ABCDEF 12 11 10 9 8 7 6 5 4 3 2 1 UNDERCUT RESTROOM DOORS AND OFFICE DOOR MIN. 3/4" FOR MAKE-UP AIR. PROVIDE MANUAL VOLUME DAMPER AT ALL DIFFUSERS IN ACCESSIBLE LOCATION WHENEVER POSSIBLE.
FOR NON ACCESSIBLE LOCATIONS PROVIDE REMOTE CABLE CONTROL UNIT BOWDEN MODEL 270-301 AS MANUFACTURED BY YOUNG REGULATOR CO. OR APPROVED EQUAL. 10"x10" EXHAUST AIR DUCT DOWN TO EXHAUST
HOOD. EXHAUST DUCT SHALL OFFSET IN CEILING SPACE TO CONNECT TO ROOF EXHAUST FAN EF-3. SEE DETAIL 6, ON SHEET M4.0. SUPPLY, RETURN, OR EXHAUST DUCTWORK RUN UP BETWEEN ROOF TRUSSES. 14"x12"
EXHAUST AIR DUCT DOWN TO EXHAUST HOOD. EXHAUST DUCT SHALL OFFSET IN CEILING SPACE TO CONNECT TO ROOF EXHAUST FAN EF-1. SEE HOOD DETAILS ON DRAWING M3.0. SEE DETAILS ON SHEET M3.1 FOR
FIRE PROTECTION OF DUCTWORK. SEE DETAIL 18 ON SHEET M3.0 FOR EXHAUST DUCT TRANSITION. 14"x12" EXHAUST AIR DUCT DOWN TO EXHAUST HOOD. EXHAUST DUCT SHALL OFFSET IN CEILING SPACE TO CONNECT
TO ROOF EXHAUST FAN EF-2. SEE HOOD DETAILS ON DRAWING M3.0. SEE DETAILS ON SHEET M3.1 FOR FIRE PROTECTION OF DUCTWORK. SEE DETAIL 20 ON SHEET M3.0 FOR EXHAUST DUCT TRANSITION. SEE DETAIL
8 ON DRAWING M4.0 FOR SUPPLY AIR TAKE-OFF TO CEILING DIFFUSERS. RETURN AIR TAKE-OFF TO RETURN GRILLES SHALL BE SIMILAR. FURNISH AND INSTALL 3" PVC WATER HEATER FLUE VENT TERMINATION.
RUN THRU TRUSS WEBS TO OUTFALL AT VENT ON EXTERIOR WALL. SEE EXTERIOR ELEVATION FOR HEIGHT. SEE DETAIL 2/P6.0. COORDINATE WORK WITH ALL TRADES. INSTALLATION AND TERMINATION OF THE POWERED
VENT SYSTEM FOR THE WATER HEATER SHALL BE IN ACCORDANCE WITH THE VENT AND WATER HEATER MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND LOCAL CODES AND REQUIREMENTS. DINING ROOM LIGHT FIXTURE
LOCATIONS ARE CRITICAL COORDINATE DUCTWORK LOCATIONS SO AS NOT TO CONFLICT WITH LIGHT FIXTURE LOCATIONS. THERMOSTATS SHALL BE PROGRAMMABLE WITH SUBBASE AND REMOTE TEMPERATURE SENSOR.
(PROVIDE WITH E-MAX ENERGY SAVER). GENERAL NOTES C B NOT USED D CA 13 8"Ø EXHAUST AIR DUCT UP TO GOOSENECK TERMINATION ON ROOF, 150 CFM. SEE DETAIL 2 ON SHEET M4.0. EXPOSED SPIRAL GALVANIZED
DUCTWORK TO BE DOUBLE WALLED GALVANIZED FINISH, FREE FROM SCRATCHES OR BLEMISHES, INTERNALLY LINED AND SEALED WITH DUCT SEALER COMPLETELY CONCEALED WITHIN THE DUCT JOINT. NO EXPOSED
SEALER OR TAPE WILL BE ACCEPTED. (2)22x18 SUPPLY AIR DUCTS, 6000 CFM TOTAL. CONNECT TO 66x26 SUPPLY AIR OPENING AT ROOFTOP UNIT, RTU-1. TRANSITION AS NECESSARY. 32x16 RETURN AIR DUCT,
3600 CFM. CONNECT TO 74X20 RETURN AIR OPENING AT ROOFTOP UNIT, RTU-1. 36x20 SUPPLY AIR DUCT, 7200 CFM. CONNECT TO 66x26 SUPPLY AIR OPENING AT ROOFTOP UNIT, RTU-2. TRANSITION AS NECESSARY.
28x20 RETURN AIR DUCT, 4545 CFM. CONNECT TO 74X20 RETURN AIR OPENING AT ROOFTOP UNIT, RTU-2. FURNISH AND INSTALL SMOKE DETECTOR IN THE RETURN AIR DUCT, IN ACCORDANCE WITH LOCAL CODES.
DUCT SMOKE DETECTOR WIRED BY ELECTRICAL CONTRACTOR, SEE SHEET E3.2. HUMIDITY SENSOR (REMOTE). HUMIDITY SENSOR LOCATION SHALL BE PLACED WITHIN THE RETURN AIR DUCTWORK. VERIFY EXACT LOCATION
(SEE DETAIL 9/M4.0). LOCATE THERMOSTAT CONTROLS ON WALL IN OFFICE @48" A.F.F. COORDINATE LOCATION WITH 3/E3.1 AND B/A8.1. MOUNT THERMOSTAT REMOTE SENSOR AT 60" 10 ABOVE FINISHED FLOOR.
6897453 17 19 18 15 16 14 12 12 THE INSIDE OF THE RETURN AIR DUCTS FROM THE AIR CONDITIONER SHALL BE LINED FROM THE AIR HANDLING EQUIPMENT TO A DISTANCE OF 10' FROM THE UNIT, WITH ULTRALITE
#300 -1/2" THICK, OR OTHER APPROVED DUCT LINEAR ACOUSTICAL BOARD. THE MATERIAL SHALL BE FITTED CAREFULLY ON THE INSIDE OF THE DUCT AND SHALL BE FASTENED ON WITH CEMENT SUPPLEMENTED BY
SCREWS AND WASHERS ON TOP AND SIDES OF DUCT. INSTALL SURFACE MOUNTED R-2 GRILLE HIGH AS POSSIBLE. FURNISH AND INSTALL 3" PVC WATER HEATER INTAKE ON ROOF. SEE DETAIL 2/P6.0. COORDINATE
WORK WITH ALL TRADES. CANTILEVER HOOD SUPPORT RODS AWAY FROM DUCTWORK. USE ANGLE TO OFFSET THE SUPPORTS. KEY NOTES B DUCT AND DIFFUSER PLAN 1/4"=1'-0" A M2.0 DUCT AND DIFFUSER PLAN 20
21 22 23 S S S S S 11 CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: PLOT DATE:KFC /TB 10575 N. Michigan Road Carmel, IN 46032 KT-Y0708.25.08 KT-Y07 JAN08-C 305823
2007088.16 08.25.08 S-4 50 S-4 230 19 10 S-5 775 S-1 330 S-1 330 S-2 165 S-6 775 16x16 14"Ø 8"Ø S-6 775 10x10 VD 13 14 14"Ø VD 14 14"Ø S-5 775 EF-3 ON ROOF 16"Ø S-6 775 RTU-2 ON ROOF
6 14"Ø 14"Ø 14"Ø SD S-4 225 9 S-6 775 1 5 16"Ø R-1 1140 S-6 775 30x18EF-1 ON ROOF 14x12 14x12 16 EF-2 ON ROOF 14x12 17 19 22 23 (TYPICAL) S-4 50 6"Ø 6"Ø 60x18 30x18 7 EF-5 EF-4 15 12"Ø
12"Ø 12"Ø 12"Ø 12"Ø 12"Ø 12"Ø12"Ø S-3 520 S-3 520 S-3 520 S-3 520 S-3 520 S-3 520 S-3 520 S-3 520 S-3 520 VD VD VD VDVD VD 12 (TYPICAL) (TYPICAL) 18 (TYPICAL) 18 23 (TYPICAL) R-1 1135
S-5 775 10"Ø 14"Ø 22x18 20x14 3 14x14 22x18 36x20 28x20 20x20 24x16 12"Ø VD VD VD 15 15 VD 6"Ø 12 (TYPICAL) R-2 1800 R-2 1800 VD VD VD VD VD VD VD VD VD VD VD VD VD VDVD VD 14"Ø 14"Ø
14"Ø 12"Ø 14"Ø S-2 165 6"Ø 10x8 10 10 06.25.09 REVISION 10