HomeMy WebLinkAboutE100 Electrical Site Lighting & PowerGENERAL NOTES A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED. B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE LATEST EDITION ADOPTED BY INDIANA, THE INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL /MUNICIPAL CODES, AND THE AUTHORITY HAVING JURISDICTION. C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH. D. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING MATERIAL. E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS. F. FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND MANUFACTURER'S WRITTEN RECOMMENDATIONS. I. HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME RUNS MAY BE COMBINED AT THE CONTRACTOR'S DISCRETION NOT GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL CONDUCTORS, AND A GROUNDING CONDUCTOR. EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A DEDICATED NEUTRAL BACK TO THE PANEL. CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL USE LINK SEALS. WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED NOT EXCEEDING INTERVALS OF 48 INCHES, AND NOT MORE THAN 6 INCHES FROM CABINETS, BOXES, FITTINGS, OUTLETS, RACKS, FRAMES AND TERMINALS. M. ALL SITE WIRING FOR LIGHTING FIXTURES SHALL BE IN CONDUIT, SIZE #10 AWG MINIMUM. N. COORDINATE INSTALLATION OF PRIMARY CONDUIT WITH DUKE ENERGY PRIOR TO CONSTRUCTION. J. K. L. 0 SHEET KEYNOTES NEW DUKE ENERGY 400A, 240 120V, SINGLE PHASE METER. 2. PROVIDE NEW POLE MOUNTED LIGHTING LITHONIA DM19AS2 -250M -SR5S- 120- SPA -SF WITH LITHONIA POLE STS- 20 -5 -5F OR APPROVED EQUIVALENT. 3. PROVIDE NEW POLE MOUNTED LIGHTING LITHONIA DM28AS2 -250M -SR5S- 120 SPA -SF WITH LITHONIA POLE STS- 20 -5 -5F OR APPROVED EQUIVALENT. 4. PROVIDE NEW FLAG LIGHTING LITHONIA 7000 -70M- 120 -YM -BL OR APPROVED EQUIVALENT. 5. PROVIDE 6 POLE, NEMA -1 RATED, MAGNETICALLY HELD CONTACTOR WITH REMOTE PHOTOCELL. MOUNT THE CONTACTOR INSIDE MECHANICAL ROOM. ALL PARKING, FLAG AND PERIMETER LIGHTINGS SHALL BE CONTROLLED FROM THIS DEVICE. 6. STUB 1" CONDUIT FROM POLE BASE AND CAP FOR FUTURE PARKING LOT LIGHTING. SCALE: 1/16" 1' -0" TURN UP AT SERVICE POLE 0 r 4" SCHEDULE 80 PVC 4 CONDUIT FOR DUKE ENERGY PRIMARY 4' 8' 16' ELECTRICAL SITE LIGHTING AND POWER PLAN Carmel Redevelopment Commission 111 West Main Street Carmel, Indiana 46032 317.571 -2787 (ARTS) RS C C G) E to 0 Scope Drawings: These drawings indicate the general scope of the project in terms of architectural design concept, the dimensions of the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the Contract. On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of the work. Revisions: Issue Data 01/20/09 Drawn By KIA Checked By BKS Drawing Title: ELECTRICAL SITE LIGHTING AND POWER PLANS Certified By e �vaemeen RS !�v mss.. a fidk /ON Ai. /3 7 1' 111 PE19700197 ms m STATE OF tr 77 L'Acquis Project Number: 08109