HomeMy WebLinkAboutE400 Electrical One-Line & Riser DiagramONE LINE DIAGRAM LEGEND
�ocAF
»AT
CU -1
240/2
32.9
CONTACT NORMALLY CLOSED
KLP -2, 25,27
2 #8, 1- #10(G), 1" C.
2P -50A
1
CU -2
240/2
32.9
FUSE. 'zzA' INDICATES FUSE RATING
KLP -2, 29,31
2 #8, 1- #10(G), 1" C.
2P -50A
1
CU -3
240/2
32.9
ma
LP -1, 12,14
2 #8, 1-#10(G), 1" C.
2P -50A
1
CU -4
240/2
32.9
(3)
400 -5A f
LP -1, 16,18
2 #8, 1-#10(G), 1" C.
2P -50A
1
SE -1
120/1
4.3
1/2
LP -1 -26
2-#12, 1-#12(G), 3/4" C.
1P-20A
1,2
SE -2
120/1
4.3
TVSS
1/2
LP -1 -28
2 #12, 1- #12(G), 3/4" C.
1P -20A
1,2
SE -3
120/1
4.3
SHUNT TRIP
1/2
LP -1 -30
2 #12, 1- #12(G), 3/4" C.
1P-20A
1,2
AHU -1
240/2
1
LP -1, 11,13
2-#12, 1-#12(G), 3/4" C.
2P -20A
1,2
AHU -2
240/2
1
LP -1, 15,17
2 #12, 1- #12(G), 3/4" C.
2P -20A
1
AHU -2
240/2
1
LP -1, 19,21
2 #12, 1- #12(G), 3/4" C.
2P -20A
1
AHU -2
240/2
1
LP -1, 23,25
2 #12, 1- #12(G), 3/4" C.
2P -20A
1
GENERAL POWER CONNECTION SCHEDULE NOTES:
(G) SIZED PER BRANCH CIRCUIT UNLESS SHOWN TO BE SIZED DIFFERENTLY. ALL CONDUCTORS TYPE AWG. DUAL ELEMENT
UNIT TO BE UN FUSED.
WITH MECHANICAL CONTRACTOR.
COMPLETE.
TYPE FUSE
CIRCUIT TO INCLUDE ONE (1) GREEN GROUNDING CONDUCTOR
AND PROPER VOLTAGE. IF FUSE SIZE NOT SHOWN,
POWER CONNECTION SCHEDULE NOTES:
1. PROVIDE NEW DISCONNECT. COORDINATE INSTALLATION
2. INSTALL PROVIDED WALL MOUNT SPEED CONTROLLER
ONE LINE DIAGRAM LEGEND
�ocAF
»AT
CIRCUIT BREAKER (OPEN) 'xxAF' INDICATES FRAME SIZE
'yyAT' INDICATES TRIP SIZE
---11--
CONTACT, NORMALLY OPEN
CONTACT NORMALLY CLOSED
l
YYA
DISCONNECT SWITCH
H UNFUSED. YYA INDICATES SWITCH RATING
1
YYA
DISCONNECT SWITCH AIR BREAK WITH FUSE. 'zzA' INDICATES FUSE RATING
'YYA' INDICATES SWITCH RATING
11 zzA
FUSE. 'zzA' INDICATES FUSE RATING
GROUND CONNECTION SYSTEM AND OR EQUIPMENT
I`:J
MOTOR AND LABEL. '3' DENOTES HORSEPOWER
lXX- XX -X -Xl
ma
PANELBOARD
E 3
MAGNETIC STARTER WITH NEMA SIZE INDICATOR
Q
xxx KVA
xxxV x0 xW PRI
MOUNTED TRANSFORMER
Tx I PAD
xxxY /xxxV x0 xW SEC
(3)
400 -5A f
CURRENT TRANSFORMER. '3' INDICATES QUANTITY, '400 -5A' INDICATES RATIO
A
3 PHASE, 3 WIRE DELTA CONNECTION
_EY
3 PHASE, 4 WIRE WYE CONNECTION (GROUNDED NEUTRAL)
AFD
ADJUSTABLE FREQUENCY DRIVE. '3' REFERENCES DETAIL NUMBER
l
(41)
OPEN DISTRIBUTION FUSED CUT -OUT. 15KV -110KV L1 W(B1 L),
100A, 10KAIC, PARALLEL GROOVE LAMPS, NEMA HEAVY DUTY "B"
BRACKETS. A.B. CHANCE (HUBBELL) C710112PB. PROVIDE POLE
MOUNTING HARDWARE AS REQUIRED
-0 0--Il
SURGE ARRESTER. RATED 3KV, 2.55KV MCOV. RISER -POLE STYLE
FOR MOUNTING OVER THE ARM. OHIO BRASS RISER -POLE DYNAVAR
PVR 221603 WITH PVR BRACKET
V
MEDIUM VOLTAGE TERMINATION. HEAT SHRINK STYLE, SOLID END
COMPRESSION CONNECTOR. RAYCHEM OR EQUAL BY MAC PRODUCT,
OKONITE, OR 3M
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSOR
DIGITAL METERING
M
ST
SHUNT TRIP
TAP PER NEC 10' TAP
RULE (TYPICAL OF 3)
LP -1
42 CCT
18 KAIC
(2) 3 350 KCMIL, 2 #1G, (2) 2 -1/2 "C
(3) 3/0, #6G.,2 "C
SCALE: NONE
EXISTING
PANEL
NEMA -3R
-I 200AS
200AF
PROVIDE NEW JUNCTION
BOX IN CEILING SPACE.
SPLICE AND EXTEND
EXISTING CIRCUITS AS
NECESSARY.
RELOCATE EXISTING
PANEL AS SHOWN
(3) 3/0 #6G., 2" C.
ONE -LINE DIAGRAM
KLP -2
42 CCT
18 KAIC
DUKE ENERGY 240/120V
SINGLE PHASE PRIMARY
UTILITY OWNED 120/240V
1- PHASE,600A METER
MOUNT ON EXTERIOR WALL
7 -WALL MOUNTED 600A, NEMA 3R RATED
WIRE-WAY PER NEC REQUIREMENTS
(3) 3/O, #6G.,2 "C
UTILITY OWNED METER.
COORDINATE WITH DUKE
ENERGY FOR CONNECTION
REQUIREMENTS
WIRE -WAY, METER RISER
SCALE: NONE
WALL MOUNT WIRE -WAY ABOVE
THE DISCONNECT AS SHOWN
DISCONNECT SERVING
EXISTING PANEL
GROUND LEVEL
POWER CO\
\ECTIO\ SCHED„LE
EQUIPMENT
VOLTS/
POLE
MCA
KW
HP
PANEL CIRCUIT
NUMBER
BRANCH CIRCUIT
GENERAL NOTES
A. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE
APPROXIMATE. ALL LOCATIONS SHALL BE FIELD VERIFIED.
B. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE LATEST EDITION ADOPTED BY INDIANA, THE
INDIANA ELECTRICAL CODE AMENDMENTS, LOCAL /MUNICIPAL CODES,
AND THE AUTHORITY HAVING JURISDICTION.
C. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR
VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT
LESS THAN 12" IN LENGTH, NOR GREATER THAN 36" IN LENGTH.
D. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE
CONDUIT SEALING MATERIAL.
E. ALL CABLE SIZES SHALL UTILIZE COPPER CONDUCTORS.
F. FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN
ROUTING CONDUIT. ALL CONDUITS CROSSING EXPANSION JOINTS
SHALL BE INSTALLED WITH EXPANSION FITTINGS. EXPANSION FITTINGS
SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND
MANUFACTURER'S WRITTEN RECOMMENDATIONS.
G. HOME RUNS SHALL NOT BE COMBINED IN A RACEWAY UNLESS SHOWN
ON THE CONTRACT DRAWINGS. SINGLE PHASE BRANCH CIRCUIT HOME
RUNS MAY BE COMBINED AT THE CONTRACTOR'S DISCRETION NOT
GREATER THAN (3) PHASE CONDUCTORS, (3) NEUTRAL CONDUCTORS,
AND A GROUNDING CONDUCTOR.
H. EACH SINGLE PHASE BRANCH CONDUCTOR SHALL HAVE A DEDICATED
NEUTRAL BACK TO THE PANEL.
I. CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL
USE LINK SEALS.
J. WHERE LOW VOLTAGE (CONTROL) CABLING IS ALLOWED TO BE
INSTALLED WITHOUT A RACEWAY, IT SHALL BE SUPPORTED PER
SECTION 260523 NOT EXCEEDING INTERVALS OF 48 INCHES, AND NOT
MORE THAN 6 INCHES FROM CABINETS, BOXES, FITTINGS, OUTLETS,
RACKS, FRAMES AND TERMINALS.
DISCONNECT
REMARKS
0-4
g g
0/6
4t4 I
u 1
Carmel
Redevelopment Commission
111 Welt Mak Street
Cannel, Wilma 46032
317.571 -2787 (ARTS)
3 r�
Li.o
o
J
2 I
cc W
N
as
U
C
to
C
Scope Drawings:
These drawings indicate the general scope of the project
in terms of architectural design concept, the dimensions of
the building, the major architectural elements and the type
of structural, mechanical and electrical systems.
The drawings do not necessarily indicate or describe all
work required for full performance and completion of the
requirements of the Contract.
On the basis of the general scope indicated or described,
the trade contractors shall furnish all items required for the
proper execution and completion of the work.
Revisions:
Issue Date
01/20/09
Drawn By
KIA
Checked By
BKS
Drawing Title:
ELECTRICAL
ONE -LINE
AND RISER
DIAGRAM
PLANS
Certified By
a0a
1 I
a PE19700197
v S :ce: CI A: A NYDIPAIV
7
L'Acquls Project Number:
08109