HomeMy WebLinkAbout04090014 Townhomes at Guilford, Construction Plans pg. 231 1 PPV, LLC 9551 Delegate's Row, Indianapolis, Indiana 46240 Degree Of Bend 6" 8" 10" 12" 14" 16" 18" 20" 24" 30" 90; Tees Plugs 27' 35' E 50' 58' 65' 73' PRESSURE PIPE JOINT RESTRAINT TABLE Length Of Pipe To Be Restrained In Each Direction From 1/4 Of Bend Based On 150 PSI Test Pressure Degree Of Bend 6" 8" 10" 12" 14" 16" 18" 20" 24" 30" 90; Tees Plugs 27' 35' 42' 50' 58' 65' 73' 80' 95' 115' 45° 7' 9' 11' 13' 15' 17' 19' 21' 24' 29' 22 -1/2' 3' 4' 5' 6' 7' 8' 9' 10' 12' 14' 11 -1/4° 2' 2' 3' 3' 4' 4' 4' 5' 6' 7' DATE: 9/3/04 PROJECT NO.: 4831.002 DRAWN BY: DCC CHECKED BY: SHEET TITLE: WATER DETAILS AND SPECIFICATIONS DRAWING FILES: N: \4K \4831 \002 \DWGS \C702.DWG SHEET NO.: C702 BLOCKING FOR PLUGS BENDS BLOCKING FOR TEES WYES PIPE SIZE OUTSIDE FACE AREA (SQ. FT.) SIZE OF 1 SIZE OF RUN BRANCH OUTSIDE FACE AREA (SQ. FT.) PLUG 90' BEND 45' BEND I 22 1/2' 11 1/4' 20" 16 25 14 7 4 20" 16" 12 16" 12 16 9 5 3 12" 7 OR 1(C 1 12" 7 9 5 3 2 16" 5 10" 4 7 4 2 1 12" 7 8" 3 5 3 2 1 12" 10" 6 OR 8" 4 6" 2 3 2 1 1 6" 2 4" 2 3 2 1 1 LESS 4" 2 SCOPE OF WORK: A. The work required under this section includes all cold water distribution lines, valves, and related items including excavating and backfilling necessary to complete the work shown on the drawings. The ends of water service lines shall be tightly plugged or capped at the terminal points pending the connecting to all such lines of the ding piping as specified in the plumbing specifications and architectural 2. MATERIALS: WATER MAINS A. Cast Iron Pipe: Cast iron pipe shall meet AWWA Specification C -106 with push —on joints meeting AWWA Specification C -111. Wall thickness shall be determined from Table 6.4 in AWWA —106. Ductile iron pipe shall meet AWWA C -150 and C -151 Specifications. Pipe to be cement lines per AWWA C -104. B. Copper Tubing: Shall be seamless, "K" copper tubing complying with Federal Specification WW —T -799. Fittings shall be wrought copper with compression fitttings or cast C. Fire Its: Shall comply with AWWA Specification C -502 and shall meet local standards and requirements, particularly as to nozzle diameters and threads, direction of opening and dimensions of operating and cap nuts. Fire Hydrants shall have one pumper and two hose nozzles. A valve opening not less than 5 inches and a 6 inch inlet connection. The length of the hydrant barrel shall be determined by the specified depth of over over the pipe. D. Valves: All valves and stops shall have ends suited or adapters shall be provided for the proper installation in the lines in which they are located. Valves shall meet local standards or in the absence of such standards, the following requirements: 1. Valves in cast iron pipe shall be iron body, bronze mounted, disc gate valves conforming to AWWA Specification C -500. They shall open in the some direction as lose used in the local waterworks system. Valve stems shall terminate in 2 inch wrench nuts. Furnish two (2) keys. 3. APPLICATION: 2. Valves in copper pipe shall be standard brass body, round —way, ground —key stops with T heads. Furnish two (2) keys. E. Valve Boxes: Shall meet local standards or in the absence of such, shall comply with the following requirements: 1. For iron body valves, boxes shall be approved standard buffalo —type, cast iron, adjustable shaft boxes, having a minimum shaft diameter of 5 -1/4 inches. 2. For brass body valves (stops) boxes shall be approved standard cast iron extension service boxes, having a minimum diameter of 2 -1/2 inches and having lid held in place by a brass or bronze bolt. The castings shall be coated with two coats of coal —tar pitch varnish. Furnish two (2) keys for bolt in lids. F. Stops: Stop shall be those manufactured by Ford or Mueller Corporation with AWWA toper thread, and with copper compression type fitting on outlet, or equal. G. Blow —off Valves: Blow —off valves shall be those manufactured by Muller Corporation (H -10283 or H- 10291), or equal. H. Angle Valves: Angle valves at the end of water service stub are to be copper compression type fitting also, and are to be protected with plastic bag over the valve. I. Taps: 3/4" taps in lines smaller than 4 inches shall be only by tapped tee or tapping saddle. Water service lines should be marked on curbs with a stamped "W placed while pouring curbs. A. Permits and Codes: The intent of this section is the specifications if that the contractor's bid on the work covered herein shall be based upon the drawings and specifications but that the work shall comply with all applicable codes and regulations. Contractor shall furnish all necessary bonds to get permits for cuts and connections. B. Existing Improvements: Maintain in operating condition all active utilities and sewers and other pipe system that may be encountered. C. Trenching: Lay all pipe in open trenches, except whan local authority gives written permission for tunneling. Provide a separate trench for the water line at least 10 feet horizontally from any sanitary sewer. In locations where separate trenches for sewer and water lines are impracticable, lay the water pipe on a solid shelf at least 18 inches above the top of the sewer. D. Width of Trench: Excavate trenches minimum of pipe diameter plus 12 E. Sheeting and bracing: Sheet and brace trenches as necessary to protect workmen and adjacent structures. All trenching shall comply with the Occupational Safety and Health Administration Standards. F. Water Removal: Keep trenches free from water while construction therein is in progress. Under no circumstances lay pipe or appurtenances in standing water. Conduct the discharge from trench dewatering to drains or natural drainage channels. G. Grading Trench Bottoms: The bottom quadrant of the pipe shall be fully and uniformly supported. The full load shall rest on the barrel of the pipe. The trench may be excavated to a depth of 4 inches or more below final grade with sand, crushed stone or gravel backfill to bring it back to pipe laying grade. For a depth of at least 12 inches above the top of the pipe backfill with earth or granular material free from large stones, roots or frozen clogs. Tamp this backfill thoroughly taking care not to disturb the pipe. Backfill under walks, parking areas, driveways and streets with granular material only and tamp thoroughly, by approved methods. Trenches parallel to and within 10 feet of paved roadways shall be constructed the same. H. Tests: Before joints are covered, fill the piping with water, opening hydrants or at least two hours at a pressure of 100 pounds per square inch. Inspect all joints for leakage and remedy any leaks. Upon completion of the water distribution mains, flush out the system until the water runs clear. As soon as the system has been flushed out, it shall be sterilized in accordance with the requirements of City of Carmel. I. If a horizontal distance of 10 feet cannot be maintained between the water line and and a sanitary sewer line, one of the following shall be done. a. Water line laid in a separate trench and 18" above sewer. b. Water line laid in same trench on a bench of undisturbed earth and sewer at least 18" below bottom of water line. Gate Valves Valve Boxes Where water lines and sewers cross and the water line cannot be placed above the sewer with a minimum of 18" vertical clearance, the sewer must be constructed of water works grade cast iron pipe with mechanical joints within 10 feet of the water line. J. Utilities: It shall be the responsibility of each contractor to verify all existing utilities and conditions pertaining to his phase of the work. It shall also be the contractors responsibility to contact the owners of the various utilities before work is started. The contractor shall notify in writing the owners or the engineer of any changes, errors or omissions found on these plans on in the field before work is started or resumed. K. New Water Main Construction: Contractor to record dimension of each water stub and valves from nearest fire hydrant measured along water main. The locations of hydrants and water valves, along with any other construction changes are to be incorporated on the original construction drawings and "Record Drawing" prints submitted to Engineer's Office as soon after completion of construction as possible. Pipe Tracing Tape A. All pipe shall be traced with "Terra Tape" by Reef Industries, Inc., P.O. Box 33248, Houston, Texas 77033 or equal. tape shall be "Detectable" type imprinted with "Caution Buried Water Line Below A. All gate valves shall be iron body, bronze mounted, double disc, parallel seat type gate valves, conforming to AWWA Standard Specifications C500. They shall open in a counter clockwise direction. Valves placed in a valve box shall terminate in 2 inch square operating nut and have non rising stems. One valve wrench shall be supplied to the Owner for this project. Gate valves shall be as made by Kennedy Valve Manufacturing Co., Inc., Elmira, New York, Mueller or equal. A. Valve boxes shall be a three —piece cast iron type (base, center section, and sliding type adjustable extension) together with a "stay —put" cover marked "WATER The base shall be of the size recommended by the manufacturer for the size valve with which it is to be used. Wall thickness of the base and vertical sections shall not be less than 3/16 inch, and each valve box shall have a minimum shaft diometer of 5-1/4 inches. BACKFILL WITH EXCAVATED MATERIAL 0.D. OF WATERMAIN 3/4 "x18" ANCHOR BOLTS (4 REVD) FITTING TO SUIT MECHANICAL JOINT r MINIMUM O.D. 1' -0" TYPICAL WATER MAIN INSTALLATION OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR 22 1/2' 11 1/4' BENDS. PLAN 5" DIAM. WASHER, 1" THICK ANCHOR BLOCK TO BE OF CLASS "B" CONCRETE STRAP IRON ANCHORS 2" WIDE x 1/2" THICK DOWNWARD BEND DIG OUT EACH JOINT. PIPE TO REST ON FIRM EARTH USE TAPPING SLEEVE VALVE FOR CONFECTIONS UNDER PRESSURE CONNECTION TO EXISTING MAIN 1 1 -1 1 1 -1 1 1-1 1 1 -U U OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR 90' 45' BENDS. PLAN EXISTING MAIN cl OUTSIDE FACE AREA AS NOTED IN TABLE. SECTION "C —C" NOTE: ALL CONCRETE BLOCKING TO CONSIST OF CLASS "B" CONCRETE POURED AGAINST FIRM GROUND. ,111, ■I1, V SET TOP FLUSH WITH FINISHED GRADE POSI —CAP OR EQUIVALENT TO BE INSTALLED ON ALL VALVES OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR TEES WYES. FOR PLUGS. PLAN DETAIL CONCRETE BLOCKING TYPICAL UTILITY CROSSING III SECTION "D —D" SANITARY SEWER GATE VALVE AND BOX WATER MAIN 0 z z ADJUSTABLE VALVE BOX y� Restrained Joints Shall Be Mechanical Joint With Retainer Glands, US Pipe TR Flex Joint System, US Pipe Field LOK Gasket System, Or Equal. NOTE: THE ABOVE RESTRAINED JOINT LENGTHS ARE MINIMUM LENGTHS THE DESIGN ENGINEER SHALL DETERMINE IF LONGER LENGTHS ARE REQUIRED. CITY OF CARMEL STAN DAR D DETAILS Date: March 2001 Scale: Not To Scale TITLE: JOINT RESTRAINT TABLE Drown Hy: Jones Henry Engineers, Inc. Drawing Name: CW10 Existing Water Main Tapping Sleeve Varies Bend As Required Valve Varies Note: A/l Joints Shall Be Restrained Except In Run Of Tee. PLAN Notes: 1) Megalug flanges shall be used for oll mechanical joints. 2) Bell end pieces of pipe 4 if and smaller shall be considered scrap, and shall not be installed into system. New Pipe Shall Be Installed Under The Existing Water Main y New Water Main Date: March 2001 12 Min. See Trench Detail For Backfi /l Requirements vvvvvvvvvv vvvvvvvvvvv vvvvvvvvvv vv vvvvv vvv v vvvv CITY OF CARMEL STANDARD DETAILS Scale: Not To Scale SECTION TITLE: Drawn es Henry Engineers, Inc. Existing Water Main New Water Main Bed Pipe In Specified Granular Bedding Material Hand Tamped In 6" Layers To Pipe Centerline Bedding Material Shall Conform To INDOT 903.02, Size No. 8 WATER MAIN CONNECTION DETAIL Drawing Name: CW5 cb Curb Box With Cover Service Sadd /e Must Be Omitted For Services 1" And Smaller And Direct Taps Made To Ductile Iron Pipe, Class 350 Or Greater. (Verify With Owner For Pressure Class DIP.) Curb Stop Corporation Stop Mueller H- 15008, Or Equal Water Main Doub /e Strap Service Sadd /e Length Varies Copper Service Line Concrete Block (Verify) CITY OF CARMEL STANDARD DETAILS Date: Mach 2001 Scale: Not To Scale NOTE: 1) 1" Or Smaller Service Line Shall Be Direct Tap Unless Approved By Carmel Utilities. 2) Corporation Stop Shall Be Brand And Model Approved By Carmel Utilities. 3) Service Line Tap Shall Be Installed With A Min. Horz. Seperation Of 24". 4) 2 inch taps and smaller shall not be installed within 18 inches of mechanical joints and bells. TITLE Dfu Jones Henry Engineers, Inc. WATER SERVICE DETAIL Drawing Name: CW4 Notes: Water Main Hydrant Assem Restrained 1. At High Points Along Main Water Line Where Indicated On Drawings, Anchoring Tee Shall Be Set ,4t 45" Angle Upwards And Connected To 6" 45' Bend. Main Water Line Shall Be Lowered To Provide Sufficient Cover As Specified. 2. All Joints Shall Be Restrained Except In Run Of Tee. 3. Hydrants Shall Be Set At 500' Max. Horizontal Distance, Or Less ,4s Specified By Fire Department 4. All valves must include Posi —Cap or equivalent Length And Fittings As Required r Mueller Centurion A -423, Or Equal Painted 'Safety Yellow" CITY OF CARMEL STANDARD DETAILS 1 -0" Min. Bedding Material Conforming To INDOT 90302, Size No. 8 One 8''8'"16" Solid Conc. Block Or 6'Min. C /ass '5 Concrete Base On Undisturbed ground. 5. Hydrant Valves must be restrained to the tee with either all thread, or an anchoring tee. Dote: March 01 I scale: Not To Scale TnLE: Drown By ga Inc FIRE HYDRANT ASSEMBLY !Drawing Name: CW8 cn CD w CC S OON T 6'''' ��P�� No. STATE OF C 4 1 1 ND1AN z 144 /4 NAl \\o 0000075 11un11nnIttu u0 I 3,-1, DATE: 9/3/04 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF THE SCHNEIDER CORPORATION, AND ARE NOT TO BE USED OR REPRODUCED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF THE SCHNEIDER CORPORATION. COPYRIGHTED BY THE SCHNEIDER CORP. (2004) ‘b Schneider THE SCHNEIDER CORPORATION 12821 E. New Market Street Suite 100 Carmel, IN 46032 Telephone: 317.569.8112 Fax: 317.826.6410 www.schneidercorp.com Architecture Civil Engineering Environmental Engineering Geotechnical Services GIS *LIS Home Builder Services Interior Design Land Surveying Landscape Architecture Transportation Engineering COVER AS SPECIFIED Property Line Property Line