HomeMy WebLinkAboutE202 Electrical Lighting PlansGENERAL NOTES
A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE
APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED.
B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE LATEST EDITION ADOPTED BY INDIANA, THE
INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL /MUNICIPAL CODES,
AND THE AUTHORITY HAVING JURISDICTION.
C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR
VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT
LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH.
D. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE
CONDUIT SEALING MATERIAL.
E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS.
F. FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN
ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS
SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION FITTINGS
SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND
MANUFACTURER'S WRITTEN RECOMMENDATIONS.
I. HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN
ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME
RUNS MAY BE COMBINED AT THE CONTRACTOR'S DISCRETION NOT
GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL CONDUCTORS,
AND A GROUNDING CONDUCTOR.
J. EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A DEDICATED
NEUTRAL BACK TO THE PANEL.
K.
L.
CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL
USE LINK SEALS.
WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE
INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED NOT
EXCEEDING INTERVALS OF 48 INCHES, AND NOT MORE THAN 6 INCHES
FROM CABINETS, BOXES, FITTINGS, OUTLETS, RACKS, FRAMES AND
TERMINALS.
1 SHEET KEYNOTES
1. CONTROL WITH PHOTOCELL AND CONTACTOR. TYPICAL FOR ALL
EXTERIOR LIGHTING.
2. PROVIDE 4" OPEN DOWNLIGHT TYPE 'A' COOPER LIGHTING
C60 -18 —E- 6050 —W OR APPROVED EQUIVALENT. INCLUDE EMERGENCY
BATTERY MODULE WHERE SHOWN.
3. PROVIDE 6" OPEN DOWNLIGHT TYPE 'E2' COOPER LIGHTING
C60- 18 —E —EM- 6050 —W WITH EMERGENCY BATTERY MODULE AND
REMOTE TEST SWITCH OR APPROVED EQUIVALENT.
4. PROVIDE WALL MOUNTED LIGHTING TYPE 'D' COOPER LIGHTING
MH— WP- 70- 120 —PC OR APPROVED EQUIVALENT WITH REMOTE
EMERGENCY BATTERY PACK AT ALL EXIT DOORS.
5. PROVIDE PENDENT TYPE 'F' COOPER LIGHTING
8T— EIVM -2 -32- 120 —EB81 OR APPROVED EQUIVALENT. INCLUDE
EMERGENCY BATTERY PACK FOR THE SECOND FIXTURE IN MECH.
ROOM TYPE 'F1'. MOUNT SUSPENDED FROM CEILING. COORDINATE
MOUNTING LOCATION WITH MECHANICAL CONSULTANT.
6. PROVIDE EMERGENCY HEAD TYPE 'X2' COOPER LIGHTING LM1 SERIES
OR APPROVED EQUIVALENT.
7. PROVIDE EXIT SIGN AND EMERGENCY LIGHT COMBO TYPE 'X' COOPER
LIGHTING CCX1- 7- 1 —R —WH- 120 —DH OR APPROVED EQUIVALENT.
8. REMOVE AND REINSTALL FIXTURES IN THIS AREA TO ALLOW FOR
CEILING WORK.
9. SAME AS TYPE 'E2' WITH 120V DIMMING BALLAST.
10. SAME AS TYPE 'A' WITH 120V DIMMING BALLAST.
PROVIDE RECESSED TYPE 'F3' COOPER LIGHTING
WTS- 2 -32 —W- 120 —EB8 COMPLETE WITH LENS OR APPROVED
EQUIVALENT. INCLUDE EMERGENCY BATTERY PACK FOR THE SECOND
FIXTURE TYPE 'F2'.
12. PROVIDE LUTRON NOVA —T SERIES DIMMERS OR APPROVED
EQUIVALENT.
13. PROVIDE RECESSED TYPE 'F4' COOPER LIGHTING
8T— SN -1 -32- 120— ER -8 -1 COMPLETE WITH RED US FLAG ROSCO
SLEEVE 4' T8 AND END CAP OR APPROVED EQUIVALENT. MOUNT IN
THE INSIDE ARCHITECTURAL COVE. REFER TO ARCH. DRAWING FROM
EXACT MOUNTING LOCATION.
14. PROVIDE RECESSED TYPE 'F4' COOPER LIGHTING
8T— SN -1 -32- 120— ER -8 -1 COMPLETE WITH WHITE US FLAG ROSCO
SLEEVE 4' T8 AND END CAP OR APPROVED EQUIVALENT. MOUNT IN
THE INSIDE ARCHITECTURAL COVE. REFER TO ARCH. DRAWING FROM
EXACT MOUNTING LOCATION.
PROVIDE RECESSED TYPE 'F4' COOPER LIGHTING
8T— SN -1 -32- 120— ER -8 -1 COMPLETE WITH BLUE US FLAG ROSCO
SLEEVE 4' T8 AND END CAP OR APPROVED EQUIVALENT. MOUNT IN
THE INSIDE ARCHITECTURAL COVE. REFER TO ARCH. DRAWING FROM
FXACT MOUNTING I ()CATION
EXISTING SIGNAGE
LIGHTING TO REMAIN
SCALE: 1/8" 1' -0"
0
0
b
U
(I)
EXISTING SIGNAGE
LIGHTING TO REMAIN
ELECTRICAL LIGHTING EXISTING /DEMOLITION PLAN *AV
SPECIAL REC.
WITH STARTER
TO REMAIN.
5
D
EXISTING SIGNAGE
LIGHTING TO REMAIN
SCALE: 1/8" 1' -0"
4
►,4
A I.
0
4'
b b
8'
16'
f
OA
2
15
h F4 2 08
n 4 n
ELECTRICAL LIGHTING FIRST FLOOR PLAN
EXISTING SIGNAGE
LIGHTING TO REMAIN
Cr) r4
CD/
w
z
z
V z
E
a
1 O
O
Q
m
111 West Main Street
Carmel, Indiana 46032
317.571 -2787 (ARTS)
co
co
C
C
tQ
0
Scope Drawings:
These drawings indicate the general scope of the project
in terms of architectural design concept, the dimensions of
the building, the major architectural elements and the type
of structural, mechanical and electrical systems.
The drawings do not necessarily indicate or describe all
work required for full performance and completion of the
requirements of the Contract.
On the basis of the general scope indicated or described,
the trade contractors shall furnish all items required for the
proper execution and completion of the work.
Revisions:
Issue Date
01/20/09
Drawn By
KIA
Checked By
BKS
Drawing Tuts:
ELECTRICAL
LIGHTING
PLANS
Certified By
‘,01,11 (tw
Sib?.
s
197 0197
a
Drawing Number:
202
L'Acquis Project Number:
08109