POWER PLAN 1/4"=1'-0" A POWER NOT USED D PLAN GENERAL NOTES C J. K. L. M. N. ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE NEMA-1 FOR INTERIOR AND NEMA 3R FOR EXTERIOR. IN COASTAL REGIONS
THE STANDARD FOR OUTSIDE SHALL BE NEMA-4X. PER SECTION 210.8(B)(2) NEC 2005, ALL 15 AND 20A, 120V RECEPTACLES IN COMMERCIAL KITCHENS ARE REQUIRED TO BE GFCI PROTECTED. THIS INCLUDES
ISOLATED GROUND RECEPTACLES. DO NOT MEASURE/LOCATE OUTLETS ON DRAWINGS. USE DIMENSIONS PROVIDED. CONDUIT MAY RUN UNDER SLAB AT G.C.'S DISCRETION. PROVIDE ESCUTCHEON PLATES AND SEALANT
AT ALL UTILITY PENETRATIONS INTO WALLS, CEILINGS AND FLOORS. DO NOT USE CAULKS OR EXPANDING FOAM FOR SEALANT. KEY NOTES B 123456 E3.0 POWER 7 FLOOR PLAN 89 HORIZONTAL DIMENSIONS TO J-BOXES
ARE FROM FACE OF STUD TO CENTER OF BOX, U.O.N. VERTICAL DIMENSIONS TO J-BOXES ARE FROM FIN. FLOOR TO CENTER OF BOX, U.O.N. ALL CONDUIT DROPS ARE INSIDE WALLS U.O.N. SEE ARCH. DWGS FOR
WALL DIMS. ALL J-BOX CIRCUITS, CONDUITS, FIXTURES, ETC. SHALL BE AS INDICATED ON THE ELECT. DWGS AND AND SPECS. CONTRACTOR TO VERIFY UNDERGROUND CONDUIT LOCATIONS PRIOR TO POURING SLAB.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THIS DATA ON THE LOCATION OF ELECT. ROUGH-INS WITH INFO PROVIDED ON THE ARCH. AND STRUCT. DWGS AND THE EQUIPMENT ACTUALLY SUPPLIED,
AND TO CONFIRM THE CORRECTNESS OF ANY DIMENSIONS HEREIN. LOCATIONS OF ALL OUTLETS MAY BE RELOCATED TO NEAREST STUD. DO NOT CUT INTO STUDS. FOR EXACT LOCATIONS OF KITCHEN & MECHANICAL
EQUIPMENT AND POINTS OF CONNECTION, REFER TO KITCHEN & MECHANICAL EQUIPMENT DRAWINGS AND MANUFACTURER'S SHOP DRAWINGS. ALL CIRCUIT FEEDERS AND DISCONNECTS SHALL BE SIZED BY NEC. CONTRACTOR
SHALL VERIFY CIRCUIT BREAKER, DISCONNECT SWITCH, STARTER AND FUSE SIZES WITH SELECTED EQUIPMENT MANUFACTURER'S SHOP DRAWINGS PRIOR TO PLACING ORDER AND PROVIDE EVERYTHING AS REQUIRED.
A. B. C. D. E. F. G. H. I. 9'-9" (+18) A-6 F.O. STUD 2'-3" 13'-912"(+18") B-38 D-19:21 D-34 H-7 812"(+18") F.O. STUD 2 1'-10" (+18") 2 LIGHTING CONTROL RELAY PANEL. SEE 8/E6.0. A-9:11
20'-4" (+(+102") REFER TO ROOF PLAN. INSTALL SURFACE MOUNTED IN CONDUIT RUNNING ON KITCHEN SIDE OF CABINETRY REAR WALL. CONNECT MAPS LINE CIRCUIT BREAKER PANEL VIA UTILITY CHASE IN CEILING
TO 3 POLE, 125 AMP CIRCUIT BREAKER IN MAIN SWITCHBOARD. SEE SHEET E2.0. VERIFY ALL REQUIREMENTS WITH ACTUAL EQUIPMENT SPECIFIED. THE MANUFACTURER WILL FULLY PRE-WIRE THE COMPLETE MAPS
LINE AT THE FACTORY. THE UNITS WILL THEN BE PULLED APART FOR SHIPPING PURPOSES. ALL CONNECTION POINTS WILL BE MARKED. THE CONDUIT RUNS WILL BE COILED UP FOR FIELD INSTALLATION. SOME
ELECTRICAL COMPONENTS MAY BE REMOVED FOR EASE OF DISASSEMBLING THE LINE-UP. THE ELECTRICAL CONTRACTOR WILL BE FULLY RESPONSIBLE FOR MAKING THE PROPER FIELD CONNECTIONS FROM THE ROUGH-IN
LOCATION TO THE MANUFACTURER PROVIDED BREAKER PANEL BOX. IN ADDITION, THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR ANY SPLICE POINTS AND/OR JUNCTION BOXES THAT NEED TO BE RECONNECTED.
SOME ELECTRICAL COMPONENT ASSEMBLY MAY ALSO BE REQUIRED. ANSUL J-BOX -LOCATE ABOVE CEILING. LOCATED INSIDE SHELL OF HEATER. CONDENSING UNIT. SEE SCOPE OF WORK. TWIST-LOCK RECEPTACLE.
SWITCHGEAR LOCATION. CONDUIT DROP FROM ABOVE SIGN ELEMENT. THIS ITEM SHALL BE HARD-WIRED. 14'-11" (+42") CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: PLOT DATE:KFC