HomeMy WebLinkAbout200708816_510_KT_Y07-E6_0.pdf E6.0 ELECTRICAL DETAILS 20A HAND-OFFAUTOMATIC (HOA) SWITCH. MOUNT IN ENCLOSURE SEQUENCE OF OPERATIONS: * SET TIME CLOCK FOR THE HOURS THE STORE WILL BE OCCUPIED-COORDINATE WITH OWNER'S REPRESENTATIVE. * ADJUST PHOTOCELL TO ACTIVATE WHEN AMBIENT LIGHT APPROXIMATES DUSK -COORDINATE WITH OWNER'S REPRESENTATIVE * SET BOTH SWITCHES TO THE "AUTOMATIC" POSTITION. SIGNS AND LIGHTS WILL NOW BE ENERGIZED WHEN THE TIME CLOCK INDICATES THE STORE IS OCCUPIED AND THE PHOTOCELL INDICATES LOW LIGHT LEVELS. * WHEN THE STORE CLOSES BUT IS STILL OCCUPIED, THE SIGNS/BUILDING LIGHTS SWITCH SHOULD BE TURNED TO "OFF" TO EXTINGUISH THESE LIGHTS. * WHEN THE CREW LEAVES THE TIMECLOCK WILL TURN OFF ALL EXTERIOR LIGHTS -THE 30 MINUTE DELAY TIMER IS USED TO PROVIDE POWER TO THE SITE LIGHTS FOR ENOUGH TIME TO ALLOW THE CREW TO LEAVE SAFELY. 120V COIL SIGN/BLDG. LTS. SITE LTS. H O A 120V COIL 0 30 H O A N L 120v SPARE CIRCUIT PANEL "B" NORMALLY OPEN ELECTRICALLY HELD RELAY WITH 120V COIL AND 30 AMP CONT. DUTY CONTACTS FOR BUILDING LIGHTS LIGHTS AND SIGNAGE MOUNT IN ENCLOSURE NORMALLY OPEN ELECTRICALLY HELD RELAY WITH 120V COIL AND 30 AMP CONT. DUTY CONTACTS FOR SITE LIGHTS MOUNT IN ENCLOSURE 30 MINUTE TWIST TIMER FOR PARKING LOT LIGHT DELAY MOUNT IN ENCLOSURE 20A HAND-OFFAUTOMATIC (HOA) SWITCH. MOUNT IN ENCLOSURE TIMECLOCK TORK #1101 MOUNT ON WALL ABOVE ENCLOSURE PHOTOCELL TORK #2101, MOUNT FACING NORTH. CALIBRATE TO OPERATE WHEN AMBIENT LIGHT APPROXIMATES DUSK. COORDINATE WITH OWNER'S REPRESENTATIVE #64A COIL TERMINAL OF FAN CONTACTOR TO RELAY "BC" ON DETAIL 14, SHEET E6.0 LTB-3 12.5-20 TON VOYAGER UNIT J2-6 J2-5 J2-4 J1-8 P7-8 72A(PR) J2-3 J2-2 (ROOF TOP UNIT) J1 CTI J2-1 TO RELAY "BC" ON DETAIL 14, SHEET E6.0 NOTE: SEE E3.1 FOR LOCATION SEQUENCE OF OPERATION: WHEN SPST SWITCH IS IN THE DOWN POSITION (OFF), RELAY "LC" CONTACTS SHALL ENERGIZE, DISABLING POWER TO THE KITCHEN LIGHTS, SERVING AREA LIGHTS, REST ROOM LIGHTS, WALK-IN REFRIGERATION LIGHTS, AS WELL AS RELAYS "R3" AND "BC". IN ADDITION: CONTACT LC-7 SHALL ENABLE THE EXHAUST FAN CONTROL RELAY "R3" TO SENSE THE "OCCUPIED" OR "UNOCCUPIED" CONDITION (REFER TO DET. 2, SHT E6.0 FOR SEQUENCE OF OPERATION). ACTIVATION OF RELAY "BC" (BLOWER CONTROL) SHALL CAUSE THE CORRESPONDING TERMINALS ON ALL ROOF TOP UNITS TO START THE BLOWERS ON RTU-1 AND 2. EACH RTU BLOWER MOTOR SHALL RUN CONTINUOUSLY UNTIL EITHER "BC" IS DEACTIVATED BY TURNING OFF THE KITCHEN LIGHTS OR WHEN A SMOKE DETECTOR ON AN INDIVIDUAL SHALL SHUT THAT UNIT DOWN INDIVIDUALLY AS REQUIRED BY NFPA. TO DETAIL 3 ON SHEET E6.0 SPARE COOLER/FREEZER LIGHTS KITCHEN/RESTROOM LIGHTS (SEE 2/E6.0) 120V PANEL "B" SPST SWITCH IN MGR.'S OFFICE, OR AS SHOWN. INSTALL INVERTED CIRCUIT BREAKERS (TYP) REFER TO PANEL BOARD SCHEDULES C KITCHEN LIGHTS SERVING AREA LIGHTS "LC" LC-2 3 4 5 6 7 8 C R3 NORMALLY CLOSED ELECTRICALLY HELD, 120 VOLT AC 20 AMP CONTINUOUS DUTY LIGHTING CONTACTOR 1 R3-1 4 SPARE TO RTU-2 TO RTU-1 TYPE I HOOD EXHAUST FAN CONTROL "BC" SPARE M TO DETAIL 3 ON SHEET E6.0 REFER TO NOTES ABOVE BC-4 3 2 1 RTU BLOWER CONTROL RELAY C ELECTRICALLY HELD RELAY W/120V COIL AND 20AMP CONTINUOUS DUTY LIGHTING CONTACTS (TYP.) CIRCUIT BREAKER FROM ELECTRICAL PANELS 120V "PANEL-_" SPARE SPARE SPARE SPARE DINING LTS C "FC" FC-1 2 3 4 5 6 7 8 LIGHTING CONTROL SWITCH IN MGR.'S OFFICE OR AS SHOWN DINING LTS. TRACK DINING LTS. TRACK DINING LTS/FURN RIDID STEEL CONDUIT THRU SLAB EARTH PAD SAND GRAVEL SLAB TOP OF SLAB ELECTRICAL METALLIC TUBING NOTE: GREEN GROUND WIRE REQUIRED IN ALL CONDUITS, SIZED PER N.E.C. REQUIREMENTS. SCHEDULE 40 PVC DRIVE-THRU COMMUNICATIONS ISOMETRIC N.T.S. 16 NOT USED 4 RTU-FAN INTERLOCK N.T.S. 3 EXTERIOR LIGHTING CONTROL SCHEMATIC N.T.S. 8 LIGHTING CONTROL RELAY -FRONT N.T.S. 18 LIGHTING & CONTROL RELAY -REAR N.T.S. 14 HOOD SHUT-DOWN DETAIL N.T.S. 2 UNDER SLAB CONDUIT N.T.S. 17 CONTRACT DATE: BUILDING TYPE: PLAN VERSION: SITE NUMBER: STORE NUMBER: PLOT DATE:KFC /TB 10575 N. Michigan Road Carmel, IN 46032 KT-Y0708.25.08 KT-Y07 JAN08-C 305823 2007088.16 08.25.08 AFTER COMPLETION AND TESTING OF THE INTERLOCK SYSTEM SHOWN BELOW, BUT BEFORE PUTTING IT INTO OPERATION, PROGRAM THERMOSTATS FOR RTU1 AND RTU2 TO INITIATE "OCCUPIED" TEMPERATURE SETTINGS AT TIME OF ARRIVAL OF FIRST EMPLOYEE OR MANAGER (APPROXIMATELY 8:00 A.M.). NOTES: 1. REFER TO THE ELECTRICAL ROOF PLAN, SHEET E3.2 FOR UNIT LOCATIONS AND FURTHER ELECTRICAL REQUIREMENTS. 2. REFER TO THE MECHANICAL SCHEDULES ON SHEET M1.0 FOR ELECTRICAL REQUIREMENTS. C NEUT (D-23) FAN CONTROL RELAY C THIS INTERLOCK SYSTEM IS INTENDED TO: 1. MAKE AVAILABLE A FULL VOLUME OF OUTSIDE AIR TO THE BUILDING WHEN ALL EXHAUST FANS ARE ACTIVATED BY THE "OCCUPIED" RELAY. SEQUENCE OF OPERATION: OCCUPIED: ALL KITCHEN EXHAUST FANS SHALL RUN WHEN "R3" IS ENERGIZED INDICATING AN "OCCUPIED" CONDITION, AN AUXILIARY CONTACT IN EACH EXHAUST FAN MOTOR STARTER SHALL CLOSE, TURNING ON THE CORRESPONDING HOOD WORK LIGHTS, INDICATING THAT THE EXHAUST FAN STARTER HAS BEEN ACTIVATED. SPACE THERMOSTAT SENSORS SHALL CYCLE ROOF TOP UNITS TO MAINTAIN "OCCUPIED" SPACE TEMPERATURES. BLOWER MOTORS SHALL OPERATE AS NOTED IN DETAIL 14, SHT E6.0. UNOCCUPIED: KITCHEN EXHAUST FANS SHALL CEASE OPERATION WHEN RELAY "R3" IS DE-ENERGIZED CORRESPONDING TO TURNING OFF THE LIGHT SWITCH IN THE KITCHEN. SPACE THERMOSTATS SHALL CYCLE ROOFTOP FANS AND HEATING OR COOLING TO MAINTAIN "UNOCCUPIED" SPACE TEMPERATURES. EMERGENCY OPERATION: UPON ACTIVATION OF ANY HOOD FIRE SUPPRESSION RELAY, A RELAY IN THAT FIRE SUPPRESSION SYSTEM SHALL CAUSE THE SHUNT TRIP CIRCUIT BREAKER IN PANEL "H" TO OPERATE, THUS REMOVING POWER FROM ALL DEVICES CONNECTED TO THAT PANEL. EXHAUST FANS SHALL NOT BE AFFECTED BY THIS ACTION AND SHALL CONTINUE TO BE CONTROLLED BY THE "OCCUPIED" OR "NON-OCCUPIED" CONDITIONS LISTED ABOVE. HARDWARE SPECIFICATIONS: HOFFMAN A-HE SERIES WITH HINGED COVER AND CYLINDER KEY LOCK SET. RELAYS: SQUARE-D CLASS 8501, RS43, V20 WITH SOCKET BASE. "LC" SEE DETAIL 14, SHEET E6.0 7 H-12 NEUTRAL YER053 H-12 120V EF1 EF2 EF3 REMOVE JUMPER 24 VAC SMOKE DETECTORS LOCATED IN RETURN AIR DUCTS. INCLUDE IN SUPPLY DUCTS ONLY WHERE REQUIRED BY LOCAL CODE. WIRE TO SHUTDOWN AC UNITS UPON DETECTION OF SMOKE. RTU TERMINAL STRIP (LTB1) JUMPER 30A, 3P, 240V NON FUSED, NEMA 3R DISCONNECT SWITCH ON ROOF FAN MOTOR STARTER. SEE PLANS FOR CIRCUIT BKR. NUMBER IN PANEL "D" 30A, 3P, 240V NON FUSED, NEMA 3R DISCONNECT SWITCH ON ROOF FAN MOTOR STARTER. SEE PLANS FOR CIRCUIT BKR. NUMBER IN PANEL "D" FAN MOTOR STARTER. SEE PLANS FOR CIRCUIT BKR. NUMBER IN PANEL "D" 30A,2P, 240V NON FUSED, NEMA 3R DISCONNECT SWITCH ON ROOF O.L. O.L. HOOD LIGHTS 12.5-20 TON VOYAGER UNIT SMOKE DETECTOR ALARM CONTACTS HOOD LIGHTS HOOD LIGHTS O.L. NEUT PANEL H NEUTRAL STH HOOD FIRE EXTINGUISHER CONTACTS PANEL H SHUNT TRIP FEEDER BREAKER IN MSB LIGHTING CONTACTOR 3P, 100A 10 6-25-09 REVISION 10