HomeMy WebLinkAbout09010051 New Tenant Space for Sun Tan City pg. ITANNING BED AIR LOADS
BED 'E
DESCRIPTION
VERSA SPA
NO AIR, NO VENT, 20 AMP GFI DEDICATED CIRCUIT 42" HIGH
AMBITION 300
REQUIRE AIR LOAD 3/4 TON
SOLTRON
SEASHELL.
WITH FAN. REQUIRED AIR LOAD 3/4 TON
STAND
UP CAPSULE
141/0 DRESSING ROOM, REQUIRED AIR LOAD 1 1/2 TONS; 2500 CFM
PRESTIGE 1100
REQUIRED AIR LOAD 2 TON. VENT 1200 CFM.
OPEN SUN 1050
REQUIRED AIR LOAD 3.5 TONS,
12 VENT TO OUTSIDE THRU ROOF.
SUNDASN 232
REQUIRED AIR LOAD 1/2 TON
WINE
Fll I�
3 11
i
12 {oPFCTIrF
13 PRFSTIC F
OFFICE
14
UTILITY
ROOM
01 MECHANICAL PLAN
UNISEX
TOILET
03/M1.01
EQUIPMENT 50- IEDULE
RTU -1
YORK DM120N15P2 10 TON GAS FIRED RTU OR EQUAL.
INCLUDE ROOF CURB, ECONOMIZER,BAROMETRIC RELIEF AND HONEYWELL
#16700 PROGRAMMABLE THERMOSTAT WITH REMOTE SENSOR. VOLTAGE
208/230V 3 PHASE/ MCA 55A/ MAX FUSE OR BREAKER 70A
RTU -2
YORK IS DM0g0N10P2 10 TON GAS FIRED RTU OR EQUAL.
INCLUDE ROOF CURB, ECONOMIZER,BAROMETRIC RELIEF AND HONEYWELL
#18700 PROGRAMMABLE THERMOSTAT WITH REMOTE SENSOR. VOLTAGE
208/230V 3 PHASE/ MCA 41.6A/ MAX FUSE OR BREAKER 50A
REGISTERS AND GRILLS
META /A I RE #4004SP -1 SERIES DOUBLE DEFLECTION
DIFFUSERS WITH ADJUSTABLE SCOOP.
S1 -24 "x12"
S2- 14 "x6"
S3- 2O "X8"
54- 14 "X8" SIDEWALL REGISTER WITH DAMPER
55 -2'x2' LAYIN WITH DAMPER
SYMBOL LEGEND
1
ROOM NUMBER
12 EXHAUST VENT THROUGH ROOF.
SEE DETAIL 02/M1.01
AIR BALANCE SCHEDULE
RTU #1O.A.
RTU 2 O.A. 0 00 CFM
BATH EXHAUST -100 CFM
OPEN SUN 1050 -1750 CFM
SPACE 50 CFM
LL
CAP WITH BIRD SCREEN
TALL CONE FLASHING
2k._ I64 PAINT GRIP SNAP LOCK
USE 45' TO OFF SET
124 PANT GRIP SNAP LOCK PIPE
VENT FLEX HOSE PROVIDED BY OTHERS
OZ OPEN SUN 1050 DUCT
NOT TO SCALE
MECHANICAL NOTES:
(SWEET NOTES AND GENERAL NOTES PERTAINING TO THIS S1-1
ALL DUCT WORK INCLUDING PLENUMS AND SPIRAL
PIPE TO BE PAINT GRIP READY.
INSTALL ACOUSTICAL LINER AND CANVAS CONNECTORS
FOR SUPPLY AND RETURN PLENUMS. RETURN TO HAVE
ELBOW WITH 2' DUCT
PROVIDE AND INSTALL PIPE RING COLLARS AROUND SPIRAL
DUCT WHERE IT PENETRATES UTILITY ROOM BATHROOM.
PROVIDE CONDENSATE TRAPS WITH CLEANOUT TO RUN
TO NEAREST ROOF DRAIN.
CONTRACTOR 15 TO VERIFY ELECTRIC REQUIREMENTS BEFORE
ORDERING EQUIPMENT.
CONTRACTOR TO VERIFY STRUCTURAL LOADS
(APRPROX. 1200 LB5. EACH) AND STEEL REQUIREMENTS
ON BUILDING SYSTEM PRIOR TO INSTALLING NEW EQUIPMENT.
CONTRACTOR TO VERIFY THAT PLENUMS FIT BETWEEN BAR JOIST,
ADJUST AS NEEDED.
PROVIDE 100cfm BATH FANS AND WALL CAPS.
VENT DRYER TO OUTSIDE USING (2) 4" ALUMINUM DUCTS
(NO SCREWS IN PIPE) TAPE JOINTS USING FOIL TYPE TAPE.
(STACKABLE DRYERS). USE BOOSTER FANS W/ BACK DRAFT
DAMPER AND PRESSURE SENSOR
VENT OPEN SUN 1050 USING PAINT GRIP SNAP LOCK PIPE AS PER
DETAIL 02/M1.01.
PROVIDE AND INSTALL RETURN DUCT MOUNT SMOKE DETECTOR TO
SHUT DOWN RTU -1, 4 2 OR AS PER LOCAL REQUIREMENTS.
ALL MECHANICAL WORK TO BE PERFORMED PER LOCAL CODE
REQUIREMENTS.
2gxlq ELBOW CONNECTS TO PLENUM KEEP TIGHT TO BAR JOIST.
1.4VAC CONTRACTOR TO INSTALL GAS PIPING OR CONTRACT
LOCAL PLUMBING CO. GAS PIPING UP THROUGH BOTTOM OF
RTU -1 4 2.
CONTRACTOR TO VERIFY ROOF PITCH PRIOR TO BEGINNING
CONSTRUCTION
HVAC CONTRACTOR TO SET ROOF CURB COORDINATE FLASHING
WITH ROOFER.
COORDINATE THERMOSTAT LOCATIONS IN OFFICE WITH OFFICE
LAYOUT.
USE HONEYWELL T -8000 THERMOSTATS ON ALL UNITS WITH REMOTE SENSORS
1---
tD
u
Q
rf-
tn
0
NOTE
SYMBOL
OL
W
z
on INTERIOR ELEVATION
NOT TO SCALE
1-
Keyes Architects and Associates expressly reserves its common —law
copyright and other property rights in these documents. These documents
are considered proprietary information and shall not be upgraded, changed
or copied in any form or matter whatsoever nor are they to be assigned
to any third party without first obtaining the express written permission
and consent of Keyes Architects and Associates, 3005 Taylor Boulevard,
Louisville, Kentucky 40208
PROJECT NO:
08- STCO11
DRAWN BY:
BRB/LRS/CDM
DATE:
11-19-08
REVISIONS:
w X N
00
m d-
I —I o
H U
0 0 z U
Zw W z
z
W
U
El" E
O O w w
I— O
_J
ci) zw
Q m CI)
CL 5
N 2 O
O
U w
rrittito
MECHANICAL PLAN
AND DETAILS
Z
n
Z
W
M1.01
0
00
N
0
C
W Y
0 I—
co W
IX
O
J
H
o
o O