April 8, 2010 Gary Mr. Ga R. Duncan, Jr., P.E. Assistant City Engineer City of Carmel WOOLPERT Department of Engineering One Civic Square Carmel, TN 46032 Woolpert 7635 Interactive Way RE: ITT Building Expansion Project Review #1 Suite 100 Dear Mr. Duncan: Indianapolis, IN 46278 -2727 317.518.3396 We are in receipt of the Engineering Department review letters for the above listed Office: 317.299.7500 project, dated 3/15/10 and 3/24/10. The following responses have been provided to address your review comments: Fax: 317.291.5805 www.woolpert.com Construction Drawing Review Comments: 36. These notes have been added to sheet C201 in the Site and Utility Notes. 37. This note is provided on sheet C300. 38. All current easements are shown on this plan set. 39. Comment rescinded by Engineering Department per 3/24/10 letter. 40. This note has been provided on sheet C201. 41. The swale along the south of the site contains a sub- surface drain. The detail on sheet C401 has been revised to specify double wall HI -Q pipe (with off -set perforations per John Thomas). 42. This development will not be platted. 43. Comment rescinded by Engineering Department per 3/24/10 letter. Additional Review Comments: 1. The location of the construction entrance was acceptable to John Thomas, given the low amount of runoff this swale receives and the inlet protection provided at the downstream inlet during construction. 2. Duke Realty has reviewed the plans and approved this earthwork to take place. 3. A note has been added to sheets C110 and C111 stating that construction traffic is required to enter Hamilton Crossing from the north entrance-off of Illinois Street. 4. The drainage summary has been revised to include both existing and proposed 10 and 100 -year release rates. The master plan does not give an allowable release rate, only an allowable Curve Number. 5. An exhibit is enclosed that shows the flood routing from the site to the off -site detention pond at the southwest end of Hamilton Crossing. Flood water will be contained along Hamilton Crossing Boulevard and not impact adjacent buildings. This exhibit will be added to the Drainage Report. 'these responses should address all of your comments. Please contact me daily further questions. Sincerely, WOOLPERT, INC. Jon Sheidler, PE Project Engineer Cc: Nick Redden, Department of Engineering Angie Conn, Department of Community Services April 8, 2010 Mr. John Thomas Stormwatcr Administrator City of Carmel WOOLPERT Department of Engineering One Civic Square Carmel, IN 46032 Woolpert 7635 Interactive Way RE: ITT Building Expansion SWPPP Review Suite 100 Dear Mr. Thomas: Indianapolis, IN 46278 -2727 317.51 8.3396 We are in receipt of your review letters for the above listed project, dated 4/6/10. Office: 317.299.7500 The following responses have been provided to address your review comments: Fax: 317.291.5805 Construction SWPPP Review Comments: www.woolpert.com 6b. These notes have been added to sheet C201 in the Site and Utility Notes. 8. The inlet protection for this inlet structure has been clarified on sheet C110. 8a. The tree protection fence has been shown on sheet C110 and the silt fence along the south property line has been revised accordingly. 9. Step 3 in the Construction Sequence has been revised accordingly. Post Construction SWPPP Review Comments: 1. A SWPPP and BM P Operation and Maintenance Manual has now been provided. 2d. A planting schedule for the rain garden has been provided on sheet C400. A reference to this schedule has been added to the legend on sheet CI 11. 2e. The underdrain detail, now provided on sheet C401, has been revised to specify double walled pipe with off -set perforations. C111 has also been revised to clarify this. We took into consideration your suggestion of outletting the roof drains further east and routing that water through the swale as a bioswale, however the required depth of the roof drains would push the swalc too deep in order for them to daylight into the swale and drain with sufficient slope west to the outlet. Other "green" BMP method were also previously considered, but due to the tight conditions behind the building expansion, providing the Aqua -Swirl just upstream of the Rain Garden was the best feasible solution, We also looked into your suggestion of providing poppys and cosmos in the rain garden in addition to the wet mesic prairie mix. The landscape architect has recommended installing potted perennials for initial aesthetics, rather than the poppys and cosmos due to the differences in maintenance requirements. We will review this with the owner and proceed if directed to do so. These responses should address all of your comments. Please contact me if any further questions. Sincerely, WOOLPERT, INC. t Jon Sheidlcr, PE Project Engineer Cc: Angie Conn, Department of Community Services March 30, 2010 Mr. David Littlejohn iW wry. Alternative Transportation Coordinator l4 City of Carmel WOOLPERT Department of Community Services One Civic Square Carmel, IN 46032 Woolpert 7635 Interactive Way RE: ITT Building Expansion Suite 100 Dear Mr. Littlejohn: Indianapolis, IN 46278 -2727 317.518.3396 We are in receipt of your review letter for the above fisted project. This letter is to Office: 317.299.7500 address your comment(s) as followings: Fax: 317.2915805 Alternative Transportation Review Comments: www.woolpert.com 1. Bicycle parking was provided for this facility in the plans for the parking expansion, approved on 8/31/09, Docket No. 09060015ADLS. 310 parking spaces are required for this site, based on final square. footage. 33 parking spaces are being provided along with 16 bicycle spaces in the parking expansion project currently under construction, which satisfies the requirement. Please contact me if any further questions should arise. Sincerely, WOOLPERT, INC. Jon Sheidler, PE Project Engineer Cc: Angie Conn, Department of Community Services Conn, Angelina V From: Mindham, Daren Sent: Wednesday, March 24, 2010 11:52 AM To: 'Jon.Sheidler@ Woolpert.com' Cc: Conn, Angelina V Subject: Docket No. Assignment: ITT building expansion #10020013 DP Amend /ADLS Amend, 10020014 ZW) Attachments: Treedetail Carmel.pdf; Shrubdetail Carmel.pdf; Evergreendetail- Carmel.pdf; basket.staking.pdf Jon: I will be taking over the plan review for Scott Brewer while he is out on personal leave. Please let me know if you have any questions in regards to my comments and from your conversations with Scott. Below are comments for this project specifically addressing the area of landscaping. I have reviewed the drawings submitted for the March 17, 2010 Technical Advisory Committee and present the following comments: URBAN FORESTRY REVIEW COMMENTS 1) The Plant Schedule will need to have the quantity of each plant listed in a separate column. 2) The staking style on the evergreen trees is not advised. This `X' shape staking style tends to lead to trunk damage. As the tree moves side to side it rubs on the stake. I have attached the City of Carmel's standard plant material planting details for your use. Please illustrate how these comments will be addressed by letter or revised plan. If you have any questions, feel free to contact me. Thanks. Daren Mindham Urban Forester A x w 1 #'1 n� a, t �l -.7 o p er+ z ra &ice I 4 'Nf,t s EL March 24, 2010 Mr, Jon Sheidler, P.E. J AMES BRAINAR MAYOR Woolpert, Inc. 7635 Interactive Way, Suite 100 Indianapolis, IN 46278 RE: ITT Building Expansion Project Review 41 Supplemental Comments Dear Mr. Sheidler: 39. Please provide the requisite stone water /drainage information required by Section 100 of the Stonn Water Technical. Standards Manual on the plan sheets. The Department of Engineering rescinds this comment. 43. Please add the City of Cannel Curbing Policy to the construction plans. The Department of Engineering rescinds this comment. Based upon additional review, the City provides additional comments: 1. Please confirm with John Thomas that locating the construction entrance in an existing swale is acceptable. 2. Please verify that approval for earthwork off of the property has been obtained. 3. Please indicate where construction traffic will enter /exit the public right-of-way. 4. Please revise the drainage summary to include the following: Existing 10 and 100 -year release rates. 10 and l00 -year release rates with improvements.. Maximum allowable release rates per master plan. 5. Please indicate flood route off -site to detention facilities. If you have questions, please contact me at 571 -2441. Since r 1 P" 4 4. R .Du+►:• J r.,P'. Assistant CityEngi er Department of Engineering cc: Angelina Conn, Department of Community Services John Duffy, Carmel Utilities Paul Pace, Carmel Utilities Paul Arnone, Carmel Utilities Greg Hoyes, Hamilton County Surveyor's Office Greg llko, Crossroad Engineers, PC Department Review/File Copy issvrapps \user data\z \shared\DH ILL \PRO.)REV 101ITTBUILDING EXPANSIONREV# I SUPPLEMEN1 AL.doc DI_.IAkrX1ENT OF ENGINF'i ?i21Nt; ONE Civic SQUARE, CARMEL, IN 46032 OFFICE 3 17.571.2441 FAX 317.571.2439 EMAIL engineerin0( :trmel.in.s.tm CARMEL TECHNICAL ADVISORY COMMITTEE MEETING AGENDA Date: Wednesday, March 17, 2010 Place: Planning /Zoning Dept. Conference Room, 3rd Floor, 1 Civic Square, Cannel City Hall Start Time: 9:00 a.m. 9:00 a.m. Docket No. 10020009 SP: Reading Tree Park Secondary Plat. The applicant seeks secondary plat approval for 4 residential lots on 7.02 acres. The site is located adjacent to the Monon Greenway, at 212 W 136th Street. It is zoned R -1 /Residence, partially within the US 31 Overlay Zone. Filed by Greg Ilko of CrossRoad Engineers, PC for Reading Tree Park, LLC. 9:15 a.m. Docket No. 10020010 TAC: Mayflower Park, Blk 1, Lot 1A Dreyer Reinhold Racing. The applicant seeks approval for a building addition. The site is located at 4501 W. 99th St. The site is zoned I- 1/Industrial. Filed by DeBoy Land Development Services for DJ Reinhold Realty LLC. 9:25 a.m. Docket No. 10020012 ADLS Amend: Silver Convenience Center Fueling Center (Shell). The applicant seeks approval for exterior building modifications, a gas canopy with pumps, and landscape signage changes. The site is located at 808 W. Main St. The site is zoned OM/MU Old Meridian District. Mixed Use Subarea. Filed by Jim Koch of Convenience Centers, LLC. 9:35 a.m. Docket No. 10020013 DP Amend /ADLS Amend: Hamilton Crossing West, Bldg 5 ITT Building Expansion. The applicant seeks design approval for a building expansion, as well as a zoning waiver request: Docket No. 10020014 ZW Ch. 23B.08.03.A.1: Building Height and No. of floors The site is located at 13000 N. Meridian St. and is zoned B- 2/Business within the US 31 Overlay Zone. Filed by Jon Sheidler of Woolpert for ITT Educational Services, Inc. Veolia Water Indianapolis, LLC (VWI) is the contract operator for the Indianapolis Water (IW) utility, and as such, has reviewed the Agenda Topics listed above. None of the described and addressed properties fall within, or near any of IW's protected wellheads, therefore IW has no objection to any of these four listed locations. Page 1 of 1 Filename: TAC2010 -0317 (2) 3/5/2010 Carmel Clay Schools comments: CARMEL TECHNICAL ADVISORY COMMITTEE MEETING AGENDA Date: Wednesday, March 17, 2010 Place: Planning /Zoning Dept. Conference Room, 3rd Floor, 1 Civic Square, Carmel City Hall Start Time: 9:00 a.m. 9:00 a.m. Docket No. 10020009 SP: Reading Tree Park Secondary Plat. The applicant seeks secondary plat approval for 4 residential lots on 7.02 acres. The site is located adjacent to the Monon Greenway, at 212 W 136th Street. It is zoned R -1 /Residence, partially within the US 31 Overlay Zone. Filed by Greg Ilko of CrossRoad Engineers, PC for Reading Tree Park, LLC. Carmel Clay Schools comment sent to submitter: Mr. liko: received the Secondary Plat drawings for the above subject project. Although the drawings do not depict what the roadway development might be I want to pass along my comments related to school transportation. Carmel Clay Schools buses will generally not enter a dead -end or cul -de -sac; this is particularly applicable to our large neighborhood buses. Appropriate space for school age children to wait for bus pickup should be provided at the entrance to the development at 136th Street. 9:15 a.m. Docket No. 10020010 TAC: Mayflower Park, Blk 1, Lot 1A Dreyer Reinhold Racing. The applicant seeks approval for a building addition. The site is located at 4501 W. 99th St. The site is zoned I- 1/Industrial. Filed by DeBoy Land Development Services for DJ Reinbold Realty LLC. CCS: No comment. 9:25 a.m. Docket No. 10020012 ADLS Amend: Silver Convenience Center Fueling Center (Shell). The applicant seeks approval for exterior building modifications, a gas canopy with pumps, and landscape signage changes. The site is located at 808 W. Main St. The site is zoned OM/MU Old Meridian District Mixed Use Subarea. Filed by Jim Koch of Convenience Centers, LLC. CCS: No comment. :t5 a.m. 1 ocket No. 10020013 DP Amend /ADLS Amend: Hamilton Crossing West, Bldg 5 ITT Building Expansion. The applicant seeks design approval for a building expansion, as well as a zoning waiver request: Docket No. 10020014 ZW Ch. 23B.08.03.A.1: Building Height and No. of floors The site is located at 13000 N. Meridian St. and is zoned B- 2/Business within the US 31 Overlay Zone. Filed by Jon Sheidler of Woolpert for ITT Educational Services, Inc. CCS: No comment.. Page 1 of 1 Filename: TAC2010 -0317 (2) March 15, 2010 CI1 j 7 1 EL Mr. Jon Sheidler, P.E. JAMES BRAINARD, MAYOR Woolpert, Inc. 7635 Interactive Way, Suite 100 Indianapolis, IN 46278 RE: ITT Building Expansion Project Review #I Dear Mr. Sheidler: The City received your construction plans on February 19, 2010. The project is scheduled for review at the March 17, 2010 Technical Advisory Committee meeting. We offer the following comments: GENERAL INFORMATION 1. These comments represent the Department of Engineering's first review of the preliminary development plans for this project. 2. We request that all responses to our comments be provided in writing and be accompanied by a drawing reflecting the requested revisions. Failure to provide written responses may result in the delay of the review process. 3. It is critical that this office be made aware of all modifications made on the plans being re- submitted,. particularly if any such changes are considered -new" or fall outside of our previous reviews. Please provide revised plans including all revisions. Please notify us of any changes and specifically state any changes, including changes resulting from Plan Commission, BZA or other committee meetings. 4. We have engaged Crossroad Engineers, PC to review all drainage plans and drainage calculations submitted to this office for review. If you have not already done so, please provide a set of drainage plans and calculations to their office for review. We will share Crossroad's comments as they are received. 5. Final drawings will not be approved for construction until: a. All Engineering Department and Utility Department and Hamilton County Surveyor issues have been resolved. b. All bonds and performance guarantees are posted. c. A11 Board of Public Works and Safety approvals and any other governing agency approvals (if required) are obtained. d. All off -site easements necessary to install utilities to serve the development are secured. e. SWPPP is approved. f. All fees are paid. 6. The Department reserves the right to provide additional comments based upon subsequent reviews. 7. An approved Storm Water Management Permit is required prior to commencing any earth disturbing activity. Please contact Mr. John Thomas regarding storm water quality requirements. 8. An approved right -of -way permit is required prior to commencing any work in the public right-of-way. 9. If it will be necessary to relocate existing utilities, the costs for such relocation shall be borne solely by the developer. Any utility poles requiring relocation shall be relocated to within one -foot of the outside edge of the proposed right -of -way. 10. The Department requires that the construction drawings be developed in accordance with the City of Cannel digital submission standards and that all required submittals for primary plat, DEPARTMENT op E\c;JNF:FRING Opt- Civic SQUARE, CARMEL, IN 46032 Opnc:E 317.571.2441 FAX 317.571.2439 E5MAI cnginc&'rt[tp.',@K,uTh I.in.gov Mr. Jon Sheidler, P.E. March 15, 2010 RE: ITT Building Expansion Project Review 1 Page 2 of 4 secondary plat, and construction drawings be made: The digital files must be submitted to the Department of Engineering prior to the approval of the construction plans. Please contact the City GIS Department for the requirements. 11. Jurisdictions: a, The project site is located within current City of Cannel Corporate Limits. b. Perimeter Street and Right -of -Way City of Carmel (West 131' Street) c. Water— City of Cannel Utilities d. Sanitary Sewers City of Carmel Utilities e. Storm Sewers /Drainage —'City of Carmel. f. Legal Drains Hamilton County Surveyor's Office. 12. Drawings submitted for approval: a. The design engineer must certify all drawings submitted for final approval. b. This office will require 9 =sets of drawings for approval after all issues have been resolved. The drawings will be as approved and signed by the City Engineer and by Catniel Utilities. The Owner will receive 3 sets, one of which must be maintained on the construction site at all times. If this project is subject to review and approval by the Hamilton County Survey or's Office, a total of 11 sets will be required for final approval. 13. Carmel Utilities will provide separate reviews of this project for water issues. Please assure that copies of al1 drawings are sent to: Paul Pace Paul Arnone Carmel Utilities Distribution Carmel Utilities Collection 3450 West 131 Street 901 North Range Line Road Westfield, I.N'46074 Carmel, IN 46032 14. Carmel Utilities subscribes to "Holey;Moley" who should be contacted directly for all water main locations. 15. The following items will be sent electronically upon request regarding this correspondence and project; a. Project Approval Checklist b. Performance /Maintenance Guarantees c. Utility Jurisdictions /Right of Way Permits d. Availability (acreage) Fees BOARD OF PUBLIC WORKS AND SAFETY 16. A schedule for Board of Public Works and Safety meeting dates and agenda deadlines will be sent electronically for your use upon request. Please use the Engineering Department deadlines for submissions to the Board. 17: Any submission to the Board requires prior approval by the Carmel Clay Plan Commission and /or the Board of Zoning Appeals (if applicable) and completion of review by the Technical Advisory Committee. All written requests to be placed on the Board's agenda must include; the appropriate Docket Number and the date (or dates) of approval by the Plan Commission and /or the Board of Zoning Appeals (if applicable). 18. Water Availability and Sanitary Sewer approval from the Board will be required. This is an EDU approval based upon the proposed use of the site Reference Items #33 to #35 below for additional details /explanations. Please note that if an entryway or other irrigation system is planned for this development, additional Water Availability Approval from the Board will be required and additional Water Connection Fees will be assessed based upon the size and usage of the system as determined by the Director of Carmel Utilities. 19. Commercial Curb Cut Approval. Please provide 81/2 x 11 exhibits with the request for approval. Provide all pertinent information including lane widths, overall width, radii lane markings, location of opposing drives or streets, relationship to the location of previous curb cut, etc. Mr. Jon Sheidler, P.E. March 15, 2010 RE: ITT Building Expansion- Project Review 41 Page 3 of 4 20. Temporary Construction Entrance Approval. The temporary construction entrance is shown at a location that does not intersect with a City street; therefore, an approval from the Board will not be required. 21. The installation of any permanent, privately .owned and/or maintained improvement (signs, decorative street signs, :walls, streetlights, etc.) within dedicated right of way or dedicated easements requires the execution of a Consent to Encroach Agreement between the Owner and the City of Carmel. Such agreements are executed by the Board of Public Works and Safety. The City Engineer may approve irrigation system agreements. 22. Secondary Plat approval if applicable. All perfonnance guarantees must be posted prior to submission of secondary, plats for Board of Public Works and Safetyapproval. 23. Dedication of right-of-way if not platted. This is based upon the City of Cannel 20 -Year Thoroughfare Plan requirements. Dedication_ documents are available upon request. Please be advised that all Right of Way Dedications must be- accompanied °bya Sales Disclosure Agreement completed by the owner for the property being dedicated to the City. The dedication document cannot be recorded without a completed Sales Disclosure. The form is available upon request. 2d. Any open pavement cuts of either Old Meridian Street or Grand Boulevard, other than those required for the curb and median cuts, will require Board approval. BONDING REQUIREMENTS 25. Please contact Mr. Dave Barnes to review performance guarantee requirements. 26. The amount of the Performance Guarantee is based upon a certified Engineer's Estimate for 100% of the cost of labor and materials to construct the individual improvements, to be provided by the design engineer. Please provide detailed Engineer's Estimates for each improvement including quantities, unit costs, pipe sizes, and materials, etc. 27. Upon completion and release of individual Performance Guarantees: a three -year Maintenance Guarantee will be required (see Street Sign comments above). The Maintenance Guarantee amount is based upon 15% of the Performance amount for Streets and Curbs and l0 %o- of the Performance amount for all other improvements. 28. Performance Guarantees may be Performance or Subdivision Bonds or Irrevocable Letters of Credit. 29. Please reference the available enclosures for more detailed explanation of our procedures. RIGHT OF WAY PERMIT AND BONDING 30. Any work in the dedicated right -of -way will require an approved Right -of -Way Permit and a License Pennit Bond. 31. The bond amount is determined by our Right -of- -Way Manager. However, if the work is included in the scope of work of a required and posted Performance Guarantee, the Performance Guarantee may be used to satisfy the bond requirements of the Right -of -Way Permit. 32. Please contact our Right-of-Way Manager, Fred Glaser, to arrange right of waypernitting and bonding. AVAILABILITY AND CONNECTION FEES 33. We defer to Carmel Utilities regarding this issue. 34. If an entryway or overall site irrigation system is planned for this development, additional Water Connection Fees will be assessed based upon the size and usage of the system and upon the recommendations of the Director of Carmel Utilities. 35. These fees are required to be paid prior to final approval of construction plans by Engineering and prior to issuance of building_pernits by Building Codes Services. Please confirm these fees and calculations with Carmel Utilities. CONSTRUCTION DRAWING REVIEW COMMENTS Mr. Jon Sheidler. P.E. March 15, 2010 RE: ITT Building Expansion Project Review 41 Page 4of4 36. General Comments a. This project is subject to the City's Storm Water Management and Storm Water Quality Ordinances. b. Please add the following note to the drawings: IF IT WILL BE NECESSARY TO RELOCATE EXISTING UTILITIES, THE EXPENSE OF SUCH RELOCATION SHALL BE THE RESPONSIBILITY OF THE DEVELOPER. ALL UTILITY POLES SHALL BE LOCATED WITHIN ONE -FOOT OF THE PROPOSED RIGHT-OF- WAY." 37. Please add note stating "NO EARTH DISTURBING ACTIVITY MAY COMMENCE WITHOUT AN APPROVED STORM WATER MANAGEMENT PERMIT" to construction set. 38. Provide all current easements for entire tract to pertinent sheets with correct calls for each. 39. Please provide the requisite stone water /drainage information required. by Section 100 of the Storm Water Technical Standards Manual on the plan sheets. 40. Please add 'note _as required in Storm Water Technical Standards. Manual Section 102 "Permit Requirement and Procedures;" Article 102.02 vii pertaining to construction and approval of storm sewer systems to all storm sewer plan and profile sheets. 41. All swales on site must have sub- surface pipe installed. Pipe to conforin to requirements of Storm Water Technical Standards Manual and shall be double wall, HI--Q pipe. 42. Will this development be platted? 43. Please add the City of Carmel Curbing Policy to the construction plans. If you have questions, please contact me at 571- 2441. Sincerely, Nicholas J. Redden, A.E. Plan Review Coordinator Department of Engineering cc: Angelina Conn, Department of Community Services John DuftY, Carmel Utilities Paul Pace, Carmel Utilities Paul Arnone, Cannel Utilities Greg Hoyes, Hamilton County Surveyor's Office Greg Ilko, Crossroad Engineers, PC Department Review/File Copy issvrappsluser datalz_ \shared\DH ILL PRWREV I own. 3UILDING EXPANS LONR EVfl 1 ,.`c S� EY -F�Fj L t i ce. A' ®l ti C i t t: l/ ,thy 1, 1 11 L tt f, m 1 1 t f� J 'F a t I o t l 7...-4-444- mo :p V �f a V� tiv 'b L? e, ‘,.j z )Y L -2 6-.m."" a Jg t i r 1 Kenton C. 'Ward, UF.211 Suite i Zig Surveyor of :Hamilton County One .Hamilton County Square 'Thane (317) 776 -8495 .;toblesville, Indiana 4606o-2230 `Fax (317) 776 9628 March 8, 2010 Woolpert ATTN: Jon Sheidler, P.E. 7635 Interactive Way, Suite 100 Indianapolis, IN. 46278 -2727 VIA E- MAIL: Jon.Sheidler @Woolpert.com RE: ITT Building Expansion Dear Mr. Sheidler: We have reviewed the construction plans submitted to the Hamilton County Surveyor's Office on February 22, 2010, for this project and have the following comments: 1. The proposed project falls in the incorporated area and MS4 jurisdiction of the City of Carmel. 2. The proposed project DOES NOT fall in a Carmel Wellhead Protection Zone. 3. The proposed project falls in the J.R. Collins Regulated Drain Watershed. 4. The proposed project is within the master drainage plan for Meridian Corners and is within the allowable parameters set out by that master plan. 5. No Regulated Drain Permits will be needed from our office. Should you have any questions, I can be reached at 317- 776 -8495. Sincerely, 5iateti 6rA Greg Hoyes, AC, CFM, CPESC Plan Reviewer CC: Christine Barton-Holmes Carmel DOCS John Thomas Carmel Engineering Dave Barnes Carmel Engineering Greg Ilko Crossroad Engineers Conn, Angelina V From: Conn, Angelina V Sent: Tuesday, February 23, 2010 9:33 AM To: 'John Molitor'; Hollibaugh, Mike P Cc: Holmes, Christine B Subject: RE: ITT Building Expansion John- I agree that only one zoning waiver will suffice. Mike unless I hear otherwise from you within the next few days, I will only have the petitioner utilize the one waiver. Thank you for your help! -Angie Conn, Planning Administrator From: John Molitor [mailto:jmolitor @prodigy.net] Sent: Monday, February 22, 2010 4:33 PM To: Conn, Angelina V; Hollibaugh, Mike P Cc: Holmes, Christine B Subject: Re: ITT Building Expansion The second floor standard wouldn't even be eligible for a zoning waiver, since it would take a waiver of more than 35% if the second floor will comprise 50% of the GFA. Therefore, unless the Director believes that this request should be heard by the BZA as a variance, I would recommend that the waiver of the 3 -floor requirement be treated as sufficient (going hand -in -hand with the GFA issue). John From: "Conn, Angelina V" <Aconn©carmel.in.gov> To: "Hollibaugh, Mike P" <MHollibaugh @carmel.in.gov John Molitor <jmolitor @prodigy.net> Cc: "Holmes, Christine B" <cholmes @carmel.in.gov> Sent: Mon, February 22, 2010 3:55:07 PM Subject: FW: ITT Building Expansion John Mike ITT will seek one zoning waiver for building height being less than 38 -ft and not having 3 occupiable floors (only 2), with its building addition petition (DP Amend /ADLS Amend). Do they also need a separate zoning waiver for first floor gross floor area and the second floor gross floor area, or would the first waiver cover that, since they go hand in hand? Pleases skim over the email chain below for background, and let me know your thoughts. Thank you! -Angie Conn, Planning Administrator From: Paul G. Reis [mailto:preis @kdlegal.com] Sent: Monday, February 22, 2010 3:36 PM To: Conn, Angelina V Cc: Sheidler, Jon Subject: RE: ITT Building Expansion Angie I don't have a copy of what was filed. But since this is a building addition (vs new building) and we have filed the waiver for 2 floors vs 3, l think it is an administrative determination whether 23B.08.05 applies in light of the waiver for building height and floors. Let Jon and I know and we can prepare an additional waiver if necessary. 1 Carmel De &rtmen Q. 5."6"),\\i U �aaae:�c Q C&r nel, y k 46032 z F February 22, 2010 Jon Sheidler Woolpert, INC. 7635 Interactive Way, Suite 100 Indianapolis, IN 46278 RE: ITT Parking Expansion Carmel, IN for TAC Meeting Order Number: 70255.99 Dear Mr. Sheidler: The information for the above referenced project has been reviewed. At the present time, I see nothing in the plans that would hamper law enforcement efforts. If we can be of any further assistance to you, please contact us. Respectfully, Michael D. Fogarty Chief of Police MDF:vb cc: Dept. of Community Services (317) 571 -2500 A Nationally Accredited Law Enforcement Agency ]Ca$ (317) 571 -2512 Conn, Angelina V From: Conn, Angelina V Sent: Thursday, January 28, 2010 2:30 PM To: 'Sheidler, Jon' Cc: Holmes, Christine B; 'John Molitor' Subject: Hamilton Crossing West, building 5 ITT expansion Hi, Jon- I read through the ordinance, and you have to submit a Development Plan application with the ADLS application. You are over the 20% gross floor area expansion limit to not have to submit a DP, per•chapter 23B.02.A.1. Also, I have emailed our attorney to see if you have to comply with the minimum building height requirement of 38 -ft and 3 occupiable floors, since this is a building addition. And, I urge you to look through the US 31 Overlay requirements to see if you might need any other variances. Also, here is a weblink to the plan commission info packet, for the original 2002 approval, if you want to use any of it http: /cacdocs.ci.carmel.in.us /Weblink /DocView.aspx ?id= 247765 &dbid =0 Angie Conn, Planning Administrator Planning Zoning Dept City of Carmel 1 Civic Square, 3rd Floor Carmel, IN 46032 0:317- 571 -2417 F: 317 571 -2426 E: aconn(.tbcarmel.in,gov Website Ptease.consitirer the environment before printing this e -magi 1 7 C. ,:e ,vtINER 54 City of Carmel DEPARTMENT OF COMMUNITY SERVICES January 15, 2010 Mr. Jon Sheidler Woolpert, Inc 7635 Interactive Way ste 100 Indianapolis, IN 46278 RE: ITT Parking Expansion Dear Mr. Sheidler: The following letter represents comments for this project specifically addressing the area of alternative transportation. I have reviewed the project submitted for the March 17, 2010 Technical Advisory Committee meeting, and offer the following comments: Alternative Transportation Review and Comments 1) Please refer to the City of Carmel's Parking Ordinance to ensure that this project will comply with the city's bicycle parking requirements. We request that all responses to our comments be provided in writing. Failure to provide written responses may result in delay of the review process. It is critical that this office be made aware of all modification made on the plans being re- submitted, particularly if any such changes are considered "new" or fall outside of our previous reviews. Please provide revised plans indicating all revisions. Please notify us of any changes and specifically state any changes, including changes resulting from Plan Commission, Special Studies or other committee meetings. The Department of Community Services reserves the right to provide additional comments based on subsequent reviews. If you have questions, please contact me at 571 -2417. Sincerely, David Littlejohn Alternative Transportation Coordinator Department of Community Services cc: Angie Conn, Department of Community Services Engineering Department Review Project File Page 1 ONE CIVIC SQUARE CARMEL, INDIANA 46032 317/571-2417