HomeMy WebLinkAboutM202 Kitchen Plan & Exhaust FanFAN
FAN
UNIT
TAG
EXHAUST
GREASE
CUP
GRAVITY
DAMPER
WALL
MOUNT
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
1
TYPE
0
UNIT
NO.
FAN UNIT MODEL
MODEL
TAG
CFM
S.P.
RPM
H.P.
0
VOLT
FLA
WEIGHT (LBS.)
1
NCA18HPFA
NCA18HPFA
10.2
2450
1.750
1205
1.500
1
230
10.2
176.18
FAN
UNIT
NO.
FAN
UNIT
TAG
EXHAUST
GREASE
CUP
GRAVITY
DAMPER
WALL
MOUNT
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
1
TYPE
0
YES
YES
YES
YES
FAN
UNIT
NO.
OPTION (Qty. Descr.)
ROW
1
1 Wallmount 27.5 sq. x
2"
HOOD CONFIG.
END TO
END
ROW
ALONE
ALONE
NO.
TAG
PACKAGE
LOCATION
SWITCHES
ROOFTOP
STARTERS
OPTION
FANS CONTROLLED
LOCATION
QUANTITY
TYPE
0
H.P.
VOLT
FLA
1
210110FP
Wall Mount In SS Box
Face Mount Right Side
Hood
1 Light
1 Fan
Exhaust On In Fire, Fans On /Off
Thermostatically Controlled
Exhaust
1
1.500
230
10.2
Hood 1
#11111 ,N issma imasm
JOB CARMEL VFW
LOC�1 TION
1 /12/09
JOB 893442
LAP IV
.L) WO' 893442
.DRA WN BY RDR
REV 1.00
HOOD INFORMATION
HOOD
NO.
MODEL
5424
ND -2
LENGTH
12' 3.00"
MAX.
COOKING
TEMP.
450 Deg.
EXHAUST PLENUM
TOTAL
EXH. CFM
2450
RISER(S)
WIDTH LENG. DIA. CFM
S.P.
16"
2450
1.106"
SUPPLY PLENUM
TOTAL
SUP. CFM
0
RI
WIDTH
LENG.
DIA.
CFM
S.P.
HOOD INFORMATION
HOOD
NO.
FILTER(S)
TYPE
Stainless Steel (High E
QTY.
3
5
HEIGHT
16"
16"
LENGTH
16"
20"
LIG
QTY.
4
TYPE
Screw In Halogen Bulb,
WIRE
GUARD
NO
UTILITY CABINET(S)
LOCATION
FIRE SYSTEM
TYPE
SIZE
ELECTRICAL
MODEL
SWITCHES
QUANTITY
LOCATION
FIRE
SYSTEM
PIPING
NO
HOOD
WEIGHT
687
LBS
HOOD OPTIONS
FAN OPTIONS
IT IS THE RESPONSIBILITY
OF THE ARCHITECT /OWNER TO
ENSURE THAT THE HOOD CLEARANCE
FROM LIMITED COMBUSTIBLE
AND COMBUSTIBLE MATERIALS
IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
HOOD
NO.
OPTION
LEFT END STANDOFF
3" Wide
BACKSPLASH
80.00" High X 150.00" Long 430 SS
LEFT SIDESPLASH
80.00" High X 54.00" Long 430 SS
BACKSPLASH INSIDE CORNER
80.00" High X 4.00" Long
430 SS
FIELD
WRAPPER 6.00" High Front, Right
RIGHT END PANEL
36" Top Width, 32" Bottom Width, 45" High
430 SS
FAN ACCESSORIES
EXHAUST RISER
HANGING ANGLE
16" STAINLESS STEEL
(HIGH EFFICIENCY)
3.00" INTERNAL STANDOFF
GREASE DRAIN
WITH REMOVABLE CUP
END PANEL
G
P
4.0000
54.0000
BACKSPLASH 80.00"
HIGH X 150.00" LONG
36.0000
EQUIPMENT
BY OTHERS
FIELD WRAPPER 6.00" HIGH
7 Z
(SEE HOOD OPTIONS TABLE)
SCREW IN HALOGEN
ULB, STANDARD INCANDESCENT
i 00
LIGHT FIXTURE
45.0000
SECTION VIEW MODEL 5424ND-2
CAPTIVE —AIRE HOODS ARE
BUILT IN COMPLIANCE WITH
NFPA #96
AND ARE RECOGNIZED BY ONE
OR MORE OF THE FOLLOWING:
NSF INTERNATIONAL
ETL LISTED FILE# 3054804 -001
48.0' MAX
24.0000 NOM.
78.0000
102.
AFF MIN.
I
000
Cen ±rif uga
C RO R
HOOD
CONSTRUCTION
430 SS
Where Exposed
fiff
54.0000
3.0000J
B
—3.0000
igh Press (Fan #1
F
HT
U.L. Listed Screw In Halogen Bulb
0
NOTE:
PLAN VIEW Hood #1
12' 3.00" LONG 5424ND -2
Additional hanging angles provided for hoods longer than 12 ft.
\CA1 8
r
W
us
16.0000
PFA)
Al A,
4.1
16.0000
Field Cut
12' 3.00 "Nom. /12' 3.00 "OD
FEATURES:
WALL MOUNTED FANS
RESTAURANT MODEL
UL762 UL705
AMCA SOUND AND AIR CERTIFIED
WIRING FROM MOTOR TO DISCONNECT SWITCH
WEATHERPROOF DISCONNECT
HIGH HEAT OPERATION 300 °F (149 °C)
GREASE CLASSIFICATION TESTING
NORMAL TEMPERATURE TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING AIR AT 300 °F (149 °C)
UNTIL ALL FAN PARTS HAVE REACHED
THERMAL EQUILIBRIUM, AND WITHOUT ANY
DETERIORATING EFFECTS TO THE FAN WHICH
WOULD CAUSE UNSAFE OPERATION.
ABNORMAL FLARE —UP TEST
EXHAUST FAN MUST OPERATE CONTINUOUSLY
WHILE EXHAUSTING BURNING GREASE VAPORS
AT 600 °F (316 °C) FOR A PERIOD OF
15 MINUTES WITHOUT THE FAN BECOMING
DAMAGED TO ANY EXTENT THAT COULD CAUSE
AN UNSAFE CONDITION.
OPTIONS:
A
ELECTRICAL PACKAGES
ELECTRICAL PREWIRE PACKAGE
DRAWING NUMBER
210110FP
JOB NAME CARMEL VFW
JOB NUMBER
893442
CONTROL INPUT 120VAC H1 =LINE, N1= NEUTRAL 15A BKR DO NOT WIRE TO SHUNT TRIP
BREAKER
9
21
23
24
2
3
4
5
6
7
8
10
11
H1
BK
BK
12 BK
13
14
16
17
18 INPUT
2 WIRE
1 PHASE
19
20
22
FS -01
BL F .2 I5
(Fan Switch Shown
TI 04 CInsitalled)
18 11 15 0 OR Al A2
TI -04 DS Delay
TIMER (30 min)
R1 -1
BK N CO3„S
0
NO
H2
Al
WH
WH
DS -1 TI -04
DS1S -04
WH
I Al A
a Cl C 0 NC1t� BK
NO �NO1tS BK� -_tiWH_
0
LIGHT INPUT 120VAC H2 —H5 =LINE, N2 —N5= NEUTRAL
15 15A BKR LS -01
BR B 6,-BK WH -0 W cS
1 PHASE 230V
C -1
L1 1 T1 21
WH
0N26\--
(EXH -1 GR
22 1
NOTE 1: DUCT THERMOSTATS FIELD WIRED WHEN RISERS SHIPPED LOOSE. IF MULTIPLE THERMOSTATS, THEY ARE WIRED
DATE
1/12/2009
DRAWN BY
220V /1Ph, W/ 1 Exhaust Fan,
Exhaust in Fire, Fan On /Off
Thermostatically Controlled
(One Stat Per Exhaust Riser).
Label
ST
FS
MS
R1
LS
GP
TX
GR
DS
Description
Starter
Fan Switch (Lighted)
MicroSwitch (Ansul PyroChem)
Relay DPDT
Light Switch (1400W max)
Hood Light(s)
General Purpose Relay DPDT
Transformer
Contactor
Ground
Duct Thermostat (See Note 1)
TI -04,07 Off Delay Timer RZ7- FSB3HU23
Spare Relay
Contacts
C -RD
N0 -BL
NC -PR
1 NC 3
4 NO 6
7 COM 9
A COIL B
R1-R5
RELAY Spare Relay Contacts
R2 -1 TERMINAL FOR FIELD
NC C WIRING TO BUILDING FIRE
PANEL, DRY CONTACTS
FOR SIGNAL ONLY
-ON 04(S
-0NC4S
---0 C4
MS -1, MS -2 MicroSwitch
Ansul Pyrochem
C -RD C -RD
NO -BK NO -BK
NC -BR NC —BR
SPARE RELAY CONTACTS CAN
BE USED TO CONTROL ITEMS
REQUIRING SHUT DOWN WHEN
THE FIRE SYSTEM
DISCHARGES, SUCH AS SHUNT
TRIP, SIGNALS, ETC...
12 x 18 x 6 Box
IN PARALLEL WITH DS -01
Motor Type PH Volt HP FLA BREAKER
Exh -1 Exh 1 230 1.5 10.2 15 Amp
BK BLACK
BL BLUE
BR BROWN
OR ORANGE
RD RED
WH WHITE
NOTES
DENOTES FIELD WIRING
DENOTES INTERNAL WIRING
WIRE COLOR
YW YELLOW
GY GRAY
PR PURPLE
OR /BL ORANGE /BLUE (STRIPE)
BL /RD BLUE /RED (STRIPE)
RD /GN RED /GREEN (STRIPE)
DRAWING SHOWN DE- ENERGIZED
NOTE: IF WALL MOUNT PREWIRE, OR FIELD
INSTALLED FIRE SYSTEM MICROSWITCH, THE
TERMINALS SHOWING FACTORY WIRING MUST
BE FIELD WIRED.
CA ;4'
W
1.4 w
z
C z
z
4t
o
0-4 U
Carmel
Redevelopment Commission
111 West Main Street
Cannel, Indiana 46032
317.571 -2787 (ARTS)
IH
W
0
a
co
C
Scope Drawings:
These drawings indicate the general scope of the project
in terms of architectural design concept, the dimensions of
the building, the major architectural elements and the type
of structural, mechanical and electrical systems.
The drawings do not necessarily indicate or describe all
work required for full performance and completion of the
requirements of the Contract.
On the basis of the general scope indicated or described,
the trade contractors shall furnish all items required for the
proper execution and completion of the work.
Revisions:
Issue Date
01/20/09
Drawn By
oso
Checked By
AJ M
Drawing Tide:
Kitchen Hood
And
Exhaust Fan
Drawing Number:
2 i
,I 2
L'Acquis Project Number:
08109