t/ with your receipt information. A ~~3 a A~ ~ a ~ ~ ~ ~~ t 1 $95.70 ~ OCT 14,2002 Late fees if paid after OCT 14,2002 Water charges ~ $1.96 Sewercharges $3.44 DETAIL OF CHARGES ON BACK Cnmvmpuon x 100 CU Fi 50 36 za Iz 0 Oct Nov Dcc Jav Feb Mar Apr May Jun Jul pug Sep ,, _ INDIANAPOLIS WATER COMPAN'l MONTHLY STATEMENT "` DEPARTMENT OF PUBLIC WORKS '- , .. Customer number: 000326437 PO BOX 1220 Site number: 000267612 INDIANAPOLIS, IN 46206 Billing date: Aug 28,2002 Due date: SEP ]4,2002 Late payment date: SEP 14,2002 r~~.,1 ~ oieiesne Lobby hours: Mon-Fri: 8:00-4:30 TOM WOOD JAGUAR VOLVO INC Customer service hours:. Mon-Fri: 8:00 - 6:00 3455E 96TH ST INDIANAPOLIS, IN 46240-1425 Customer service: 1-317-631-1431 i ~ ~ Toll free: 1-877-631-1431 j I~LJ~II~~~~IJJ~JIL~~~~~ILLJ~~I~I~I~L~I~I~~I~I~~J~II TDD: 1-317-z63-63oa i ' ~ '0' 1' 0 Last statement $93.36 Payment(s)received $93.36 - Watercharges $71.04 Sewer charges $44.46 Tax $3.55 ,~ 1 :~ ~~ ~~ a~,~y ;~ D ~ ~ ~ ~a ~~~ G~ti ~ ~ $119.05 ~' ~ SEP 14,2002 :. yl Late fees if paid after SEP 14,2002 i+ Water charges $2.34 Sewer charges $4.45 `.1 '1 You now have the availability of paying your bill at Union Federa] Bank locations for a minimal fee of $1.00 for bank account holders and $2.00 for non-bank accountholders. If you have adisconnect notice and pay [he bill on [he disconnect date, you must contact the call center at 631-143 t with your receipt information. DETAIL OF CHARGES ON BACK Consump~ioo x 100 N Fr 50 36 .a + ~ 0 Sep Oct Nov Dec .ly Fab Ma Apr May Jm 1W Aug ll -n' Y.' ~ -... n t >` t :v , ~ ~ 1^. { ~3 a _ ~> i 4 t ~_ t' ' r a a~ ~r ~. s k a ri a ~ .. i ~y i , .3w9;{'Y. 3i!r'~'f~'Aq .3.n~tFS-f<h. ~' :.. _ ..~1. WATER COMPANY OF PUBLIC WORKS 1220 ,IN 46206 ~,~n~l~~lln~l~l~n~~~nllo~~i~n~o~l~i~l~n~l~n~i~ul~l~~ C43B1 P70045"^"AUTO"5-DIGIT 46240 10045 1 AV 0.278 TOM WOOD JAGUAR VOLVO INC 3455E 96TH ST INDIANAPOLIS IN 46240-1425 Last statement $ 123.73 Payment(s)received $ -123.73 Water charges $ 57.07 Sewer charges ~ $ 33..4.; Tax $ 2.85 3~ a~ `~ a ~ ,, ~~ ~ ~~~~a ~~~ - ~i11~1 i1o $93.36 ~ AUG 16,2002- Late fees if paid after AUG 16,2002 WATER CHARGES $ 1.92 SEWER CHARGES $ 3.34 _.. • l ,. . MONTHLY STATEMENT Customer number: 000326437 Site number: 00026 76 1 2 Billing date: Ju130.2002 Due date: AUG 16.2002 Late pa}intent date: AUG 16,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: 8:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-631-1431 TDD: 1-317-263-6308 '1' ~ 0' 1 You now have the availability of paying your bill at Union Federal Ban}: locations for a minimal fee of $1.00 for bank account holders and $2.00 for non-bank account holders. If you have a disconnect notice and pay [he bill o.^. the disconnect date. you must contact the call center a[ 631-1431 with your receipt information. DETAIL OF CHARGES ON BACK CONSVMPf10N x IOD C~~FT 68 36 ,a r_ 0 Aud ~ ~t Nw' 4c lan ieL Ma AP Ma> lun IW • • ,' '. ~ ~ - _ 1~ r~'{ c i Y: • L .~ Y~:~ a. { _- -- - t ti b rvN+ - ~ ,~+ tl r ~ , t 2' ~ - ~ ~ , Z ~ INDIANAPOLIS WATER COMPANY `• ~, DEPARTMENT OF PUBLIC WORKS PO BOX 1220 INDIANAPOLIS, IN 46206 Ill~~l~lll~l~l~lll~lIII,~~~,~II~I~111~1~111~11~1111~1,1~~11~11 C43B1 P10268"""AUTO"6-DIGIT 46240 10268 1 AV 0.278 TOM WOOD JAGUAR VOLVO INC 3455 E 96TH ST INDIANAPOLIS IN 46240.1425 x Last statement $ 88.70 Payment(s)received $ -88.70 Water charges $ 73.58 Sewer charges $ 46.47 Tax $ 3.68 • 1 ~ $ 123.73 • ~ JUL 15,2002 Late fees if paid after JIJI.15,~002 WATER CHARGES $ 2.42 SEWER CHARGES $ 4.65 l r MONTHLY STATEMENT. Customernutnber: 000326437 Site number: 000267612 Billing date: Jun 28,2002 Due date: JUL 15,2002 Late payment date: JUL 15,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: 8:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-631-1431 TDD: 1-317-263-6308 ~°aM~ C~ ~o DETAIL OF CHARGES ON BACK CONSUMPnON x 100 N FT 36 e 0 IW Aux Sep (Y~ Nw R[ lan kD Ma Ap May Iw l:ronl, :n•ii rofoe rnnonm...:..e l.: r...... is `.... ' .. ... . _ INDIANAPOLIS WATER COMPANY PO BOX 1220 INDIANAPOLIS, IN 46206 I~I~~I~II~~~~I~I~I~~III~~~~~II~I~~~III~~~I I~~~I~~~I~~II~~I~~II C3i B7 P5464"""AUTO"5•DIGIT 46240 5464 1 AV 0.255 TOM WOOD JAGUAR 3473E 96TH ST INDIANAPOLIS IN 46240-3700 Last statement $ 17.67 Payment(s)received $ -17.67 Fire service chazges - $ 16.83 Tax $ 0.84 MONTHLY STATEMENT Customer number: 000003887 Site number: 000003803 Billing date: May 22,2002 Due date: JiJN 08,2002 Late payment date: JiJN 08,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: 8:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-63I-1431 TDD: I-317-263-6308 Y/ ~0~3122°J ~ ~s g1 • 1 1 $ 17.67 • ~ ~ JUN 08,2002 Late fees if paid after JiJN 08,2002 FIRE SERVICE CHARGES $ 0.71 .V. nr~rF Fn« nM rn.....Mnnm mninn mbF m.m.an, y Graph indicates c3nsumption history DETAIL OF CHARGES ON BACK CONSl1MPIlON n 8 6 d 0 ' iw ~m woi uv m Nw oec ~~ xe my wa, mar PO BOX 1220 INDIANAPOLIS, IN 46206 IIII~I~IIIIIIIII~I~~IIIIIII~~II~IIII~~I~IIIII~~I~II~IIIII~IIII C37BIP10163******AUTO**5-DIGIT 36Zd0 IOI63 1 AV 0.255 TOM WOOD JAGUAR VOLVO INC 3355E 96TH ST INDIANAPOLIS IN 36240-13'!5 1 e Last statement $ gg,70 Payment(s)received $ O,Op Water charges $ 54.53 Waterotiier $ 1.85 Sewer charges $ 31.44 Sewer other $ 3.14 Tax $ 2.73 '~ •~~x,~eo $182.39 e ~ ~ MAY 17,2002 Late fees if paid after MA'Y 17,2002 WATER CHARGES $ l.gs SEWER CHARGES $ 3.46 Customer number: 000326437 Site number: 000267612 Billing date: Apr 30,2002 ~ Due date: MAY 17,2002 Late payment date: MAY 17,2002 Lobby hours: Mon-Fri: 8:00 - 4:30 Customer service hours: Mon-Fri: 8:00 - 6:00 Customer service: 1-317-631-1431 Toll free: 1-877-631-1431 TDD: ~ 1-317-263-6308 ee' ~ e e e y t$$ess3 DETAIL OF CHARGES ON BACK CONSUMPTION x I W N FT m 30 m to 0 wy Iw iw w~e.ko ui Nm~ na~ ioe r<e su9 wp ;: ~, - :. _ _--_ _. I: ~- __ __ .` / ~ INDIANAPOLIS WATER COMPANY DEPARTMENT OF PUBLIC WORKS MONTHLY STATEMENT PO BOX 1220 INDIANAPOLIS, IN 46206 Account Number: 000326437 Billing Date: Feb 28,2002 Business Hours: Mon-Fri: 8:00 - 4:30 I~I~~I~II~~~~I~I~I~~III~~~~~~II~I~~i~~l~l~l~l~~l~l„I~I~~~I~II Mon-Fri: 8:00-6:00 C2681 P4664"""AUTO"6-DIGIT 46240 assa i Av o.2ss Customer Service: 1-317-631-1431 TOM WOOD JAGUAR VOLVOINC Toll Free: 1-877-631-1431 3455E 96TH ST TDD: 1-317-263-6308 INDIANAPOLIS IN 46240-1425 ~ •• ~ ~ LAST STATEMENT $ 91.17 PAYMENT(S)RECEIVED $ -91.17 WATER CHARGES $ 57.07 TAX $ 2.85 SEWER CHARGES $ 33.44 ~~ ~~ ~~~~~~~! ~~ ~~ C ~ ~~' _ v Late Fees: WATER SEWER Total Due after Mar 17,2002 $ 93.36 Mar 17,2002 $ 2.01 $ 3.34 $ 98.71 CONS ao 30 zo io 0 Mar pp MeY Jun J~J pr•9 Sp M Nov Cec Jan Feb e dY>rd- > ~y 4 1 _ _ Y 1 v i ; i Sfd ~r }-J~~n~^R~ ~~ ` M-^ ~ * 6 44 ~1 P~ % _. ~ • % RSD 'S ~ ~ i ~ f \' yr ... - , J t t - _ ~. ~ ~. ~d t h.. .~ _ _ . . ~~ r= ~ y ; r t ~ ~, ~ 1~' y '`K i i ') s ' , r ~ f 1 . J- v~ , i r ., Y a ~+~-' S a~ '-. ~ r n x~J t ~~' c - -l~.'Y'~c 4t n R. 4. - y'`~i`i +~~2 11~ : , v~r~4 1 Y~ r o I y ,~ ,"'r ~ ~' '' _ - s' ! J .n't'~ rr ~` ~ _ - Pea / Fr,,.. _.. t ~ __:. .: :. __ ..' r INDIANAPOLIS WATER COMPANY MONTHLY ST~4TEMENT DEPARTMENT ^F PUBLIC WORKS PO BOX 1220 ` " INDIANAPOLIS, IN 46206 Account Number: 000326437 Billing Date: Jan 30,2002 Business Hours: Mon-Fri: 8:00 - 6:00 I~I~~I,II~~„I,I~I„III,.....II,I,~I~~I~I~I~I~~I~I~~I~I~~,I~II C29B1 P6500"""AUTO"5-DIGIT 46240 Customer Service: 1-317-631-1431 ssool Avo.2ss Toll Free: 1-877-631-1431 TOM WOOD JAGUAR VOLVO INC TDD: 1-317-263-6308 3455E 96TH ST INDIANAPOLIS IN 46240-1425 ~ ~~ LAST STATEMENT $ 76.89 In June 2001, the City-County Council PAYMENT(S)RECEIVED $ -76.89 passed an ordinance creating the stormwater Management District n WATER CHARGES $ 54.53 Marion County. Under the terms of the TAX $ 5.20 ordinance stormwater fees have been SEWER CHARGES ~ $ 31.44 accruing since September 6, 2001. Starting on your next bill, residential (~ customers well see itemized amounts of /~ $1.25/month retroactive to September 6, (` 2001. For more information on the stormwater utility please open the insert (~/~ ~ n ~0 / included with this bill. V • ~ $ 91.17 ~ Feb 16,2002 Late Fees: WATER $ 2.00 SEWER $3.14 Total Due after Feb 16,2002 $ 96.31 ~oNs ao 30 20 io 0 Gen Ma 40~ May Jun JW .u9 Se0 Oa No. G+! Jan BARNES &THORNBURG 11 South Meridian Street Indianapolis, Indiana 46204-3535 U.S.A. (317) 236-1313 Fax (317) 231-7433 Thomas H, Engle www.btlaw.com (3J 7) 231-7499 Email tengle®bdaw.com May 7, 2003 VIA FEDERAL EXPRESS ~y Ramona Hancock Pr ('!~~\!E~ Plan Commission Secretary P~~Y ~ ''~;~~3~ Carmel/Clay Plan Commission r,o Department of Community Services ~~"'~ One Civic Square Carmel, Indiana 46032 RE: East 96`h Street Auto Park Tom Wood Jal;llar; 68-03 DP/ADCs Dear Ms. Hancock: On behalf of Tom Wood Jaguar, I am enclosing twenty (20) Infornrational Packets for the above listed application appearing on the May 20, 2003 agenda of the Plan Commission. The drawings included have been revised per the discussion at the April 16, 2003 TAC Committee meeting. Please call myself or my colleague Lawrence Lawhead if you need anything else at this time. Thanks for your assistance. Since Thomas H. En l~ g Enclosures c: Lawrence E. Lawhead fVfJ$01 THE 585R81 v1 Indianopolls Fort Wuyne South 6cnd Elkhart ChicH[;o Wnshingron, U.C. /6/03 • , FUSION AND SEDIMENT CON'1~COL PLAN TECHNICAL REVIEW AND COMMENT Hamilton County Soil and Water Conservation District 1108 South 9ih Street, Noblesville [N 46060 Ph- 317-773-1432 or Email at john-south@iaswcd.org PROJECT NAME: Tom Wood Jaguar Land Rover Volvo SUBMITTED BY: Mr. Larry Heid Tom Wood ]nc 3003 E. 96°' Street, Suite 201 Indianapolis, IN 46280 317-574-0143 REVIEWED BY: John B. South P.E. Mr. Roger Ward Roger Ward Engineering 6285 North college Avenue, Suite 2 Indianapolis, IN 46220 Certified Professional in Erosion and Sediment Control PLAN REVIEW DATE: April 8, 2003 Acreage: 12 ac LOCATION: West of 96"' Stand Gray Road (~ ~~ l~~ ,Q~/~ s LEGAL DESCRIPTION: Sec. 8 TOWNSHIP: 17N RANGE: 4E CIVIL TOWNSHIP: Clay SOIL SURVEY MAP SHEET: 57 The technical review and comments are intended to evaluate the completeness ojthe erosion and sediment control plan for the The erosion and sediment control plan submitted was not reviewed for the adequacy of the engineering design. All included in the plan, as well as those recmmnended in the comments should be evaluated as to their feasibility by a qualifred individual with structural practices designed by a qualified engineer. The plan has not been reviex~ed for local, state, or federal permits that may be required to proceed with this project. Additional information, including design calculations may be requested to further evaluate the erosion and sedinrenl control plan. The erosion and sediment control plan has been reviewed and it has been determined that the plan: Satisfies the minimum requirements and intent of 3271AC 15-5 (Rule 5). Notification will be forwarded to the Indiana Department of Environmental Management. X Does not satisfy [he minimum requirements and intent of 3271AC IS-5 (Rule 5); deficiencies are noted in the checklist and in the comments section. Deficiencies constitute potential violations of the rule and must be adequately addressed for compliance. The information necessary to satisfy the deficiencies must be submitted: Proper bnplemenration of the erosion and sediment control plan and inspections of the consvruction site by the developer or a li representative are necessary io minimize ojjsite sedimentation. The developer should be mvare that unforeseen conriruction activities and weather conditions might affect the performance of a practice or the erosion and sediment control plan. The plan mull be a flexible document, with provisions to modify or substitute practices as necessary. Revised 4 / 97 PROJIrCT: Tom Wood .•tar Land Rover Volvo Page 2 of 3 • ARE THE FOLLOWING ITEMS ADEQUATELY ADDRESSED ON THE PLANS ? (Al[ Ptans Must 6tctude Appropriate Legends, Scales, and Nortk Arrow) (items that are Not Applicable ro this Prnject are designated by NA) Yes No PROJECT INFORMATION X IA Project Location Map (Show project in relation to odder areas ofthe county) X lB Narrative Describing the Nature and Purpose of the Project x 1 C Location of Planned and/or Existing Roads, Utilities, Structures, Highways, etc. x tb Lot and/or Building Locations X lE Landuse of Adjacent Areas (Show [he Entire Upstream Watershed and Adjacent Arens Within 500 Feet of the Property Lines) Yes No TOPOGRAPHIC, DRAINAGE, AND GENERAL SITE FEATURES X 2A Existing Vegetation (Identify and Delineate ) x 2B Location and Name of All Wetlands, Lakes and Water Courses On and Adjacent to the Site x 2C 100 Year Floodplains, Floodway Fringes, and Floodways (Note if None) X 2D Soi1S Informafion (lfhydric soils are present, it is the responsibility of the owner/developer to investigate the existence of wetlands and to obtain permits from the appropriate government agencies.) x 2E Existing and Planned Contours at an Interval Appropriate to Indicate Drainage Patterns x 2F Locations of Specific Points Where Stormwater Discharge Will Leave the Site X 2G Identify All Receiving Wafers (If Discharge is to a Separate Munic~'pal Storm Sewer, Identify the Name of the Municipal Operator and the Ultimate Receiving Wgter) x 2H Potential Areas Where SCorm water May Enter Groundwater (Noce ijNone) X 2I Location of Stormwater System (Include Culverts. Storm Sewers, Channels, and Scales) Yes No LAND DISTURBING ACTIVITIES x 3A Location and Approximate Dimensions of All Disturbed Areas [i. e., Construction Limits] (Areas Where Vegetative Cover Will Be Preserved Should be Clearly Designalea~ X 3B Soil Stockpiles and or Borrow Areas (Show Locations or Note ijNone) Yes No EROSION AND SEDIMENT CONTROL MEASURES x 4A Sequence of When Each Measure Will Be Implemented (Retarive ro Earth Disturbing Activities) X 4B Monitoring and Maintenance Guidelines for Each Measure x 4C Perimeter Sediment Control Measures (Location, Construction Derail, Dimensions, and Specifications) X 4D Temporary Seeding (Specifications; including Seed Mix, Fertilizer, Lime, and Mulch Rates) X 4E Temporary Erosion and Sediment Control Measures (L.ocalion, Construction Detail, Dimensions, and Specifications) x 4F Permanent Erosion and Sediment Control Measures (Location, Construction Detail, Dimensimrs, and Spectficarions) x 4G Storm Drain Inlet Protection (Location, Construction Derail, Dimensions, and Specifications) X 4H Stormwater Outlef Protection (Location, Construction Detaif, Dimensions, and Specifications) X 41 Stable Construction Entrance (Location, Construction Derail, Dimensions, and Specifications) N/A 4J Erosion and Sediment Control on Individual Building Lots (Specifications) X 4K Permanent Seeding (Specifications; Including Seed Mix, Fertilizer, Lime, and Madch Rates) Revised 4197 ~OSION AND SEDIMENT CON~L PLAN TECHNICAL REVIEW COMMENTS PROJECT: Tom Wood Jaguar Land Rover Volvo Page 3 of 3 Note: All erosion and sediment control measures shown of the plans and referenced in this review must meet [he design criteria, standards, and specifications outlined in the "Indiana Handbook for Erosion Control in Developing Areas".from the lndianu Department of Natural Resources, Division of Soil Conservation or similar Guidance Documents. 4A. Erosion and sediment control construction sequence needs to be unique for this site. Note, while the building is being constructed, all disturbed areas should be protected with gravel, paving or grass. Please consider this in your sequence. 4C. Storm water from this site is going to flow west overland to Carmel Creek or north into the existing swale and flow into Carmel Creek. I would suggest the floodway be seeded with a temporary grass prior to construction and check dams be installed in the Swale prior to construction. These measures along with the silt fence and construction entrance would be the perimeter practices. In addition, a berm could be built along the west boundary of the pad to create a ponding situation as the fill is added to the rest of the site. 4H. Provide riprap detail for storm sewer outfall. Note; IDEM will be notified when the plan is approved. Ce: Carmel DOCS Ha. Co. Surveyor File TRANSMITTAL ,,~,, ROGER WARD CIVIL ENGINEERS - ENGINEERING LAND SURVEYORS INCORPORATED DEVELOPMENT CONSULTANTS 6285 N. College Avenue, Suite 2 -Indianapolis, IN 46220 - 317-251-1738 Fax: 251-1923 TO: BARNES 8 THORNBURG 11 SOUTH MERIDIAN STREET INDIANAPOLIS, IN 46204-3535 PHONE #: 236-1313 WE ARE SENDING YOU: X Attached Faxed DATE: 3/2812003 JOB NO. TWI.001 ATTN: LAWRENCE E. LAWHEAD RE: TOM WOOD JAGUAR LAND ROVER VOLVO FAX #: 231-7433 ~-r -.~ -~ ~~\ /. -~3~ t\ Total pages, including cover sheet => , 1 <r RECF~~ED '- ,r~R 28 ?,Ou~~ ~~, DOCS For approval X For your use REMARKS: X As requested Other For review and comment Thank C.C ROGER WARD If enclosures are nol as noted, kindly notify us at once. Dobosiewicz, Jon C From: Morrissey, Phyllis G Sent: Friday, March 21, 2003 4:10 PM To: Hollibaugh, Mike P; Dobosiewicz, Jon C; Lillig, Laurence M; Pattyn, Dawn E; Brewer, Scott I Subject: new filing DP/ADCs from Tom Wood Jaguar on 96th Street. Larry Lawhead, 231-7262 JBgEPio Pj..Monxiaaety Offce Manager City of Carmel, DOCS One Civic Square Carmel, IN 46032 Phone 317/571-2417 Fax 317/571-2426