HomeMy WebLinkAboutE500 Electrical Detail SheetSCALE: NONE NOTES: 3/4" DIA. X 10' LONG COPPER CLAD STEEL GROUND ROD J FINISHED FLOOR EXOTHERMICALLY WELD CABLE TO GROUND RODS CONC. BASE WITH 1" CHAMFER: PROVIDE VERY HIGH QUALITY SMOOTH FINISH #6 AWG GROUND WIRE FINISH GRADE GROUND ROD 8 #8 VERT. BARS W/ #3 TIES 16" O.C. SCALE: NONE "FS" BOX WITH STAINLESS STEEL COVER PLATE AS REQ'D. THREADLESS CONNECTOR SCALE: NONE COUPLING SCALE: NONE 7-KITCHEN HOOD 10 -0" POLE BASE COVER ori) �(OL� 014 0 24" DIA. PANEL 3/0 COPPER CABLE HANDHOLE SERVICE GROUNDING ELECTRODE ARRANGEMENT DETAIL MOUNTING BOLT LAYOUT PER MFGR. TEMPLATE s GROUT BASE THREADLESS CONNECTOR KITCHEN WATERPROOF ('j"\ PEDESTAL RECEPTACLE 3/0 COPPER CABLE POLE BASE DETAIL 30" AFG SHUNT -TRIP DEVICE LOCATED IN PANEL Oi CONTACT CLOSURE (FUSIBLE LINK) ACTIVATED BY HEAT OR FIRE. PROVIDED WITH HOOD. 120V. TO SERVE FIRE PROTECTION SYSTEM IN HOOD. O3 3P. CIRCUIT BREAKER FOR NP. EQUIP. UNDER THE HOOD. KITCHEN HOOD SHUNT TRIP WIRING DIAGRAM NOTES: CONTROL STATION (BY OTHER DIVISION) GAS VALVE SHUT OFF WIRING DIAGRAM CONTROL CONDUIT AND WIRING TO GAS VALVE RELAY RELAY PANEL BY DIV. 26 NOTES: SCALE: NONE TO SOLENOID VALVE GAS VALVE CONTROL STATION FURNISHED OTHER DIVISION. INSTALLED AND WIRED BY DIV. 26 GAS VALVE SHUTOFF SYSTEM DETAIL SCALE: NONE TO 240/120V PANEL PER 240V, 30 FREEZER POWER PLANS FEED PER EQUIPMENT CABLE AND CONDUIT SCHEDULE 240V, 3P FUSED DISCONNECT SWITCH (BY FREEZER MFR.) CONDUIT AND WIRING (BY DIV. 26) O 000 4 CONTROL id.)4 I r SCALE: NONE TO 240/120V PANEL PER PLANS 240V, 30 COOLER POWER FEED PER EQUIPMENT CABLE AND CONDUIT SCHEDULE 240V, 3P FUSED DISCONNECT SWITCH (BY COOLER MFR.) SCALE: NONE RELAY PANEL (BY OTHER DIVISION) 120V. OPEN SFRJT EVAPORATOR EQUIPMENT (THERMOSTAT, SOLENOID VALVE, DRAIN HEATER AND AND TERMINAL BLOCK BY FEEDER MFR). WIRING. 4#1 0, #1 OG., 3/4 "C. CONDUIT AND WIRING (BY DIV. 26) GAS VALVE RELAY PANEL FURNISHED OTHER DIVISION. INSTALLED AND WIRED BY DIV. 26 r EVAPORATOR EQUIPMENT (THERMOSTAT, SOLENOID VALVE, DRAIN HEATER AND AND TERMINAL BLOCK BY FEEDER MFR). WIRING. 1. ALL EQUIPMENT SHOWN DARK IS TO BE PROVIDED AND INSTALLED. 2. ALL EQUIPMENT SHOWN SHADED IS BY FREEZER MANUFACTURER. 3. SHOULD THE FREEZER EQUIPMENT CONTRACTOR PROVIDE A FREEZER UNIT MANUFACTURER THAT REQUIRES ADDITIONAL CONDUIT AND WIRING THAN SHOWN, THE COST FOR SUCH WORK SHALL BE THE RESPONSIBILITY OF THE FREEZER EQUIPMENT CONTRACTOR. FREEZER WIRING DIAGRAM TO 240/120V PANEL PER PLANS 2#10, #10G., 3/4 "C. JUNCTION R S) BOX BY EVAPORATOR COOLER MFR THERMOSTAT AND SOLENOID 4 #10, #10G., 3/4 "C. VALVE BY COOLER MFR. 1. ALL EQUIPMENT SHOWN DARK IS TO BE PROVIDED BY DIVISION 26. 2. ALL EQUIPMENT SHOWN SHADED IS BY OTHER DIVISION. 3. SHOULD THE COOLER EQUIPMENT CONTRACTOR PROVIDE A COOLER UNIT MANUFACTURER THAT REQUIRES ADDITIONAL CONDUIT AND WIRING THAN SHOWN, THE COST FOR SUCH WORK SHALL BE THE RESPONSIBILITY OF THE COOLER EQUIPMENT CONTRACTOR. COOLER WIRING DIAGRAM z J cn cn ow z o J p0 Cn un F- z z l' z o 111 West Main Street Carmel, Indiana 46032 317.571 -2787 (ARTS) C co C E Scope Drawings: These drawings indicate the general scope of the project in terms of architectural design concept, the dimensions of the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the Contract. On the basis of the general scope indicated or described, the trade contractors shall furnish all items required for the proper execution and completion of the work. Revisions: Issue Date 01/20/09 Drawn By KIA Checked By BKS Drawing Title: ELECTRICAL DETAIL SHEET Certified By itST Drawing Number: 5 0 L'Acquls Project Number: 08109