WATER & GAS PLAN 1/4"=1'-0" A NOT USED E KEY NOTES B 1-1/2" GAS UP TO RTU WITH DIRT LEG, GAS COCK, UNION. 1 1/4" GAS DOWN TO WATER HEATER WITH GAS COCK, DIRT LEG AND UNION. 1/2" TEMPERED
WATER DOWN IN WALL TO HAND SINK. 1" HOT AND 1" COLD WATER LINES DOWN TO WATER HEATER. 1/2" HOT AND COLD WATER LINES DOWN IN WALL TO PREP SINK. 1/2" HOT AND COLD WATER LINES DOWN IN WALL
TO THREE COMPARTMENT SINK. NOT USED. 1/2" COLD AND HOT WATER DOWN IN THE WALL TO THE MOP SINK. 1/2" CW DOWN IN WALL TO WATER CLOSET FLUSHOMETER TANK. REDUCED PRESSURE BACKFLOW PREVENTER
LOCATED ABOVE THE CEILING IF ALLOWED BY LOCAL UTILITY. PROVIDE SHUT-OFF VALVES AT BOTH SIDES OF BACKFLOW PREVENTER. PIPE RELIEF TO HUB DRAIN. VERIFY LOCATIONS WITH CIVIL DWGS. VERIFY
WATER SERVICE REQUIREMENTS WITH CITY. 1/2" TEMPERED WATER LINES DOWN IN WALL TO LAVATORY. 3/4" CW DOWN TO WATER FILTER. 1/2" FW FROM WATER FILTER S-592 TO P-001 & P-451.FILTERED WATER
CONNECTION AFTER SECOND WATER FILTER. SEE RISER DIAGRAM ON DRAWING P5.0. 1/2" CW DOWN IN WALL TO TO WATER CLOSET FLUSH VALVE & R.O. SYSTEM. 1/2" CW DOWN IN WALL TO EXTERIOR HOSE BIBB.
WATER DISTRIBUTION PIPING IS SHOWN ABOVE FINISH CEILING. UNDER SLAB DISTRIBUTION ALLOWED AT CONTRACTOR OPTION. COORDINATE ALL DETAILS. NO ROOF PENETRATIONS PERMITTED WITHIN THE ROOF
"WATER VALLEYS", REFER TO ROOF PLAN FOR LOCATIONS. REFER TO SHT P4.0 FOR ROUGH-IN LOCATIONS. REFER TO SHEET P5.0 FOR WATER AND GAS ISOMETRIC DRAWINGS. A. B. C. D. 123456789 10 11 12
13 14 P3.0 WATER AND GAS PLAN 15 WATER & GAS PLAN NOTES D 29 OPTIONAL COFFEE AND TEA MAKERS: VERIFY WITH OWNER IF REQUIRED. PROVIDE 1/2" FILTER WATER TO EACH IF REQUIRED. WATER HEATER
(WH-1). PIPE CONDENSATE LINE, T&P DISCHARGE AND DRAIN PAN TO FLOOR SINK. SEE WATER HEATER DETAIL 2/P6.0. BUNDLED SYRUP LINES TO BEVERAGE DISPENSERS S-532 & S-533 AND FILTERED WATER LINES
TO ICE MAKERS S-511. SEE DRAWINGS A2.0, P5.0 AND P6.0. 1/2" FILTERED WATER DOWN IN WALL TO (2) BUNN HOT WATER DISPENSERS P-721. 2" GAS DOWN ALONG WALL TO KFC & TB COOKING EQUIPMENT.
2" GAS MANIFOLD ALONG WALL TO KFC COOKING EQUIPMENT. NOT USED. NOT USED. 3" PVC EXHAUST AND INTAKE FLUES FROM WATER HEATER, PIPE INTAKE THRU ROOF AND EXHAUST THRU REAR WALL AS RECOMMENDED
BY MANUFACTURER. SEE SHEET M2.0 AND DETAIL 2/P6.0. 1/2" HOT WATER DOWN IN WALL CONNECT TO RETHERMALIZER HOT WATER CONNECTION. 1" GAS CONNECTION TO RETHERMALIZER AND 1" GAS CONNECTION
TO FRYER. PROVIDE FLEXIBLE HOSE KIT AS INDICATED ON ARCHITECTUAL DRAWING A2.1. 1" GAS CONNECTION TO EACH PRESSURE FRYER, 1 1/4" GAS CONNECTION TO 6 HEAD FRYER AND 1 1/2" GAS CONNECTION
TO DUAL FRYER. PROVIDE FLEXIBLE HOSE KIT AS INDICATED ON ARCHITECTUAL DRAWING A2.1. EMERGENCY GAS SHUT-OFF VALVE LOCATED BELOW CEILING. NOT USED. 1/2" COLD WATER TO REVERSE OSMOSIS FILTER
P-305 AND 1/2" FILTER WATER FROM REVERSE OSMOSIS FILTER. PROVIDE SHUT-OFF VALVE ON CW PIPE PRIOR TO CONNECTION TO FILTER. 20 24 26 27 28 25 23 21 22 17 19 18 16 30 CW TW HW TW HW CW
CW G FWG CW CW TW HW HW G CWHW CW HW CW G TW HW CW HW FW CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: PLOT DATE:KFC /TB 10575 N. Michigan Road Carmel, IN 46032
KT-Y0708.25.08 KT-Y07 JAN08-C 305823 2007088.16 08.25.08 10 10 06.25.09 REVISION 10