HomeMy WebLinkAboutC502 Utility DetailsSTORM SEWER NETWORK DATA TABLE
STRUCTURE TYPE SIZE DETAIL CASTING
CAST IRON CAP
INSTALLED FLUSH WITH
FINISHED GRADE IN
PAVEMENT AREAS
COMPACT GRANULAR
BACKFILL MATERIAL
UNDER PAVEMENT AREAS
2 45' BENDS OR
LONG RADIUS 90'
BEND
SA-1 NO SCALE
TC= ELEVATION
18 "x18 "x6" CONC. PAD
PVC CAP (SCH 40)
INSTALLED FLUSH WITH
FINISHED GRADE IN
UNPAVED AREAS
:111 111 111-11
BACKFILL WITH
SELECT EXCAVATED
MATERIAL FOR
UNPAVED AREAS
EXTENSION SAME
SIZE AS SEWER
UP TO 6" DIAMETER
SEWER CLEANOUT
TYPICAL SANITARY SEWER SPECIFICATIONS
TO BE USED FOR PRIVATE SEWER DEVELOPMENT
WITHIN
CLAY TOWNSHIP REGIONAL WASTE DISTRICT
REVISED MAY, 2002
1. Standard specifications of the Clay Township Regional Waste District (District) and Indiana
Department of Transportation shall apply for all work and materials. Pipe shall be installed in
accordance with Section 715 of the latest edition of the Indiana Department of Transportation
Standard Specifications.
2. Sanitary sewer pipe shall be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321.
PVC pipe shall have a grooved bell and gasket. The pipe shall be made of PVC plastic having a cell
classification of 12454B.
3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in
sizes through 8" shall be molded in one piece with elastomeric joints and minimum socket depths as
specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in
accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of
fittings shall be SDR 26 as defined in section 7.4.1 of specifications. Gaskets for elastomeric joints
shall be molded with a minimum cross sectional area of 0.20 square inches and conform to ASTM
F -477 specification.
4. All sanitary manholes shall be Aprecast concrete@ manholes in accordance with ASTM C -478 and
Section 720. 0 -rings shall conform to C -443. Kent Seal or equivalent shall also be applied to all
joints and between riser rings and castings. Manhole step spacing shall be no more than 16- inches.
Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method
for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test.
A Installation and operation of vacuum equipment and indicating devices must be in accordance with
manufacturer =s recommendations and performance specifications which have been provided by the
manufacturer and accepted by the Engineer. The vacuum equipment must be capable of testing the
entire manhole, including the casting and riser rings.
B. With the vacuum tester set in place:
1. Connect the vacuum pump to the outlet port with the valve open.
2. Draw a vacuum of ten (10) inches of Hg. and close the valve.
C. Accepted standards for leakage will be established from the elapsed time for a negative pressure
change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate
for a four (4) foot diameter manhole must be in accordance with the following:
Minimum Elapsed Time for a
Manhole Depth Pressure Change of 1 Inch Hg
10 feet or less 60 seconds
>10 feet but <15 feet 75 seconds
>15 feet but <25 feet 90 seconds
For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six
(6) feet in diameter, add an additional thirty (30) seconds to the time requirements for four (4) foot
diameter manholes. For all manholes deeper than twenty -five (25) feet. Engineer will determine the
applicable minimum elapsed time.
D. If the manhole fails the test, necessary repairs must be made and the vacuum test and
repairs must be repeated until the manhole passes the test.
E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be
disassembled and the joint sealants replaced.
F. Manholes will be subject to visual inspection with all visual leaks being repaired.
5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches
below each joint. The appropriate primer shall be applied prior to applying the rubber coating.
Inside joints to be filled with precoat plug material.
6. The manhole chimney =s including all riser rings shall be sealed using Infi Shield AUnibandc. or
approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall
be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section
to 2- inches over the flange of the manhole casting frame.
7. The casting elevations are set by plan. However, the castings are to be adjusted in the field by
the Engineer =s representative, should a discrepancy occur between plan grade and existing grade.
New manhole ring and cover shall be installed to establish grade. Maximum height of adjusting rings
shall be 12- inches.
8. Backfill around all structures and all cuts under paved areas with granular material. Trenches
opening within 5 -feet of paved roadways shall be backfilled with granular material in accordance with
Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum
of 6 months after backfill has been in place.
9. The Contractor shall be responsible for verifying that all state highways, city, and county permits
have been obtained by the developer prior to start of construction.
10. The Contractor shall be required to furnish the developer =s Engineer with a set of prints, marked
in red pencil, showing actual sewer location and invert, to include lateral location, depth and length.
Such Aas built@ prints must be received by the Engineer before the final contract payment can be
authorized. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a
metal fence post set immediately above the said termination point.
11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said
test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a
representative of the District. The testing shall be in accordance with Table 1. Add 0.5 psig for
each foot of water above the sewer line being tested.
12. Deflection tests shall be performed on all flexible* pipe after the final backfill has been in place
at least 30 days. No pipe shall exceed a vertical deflection of 5% deflection test results. *The
following are considered non flexible pipes: concrete pipe, ductile iron pipe, and cast iron pipe). The
deflection test shall be performed with a nine -point mandrel. Proving rings shall be available.
13. All mandrel testing shall be observed by a professional engineer representative for certification and
a representative of the District.
14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of
withstanding a low pressure air test without leakage.
15. Bedding for flexible pipe shall be No. 8 crushed stone from 6- inches below the pipe to
12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below
the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or
equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding.
16. Water and sewer line crossings and separations shall be in accordance with 327€AC 3 -6 -9.
17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be
properly protected and /or barricaded when left unattended.
18. No water shall be permitted to flow into the sanitary sewer system during construction.
Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be
directed to a storm outlet in accordance with state and federal laws and regulations (327 -IAC
3- 6 -20). Any pipe entering existing sewers shall be plugged with screw type mechanical, braced plug
until such time as all tests on the sewers have been completed and the lines have passed all punch
lists.
19. All sewer laterals installed by the mainline Contractor shall be bedded the same as the main line
sewer.
20. Forty -eight (48) hours notice shall be given to the District prior to the start of sewer
construction. Also, 48 hours notice shall be given prior to doing any testing done on the sewer.
21. Manhole castings shall be stamped SANITARY SEWER, Neenah Casting R 1642A or equal and be
self sealing type. The casting flange shall be 34 inches and the clear opening shall be 24 inches.
Waterproof castings shall be Neenah R- 1916 -F1 and stamped SANITARY SEWER.
22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are:
Size of Pipe Minimum Constructed Slope
8 -inch
10 -inch
12 -inch
15 -inch
18 -inch
0.40%
0.28%
0.22%
0.15%
0.12%
23. The Contractor shall provide measurements of the slope of the sewer for each manhole section
as construction progresses. Such measurements shall be certified by a Registered Land Surveyor or
Engineer and be available on -site for observation by the District =s Inspector. No more than three
manhole sections can be constructed in advance of such measurements.
24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other
affected sewer sections shall be reconstructed to meet such minimum slopes.
25. Laterals are to be traced with a minimum size of 14 gauge wire from the wye to the terminus.
The contractor for the building or home will extend the wire from this terminus to the building
cleanout adjacent to the building.
PLAN VIEW
Grooved end on outlet end
Tongue end on inlet end
`Grooved (or tongue) to be the
same as on Standard Reinforced
Concrete Pipe ASTM Designation
C 76
NOTES=
1 1/2' R
Pay length of culvert
1. CONCRETE IN THESE END SECTIONS SHALL BE THE SAME GRADE AND
STRENGTH AS SPECIFIED FOR REINFORCED CONCRETE PIPE, ASTM
DESIGNATION C 76 CLASS II. as set out in the Standard Spec's.)
2. REINFORCEMENT IN THE "C" PORTION SHALL BE THE SAME AS SPECIFIED
FOR REINFORCED CONCRETE, ASTM DESIGNATION C 76, CLASS II FOR THE
SIZE OF CONNECTING PIPE.
3. REINFORCEMENT IN THE "B" PORTION SHALL HAVE A CROSS SECTIONAL
AREA EQUAL TO THAT OF ONE LAYER OF STEEL IN THE "C" SECTION.
4. THE END OF PIPE CULVERT SHALL BE PLACED IN THE CONCRETE END
SECTION SO THAT THE FLOW LINES ARE FLUSH. THE JOINT SHALL BE
COMPLETELY FILLED WITH MORTAR.
5. IN 3:1 OR 4:1 FILL SLOPE, CHANGE TO THE SLOPE OF THE END SECTION
IN A SMOOTH, PLEASING TRANSITION APPROXIMATELY 10' -0" IN LENGTH.
6. VARIATIONS IN DIMENSIONS THE THICKNESS OF THE CONCRETE, THE
POSMON OF STEEL, AND THE INTERNAL DIAMETER OF THE PIPE SHALL
CONFORM WITH THE VARIATIONS IN DIMENSIONS AS PROVIDED IN THE
SPECIFICATIONS FOR REINFORCED CONCRETE CULVERT, STORM DRAIN,
AND SEWER PIPE, ASTM DESIGNATION C 76.
7. WHERE VITRIFIED CLAY CULVERT OR CAST IRON CULVERT PIPE
IS USED, A PIPE END SECTION COMPARABLE TO THAT AS SHOWN
FOR METAL OR CONCRETE SHALL BE FURNISHED AND SHALL BE AS
APPROVED BY THE PROJECT ENGINEER.
8. END SECTIONS WILL BE PAID FOR AT THE CONTRACT UNIT PRICE EACH
FOR PIPE END SECTION COMPLETE IN PLACE AND ACCEPTED.
9. CONCRETE PIPE TOE ANCHORS SHALL BE REQUIRED ON ALL CONCRETE
PIPE SECTIONS. THE COST THEREOF SHALL BE INCLUDED IN THE
CONTRACT UNIT PRICE PER EACH FOR PIPE END SECTIONS.
PRECAST
REINFORCED
CONCRETE
GROUT
BENCH r-
PRECAST OR MONOLITHIC BOTTOM
DIMENSION REFERS
TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
RE ELEV. RE ELEV.
MAX. 8" OF CONC. RISERS
-1 /2" MORTAR GROUT
(SIDES TOP OF
ADJUSTING RINGS)
SSD
(4' MAX. DEPTH)
s" "C" DIMENSION REFERS
MIN TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
CONCRETE THICKNESS
6"- UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
1 l
STEPS REQUIRED
o WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
SSD (4' MAX. DEPTH)
D
o •a a a
SECTION Y Y
SECTION A A
SLOPE DETAIL
DIMENSIONS OF PRECAST CONCRETE
STORM MANHOLE
WITH CONE TYPE REDUCER
NO SCALE
TC ELEVATION
FLAT TOP
STEPS REQUIRED
WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
CONCRETE THICKNESS
6 UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
STORM SEWER MANHOLE
WITH FLAT TOP REDUCER
:I ;I i 6 J NO SCALE
DIA, T (min) A x C x D x E x K Ri R2 Approx.
Welght
12' 2• 5' 4'-3' 6' -2' 2' 1.3 10 1/8' 9' 800
15' 2 1/4' 7' 4' -0 6' -3' 2' -6' 1.5 121/2' 11' 1100
18' 21/2' 11' 4' -1' 6'-2' 3' -0 1.8 15 1/2• 12' 1300
21' 2 3/4' 11' 3' -6' 6' -3' 3' -6' 2.1 16 1/8' 13' 1500
24' 3" 1' -0' 2' -8' 6'-3 4'-0' 2.3 16 3/16' 14' 1800
27" 3 1/4' 1' Y-5' 6' -3' 4'-6' 2.6 18 9/16' 14 1/2" 2100
30' 31/2' 1' 1' -10' 6'-3" 5' 2.9 18 1/2' 15' 2400
33 3 3/4' 1' -3 3' -6' 8' -3' 5' -6' 3.1 23 3/4' 17 1/2' 4100
36' 4• 1' -S 3' -1' 8' -3 6' -0' 3.4 24 5/16" 20' 4200
x Tolerance 1'
Riprap to be placed
on side slope when
called for on plans.
PRECAST BOTTOM SECTION
48" PRECAST RISER
REINFORCED CONCRETE
Bolts (See Sheet ME -1
END SECTIONS
NOTE INSPECT ALL SEWERS AS TO ELEVATION,
GRADIENT, ALIGNMENT JOINT BY INSPECTING
ENGINEER PRIOR TO BACKFILL OVER PIPE
4* MIN.
(BELOW THE BARREL
AREAS NOT SUBJECT TO VEHICULAR TRAFFIC MAY BE BACKFILLED WITH CLEAN FILL
MATERIAL FREE OF ANY ROCKS LARGER THAN 6 FROZEN SOIL WOOD OR OTHER
EXTRANEOUS MATERIALS.
NO SCALE
NO SCALE
MINIMUM WIDTH= 7/
1.25 O.D. 12"
i 1
,44 r mil
AV'
41:
tt
GRADE
SSD CONNECTION
4" MIN.
PRECAST CONC.
BOX
NO SCALE
SEE STORM INFORMATION FOR CASTING
AREAS SUBJECT TO
VEHICULAR TRAFFIC
BACKFILL WITH CLEAN
GRANULAR MATERIAL
PER REQUIREMENT OF
INDIANA DEPARTMENT
OF HIGHWAYS
(MECHANICAL COMPACTION
0 95% PROCTOR DENSITY)
1/2 O.D.
3" MIN.
(BELOW THE BELL)
L- CLEAN LOW VOID SAND
OR OTHER NON COMPRESSIBLE
FINE LOW VOID MATERIAL
APPROVED BY CITY ENGINEER
"B" BORROW
RIGID PIPE BEDDING DETAIL (STORM)
NO SCALE CONCRETE PIPE AND CMP
EJIW NEENAH TYPE USE A B
1022 -1 HD R- 1772 -A TYPE "A" INLET GRADED AREAS 30" 30"
1022 -3 HD R- 1772 -C TYPE "A" INLET TRAFFIC AREAS 30" 30"
7490 -M1 R- 3501 -N ROLL CURB LOW POINTS 30" 30"
7495 -LH -RH R- 3501 -TL -TR ROLL CURB FLOW LEFT OR RIGHT 30" 30"
6489 R -4342 DITCH GRATE SWALES 30" 30"
GROUT
BENCH
NOTE: SHALL BE MODIFIED WITH 30 "X30" INSIDE DIMENSION
AND A 4" FLAT TOP WITH A 4" DONUT.
PRECAST TYPE 'E' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PRECAST CONC.
BOX
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
PRECAST TYPE 'J' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PIP
PRECAST TYPE 'M' INLET
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
NOTES: SIR DETAIL WITH 2' SUMP
1. SEE STORM SEWER PLAN PROFILES SHEETS TO CONFIRM PIPE LENGTHS AND STRUCTURE INFORMATION
PRIOR TO FABRICATION.
NO SCALE
STORM STRUCTURE DATA
701 END SECTION 24" ST -3A
702* CATCH BASIN 5' ST -4* R -3472
703* CATCH BASIN 4' ST -4* R- 3286 -8V
704 INLET 24x36 ST -64 R- 1878 -B76
705 INLET 24x36 ST -64 R- 1878 -B76
706 INLET 24x36 ST -63 R- 1878 -B76
706A INLET 24x24 ST -63 R -3405
707* CATCH BASIN 4' ST -4* R- 3286 -8V
708 MANHOLE 4' ST -6 R- 3286 -8V
709 INLET 30x30 ST -37 R- 3286 -8V
710 INLET 30x30 ST -37 R- 4215 -C
711 MAHHOLE 4' ST -37 R -3472
712 INLET 30x30 ST -37 R- 3286 -8V
713 INLET 30x30 ST -37 R- 4215 -C
r
1
OUTLET
iv�� n O :l ?:.i is rt ".�,.:�'.i r.:.x�.i
GREASE /OIL INTERCEPTOR
PRECAST VAULT
CASTING SCHEDULE
EJIW NEENAH TYPE USE DIM
7490 -M1 R- 3501 -N CURB INLET LOW POINT 24" X 24"
7495 -LH -RH R-3501-TL-1R CURB INLET FLOW LEFT OR RIGHT 25" X 27"
R -3405 INLET PARKING LOT 25" X 25"
R -2501 GRATE PARKING LOT 24 "o
6489 R -4342 DITCH GRATE SWALES 24 "o
REQUIRES FLAT TOP WITH 24 '0 OPENING
NO SCALE
SSD CONNECTION
(4' MAX. DEPTH)
TC TOP OF CASTING ELEVATION
MODIFIED
PRECAST TYPE 'A' INLET
0:11994194501111
m
FIED BY:
A i
f
i i
ii
l NNi1OSg 1k
#;st.i., O'r it
4 p 8TFA S.
No.10200269 1 1
'o
9
Oo
STATE OF
4/0110"
Q
�v
4i
i'4`S ONA4ENG
oh/1!1111110
to al
Drown By:
MAW
Checked By:
DJO
Quality Aseu anca
DAL
Scale:
0 scaly 1' NA'
lime
Sheet
C502
Date
08-30-04
Project Number
94501 -10040
STORM SEWER NETWORK DATA TABLE
STRUCTURE TYPE SIZE DETAIL CASTING
CAST IRON CAP
INSTALLED FLUSH WITH
FINISHED GRADE IN
PAVEMENT AREAS
COMPACT GRANULAR
BACKFILL MATERIAL
UNDER PAVEMENT AREAS
2 45' BENDS OR
LONG RADIUS 90'
BEND
SA-1 NO SCALE
TC= ELEVATION
18 "x18 "x6" CONC. PAD
PVC CAP (SCH 40)
INSTALLED FLUSH WITH
FINISHED GRADE IN
UNPAVED AREAS
:111 111 111-11
BACKFILL WITH
SELECT EXCAVATED
MATERIAL FOR
UNPAVED AREAS
EXTENSION SAME
SIZE AS SEWER
UP TO 6" DIAMETER
SEWER CLEANOUT
TYPICAL SANITARY SEWER SPECIFICATIONS
TO BE USED FOR PRIVATE SEWER DEVELOPMENT
WITHIN
CLAY TOWNSHIP REGIONAL WASTE DISTRICT
REVISED MAY, 2002
1. Standard specifications of the Clay Township Regional Waste District (District) and Indiana
Department of Transportation shall apply for all work and materials. Pipe shall be installed in
accordance with Section 715 of the latest edition of the Indiana Department of Transportation
Standard Specifications.
2. Sanitary sewer pipe shall be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321.
PVC pipe shall have a grooved bell and gasket. The pipe shall be made of PVC plastic having a cell
classification of 12454B.
3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in
sizes through 8" shall be molded in one piece with elastomeric joints and minimum socket depths as
specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in
accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of
fittings shall be SDR 26 as defined in section 7.4.1 of specifications. Gaskets for elastomeric joints
shall be molded with a minimum cross sectional area of 0.20 square inches and conform to ASTM
F -477 specification.
4. All sanitary manholes shall be Aprecast concrete@ manholes in accordance with ASTM C -478 and
Section 720. 0 -rings shall conform to C -443. Kent Seal or equivalent shall also be applied to all
joints and between riser rings and castings. Manhole step spacing shall be no more than 16- inches.
Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method
for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test.
A Installation and operation of vacuum equipment and indicating devices must be in accordance with
manufacturer =s recommendations and performance specifications which have been provided by the
manufacturer and accepted by the Engineer. The vacuum equipment must be capable of testing the
entire manhole, including the casting and riser rings.
B. With the vacuum tester set in place:
1. Connect the vacuum pump to the outlet port with the valve open.
2. Draw a vacuum of ten (10) inches of Hg. and close the valve.
C. Accepted standards for leakage will be established from the elapsed time for a negative pressure
change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate
for a four (4) foot diameter manhole must be in accordance with the following:
Minimum Elapsed Time for a
Manhole Depth Pressure Change of 1 Inch Hg
10 feet or less 60 seconds
>10 feet but <15 feet 75 seconds
>15 feet but <25 feet 90 seconds
For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six
(6) feet in diameter, add an additional thirty (30) seconds to the time requirements for four (4) foot
diameter manholes. For all manholes deeper than twenty -five (25) feet. Engineer will determine the
applicable minimum elapsed time.
D. If the manhole fails the test, necessary repairs must be made and the vacuum test and
repairs must be repeated until the manhole passes the test.
E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be
disassembled and the joint sealants replaced.
F. Manholes will be subject to visual inspection with all visual leaks being repaired.
5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches
below each joint. The appropriate primer shall be applied prior to applying the rubber coating.
Inside joints to be filled with precoat plug material.
6. The manhole chimney =s including all riser rings shall be sealed using Infi Shield AUnibandc. or
approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall
be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section
to 2- inches over the flange of the manhole casting frame.
7. The casting elevations are set by plan. However, the castings are to be adjusted in the field by
the Engineer =s representative, should a discrepancy occur between plan grade and existing grade.
New manhole ring and cover shall be installed to establish grade. Maximum height of adjusting rings
shall be 12- inches.
8. Backfill around all structures and all cuts under paved areas with granular material. Trenches
opening within 5 -feet of paved roadways shall be backfilled with granular material in accordance with
Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum
of 6 months after backfill has been in place.
9. The Contractor shall be responsible for verifying that all state highways, city, and county permits
have been obtained by the developer prior to start of construction.
10. The Contractor shall be required to furnish the developer =s Engineer with a set of prints, marked
in red pencil, showing actual sewer location and invert, to include lateral location, depth and length.
Such Aas built@ prints must be received by the Engineer before the final contract payment can be
authorized. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a
metal fence post set immediately above the said termination point.
11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said
test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a
representative of the District. The testing shall be in accordance with Table 1. Add 0.5 psig for
each foot of water above the sewer line being tested.
12. Deflection tests shall be performed on all flexible* pipe after the final backfill has been in place
at least 30 days. No pipe shall exceed a vertical deflection of 5% deflection test results. *The
following are considered non flexible pipes: concrete pipe, ductile iron pipe, and cast iron pipe). The
deflection test shall be performed with a nine -point mandrel. Proving rings shall be available.
13. All mandrel testing shall be observed by a professional engineer representative for certification and
a representative of the District.
14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of
withstanding a low pressure air test without leakage.
15. Bedding for flexible pipe shall be No. 8 crushed stone from 6- inches below the pipe to
12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below
the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or
equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding.
16. Water and sewer line crossings and separations shall be in accordance with 327€AC 3 -6 -9.
17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be
properly protected and /or barricaded when left unattended.
18. No water shall be permitted to flow into the sanitary sewer system during construction.
Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be
directed to a storm outlet in accordance with state and federal laws and regulations (327 -IAC
3- 6 -20). Any pipe entering existing sewers shall be plugged with screw type mechanical, braced plug
until such time as all tests on the sewers have been completed and the lines have passed all punch
lists.
19. All sewer laterals installed by the mainline Contractor shall be bedded the same as the main line
sewer.
20. Forty -eight (48) hours notice shall be given to the District prior to the start of sewer
construction. Also, 48 hours notice shall be given prior to doing any testing done on the sewer.
21. Manhole castings shall be stamped SANITARY SEWER, Neenah Casting R 1642A or equal and be
self sealing type. The casting flange shall be 34 inches and the clear opening shall be 24 inches.
Waterproof castings shall be Neenah R- 1916 -F1 and stamped SANITARY SEWER.
22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are:
Size of Pipe Minimum Constructed Slope
8 -inch
10 -inch
12 -inch
15 -inch
18 -inch
0.40%
0.28%
0.22%
0.15%
0.12%
23. The Contractor shall provide measurements of the slope of the sewer for each manhole section
as construction progresses. Such measurements shall be certified by a Registered Land Surveyor or
Engineer and be available on -site for observation by the District =s Inspector. No more than three
manhole sections can be constructed in advance of such measurements.
24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other
affected sewer sections shall be reconstructed to meet such minimum slopes.
25. Laterals are to be traced with a minimum size of 14 gauge wire from the wye to the terminus.
The contractor for the building or home will extend the wire from this terminus to the building
cleanout adjacent to the building.
PLAN VIEW
Grooved end on outlet end
Tongue end on inlet end
`Grooved (or tongue) to be the
same as on Standard Reinforced
Concrete Pipe ASTM Designation
C 76
NOTES=
1 1/2' R
Pay length of culvert
1. CONCRETE IN THESE END SECTIONS SHALL BE THE SAME GRADE AND
STRENGTH AS SPECIFIED FOR REINFORCED CONCRETE PIPE, ASTM
DESIGNATION C 76 CLASS II. as set out in the Standard Spec's.)
2. REINFORCEMENT IN THE "C" PORTION SHALL BE THE SAME AS SPECIFIED
FOR REINFORCED CONCRETE, ASTM DESIGNATION C 76, CLASS II FOR THE
SIZE OF CONNECTING PIPE.
3. REINFORCEMENT IN THE "B" PORTION SHALL HAVE A CROSS SECTIONAL
AREA EQUAL TO THAT OF ONE LAYER OF STEEL IN THE "C" SECTION.
4. THE END OF PIPE CULVERT SHALL BE PLACED IN THE CONCRETE END
SECTION SO THAT THE FLOW LINES ARE FLUSH. THE JOINT SHALL BE
COMPLETELY FILLED WITH MORTAR.
5. IN 3:1 OR 4:1 FILL SLOPE, CHANGE TO THE SLOPE OF THE END SECTION
IN A SMOOTH, PLEASING TRANSITION APPROXIMATELY 10' -0" IN LENGTH.
6. VARIATIONS IN DIMENSIONS THE THICKNESS OF THE CONCRETE, THE
POSMON OF STEEL, AND THE INTERNAL DIAMETER OF THE PIPE SHALL
CONFORM WITH THE VARIATIONS IN DIMENSIONS AS PROVIDED IN THE
SPECIFICATIONS FOR REINFORCED CONCRETE CULVERT, STORM DRAIN,
AND SEWER PIPE, ASTM DESIGNATION C 76.
7. WHERE VITRIFIED CLAY CULVERT OR CAST IRON CULVERT PIPE
IS USED, A PIPE END SECTION COMPARABLE TO THAT AS SHOWN
FOR METAL OR CONCRETE SHALL BE FURNISHED AND SHALL BE AS
APPROVED BY THE PROJECT ENGINEER.
8. END SECTIONS WILL BE PAID FOR AT THE CONTRACT UNIT PRICE EACH
FOR PIPE END SECTION COMPLETE IN PLACE AND ACCEPTED.
9. CONCRETE PIPE TOE ANCHORS SHALL BE REQUIRED ON ALL CONCRETE
PIPE SECTIONS. THE COST THEREOF SHALL BE INCLUDED IN THE
CONTRACT UNIT PRICE PER EACH FOR PIPE END SECTIONS.
PRECAST
REINFORCED
CONCRETE
GROUT
BENCH r-
PRECAST OR MONOLITHIC BOTTOM
DIMENSION REFERS
TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
RE ELEV. RE ELEV.
MAX. 8" OF CONC. RISERS
-1 /2" MORTAR GROUT
(SIDES TOP OF
ADJUSTING RINGS)
SSD
(4' MAX. DEPTH)
s" "C" DIMENSION REFERS
MIN TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
CONCRETE THICKNESS
6"- UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
1 l
STEPS REQUIRED
o WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
SSD (4' MAX. DEPTH)
D
o •a a a
SECTION Y Y
SECTION A A
SLOPE DETAIL
DIMENSIONS OF PRECAST CONCRETE
STORM MANHOLE
WITH CONE TYPE REDUCER
NO SCALE
TC ELEVATION
FLAT TOP
STEPS REQUIRED
WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
CONCRETE THICKNESS
6 UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
STORM SEWER MANHOLE
WITH FLAT TOP REDUCER
:I ;I i 6 J NO SCALE
DIA, T (min) A x C x D x E x K Ri R2 Approx.
Welght
12' 2• 5' 4'-3' 6' -2' 2' 1.3 10 1/8' 9' 800
15' 2 1/4' 7' 4' -0 6' -3' 2' -6' 1.5 121/2' 11' 1100
18' 21/2' 11' 4' -1' 6'-2' 3' -0 1.8 15 1/2• 12' 1300
21' 2 3/4' 11' 3' -6' 6' -3' 3' -6' 2.1 16 1/8' 13' 1500
24' 3" 1' -0' 2' -8' 6'-3 4'-0' 2.3 16 3/16' 14' 1800
27" 3 1/4' 1' Y-5' 6' -3' 4'-6' 2.6 18 9/16' 14 1/2" 2100
30' 31/2' 1' 1' -10' 6'-3" 5' 2.9 18 1/2' 15' 2400
33 3 3/4' 1' -3 3' -6' 8' -3' 5' -6' 3.1 23 3/4' 17 1/2' 4100
36' 4• 1' -S 3' -1' 8' -3 6' -0' 3.4 24 5/16" 20' 4200
x Tolerance 1'
Riprap to be placed
on side slope when
called for on plans.
PRECAST BOTTOM SECTION
48" PRECAST RISER
REINFORCED CONCRETE
Bolts (See Sheet ME -1
END SECTIONS
NOTE INSPECT ALL SEWERS AS TO ELEVATION,
GRADIENT, ALIGNMENT JOINT BY INSPECTING
ENGINEER PRIOR TO BACKFILL OVER PIPE
4* MIN.
(BELOW THE BARREL
AREAS NOT SUBJECT TO VEHICULAR TRAFFIC MAY BE BACKFILLED WITH CLEAN FILL
MATERIAL FREE OF ANY ROCKS LARGER THAN 6 FROZEN SOIL WOOD OR OTHER
EXTRANEOUS MATERIALS.
NO SCALE
NO SCALE
MINIMUM WIDTH= 7/
1.25 O.D. 12"
i 1
,44 r mil
AV'
41:
tt
GRADE
SSD CONNECTION
4" MIN.
PRECAST CONC.
BOX
NO SCALE
SEE STORM INFORMATION FOR CASTING
AREAS SUBJECT TO
VEHICULAR TRAFFIC
BACKFILL WITH CLEAN
GRANULAR MATERIAL
PER REQUIREMENT OF
INDIANA DEPARTMENT
OF HIGHWAYS
(MECHANICAL COMPACTION
0 95% PROCTOR DENSITY)
1/2 O.D.
3" MIN.
(BELOW THE BELL)
L- CLEAN LOW VOID SAND
OR OTHER NON COMPRESSIBLE
FINE LOW VOID MATERIAL
APPROVED BY CITY ENGINEER
"B" BORROW
RIGID PIPE BEDDING DETAIL (STORM)
NO SCALE CONCRETE PIPE AND CMP
EJIW NEENAH TYPE USE A B
1022 -1 HD R- 1772 -A TYPE "A" INLET GRADED AREAS 30" 30"
1022 -3 HD R- 1772 -C TYPE "A" INLET TRAFFIC AREAS 30" 30"
7490 -M1 R- 3501 -N ROLL CURB LOW POINTS 30" 30"
7495 -LH -RH R- 3501 -TL -TR ROLL CURB FLOW LEFT OR RIGHT 30" 30"
6489 R -4342 DITCH GRATE SWALES 30" 30"
GROUT
BENCH
NOTE: SHALL BE MODIFIED WITH 30 "X30" INSIDE DIMENSION
AND A 4" FLAT TOP WITH A 4" DONUT.
PRECAST TYPE 'E' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PRECAST CONC.
BOX
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
PRECAST TYPE 'J' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PIP
PRECAST TYPE 'M' INLET
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
NOTES: SIR DETAIL WITH 2' SUMP
1. SEE STORM SEWER PLAN PROFILES SHEETS TO CONFIRM PIPE LENGTHS AND STRUCTURE INFORMATION
PRIOR TO FABRICATION.
NO SCALE
STORM STRUCTURE DATA
701 END SECTION 24" ST -3A
702* CATCH BASIN 5' ST -4* R -3472
703* CATCH BASIN 4' ST -4* R- 3286 -8V
704 INLET 24x36 ST -64 R- 1878 -B76
705 INLET 24x36 ST -64 R- 1878 -B76
706 INLET 24x36 ST -63 R- 1878 -B76
706A INLET 24x24 ST -63 R -3405
707* CATCH BASIN 4' ST -4* R- 3286 -8V
708 MANHOLE 4' ST -6 R- 3286 -8V
709 INLET 30x30 ST -37 R- 3286 -8V
710 INLET 30x30 ST -37 R- 4215 -C
711 MAHHOLE 4' ST -37 R -3472
712 INLET 30x30 ST -37 R- 3286 -8V
713 INLET 30x30 ST -37 R- 4215 -C
r
1
OUTLET
iv�� n O :l ?:.i is rt ".�,.:�'.i r.:.x�.i
GREASE /OIL INTERCEPTOR
PRECAST VAULT
CASTING SCHEDULE
EJIW NEENAH TYPE USE DIM
7490 -M1 R- 3501 -N CURB INLET LOW POINT 24" X 24"
7495 -LH -RH R-3501-TL-1R CURB INLET FLOW LEFT OR RIGHT 25" X 27"
R -3405 INLET PARKING LOT 25" X 25"
R -2501 GRATE PARKING LOT 24 "o
6489 R -4342 DITCH GRATE SWALES 24 "o
REQUIRES FLAT TOP WITH 24 '0 OPENING
NO SCALE
SSD CONNECTION
(4' MAX. DEPTH)
TC TOP OF CASTING ELEVATION
MODIFIED
PRECAST TYPE 'A' INLET
0:11994194501111
co
STORM SEWER NETWORK DATA TABLE
STRUCTURE TYPE SIZE DETAIL CASTING
CAST IRON CAP
INSTALLED FLUSH WITH
FINISHED GRADE IN
PAVEMENT AREAS
COMPACT GRANULAR
BACKFILL MATERIAL
UNDER PAVEMENT AREAS
2 45' BENDS OR
LONG RADIUS 90'
BEND
SA-1 NO SCALE
TC= ELEVATION
18 "x18 "x6" CONC. PAD
PVC CAP (SCH 40)
INSTALLED FLUSH WITH
FINISHED GRADE IN
UNPAVED AREAS
:111 111 111-11
BACKFILL WITH
SELECT EXCAVATED
MATERIAL FOR
UNPAVED AREAS
EXTENSION SAME
SIZE AS SEWER
UP TO 6" DIAMETER
SEWER CLEANOUT
TYPICAL SANITARY SEWER SPECIFICATIONS
TO BE USED FOR PRIVATE SEWER DEVELOPMENT
WITHIN
CLAY TOWNSHIP REGIONAL WASTE DISTRICT
REVISED MAY, 2002
1. Standard specifications of the Clay Township Regional Waste District (District) and Indiana
Department of Transportation shall apply for all work and materials. Pipe shall be installed in
accordance with Section 715 of the latest edition of the Indiana Department of Transportation
Standard Specifications.
2. Sanitary sewer pipe shall be PVC in accordance with ASTM D -3034 (S.D.R. 35) and ASTM 2321.
PVC pipe shall have a grooved bell and gasket. The pipe shall be made of PVC plastic having a cell
classification of 12454B.
3. PVC sewer fittings shall conform to the requirements of ASTM D- 3034 -89 specification. Fittings in
sizes through 8" shall be molded in one piece with elastomeric joints and minimum socket depths as
specified in sections 6.2 and 7.3.2. Fittings 10" and larger shall be molded or fabricated in
accordance with section 7.11 with manufacturers standard pipe bells and gaskets. Wall thickness of
fittings shall be SDR 26 as defined in section 7.4.1 of specifications. Gaskets for elastomeric joints
shall be molded with a minimum cross sectional area of 0.20 square inches and conform to ASTM
F -477 specification.
4. All sanitary manholes shall be Aprecast concrete@ manholes in accordance with ASTM C -478 and
Section 720. 0 -rings shall conform to C -443. Kent Seal or equivalent shall also be applied to all
joints and between riser rings and castings. Manhole step spacing shall be no more than 16- inches.
Manholes shall be air tested for leakage in accordance with ASTM C1244 -93, Standard Test Method
for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test.
A Installation and operation of vacuum equipment and indicating devices must be in accordance with
manufacturer =s recommendations and performance specifications which have been provided by the
manufacturer and accepted by the Engineer. The vacuum equipment must be capable of testing the
entire manhole, including the casting and riser rings.
B. With the vacuum tester set in place:
1. Connect the vacuum pump to the outlet port with the valve open.
2. Draw a vacuum of ten (10) inches of Hg. and close the valve.
C. Accepted standards for leakage will be established from the elapsed time for a negative pressure
change from ten (10) inches to nine (9) inches of mercury. The maximum allowable leakage rate
for a four (4) foot diameter manhole must be in accordance with the following:
Minimum Elapsed Time for a
Manhole Depth Pressure Change of 1 Inch Hg
10 feet or less 60 seconds
>10 feet but <15 feet 75 seconds
>15 feet but <25 feet 90 seconds
For manholes five (5) feet in diameter, add an additional fifteen (15) seconds and for manholes six
(6) feet in diameter, add an additional thirty (30) seconds to the time requirements for four (4) foot
diameter manholes. For all manholes deeper than twenty -five (25) feet. Engineer will determine the
applicable minimum elapsed time.
D. If the manhole fails the test, necessary repairs must be made and the vacuum test and
repairs must be repeated until the manhole passes the test.
E. If manhole joint sealants are pulled out during the vacuum test, the manhole must be
disassembled and the joint sealants replaced.
F. Manholes will be subject to visual inspection with all visual leaks being repaired.
5. Butyl rubber coating shall be applied around each manhole joint from 6- inches above to 6- inches
below each joint. The appropriate primer shall be applied prior to applying the rubber coating.
Inside joints to be filled with precoat plug material.
6. The manhole chimney =s including all riser rings shall be sealed using Infi Shield AUnibandc. or
approved equal. Prior to placement, the top 4- inches of the manhole cone and casting frame shall
be cleaned and primed. The Uniband shall extend from 3- inches below the top of the cone section
to 2- inches over the flange of the manhole casting frame.
7. The casting elevations are set by plan. However, the castings are to be adjusted in the field by
the Engineer =s representative, should a discrepancy occur between plan grade and existing grade.
New manhole ring and cover shall be installed to establish grade. Maximum height of adjusting rings
shall be 12- inches.
8. Backfill around all structures and all cuts under paved areas with granular material. Trenches
opening within 5 -feet of paved roadways shall be backfilled with granular material in accordance with
Section 211. Backfill under sidewalks shall be granular, unless the walks are constructed a minimum
of 6 months after backfill has been in place.
9. The Contractor shall be responsible for verifying that all state highways, city, and county permits
have been obtained by the developer prior to start of construction.
10. The Contractor shall be required to furnish the developer =s Engineer with a set of prints, marked
in red pencil, showing actual sewer location and invert, to include lateral location, depth and length.
Such Aas built@ prints must be received by the Engineer before the final contract payment can be
authorized. The sanitary sewer laterals and stubs termination shall be indicated on the surface with a
metal fence post set immediately above the said termination point.
11. All sanitary sewer lines upon completion will be required to pass a low pressure air test. Said
test shall be conducted according to ASTM 1417 -92, and shall be witnessed by an Engineer and a
representative of the District. The testing shall be in accordance with Table 1. Add 0.5 psig for
each foot of water above the sewer line being tested.
12. Deflection tests shall be performed on all flexible* pipe after the final backfill has been in place
at least 30 days. No pipe shall exceed a vertical deflection of 5% deflection test results. *The
following are considered non flexible pipes: concrete pipe, ductile iron pipe, and cast iron pipe). The
deflection test shall be performed with a nine -point mandrel. Proving rings shall be available.
13. All mandrel testing shall be observed by a professional engineer representative for certification and
a representative of the District.
14. The ends of laterals are to be plugged tight with a braced plastic disc or cap capable of
withstanding a low pressure air test without leakage.
15. Bedding for flexible pipe shall be No. 8 crushed stone from 6- inches below the pipe to
12- inches above the pipe. Bedding for rigid pipe shall be No. 8 crushed stone from 6- inches below
the pipe to the spring line of the pipe and from this point to 12- inches above shall be fill sand or
equivalent. Manholes shall be placed on no less than 6- inches of No. 8 crushed stone bedding.
16. Water and sewer line crossings and separations shall be in accordance with 327€AC 3 -6 -9.
17. Trench shall be opened sufficiently ahead of pipe laying to reveal obstruction, and shall be
properly protected and /or barricaded when left unattended.
18. No water shall be permitted to flow into the sanitary sewer system during construction.
Contractor shall utilize a pump to keep the water level below the pipe. Pump discharge shall be
directed to a storm outlet in accordance with state and federal laws and regulations (327 -IAC
3- 6 -20). Any pipe entering existing sewers shall be plugged with screw type mechanical, braced plug
until such time as all tests on the sewers have been completed and the lines have passed all punch
lists.
19. All sewer laterals installed by the mainline Contractor shall be bedded the same as the main line
sewer.
20. Forty -eight (48) hours notice shall be given to the District prior to the start of sewer
construction. Also, 48 hours notice shall be given prior to doing any testing done on the sewer.
21. Manhole castings shall be stamped SANITARY SEWER, Neenah Casting R 1642A or equal and be
self sealing type. The casting flange shall be 34 inches and the clear opening shall be 24 inches.
Waterproof castings shall be Neenah R- 1916 -F1 and stamped SANITARY SEWER.
22. The minimum slope for sewer acceptance by the Clay Township Regional Waste District are:
Size of Pipe Minimum Constructed Slope
8 -inch
10 -inch
12 -inch
15 -inch
18 -inch
0.40%
0.28%
0.22%
0.15%
0.12%
23. The Contractor shall provide measurements of the slope of the sewer for each manhole section
as construction progresses. Such measurements shall be certified by a Registered Land Surveyor or
Engineer and be available on -site for observation by the District =s Inspector. No more than three
manhole sections can be constructed in advance of such measurements.
24. In the event the Contractor does not meet the minimum slopes, the sewer section and any other
affected sewer sections shall be reconstructed to meet such minimum slopes.
25. Laterals are to be traced with a minimum size of 14 gauge wire from the wye to the terminus.
The contractor for the building or home will extend the wire from this terminus to the building
cleanout adjacent to the building.
PLAN VIEW
Grooved end on outlet end
Tongue end on inlet end
`Grooved (or tongue) to be the
same as on Standard Reinforced
Concrete Pipe ASTM Designation
C 76
NOTES=
1 1/2' R
Pay length of culvert
1. CONCRETE IN THESE END SECTIONS SHALL BE THE SAME GRADE AND
STRENGTH AS SPECIFIED FOR REINFORCED CONCRETE PIPE, ASTM
DESIGNATION C 76 CLASS II. as set out in the Standard Spec's.)
2. REINFORCEMENT IN THE "C" PORTION SHALL BE THE SAME AS SPECIFIED
FOR REINFORCED CONCRETE, ASTM DESIGNATION C 76, CLASS II FOR THE
SIZE OF CONNECTING PIPE.
3. REINFORCEMENT IN THE "B" PORTION SHALL HAVE A CROSS SECTIONAL
AREA EQUAL TO THAT OF ONE LAYER OF STEEL IN THE "C" SECTION.
4. THE END OF PIPE CULVERT SHALL BE PLACED IN THE CONCRETE END
SECTION SO THAT THE FLOW LINES ARE FLUSH. THE JOINT SHALL BE
COMPLETELY FILLED WITH MORTAR.
5. IN 3:1 OR 4:1 FILL SLOPE, CHANGE TO THE SLOPE OF THE END SECTION
IN A SMOOTH, PLEASING TRANSITION APPROXIMATELY 10' -0" IN LENGTH.
6. VARIATIONS IN DIMENSIONS THE THICKNESS OF THE CONCRETE, THE
POSMON OF STEEL, AND THE INTERNAL DIAMETER OF THE PIPE SHALL
CONFORM WITH THE VARIATIONS IN DIMENSIONS AS PROVIDED IN THE
SPECIFICATIONS FOR REINFORCED CONCRETE CULVERT, STORM DRAIN,
AND SEWER PIPE, ASTM DESIGNATION C 76.
7. WHERE VITRIFIED CLAY CULVERT OR CAST IRON CULVERT PIPE
IS USED, A PIPE END SECTION COMPARABLE TO THAT AS SHOWN
FOR METAL OR CONCRETE SHALL BE FURNISHED AND SHALL BE AS
APPROVED BY THE PROJECT ENGINEER.
8. END SECTIONS WILL BE PAID FOR AT THE CONTRACT UNIT PRICE EACH
FOR PIPE END SECTION COMPLETE IN PLACE AND ACCEPTED.
9. CONCRETE PIPE TOE ANCHORS SHALL BE REQUIRED ON ALL CONCRETE
PIPE SECTIONS. THE COST THEREOF SHALL BE INCLUDED IN THE
CONTRACT UNIT PRICE PER EACH FOR PIPE END SECTIONS.
PRECAST
REINFORCED
CONCRETE
GROUT
BENCH r-
PRECAST OR MONOLITHIC BOTTOM
DIMENSION REFERS
TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
RE ELEV. RE ELEV.
MAX. 8" OF CONC. RISERS
-1 /2" MORTAR GROUT
(SIDES TOP OF
ADJUSTING RINGS)
SSD
(4' MAX. DEPTH)
s" "C" DIMENSION REFERS
MIN TO MAXIMUM PIPE SIZE
W/ 45' OR LESS ANGLE,
90' MAY BE MORE
CONCRETE THICKNESS
6"- UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
1 l
STEPS REQUIRED
o WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
SSD (4' MAX. DEPTH)
D
o •a a a
SECTION Y Y
SECTION A A
SLOPE DETAIL
DIMENSIONS OF PRECAST CONCRETE
STORM MANHOLE
WITH CONE TYPE REDUCER
NO SCALE
TC ELEVATION
FLAT TOP
STEPS REQUIRED
WHERE DEPTH EXCEEDS
6'. USE NEENAH
R- 1981 -1 OR EQUAL
CONCRETE THICKNESS
6 UP TO 8' DEPTH
8 UP TO 12' DEPTH
12 OVER 12' DEPTH
STORM SEWER MANHOLE
WITH FLAT TOP REDUCER
:I ;I i 6 J NO SCALE
DIA, T (min) A x C x D x E x K Ri R2 Approx.
Welght
12' 2• 5' 4'-3' 6' -2' 2' 1.3 10 1/8' 9' 800
15' 2 1/4' 7' 4' -0 6' -3' 2' -6' 1.5 121/2' 11' 1100
18' 21/2' 11' 4' -1' 6'-2' 3' -0 1.8 15 1/2• 12' 1300
21' 2 3/4' 11' 3' -6' 6' -3' 3' -6' 2.1 16 1/8' 13' 1500
24' 3" 1' -0' 2' -8' 6'-3 4'-0' 2.3 16 3/16' 14' 1800
27" 3 1/4' 1' Y-5' 6' -3' 4'-6' 2.6 18 9/16' 14 1/2" 2100
30' 31/2' 1' 1' -10' 6'-3" 5' 2.9 18 1/2' 15' 2400
33 3 3/4' 1' -3 3' -6' 8' -3' 5' -6' 3.1 23 3/4' 17 1/2' 4100
36' 4• 1' -S 3' -1' 8' -3 6' -0' 3.4 24 5/16" 20' 4200
x Tolerance 1'
Riprap to be placed
on side slope when
called for on plans.
PRECAST BOTTOM SECTION
48" PRECAST RISER
REINFORCED CONCRETE
Bolts (See Sheet ME -1
END SECTIONS
NOTE INSPECT ALL SEWERS AS TO ELEVATION,
GRADIENT, ALIGNMENT JOINT BY INSPECTING
ENGINEER PRIOR TO BACKFILL OVER PIPE
4* MIN.
(BELOW THE BARREL
AREAS NOT SUBJECT TO VEHICULAR TRAFFIC MAY BE BACKFILLED WITH CLEAN FILL
MATERIAL FREE OF ANY ROCKS LARGER THAN 6 FROZEN SOIL WOOD OR OTHER
EXTRANEOUS MATERIALS.
NO SCALE
NO SCALE
MINIMUM WIDTH= 7/
1.25 O.D. 12"
i 1
,44 r mil
AV'
41:
tt
GRADE
SSD CONNECTION
4" MIN.
PRECAST CONC.
BOX
NO SCALE
SEE STORM INFORMATION FOR CASTING
AREAS SUBJECT TO
VEHICULAR TRAFFIC
BACKFILL WITH CLEAN
GRANULAR MATERIAL
PER REQUIREMENT OF
INDIANA DEPARTMENT
OF HIGHWAYS
(MECHANICAL COMPACTION
0 95% PROCTOR DENSITY)
1/2 O.D.
3" MIN.
(BELOW THE BELL)
L- CLEAN LOW VOID SAND
OR OTHER NON COMPRESSIBLE
FINE LOW VOID MATERIAL
APPROVED BY CITY ENGINEER
"B" BORROW
RIGID PIPE BEDDING DETAIL (STORM)
NO SCALE CONCRETE PIPE AND CMP
EJIW NEENAH TYPE USE A B
1022 -1 HD R- 1772 -A TYPE "A" INLET GRADED AREAS 30" 30"
1022 -3 HD R- 1772 -C TYPE "A" INLET TRAFFIC AREAS 30" 30"
7490 -M1 R- 3501 -N ROLL CURB LOW POINTS 30" 30"
7495 -LH -RH R- 3501 -TL -TR ROLL CURB FLOW LEFT OR RIGHT 30" 30"
6489 R -4342 DITCH GRATE SWALES 30" 30"
GROUT
BENCH
NOTE: SHALL BE MODIFIED WITH 30 "X30" INSIDE DIMENSION
AND A 4" FLAT TOP WITH A 4" DONUT.
PRECAST TYPE 'E' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PRECAST CONC.
BOX
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
PRECAST TYPE 'J' INLET
SEE STORM SEWER NETWORK TABLE FOR CASTING
PIP
PRECAST TYPE 'M' INLET
NOTE:
1. In accordance with Indiana State
Highway Specifications
2. Minimum Concrete Compressive
Strength 4000 P.S.I.
3. Precast adjusting sections available.
NOTES: SIR DETAIL WITH 2' SUMP
1. SEE STORM SEWER PLAN PROFILES SHEETS TO CONFIRM PIPE LENGTHS AND STRUCTURE INFORMATION
PRIOR TO FABRICATION.
NO SCALE
STORM STRUCTURE DATA
701 END SECTION 24" ST -3A
702* CATCH BASIN 5' ST -4* R -3472
703* CATCH BASIN 4' ST -4* R- 3286 -8V
704 INLET 24x36 ST -64 R- 1878 -B76
705 INLET 24x36 ST -64 R- 1878 -B76
706 INLET 24x36 ST -63 R- 1878 -B76
706A INLET 24x24 ST -63 R -3405
707* CATCH BASIN 4' ST -4* R- 3286 -8V
708 MANHOLE 4' ST -6 R- 3286 -8V
709 INLET 30x30 ST -37 R- 3286 -8V
710 INLET 30x30 ST -37 R- 4215 -C
711 MAHHOLE 4' ST -37 R -3472
712 INLET 30x30 ST -37 R- 3286 -8V
713 INLET 30x30 ST -37 R- 4215 -C
r
1
OUTLET
iv�� n O :l ?:.i is rt ".�,.:�'.i r.:.x�.i
GREASE /OIL INTERCEPTOR
PRECAST VAULT
CASTING SCHEDULE
EJIW NEENAH TYPE USE DIM
7490 -M1 R- 3501 -N CURB INLET LOW POINT 24" X 24"
7495 -LH -RH R-3501-TL-1R CURB INLET FLOW LEFT OR RIGHT 25" X 27"
R -3405 INLET PARKING LOT 25" X 25"
R -2501 GRATE PARKING LOT 24 "o
6489 R -4342 DITCH GRATE SWALES 24 "o
REQUIRES FLAT TOP WITH 24 '0 OPENING
NO SCALE
SSD CONNECTION
(4' MAX. DEPTH)
TC TOP OF CASTING ELEVATION
MODIFIED
PRECAST TYPE 'A' INLET
0:11994194501111