KEY NOTES N.T.S. A ENLARGED POWER AND COMMUNICATIONS PLAN P.O.S. ISOLATED GROUND SYSTEM N.T.S. 14 (OFFICE) 1/2" = 1'-0" 3 ENLARGED INTERIOR ELEVATION (D/T WINDOW) 1/2" = 1'-0" 16 NOT
USED N.T.S. B ENLARGED INTERIOR ELEVATION (PRE PAY WINDOW) 1/2" = 1'-0" 4 E3.1 ENLARGED POWER PLAN AND DETAILS REFER TO COMMUNICATIONS SCHEDULE ON SHEET E5.0 FOR EQUIPMENT DESCRIPTIONS/MOUNTING
HTS. VIEW OF WINDOW HM 03 ISOLATED GROUND OUTLET FOR D/T SYSTEM LINE OF WORK SURFACE P 01 ISOLATED GROUND OUTLET FOR P0S SEE SHEET E5.0 SEE SHEET E5.0 VIEW TO LEFT OF WINDOW HM 04 (4)
1" DIA. CONDUITS SEE SHEET E5.0 D/T WINDOW VIEW TO RIGHT OF WINDOW CONDUIT IN WALL (TYP.) SEE SCHEDULE FOR SIZE SEE SHEET E5.0 HM 08 LINE OF CEILING 1 V 01 S 12 T 04 T 03 S 05 9'-3"
(+60") 6'-6" (+42") 6'-2" (+42") 3'-0" (+42") 3'-4" (+42") 4'-3" (+42") F.O. A-19 1 A-19 D-8 A-23 J A-15 A-17 A-17 J D-38 V 01 J J H 01 12 THERMOSTATS, REFER TO DETAIL 3/E6.0. DISPLAY
UNIT FOR HM-02. DUAL-OUTPUT DETECTOR FOR HM-02. LIGHTING CONTROL SWITCH -FRONT LIGHTING CONTROL CONTROL SWITCH -REAR 3 ISOLATED GROUND (IG) (#6 WIRE) ISO. GND N GND ~~ ISOLATED GROUND
(IG) (#12 WIRE) DEDICATED NEUTRAL COMMON GROUND (EQUIPMENT GND) INSTALLED PER N.E.C. THE DEDICATED POS POWER CIRCUIT REQUIRES AN ISOLATED GROUND IN ADDITION TO THE NORMAL COMMON BUILDING
GROUND. THE ISOLATED GROUND WIRE SERVES TWO PURPOSES: * AS A SAFETY PATH TO GROUND. * AS A ZERO REFERENCE POINT FOR ALL POS DIGITAL LOGIC. THE GROUND MUST EXHIBIT THE LOWEST POSSIBLE
IMPEDANCE TO MINIMIZE VOLTAGE TRANSIENTS AND NOISE. BE SURE TO: * USE AN INSULATED CONDUCTOR FOR THE ISOLATED GROUND WIRE. * RUN THE ISOLATED GROUND WIRE THROUGH THE SAME CONDUIT AS
THE HOT AND NEUTRAL WIRES. * INSTALL ONLY ISOLATED GROUND (IG) TYPE RECEPTACLES. * CONNECT THE ISOLATED GROUND WIRE TO BUILDING GROUND ONLY AT THE MAIN SERVICE PANEL. * VERIFY THAT IG
RECEPTACLES PRE-WIRED IN OWNER SUPPLIED EQUIPMENT HAVE A TRUE ISOLATED GROUND THAT CAN BE TRACED BACK TO THE BUILDING GROUND AT THE MAIN SERVICE PANEL. DO NOT CONNECT THE ISOLATED GROUND
WIRE TO THE THE CONDUIT, JUNCTION BOXES, THE FRAME ON A SUBPANEL, OR ANY OTHER METAL SURFACE. DEDICATED CIRCUITS: DEDICATED CIRCUITS REQUIRE A DEDICATED HOT AND A DEDICATED NEUTRAL THAT
ARE NOT SHARED WITH ANY OTHER CIRCUITS. IG RECEPTACLES MUST BE "PHASE ALIGNED" WITH THE "B" PHASE OF BUILDING SUBPANEL "A". EARTH GROUND UTILITY NEUTRAL DEDICATED HOT IG RECEPTACLE IG
RECEPTACLE SUBPANEL (OR EQUIPMENT SERVICE CABINET) CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: PLOT DATE:KFC /TB 10575 N. Michigan Road Carmel, IN 46032 KT-Y0708.25.08
KT-Y07 JAN08-C 305823 2007088.16 08.25.08 SEE SHEET E5.0 ISOLATED GROUND OUTLET FOR P0S and PRINTER SEE SHEET E5.0 SEE SHEET E5.0 SEE SHEET E5.0 SEE SHEET E5.0 QUAD OUTLET T 05 V 02
P 04 P 01 S 03 T 05 S 03 V 02 P 04 P 01 HM 02 HM 01 HM 07 ISOLATED GROUND OUTLET FOR D/T SYSTEM OUTLET FOR LOW VOLTAGE TRANSFORMER FOR D/T TIMER. P 05 P 03 ISOLATED GROUND OUTLET FOR
HELF HEIGHT REFRIGERATOR QUAD OUTLET ISOLATED GROUND OUTLET FOR D/T SYSTEM OUTLET MONITOR. ISOLATED GROUND OUTLET FOR POS ENLARGED D/T PLAN 1/2" = 1'-0" 16 JJJ JJJP 03 P 01 *SEE SCHEDULE,
B/E5.0 FOR J-BOX MOUNTING ELEVATION 2 3