HomeMy WebLinkAboutP501 Plumbing Schedules & DetailsBACKFLOW PREVENTER SCHEDULE
MARK
RPZ -1
DCV -1
LOCATION
MECH ROOM
MECH ROOM
SYSTEM
DOMESTIC COLD WATER
FIRE WATER
TYPE
REDUCED PRESSURE ZONE
DOUBLE CHECK VALVE
DESIGN
CAPACITY
(GPM)
20
300
PRESS.
DROP
(PSIG)
12
5
SIZE (IN)
1"
4"
SPECIFICATION
SECTION
MANUFACTURER WITH
MODEL NUMBER
WATTS 919 —QT —S
WATTS 757 —OSY
NOTES
1
NOTES:
1. WITH QUARTER TURNBALL VALVES AND BRONZE STARINER.
FROM WATER
SUPPLY SOURCE
3 /4 "HW (120°F)
RCP-1
3/4" HWR (120°F �HI 114S1-41
BALL VALVE
C3
SCALE: NONE
THERMOSTATIC MIXING VALVE SCHEDULE
MARK
TMV -1
LOCATION
MECH ROOM
CAPACITY
MAX MIN
FLOW FLOW
(GPM) (GPM)
17
1
PRESSURE
DROP AT
MAX FLOW
(PSI)
5
CONNECTION SIZES
HW CW TEMPER
INLET INLET OUTLET
(IN) (IN) (IN)
3/4"
3/4"
1
EXTERIOR FINISH
BRONZE
NO
0
0_
cn
0
YES
YES
YES
YES
SPECIFICATION
SECTION
221116
MANUFACTURER
WITH MODEL
NUMBER
LAWLER #801
NOTES
NOTES:
1.
PLUMBING EQUIPMENT SCHEDULE
ITEM
EXT -1
GI -1
WH -1
MAKE AND MODEL NO.
AMTROL ST -12 —C
JR SMITH 8020
JR SMITH 5509QT
DESCRIPTION
EXPANSION TANK NO. 1
GREASE INTERCEPTOR NO. 1
NON— FREEZE WALL HYDRANT WITH STAINLESS
STEEL BOX
CAPACITY
TOTAL VOLUME 4.4 GALLONS
ACCEPTANCE VOLUME 3.2
GALLONS
20 GPM /40# CAPACITY
ELECTRICAL
CHARACTERISTICS
N/A
N/A
NOTES
1
NOTES:
1. ASME RATED
ASME APPROVED TEMP. PRESSURE RELIEF VALVE,
TERMINATE RELIEF DRAIN LINE OVER NEAREST FLOOR DRAIN.
BALL VALVE (TYPICAL)
UNION (TYPICAL)
1 "CW S---
GAS SHUT —OFF VALVE
DRIP LEG
SEDIMENT TRAP
FLOOR FLOOR DRAIN
SCALE: NONE
REDUCED PRESSURE BACKFLOW
7-
PREVENTER, MAXIMUM MOUNTING
HEIGHT OF 5' -0" ABOVE FLOOR.
ri7
-AIR GAP DRAIN FUNNEL
I 11/4"GAS
Le-
TMV-1
WATER HEATER PIPING DETAIL
BALL VALVE
TO SYSTEM
PIPE DISCHARGE TO FLOOR DRAIN OR MOP SINK
BACKFLOW PREVENTER
DETAIL
Mis7
WATER HEATER
DWH -1
UNDISTURBED SOIL
ONE— QUARTER BEND
(SIZE AS NOTED ON DWG'S)
THERMOMETER
PLUMBING PUMP SCHEDULE
MARK
RCP -1
LOCATION
MECH ROOM
SYSTEM
DOMESTIC HOT WATER
TYPE
INLINE
DESIGN
CAPACITY
(GPM)
3
DESIGN
CAPACITY (FT.
HD.)
13
MIN EFF.
PUMP
SUCT.
(IN.)
3/4"
DISCH.
(IN.)
3/4"
HP
1/6
MOTOR DATA
RPM
2940
VOLTS
115
PH
SPECIFICATION
SECTION
MANUFACTURER WITH
MODEL NUMBER
NOTES
1
B &G NBF -22
1
NOTES:
1. WITH BELL GOBSL I I AQUASTAT
TYPICAL AIR INTAKE /EXHAUST VENT, INSTALL PER WATER HEATER
MANUFACTURERS REQUIREMENTS FOR MATERIALS, MAX. VENT LENGTH,
SIZE AND VENT TERMINATION REQUIREMENTS.
TANK DRAIN
CONCRETE PAD
SIZE INSTALL PER
NFPA 24
SCALE: NONE
SLUSH CONCRETE
UNDISTURBED SOIL
TYPICAL CONCRETE
THRUST BLOCK DETAIL
GAS WATER HEATER SCHEDULE
MARK
DWH -1
MARK
FD -1
FS -1
LOCATION
MECH ROOM
NOTES:
1.
FLOOR DRAIN SCHEDULE
DESCRIPTION
FLOOR DRAIN
FLOOR SINK
FUEL TYPE
NATURAL GAS
INPUT
CAPACITY
199,000
DRAIN BODY
MATERIAL
CAST IRON
CAST IRON
OUTLET
SIZE
AS
SHOWN
AS
SHOWN
HEATING CAPACITY
OUTLET
TYPE
NO HUB
NO HUB
MINIMUM
EFFICIENCY
98%
MATERIAL
NICKEL BRONZE
NICKEL BRONZE
DELIVERY
GPH
238
STRAINER
SIZE
AS
SHOWN
AS
SHOWN
RISE °F
100
TYPE
ROUND
SQUARE
STORAGE
CAPACITY
(GAL)
100
J
NO
NO
w
0 0
Q
UNIT
WEIGHT
(LBS.)
570
NO
YES
J
w
2
NO
NO
SPECIFICATION
SECTION
223400
SPECIFICATION
SECTION
221316
221316
MANUFACTURER
WITH MODEL
NUMBER
LOCHINVAR
TNR200 -060
MANUFACTURER
WITH MODEL
NUMBER
JR SMITH #2005
J.R. SMITH FIG.
#3161 -12
NOTES
NOTES
1
1
YES
YES
NOTES:
1. WITH DEEP SEAL P —TRAP.
PLUMBING FIXTURE ROUGH -IN SCHEDULE
MARK
P -1
P -2
FIXTURE TYPE
WATER CLOSET ADA
WALL HUNG LAVATORY
ROUGH —IN SIZES
WASTE
SIZE
4"
1 1 /2"
VENT
SIZE
2"
1 1/2"
CW
SIZE
1"
1/2"
HW
SIZE
1/2"
FIXTURE MOUNTING HEIGHT
SEE SPECIFICATION
SEE SPECIFICATION
SPECIFICATION
SECTION
224000
224000
NOTES
NOTES:
1.
SYSTEM RISER
FIRE SERVICE
MAIN
SCALE: NONE
RODS
FIRE SERVICE
CONNECTION
CAST IRON FLANGE
AND SPIGOT PIECE.
CAST IRON BELL
AND SPIGOT PIPE.
THRUST BLOCKING.
VENT PIPE TO BE AS HIGH AS
POSSIBLE UNDER COUNTER,
THEN DOWN THROUGH FLOOR
45 DEGREE ELBOW J' 45 DEGREE ELBOW
PIPE SLEEVE THROUGH
FLOOR, SEE SPECS.
SLOPE
VENT UNDER FLOOR,
SEE PLAN FOR LOCATION
SCALE: NONE
TO DRY PIPE SYSTEM
SIZE PER HYDRAULIC
CALCULATIONS
MAIN DRAIN VALVE
DOUBLE CHECK
DETECTOR ASSEMBLY
WITH TEST COCKS
CLEANOUT
LONG SWEEP
T.S. T.S.
90 DEGREE ELBOW
T.S.
C6 RISER DETAIL
SCALE: NONE
WASTE OUTLET FROM FIXTURE
FLOOR
WET PIPE SPRINKLER
COMBINATION "Y" AND
1/8 BEND LONG TURN
SANITARY UNDER FLOOR
SLOPE
ISLAND SINK WASTE
VENT PIPING DETAIL
7 PIPE MOUNTED AIR
COMPRESSOR, 1/3 HP,
DRY PIPE VALVE GEM
SWING CHECK VALVE WITH
AUTOMATIC BALL DRIP
120V.
u
FINISHED FLOOR
D
DRAIN LINE TO FLOOR
DRAIN OR TO OUTSIDE
OF BUILDING.
PIPE STAND BOLTED TO FLOOR
O WALL
le
l
1
ALARM BELL BY
SPRINKLER
CONTRACTOR
WIRING TO F.A.
PANEL BY E.C.
FIRE
DEPART.
CONN.
THIS WALL SHOWN ROTATED
FOR CLAIRITY
cr)
1■■■4 z
z
z
U
a
441
L.)
Carmel
Redevelopment Commission
111 West Main Street
Cannel, Indiana 46032
317.571 -2787 (ARTS)
h
0
0
a
RS
a
co
a
G)
E
U
Scope Drawings:
These drawings indicate the general scope of the project
in terms of architectural design concept, the dimensions of
the building, the major architectural elements and the type
of structural, mechanical and electrical systems.
The drawings do not necessarily indicate or describe all
work required for full performance and completion of the
requirements of the Contract.
On the basis of the general scope indicated or described,
the trade contractors shall furnish all items required for the
proper execution and completion of the work.
Revisions:
Issue Date
01/20/09
Drawn By
JJR
Checked By
JJ R
Drawing Title:
PLUMBING
SCHEDULES
AND
DETAILS
L'Acquis Project Number:
08109