HomeMy WebLinkAboutM201 Demolition Plan, New Mech PlanDIFFUSERS lii GRILLES SCHEDULE MARK MAX DIMENSIONAL DATA THROW DATA MOUNT PRESS. DROP C �N WC.) MAX NC SOUND LEVEL ACCESSORIES SPECIFICATION SECTION WITH MODEL NUMBER FACE SIZE SLOT INFO DIRECTION DISTANCE NOM. CFM BALANCE DAMPER PLENUM BOOT TAMPER- PROOF SCREWS SG 75 6X6 3/4 2- DEFLECTION 8 FRAME 0.03 <20 YES 233713 TITUS 300FS SG2 250 12X6 3/4 2- DEFLECTION 16 FRAME 0.07 <20 YES 233713 TITUS 300FS SG3 255 12X6 3/4 2- DEFLECTION 16 FRAME 0.07 <20 YES 233713 TITUS 300R5 RG1 250 12X6 3/4 1- DEFLECTION FRAME 0.07 <20 YES 233713 TITUS 350RL RG2 1050 24X12 1/2 FRAME 0.1 23 233713 TITUS 355RL RG3 2100 24X24 1/2 FRAME 0.1 23 233713 TITUS 355RL MOTORIZED DAMPER (TYP 16/16 RA GF -3 EMM 24/20 RA PI 'I* 1 6/1 6 1 6/1 6 RAIL 16/16 SA �GF -1 I AHU -1 L__\ MECHANICAL DEMOLITION PLAN SCALE: 1 /8" 1' -0" 0 4/8 OA 4' MOTORIZED DAMPER (TYP.) 8' 14/8 OA 16' AHU -4 16/16 SA GF -4 24/20 RA 16/16 SA 40 UP 40 UP 50 50 �T AHU -1 28/12 OA 14/12 12/� 16 /tfi 111 16/16-1 12/6 MECHANICAL ROOM ENLARGED PLAN SCALE: 1 /4" 1' -0" REPLACE ALL EXISTING 12" REGISTERS 0 2' 4' NOTE: OA OUTSIDE AIR SA SUPPLY AIR RA RETURN AIR 8' 16/16-J' 14/8 \--28/12 OA x -14/8 OA iYP.10 AIU- 24/20 RA AHU -3 8/6 (NP.) MECHANICAL FIRST FLOOR PLAN SCALE: 1/8" 1' -0" 0 4' 8' 16' EF -3 EXISTING ATTIC VENTILATION FAN TO REMAIN SHEET KEYNOTES 1. EXISTING EXHAUST FAN TO REMAIN. 2. TOTAL HIGH EFFICIENCY PARTICULATE GASEOUS FILTRATION SYSTEM AQE EVERCLEAR DELUXE SMOKIE EATER (SE -1, SE -2 SE -3), 115V, 1 /2HP. RUN FAN AT LOW SPEED. COORDINATE INSTALLATION WITH STRUCTURE. 3. KITCHEN EXHAUST HOOD CAPTIVEAIRE MODEL 5424 ND -2. SEE SHEET M202 FOR MORE INFORMATION. 4. EXHAUST FAN LIKE BROAN MODEL 684, 120V, 48W, 75cfm. ROUTE 40 DUCT THROUGH ATTIC AND TERMINATE WITH ROOF CAP. 5. REMOVE EXISTING AC UNIT, TURN OVER TO THE OWNER. PATCH OPENING TO MATCH EXISTING WALL. 6. REMOVE EXISTING FURNACES, REFRIGERANT PIPING AND FLUE COMPLETE. PATCH ROOF TO MATCH EXISTING. 7. WALLMOUNT EXHAUST FAN CAPTIVEAIRE MODEL NCA18HPFA. MOUNT 10' ABOVE GROUND. SEE SHEET M202 FOR MORE INFORMATION. 8. BLOWER FAN COIL CARRIER 42BVC20, TOP SUPPLY, 1800cfm, 230 -1 -60, 1.85 "S.P., 4 ROWS DX COOILNG COIL (LEFT AND RIGHT HAND COIL REFER TO PLAN), PROVIDE DISTRIBUTOR AND EXPANSION VALVE, 540cfm OUTSIDE AIR, 1HP MOTOR WITH MOTOR CONTROL WITH INTERLOCKING DISCONNECT, PROVIDE MIXING BOX (TOP /REAR INLET) WITH RAILS PER MANUFACTURER, PROVIDE THERMOSTAT. 9. GAS -FIRED INDOOR SEPARATED COMBUSTION DUCT FURNACE AIREDALE IFS125SFR(L)LN10C1, 230 -1 -60, MAXIMUM AIR TEMPERATURE RISE 100'F, MINIMUM 926cfm, STEP DOWN TRANSFORMER FROM LINE VOLTAGE TO 115V SHALL BE PROVIDEE FOR OPERATION OF THE POWER EXHAUSTER MOTOR, INSTALL AND SUPPORT UNIT PER MANUFACTURER RECOMMENDATIONS. 10. EXHAUST AIR PIPE AND COMBUSTION AIR PIPE. INSTALL CONCENTRIC VENT KIT AND TERMINATE ABOVE ROOF WITH CAP PER MANUFACTURER RECOMMENDATION. CONDENSING UNIT CARRIER 24ABS360, 230 -1 -60, 32.9MCA, 1/4HP FAN MOTOR. INSTALL UNIT PER MANUFACTURER RECOMMENDATION. 12. ROUTE REFRIGERANT PIPING FOR EACH CONDENSING UNIT INSIDE 6" PVC SLEEVE UNDER SLAB. 13. CONDENSATE DRAIN LINE, ROUTE TO FLOOR DRAIN. 14. INSTALL 36 "x36 "x24" DEEP INSULATED PLENUM BEHIND INTAKE AIR LOUVER. 15. PROVIDE CAPTIVEAIRE 16 "0 GREASE DUCT, SINGLE WALL CONSTRUCTION MADE FROM 20 GAUGE, 430 STAINLESS STEEL. INSTALL PER MANUFACTURER RECOMMENDATION. PROVIDE THERMAL CERAMICS DUCT WRAP 2x2 WHICH IS A FOIL- ENCAPSULATED, NON COMBUSTIBLE, INORGANIC, FLEXIBLE FIREPROOFING WRAP, 2 HOUR FIRE RATED ENCLOSURE. 16. CAP EXISTING DUCT. 17. 18. 11. PROVIDE 2" INSULATION ON OUTSIDE AIR DUCT. INSTALL 24 "x24" GRILLE ON BOTH SIDES OF WALL BELOW 9' -0" CEILING FOR TRANSFER AIR. 19. KITCHEN EQUIPMENT VENDOR TO LOCATE CONDENSER FOR COOLER ON WALL RACK. 20. INSTALL STATIC PRESSURE SENSOR ABOVE CEILING. SENSE PRESSURE IN ROOM, WITH REFERENCE IN ATTIC. 21. INSTALL 24 "x12" GRILLE ABOVE DOOR ON BOTH SIDES OF WALL BELOW 9' -O" CEILING FOR TRANSFER AIR. 22. NSTALL 24 "x24" GRILLE AT CEILING, DUCTED TO TO ATTIC WITH COUNTERBALANCED BACKDRAFT DAMPER SET TO +0.03 "SP. 23. INSTALL 36 "x36" EXTRUDED ALUMINUM DRAINABLE BLADE LOUVER LIKE GREENHECK ESD -202 AT 13' -O" ABOVE GROUND TO BOTTOM. REFER TO ARCH. ELEVATION DRAWING. 24. WALL MOUNT SPEED CONTROLLER FOR SMOKE EATER. SEQUENCE OF OPERATION PROVIDE TIMELOCK OR USE PROGRAMMABLE THERMOSTATS THAT HAVE OUTPUTS FOR OCCUPIED /UNOCCUPIED MODE. IN UNOCCUPIED MODE, OUTSIDE AIR MOTORIZED DAMPER SHALL REMAIN CLOSED AND RETURN AIR MOTORIZED DAMPER SHALL REMAIN OPEN. IN OCCUPIED MODE, MODULATE OUTSIDE AIR DAMPER FROM MINIMUM TO MAXIMUM POSITION AND MODULATE RETURN AIR DAMPER FROM MAXIMUM TO MINIMUM POSITION AS REQUIRED FOR VENTILATION. MINIMUM AND MAXIMUM DAMPER POSITIONS TO BE DETERMNED BY BALANCER, TO THE AIRFLOWS LISTED. VENTILATION DEMAND SHALL BE SET BY CO2 SENSORS OR STATIC PRESSURE; WHICHEVER REQUIRES GREATER AMOUNT OF OUTSIDE AIR. THRESHOLD FOR INCREASED VENTILATION AT EACH RESPECTIVE SYSTEM IS 1100 PPM, SENSED AT CO2 SENSORS. THRESHOLD FOR INCREASED VENTILATION IS +0.01 "SP, SENSED AT THE STATIC PRESSURE SENSOR. IN UNOCCUPIED MODE, CYCLE FAN ON /OFF IN RESPONSE TO HEATING /COOLING. IN OCCUPIED MODE, RUN FAN CONTINUOUSLY. IN BOTH MODES, CYCLE BURNER OR CONDENSING UNIT TO SATISFY HEATING /COOLING SETPOINTS AT AUTO- CHANGEOVER THERMOSTATS. ALL NEW DUCTWORK SHALL BE RIGID SHEET METAL, EXCEPT LAST 4' NEAREST REGISTER WILL BE FLEX DUCT. INSULATE ALL DUCTS. I- 0 W 0 CC oo N H c H H N Carmel Redevelopment Commission 111 West Main Street Carmel, Indiana 46032 317.571 -2787 (ARTS) Scope Drawings: Revisions: Drawing Title: co C C a) E These drawings indicate the general scope of the projec in terms of architectural design concept, the dimensions o the building, the major architectural elements and the type of structural, mechanical and electrical systems. The drawings do not necessarily indicate or describe all work required for full performance and completion of the requirements of the Contract. On the basis of the general scope indicated or describe the trade contractors shall furnish all items required for thi proper execution and completion of the work. Issue Date 01/20/09 Drawn By OSO Checked B! AJ M Demolition Plan, New Mech. Plan, Schedule And Sections forfIllael Rip Drawing Number: M 2 0 L'Acquis Project Number: 08109