HomeMy WebLinkAboutE301 Electrical Schedules PlansVOLTAGE:'' 240 /120 KLP-2 SECTION 1 of 1 L P_ 1 SECTION 1 of 1 MOUNTING: FLUSH PHASE: 1 WIRE: 3 NEUTRAL: 100% MAIN: MCB MCB AMPS: 200 IG: NO BUS AMPS: 225 LOAD DESCRIPTION AIC: 18,000 LOAD DESCRIPTION TP LOAD CKT OCP PH OCP CKT LOAD TP LOAD DESCRIPTION REC. HALL OVERFLOW GUN STO. R 1.4 1 20A A 20A 2 1.0 L LIGHTING KITCHEN, PANTRY CORRIDOR LIGHTING OVERFLOW, MECH. ROOM L 0.6 3 20A B 20A 4 1.0 L LIGHTING TABLE AREA, BAR LIGHTING OUTDOOR, GATHERING L 0.5 5 20A A 20A 6 0.9 R REC. TABLE, BAR, GATHERING PATIO REC. GATHERING ROOM R 0.9 7 20A B 20A 8 0 R REC. KITCHEN REC. KITCHEN PANTRY R 0.7 9 20A A 20A 10 0.7 R REC. PANTRY AHU -1 and GF -1 M 1.0 00000 11 20A B mQmQm 50A,2P 12 3,9 l*klm CU -3 K 13 20A 14 3,9 14 AHU -2 and GF -2 15 20A 50A,2P 16 3.9 CU -4 20A* B 17 19 20A 20A 20A 18 20 3.9 CONVECTION OVEN L!) to O O MJ 0) 0) 0 ry) u') 10 O T T t'J cr5 0 -5 T T AHU -3 and GF -3 1.2 R FIRE ALARM CONTROL PANEL 18 20 M 1.0 21 20A A 20A 22 1.0 M HOT WATER RECIRCULATION PUMP AHU -4 and GF -4 M 1.0 23 20A B 20A 24 0.9 M J -BOX FANS 20A, 2P M 1.0 25 20A A 20A 26 1.2 M SE -1 POOL TABLE LIGHTING L 0.2 27 20A B 20A 28 1.2 M SE -2 SPARE 34 AHU -3 GF-3 29 20A A 20A 30 1.2 M SE -3 SPARE AHU -4 GF-4 WALK -IN COOLER 31 20A B 20A 32 1.0 R STAGE RECEPTACLE SPARE PHASE TOTALS A: 25.70 B: 25.90 C: 0.00 33 20A A 20A 34 1.0 R STAGE RECEPTACLE SPARE TOTAL SECTION 1: 1.9 35 20A B 20A 36 1.0 R STAGE RECEPTACLE SPARE 0.0 0.0 37 20A A 20A 38 1.0 R STAGE RECEPTACLE SPARE 1.25 1.00 39 20A B 20A 40 0.5 30.5 SPARE SPARE 0.0 41 20A A 20A 42 SPARE PHASE TOTALS A: 22.58 B: 20.75 C: 0.00 LOAD TYPE (TP) Nonsimultaneous 0 Lighting Receptacle Motor Largest Motor Heat Kitchen Other TOTAL SECTION 1: 3.3 10.8 29.3 0.0 0.0 0.0 0.0 ALL SECTIONS: DEMAND FACTOR: 1.00 Calculation 1.00 1.25 1.00 1.00 1.00 DEMAND: 3.3 10.4 29.3 0.0 0.0 0.0 0.0 DEMAND KVA: 42.9 DEMAND AMPS: 179 VOLTAGE: 240/120 KLP-2 SECTION 1 of 1 MOUNTING: FLUSH PHASE: 1 WIRE: 3 NEUTRAL: 100% MAIN: MCB MCB AMPS: 200 IG: NO BUS AMPS: 225 AIC: 18,000 LOAD DESCRIPTION TP LOAD CKT OCP PH OCP CKT LOAD TP LOAD DESCRIPTION REACH -IN FREEZER K 1.4 1 20A A 20A* 2 0.2 K BURNER RANGE W/ OVEN EXHAUST HOOD W/ FIRE SYSTEM K 0.4 3 20A B 20A 4 1.2 K BOTTLE COOLER PIPE MOUNTED AIR COMPRESSOR R 0.5 5 20A A 20A 6 1.6 K BACK BAR REFRIGERATOR WAITRESS STATION K 0.4 7 20A B 20A 8 1.0 K BLENDER STATION ICE MAKER K 1.2 9 20A, 2P A 20A 10 0.7 K WORK TABLE WALK -IN COOLER LIGHT 1.5 K 1.2 11 0 B 20A 12 1.4 K REACH -IN FREEZER 10 HOT FOOD TABLE K 1.0 13 20A A 20A 14 1.0 K REACH -IN REFRIGERATOR GRIDDLE ON STAND K 1.0 15 20A* B 20A* 16 1.5 K FRYER KITCHEN HOOD SOLENOID VALVE CONVECTION OVEN 2 #12 &1 #12G L!) to O O MJ 0) 0) 0 ry) u') 10 O T T t'J cr5 0 -5 T T 17 9 21 20A* 13 20A, 2P 18 20 0 0 0 4 5 1 0 0 0 0 0 0 0 0 I BACK BAR COOLER DWH-1 20A EF -3 20A, 2P 20A 22 EF -1, EF -2 23 25 27 03 Q m Q m Q m Q m Q 20A 24 PARKING AND FLAG LIGHTING 20 CU -1 50A, 2P 20A, 2P 26 AHU -1 GF -1 15 28 2.4 CU -2 29 50A, 2P 20A, 2P 30 AHU -2 GF -2 SPARE 31 Wr' 32 V 33 35 20A 20A, 2P 34 AHU -3 GF-3 SPARE 20A a 36 Lighting SPARE 37 39 41 20A 20A, 2P 38 AHU -4 GF-4 WALK -IN COOLER 20A, 2P r 40 0.0 0.0 20A 42 SPARE PHASE TOTALS A: 25.70 B: 25.90 C: 0.00 LOAD TYPE (TP) Nonsimultaneous 0 Lighting Receptacle Motor Largest Motor Heat Kitchen Other 1.00 TOTAL SECTION 1: 1.9 0.5 30.5 0.0 0.0 18.7 0.0 0.0 ALL SECTIONS: 0.0 0.0 0.0 0.0 0.0 DEMAND KVA: 0.0 DEMAND AMPS: '0 23 DEMAND FACTOR: 1.00 Calculation 1.00 1.25 1.00 0.65 1.00 3/4" DEMAND: 1.9 0.5 30.5 0.0 0.0 12.2 0.0 DEMAND KVA: 45.0 DEMAND AMPS: 188 VOLTAGE: 240/120 EXISTING PANEL MOUNTING: FLUSH NEUTRAL: 100% PHASE: 1 WIRE: 3 IG NO MAIN: MCB MCB AMPS: 200 SECTION 1 of 1 AIC: 10,000 BUS AMPS: 225 LOAD DESCRIPTION TP LOAD CKT OCP PH OCP CKT LOAD TP LOAD DESCRIPTION 120/1 AWIll=W 16 20 3/4" tisi-Es NEMA 5 -20R rid BURNER RANGE W/ OVEN 0.2 120/1 KLP -2 2 20 3/4" 2 #12 &1 #12G NEMA 5 -20R II`` pal )LE ON STAND 1 m'� 1111' rALMIENCOMITIP M11 15 -..itaillIMIEM 3/4" 2 #12 &1 #12G NEMA 5 -20R EXHAUST HOOD W/ FIRE SYSTEM 0.4 P El KLP -2 3 20 3/4" 2 #12 &1 #12G NEMA 5 -20R ECTION OVEN 1.5 120/1 Eall F31/1111% 0 El 3/4" 2 #12 &1 #12G NEMA 5 -20R rit%Eril Pisimini,a:111:11 1111■111E11MVEril,d4AMEKIII 10 REACH-IN REFRIGERATOR s. Ell I. 120/1 KLP -2 I a 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 11 rIMMIENIZU110111MS111K11=1/ 1.4 120/1 KLP -2 12 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 13 WORK TABLE i PRIPMCI FillIElmalrAIK:11M1LFZI 120/1 10 2#12&1#12G MI 14 1 120/1 KLP -2 13 20 iara 2 #12 &1 #12G NEMA 5 -20R 15 ICE MAKER W/ BIN 2.4 240/1 KLP -2 9,11 r 3/4" r" Wiw Fr' We" Wr' III/ V 2 240/1 KLP -2 PHASE TOTALS A 0.00 B: 0.00 C: 0.00 LOAD TYPE (TP) Nonsimultaneous 0 Lighting Receptacle Motor Largest Motor Heat Kitchen Other TOTAL SECTION 1: 0.0 0.0 0.0 0.0 0.0 0.0 0.0 2 ALL SECTIONS: BLENDER STATION 1 120/1 KLP -2 8 20 DEMAND FACTOR: 1.00 Calculation 1.00 1.25 1.00 1.00 1.00 1 DEMAND: 0.0 0.0 0.0 0.0 0.0 0.0 0.0 DEMAND KVA: 0.0 DEMAND AMPS: '0 23 KITCHEN EQUIPMENT SCHEDULE ELECTRICAL ITEM NO. 'DESCRIPTION LOAD VOLT/ PHASE 120/1 PANEL KLP -2 CIRCUIT NO. 1 BREAKER SIZE 20 CONDUIT SIZE 3/4" WIRE SIZE 2 #12 &1 #12G CONNECTION NOTES AMPS IKW 1.4 HP RECEPT. NEMA 5 -20R DIRECT 4 REACH-IN FREEZER FRYER 1.5 120/1 KLP -2 16 20 3/4" 2#12&1#12G NEMA 5 -20R 6 BURNER RANGE W/ OVEN 0.2 120/1 KLP -2 2 20 3/4" 2 #12 &1 #12G NEMA 5 -20R )LE ON STAND 1 120/1 KLP -2 15 20 3/4" 2 #12 &1 #12G NEMA 5 -20R EXHAUST HOOD W/ FIRE SYSTEM 0.4 120/1 KLP -2 3 20 3/4" 2 #12 &1 #12G NEMA 5 -20R ECTION OVEN 1.5 120/1 KLP -2 17 3/4" 2 #12 &1 #12G NEMA 5 -20R 10 REACH-IN REFRIGERATOR 1 120/1 KLP -2 14 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 11 REACH-IN FREEZER 1.4 120/1 KLP -2 12 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 13 WORK TABLE 0.2 120/1 KLP -2 10 20 3/4" 2#12&1#12G NEMA 5 -20R 14 HOT FOOD TABLE 1 120/1 KLP -2 13 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 15 ICE MAKER W/ BIN 2.4 240/1 KLP -2 9,11 20 3/4" 2 #12 &1 #12G NEMA 6 -20R 16 BACK BAR COOLER 2 240/1 KLP -2 18,20 20 3/4" 2 #12 &1 #12G NEMA 6 -20R 17 WAITRESS STATION 0.4 120/1 KLP -2 7 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 2 21 BLENDER STATION 1 120/1 KLP -2 8 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 22 BACK BAR REFRIGERATOR 1 120/1 KLP -2 6 20 3/4" 2 #12 &1 #12G NEMA 5 -20R 23 BOTTLE COOLER 1.2 120/1 KLP -2 4 20 3/4" 2#12&1#12G NEMA 5 -20R NOTES: 1. PROVIDE DISCONNECT SWITCH 2. PROVIDE FLOOR BOX RECESSED IN CONCRETE WITH SATIN ALUMINUM ABOVE FLOOR SERVICE FITTING, EXTENDING A MAXIMUM OF 3" A.F.F. PROVIDE COMPLETE WITH DATA DEVICE AND STAINLESS STEEL COVERPLATE. ROUTE 1" CONDUIT BACK TO P.O.S. EQUIPMENT LOCATION. REFER TO DRAWING FOR EXACT LOCATION OF FLOOR BOX AND P.O.S. EQUIPMENT LOCATION. ARCHITECTURAL NT TRIP. INTERLOCK WITH HOOD CONTROLS. GENERAL NOTES A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED. B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE LATEST EDITION ADOPTED BY INDIANA, THE INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL /MUNICIPAL CODES, AND THE AUTHORITY HAVING JURISDICTION. C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH. D. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING MATERIAL. E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS. F. FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND MANUFACTURER'S WRITTEN RECOMMENDATIONS. G. HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME RUNS MAY BE COMBINED AT THE CONTRACTOR'S DISCRETION NOT GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL CONDUCTORS, AND A GROUNDING CONDUCTOR. H. EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A DEDICATED NEUTRAL BACK TO THE PANEL. I. CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL USE LINK SEALS. J. WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED NOT EXCEEDING INTERVALS OF 48 INCHES, AND NOT MORE THAN 6 INCHES FROM CABINETS, BOXES, FITTINGS, OUTLETS, RACKS, FRAMES AND TERMINALS. CO Carmel Redevelopment Commission 111 West Main Street Carmel, Indiana 46032 317.571 -2787 (ARTS) I- W 0 a. C a) E tt3 0 Scope Drawings: These drawings indicate the general scope of the project in terms of architectural design concept, the dimensions of the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the Contract. On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of the work. Revisions: Issue Date 01/20/09 Drawn By KIA Checked By BKS Drawing Title: ELECTRICAL SCHEDULES PLANS Certified By I PE19700197 A to O e g g do STATE OF o �Jpy A 4 /ONAMS 7 B. WM 775o/o/ L'Acquis Project Number: 08109