HomeMy WebLinkAbout03110037 - 182-03 Z - Inlow Park Repairs & Improvements ME101DATE:
01.14.11
PROJECT NO.:
7628.001
DRAWN BY
LIAR
CHECKED BY:
JWQ
SHEET TITLE:
I"IECI- IANICAL
ELECTRICAL PLAN
DRAWING FILES:
SHEET NO.:
N 1 11
6
[Ti
n
9
Mechanical Plan Notes:
Existing German -Rupp self priming centrifugal pump, model no
T6A60 -B with unverified capacity listed as 800 gpm 35' TDH at
1,100 RPM.
Existing 10 HP electric motor.
Existing 8" dia. PVC suction piping.
Existing 8" inlet, 6" outlet strainer.
Existing 2" domestic water service passing thru a meter and a
RPZBP(not shown).
Existing underground concrete surge tank. Exact details location, size,
configuration, etc. are unknown.
Existing 8" dia PVC main pump discharge to spray (fountain) features.
Existing floor drain.
This contractor shall provide at least the following work to establish
the cause of this pump no longer being able to "self prime
a. Review /clean the pumps internal flap valve to insure that it is
operating properly in accordance with the manufacturer's
recommendations.
b. Remove the cover plate, clean the water storage volume,
adjust the pump wear plate as recommended by the
manufacturer, reinstall the cover plate and confirm that it
seals properly.
c. Check for a worn or leaking seal or pump gasket. Replace or
adjust as necessary.
d. Establish the operating speed of the pump for comparison
with the impeller's curve data so that the NPSH required can
be established.
e. Pressure test or vacuum test and /or soap test suction piping
to check for leaks.
The purpose of this is to get this pump to be self priming as originally
designed. If additional work or material beyond items 'a.' thru 'e.'
above are necessary, the contractor shall provide a proposal to
nrnvidP this fnr review and nnssible anoroval by the
WOMENS
TOILET
SCALE: 1/4 "=1' 0"
14
SCALE: I/4 =1' -0"
EXISTING RESTROOM BLDG.
PARTIAL MECHANICAL PLAN
PUMP ROOM
MENS
TOILET
EXISTING RESTROOM BLDG.
MECHANICAL PLAN
13
Power
Meter
Replace existing strainer with new concentric 8" x 6" type 316
stainless steel hair and lint strainer. Field verify that strainer will fit in
existing dimensions before ordering. Provide filler piping as required
to suit installation. Strainer shall be appropriate model of
Neptune Benson, Recreonics, Miller- Leaman or equal.
F T 1 3 Provide wall mounted supports to carry the weight of the filled pump
discharge piping and to brace the pipe in both horizontal directions.
Braces shall be hot- dipped galvanized.
Mechanical Plan Notes (cont.):
Remove existing gauge on the pump suction and provide a new
vacuum gauge with petcock in its place. Gauge shall be minimum 2 Y2"
dial size, Ashcroft, US Gauge or equal.
Remove the existing manual air release valve and replace with new
automatic air release valve like APCO Model S -50 or equal by
Val Matic. Provide, support and brace valve outlet PVC piping over to
wall, down wall to floor and over to above the existing floor drain and
turned down.
Provide a pressure gauge with petcock on the incoming water service.
Locate after the meter. Gauge shall be minimum 2 Y2" dial, 0 -100 psi,
Ashcroft, US Gauge or equal.
This Contractor shall furnish and install a bollard style, push button
activator that shall be used to activate the existing spray park feature
controller. Supply bollard complete with all anchoring and fastening
devices, required gaskets and base skirt. Coordinate installation with
the concrete base requirements. See sheet L101 for exact location.
Coordinate with the electrical requirements. Activator shall be Rain
Drop Model BOL -A002 or an approved equal. Color selection shall be
by the Architect.
This Contractor shall replace four (4) existing butterfly valve and
handwheel assemblies connected to the spray park features. This
shall consist of two (2) 6" valves and two (2) 4" valves. Provide all
material, labor, equipment and accessories necessary to accomplish
this. See sheet L101 for exact location of this work. Provide one (1)
additional 6" and one (1) additional 4" valve and handwheel assembly
for the Owner's inventory. Assemblies available from SCS Interactive
(contact 1- 801 737 -3114, ext. 118), or an approved equal. Install per
manufacturers recommendations. Provide removed valves back to the
Owner for their inventory unless refused by them.
O
j
17
6
F 17
UNDERGROUND
SURGE TANK
Access
Transformer
Mechanical Plan Notes (cont.):
This contractor shall replace the easternmost spray feature with a
water curtain feature from RainDrop, Model RNDP -001 (available from
Rain Drop Products, LLC, 1430 -B George Rd., Ashland, OH, 44805,
1-419- 207 1229), or an approved equal. Unit shall be installed per the
manufacturer's recommendations. Provide all labor, materials,
equipment and accessories necessary to accomplish this. See sheet
L101 for exact location of this work. Provide removed feature to the
Owner's inventory unless refused by them.
WOMENS
TOILET
SCALE: 1/4 =1' -0"
0
0
O
10
11
PUMP ROOM
Provide LB for conduit to the bollard.
MI EWE
0
MENS
TOILET
EXISTING RESTROOM BLDG.
ELECTRICAL PLAN
Electrical Plan Notes:
I Power
Meter
Existing 120/240V, 10, 3W, 30 pole, 200A, MBR electrical panel.
Existing Water Odyssey spray park system controller.
Existing adjustable time clock control.
Existing Chemtrol programmable chemical controller.
Existing main pump disconnect switch.
Existing main pump adjustable time clock control used to turn pump
off automatically.
Existing disconnect switch.
Remove the existing time clock to the Owner's inventory and replace it
with an lntermatic Series ET70000C electronic time switch in a NEMA
3R case with factory installed lithium coin cell memory backup.
Contractor shall ascertain the existing pump control requirements and
match the exact time switch model before ordering. Contractor shall
provide all materials, labor, equipment and accessories; including
wiring, conduit, boxes, relays, connections, etc.; necessary to allow
the existing main pump to automatically turn on and off per an Owner
programmed sequence.
This contractor shall provide all work to allow this existing Water
Odyssey controller (CPU) to start is operating sequence upon a
signal from the proposed bollard style push button activator. This task
shall include all changes, modifications and/or additions to the CPU
necessary to accomplish this. Provide all labor, materials, equipment,
accessories and appurtenances necessary to accomplish this function
allowing it to operate in a safe and reliable manner. Work shall
include, but not be limited to, all wiring, conduit, boxes, relays,
connections, etc., necessary. Coordinate work with the installation of
the bollard and it's concrete pad.
Provide new 1" PVC conduit with 2 conductor #18 gauge or larger
wire, all as required or recommended by the bollard manufacturer.
Note that there exists substantial existing water lines, drain lines and
electrical conduit in this area. This contractor shall be responsible for
locating these and protecting them as necessary. Schematic only,
as -built plans are available to review upon request; however, there is
no guarantee of their completeness or accuracy.
UNDERGROUND
SURGE TANK
Access
Transformer
V
Vl
cc
W
W
z
E
z
W
z
Y
z
0
U)
W
J
CC
W
CO
0
z
0
3
D
ED
U
CD
2
REVISIONS
A
DESCRIPTION
DATE/INIT.
THIS DRAWING AND THE IDEAS, DESIGNS AND
CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF THE SCHNEIDER
CORPORATION, AND ARE NOT TO BE USED OR
REPRODUCED. IN WHOLE OR IN PART. WITHOUT
THE WRITTEN CONSENT OF THE SCHNEIDER
CORPORATION.
I COPYRIGHTED BY THE SCHNEIDER CORP. (2001)
Schneider
THE SCHNEIDER CORPORATION
Historic Fort Harrison
8901 Otis Avenue
Indianapolis, IN 46216 -1037
Telephone: 317.826.7100
Fox: 317.826.7200
www.schneidercorp.com
Architecture
Civil Engineering
Environmental Engineering
Geotechnicol Services
GIS LIS
Home Builder Services
Interior Design
Land Surveying
Landscape Architecture
Transportation Engineering