HomeMy WebLinkAboutC06.0 Watermain Distribution PlanCITY OF CARMEL WATER UTILITIES PROJECT LEGEND PROJECT NAME: MONON AND MAIN JOB NO. STREET NAME MAIN STREET (131ST STREET PIPE SIZE 8" PIPE TYPE D.I. PIPE TOTAL 8' PRESSURE CLASS 350 1 2 GIRARDIN BLVD. 8" D.I. 201' 350 2 GIRARDIN BLVD. 6" D.I. 101' 350 3 ELWOOD AVE. 8" D.I. 206' 350 3 ELWOOD AVE. 6" D.I. 18' 350 4 3RD AVE. NW 8" D.I. 173' 350 4 3RD AVE. NW 6" D.I. 28' 350 5 FLORENCE ST. 8" D.I. 210' 350 5 FLORENCE ST. 6" D.I. 56' 350 PRESSURE PIPE JOINT RESTRAINT TABLE LENGTH OF PIPE TO BE RESTRAINED IN EACH DIRECTION FROM CENTERUNE OF BEND BASED ON 150 PSI TEST PRESSURE DEGREE OF BEND 6 8* 10" 12" 14" 16" 18" 20" 24" 30" 90' TEES PLUGS 27 35' 42' 50' 58' 65' 73' 80' 95' 115' 45' 7' 9' 11' 13' 1 15' 17' 19' 21' 24' 29' 224 3' 4' 5' 6' 7' 8' 9' 10' 12' 14' 114 2' 2' 3' 3' 4' 4' 4' 5' 6' 7' DWN BY: GCB CHKD. BY: BSC SCALE: 1" 30' DATE: 10/19/05 FLAIR NORTH, SECTIO\ ONE L ot 22 (Plat Book 2, page 277) FH WV O ®WV La, 21 R -4 R -2 Man Hole (Telephone) RESTRAINED JOINTS SHALL BE MECHANICAL JOINT WITH MEGA -LUG GLANDS, US PIPE TR FLEX JOINT SYSTEM, US PIPE FIELD LOK GASKET SYSTEM, OR EQUAL fE RESTRAINED JOINT LENGTHS ARE MINIMUM LENGTHS. JOINT RESTRAINT TABLE Lo2O m CD BLDG. #6 EX. 8" WATER 1 MAIN (CONTRACTOR 'TO FIELD VRIFY SIZE, LOCATIOk AND DEPTH) ALDEN WAY (PRIVATE) BLDG. #7 (PRIVATE) BLDG. #4 1 1/2" LATERAL 1 1/2" LATERAL HYD. W /6" VALVE" WATER I.t w w w w 6" VALVE 8 "X8 "X6" TEE BLDG. #5 1 1 /i" LATERAL NEUMAN WAY HYD. W /6" VALVE 45' BEND I w 8"X8 "X6" TEE WATER I p. f BLDG. #9 BLDG. #10 donor i 1 1 1 1 1 BLDG. #3 1 EX. 8" WATER MAIN 1 (CONTRACTOR TO FIELD VEIRIFY SIZ LOCATION! AND DEPTH) J HYD. W /6 VALVE EYDEN CROSSING (PRIVATE) 8"X8"X6" TE 22.5' BEND 5' BEND 2" LATERAL 6" WATER BLDG. #18 BLDG. #2 BLDG. #17 1 1 /2" LATERAL HYD. W /6" VALVE-/ NORDYKE AVE. (PRIVATE) WET TA 8"X8 "X6" TEE 1 1/2" LATERAL BLDG. #16 -4111111, CONSTRUCTION LIMITS 10' LANDSCAPE SETBACK BLDG. #8 2" WATERMAIN BEDDING NOTE INFRASTRUCTURE NOTE LATERAL HYD. W /0" VALVE ALL DUCTILE IRON WATERMAINS SHALL BE BEDDED IN SAND, FROM THE BOTTOM OF THE TRENCH TO 12 INCHES ABOVE THE PIPE. ALL INFRASTRUCTURE SHALL BE INSTALLED IN ACCORDANCE WITH THE LOCAL GOVERNING AUTHORITY'S CONSTRUCTION STANDARDS. 1 WET: TA 8"X8" -TEE _L 2" LATO2AL WV yhV Storm inlet BLDG. #13 0 O Now e�• HYD. W /6" VALVE CONSTRUCTION LIMITS OLD 91.98' 101 o" EX MAIN MATERIALS NOTE B -3 All water main pipes shall be DUCTILE IRON CLASS 350. All water main fittings shall be ductile iron, cement mortar lined inside, bituminous coal tar coated outside in accordance with ANSI /AWWA C110. All buried fittings shall be of the mechanical joint type with MEGALUG joint restraints. All water service lines shall be Type "K" copper tubing conforming to ASTM B -88 and B -251. ONLY MUELLER HYDRANTS AND VALVES MAY BE USED BLUE REFLECTIVE TAPE MUST BE INSTALLED 18 INCHES ABOVE ALL WATER MAINS MEGULUGS BLOCKS TO BE USED FOR PIPE RESTRAINTS AND KICKERS NO POURED CONCRETE AROUND HYDRANTS OR FITTINGS ALL VALVES REQUIRE POSI -CAPS OR BOX -LOK TOW \E VILLIAGE (Instrument Number 9709749345) (Plat Cabinet 2, Slide 49) 0 O 6" VALVE O N Q...oncf ete 3 Lot 2 R -4 8 VALVE to 60.01' l II 1 I I WATER 1 1/r LATERAL TBM #1 BENCHMARK NOTE i1 +WM HYD. W /6" VALVE Sto r� Inlet o WV it a REV DATE DESCRIPTION DES BY APP BY m TBM 111- 1094 -01 FND. CUT 'o' TOP EAST FACE OF LITHE POLE CONCRETE BASE; LOCATED 300' SOUTH OF CARMEL DRIVE, ON WEST SIDE OF ASPHALT DRIVE AND AT SE CORNER OF #1185 CARMEL DRIVE LOT 3, OUTLOT 17 IN CARMEL SCIENCE TECHNOLOGY PARK. ELEVATION 847.83 NW CORNER TRANSFORMER PAD LOCATED 40' SOUTH OF THE CENTERUNE FO 122ND STREET AND 50 WEST OF THE CENTERUNE OF CONGRESSIONAL BOULEVARD. ELEVATION 843.80 REVISION RECORD "DON'T DIG BLIND" NORTH IN FEET 1 inch 30 ft. "HOLEY MOLEY" SEZ: "IT'S THE LAW" INDIANA UNDERGROUND PROTECTION SERVICE INC. CALL TWO WORKING DAYS BEFORE YOU DIG 1- 800 382 -5544 CALL TOLL FREE 1- 800 428 -5200 FOR CALLS OUTSIDE OF INDIANA NOTES: 1. ALL DUCTILE IRON WATERMAINS SHALL BE BEDDED IN SAND, FROM THE BOTTOM OF THE TRENCH TO 12" ABOVE THE PIPE. 2. TRACER WIRE MUST BE INSTALLED WITH ALL WATER MAINS. 3. WARNING TAPE MUST BE INSTALLED 12" TO 18" ABOVE THE WATER MAIN. Water and Sewer Under City Streets Bedding, Haunching, Initial Backfill Bedding, haunching and initial backfill materials, placement and compaction for water mains, water service laterals, sanitary mains and sanitary service laterals shall be in accordance with the standard practice of the utility that has jurisdiction over the installation. Final Backfill Final backfill for water mains, water service laterals, sanitary mains and sanitary service laterals under and within 5 —feet of pavement shall be B— Borrow for Structure Backfill meeting the material requirements of the 1NDOT and shall be compacted in 6 —inch maximum lifts to not less than 95% Standard Proctor Density for the entire depth of the material placed. The backfill for the top 6— inches of the excavation below the start of the aggregate subbase of the pavement shall be No. 53 Stone meeting the material requirements of the INDOT and shall be compacted to not less than 95% Standard Proctor Density. If the standard practice of the utility that has jurisdiction over the installation has a more stringent final backfill requirement, the more stringent requirement shall govern. Minimum Cover for Pipe Crossings of City Streets For installation of Storm Mains, Water Mains, Sanitary Mains, Water Service Laterals, Sanitary Service Laterals under City streets, regardless of the jurisdiction of the utility, the minimum cover from the top of the installed pavement to the top of the installed pipe shall be the pavement section thickness (all bituminous and aggregate material above the subgrade) plus 1 —0". If the standard practice of the utility that has jurisdiction over the installation has a more stringent cover requirement, the more stringent requirement shall govern. RCP storm sewer minimum cover heights which are less than those described will be evaluated on a case by case condition and approved only with written permission by the city engineer. ot ttt$ I Itr,I t% 0 GL 1 /4'S ,i p -E F 2� Ii N o PE10403858 STATE OF i i �O :MOIAN 4</ 'frs SS /ONA` V DATE: Z a CEC PROJECT NUMBER 051872 DRAWING NUMBER C6.0 SHEET 10OF 16