HomeMy WebLinkAbout26 Plumbing Site Utilities & Plan - PSU2.1EXISTING
4" WM
NEW
6" WM
INV.= 846.08'
DATE:
SITE UTILITY INFORMATION
CARMEL HIGH SCHOOL
FRESHMAN CENTER
520 EAST MAIN STREET
CARMEL, INDIANA 46032
GAS LOAD:
SANITARY SEWER LOAD:
STORM LOAD:
DOMESTIC WATER LOAD:
JULY OF 2002
NORTHWEST HYDRANT CLOSEST
TO EXISTING MECHANICAL ROOM
STATIC: 47 PSI
RESIDUAL: 46 PSI
NO. OF OUTLETS:
DIAMETER OF OUTLET:
FLOW: 1000 GPM
9,500,000 BTU /H
360 GPM MAXIMUM
3100 GPM MAXIMUM
86 GPM MAXIMUM
NEW
8" WM
NEW GAS SERVICE
NEW
8" WM
W W g
GAS GAS
PLUMBING SITE UTILITIES PLAN
EXISTING
10" WM
GENERAL SITE PLAN NOTES:
CONTRACTOR SHALL CONTACT HOLEY MOLEY FOR INFORMATION REGARDING NATURAL GAS SERVICES. CONTACT THE CARMEL
UTILITIES FOR ALL SITE WATER AND SANITARY SEWER INFORMATION PRIOR TO START OF WORK TO VERIFY ALL EXISTING UTILITIES
WHICH MAY BE IN CONFLICT WITH NEW BUILDING CONSTRUCTION AND NOTIFY ENGINEER PRIOR TO INSTALLATION OF ANY PIPING
OR EQUIPMENT FOR COORDINATION.
2. REFER TO SITE CIVIL DIVISION 2 DRAWINGS FOR ALL SANITARY, STORM PIPING AND MANHOLE STRUCTURE INFORMATION AND
ASSOCIATED INVERTS FOR COORDINATION WITH DOMESTIC AND FIRE PROTECTION WATER AND NATURAL GAS SERVICE PIPE
ROUTINGS. THE CONTRACTOR SHALL PROVIDE ANY NECESSARY FITTINGS FOR OFFSETS REQUIRED TO COMPLY WITH THE
HORIZONTAL AND VERTICAL CLEARANCES DESCRIBED IN GENERAL NOTE NO. 4. REFER TO SITE /CIVIL DRAWINGS FOR UTILITY
PIPING LOCATIONS AND INVERT INFORMATION.
3. CONTRACTOR TO MAINTAIN MINIMUM 10' -0" HORIZONTAL AND 18" VERTICAL CLEARANCE BETWEEN DOMESTIC AND FIRE
PROTECTION WATER SERVICE AND ALL STORM AND SANITARY SEWER PIPING PER INDIANA STATE BOARD OF HEALTH.
4. ALL WORK PERFORMED ON THE DOMESTIC WATER /FIRE MAIN FOR THIS PROJECT SHALL CONFORM WITH THE REQUIREMENTS OF
THE CITY OF CARMEL WATER UTILITY STANDARDS, SPECIFICATIONS AND DETAILS. THE CARMEL WATER COMPANY DOES NOT
SUBSCRIBE TO "HOLEY MOLEY" SO THE CONTRACTOR MUST COORDINATE DIRECTLY WITH THE UTILITY COMPANY FOR ALL WATER
MAIN SYSTEM WORK DESCRIBED. CONTACT PAUL PACE THE CARMEL WATER COMPANY (317 -571- 2648).
SITE FIRE PROTECTION PLAN NOTES:
THE WORKED DESCRIBED UNDER SITE FIRE PROTECTION PLAN NOTES" SHALL BE PERFORMED BY THE FIRE PROTECTION
CONTRACTOR AND AS DIRECTED BY SPECIFICATION SECTIONS 15300 AND 15417.
DISCONNECT AND REMOVE EXISTING POST INDICATOR VALVE (PIV).
0 REMOVE FIRE HYDRANT AND PREPARE FOR RELOCATION.
0 REMOVE PIPING AS REQUIRED TO ACCOMMODATE NEW BUILDING FOUNDATIONS.
CAP PIPING AT THIS POINT.
FLOW DATA TAKEN FROM THIS HYDRANT; STATIC 47psi; RESIDUAL 46 psi; FLOW 1000 gpm
PIPING TO BE ABANDONED IN PLACE IF NOT IN CONFLICT WITH NEW FOUNDATIONS. GROUT FILL SOLID AND CAP AS SHOWN.
EXISTING PIPING TO REMAIN.
EXISTING FIRE HYDRANT TO REMAIN.
GREASE INTERCEPTOR BY DIVISION 2.
CONNECT TO EXISTING PIPING AS REQUIRED.
DISCONNECT PIPING AT THIS POINT AND PREPARE FOR NEW CONNECTION.
NEW 4" DOMESTIC WATER SERVICE UP. REFER TO DRAWING P4.1 FOR CONTINUATION.
RELOCATED FIRE HYDRANT. AT NO TIME SHALL ALL FIRE HYDRANTS ON SITE BE OFFLINE. INSTALL PER LOCAL UTILITY AND FIRE
DEPARTMENT REQUIREMENTS. REFER TO SPECIFICATION SECTION 15417 AND HYDRANT DETAIL ON DRAWING PSU2.2 FOR
FURTHER INFORMATION.
1 4 THRUST BLOCK SEE DETAIL ON THIS DRAWING.
15 NEW ELECTRICALLY SUPERVISED POST INDICATOR VALVE. PROVIDE LOCK ON VALVE IN THE OPEN POSITION.
16 REMOVE VALVE(S) COMPLETE.
INSTALL NEW GATE VALVE IN ROAD BOX. SEE DETAIL ON DRAWING PSU3.1
(18) KNOX BOX KNOX COMPANY NO. 3200R RECESSED SECURITY BOX. MOUNT AT +48" ABOVE FINISHED SURFACE TO BOTTOM
OF BOX. CONTRACTOR MUST OBTAIN AUTHORIZATION ORDER FORM FROM LOCAL FIRE CHIEF TO PURCHASE KNOX BOX. CONTACT
GARY HOYT AND THE CARMEL FIRE DEPARTMENT (317 -571 -2600) (CALL KNOX COMPANY AT 1-800- 552 -5669)
19) FREE STANDING SIAMESE FIRE DEPARTMENT CONNECTION.
20 GREASE INTERCEPTOR BY DIVISION 2.
21 ABANDON PIPING IN PLACE
Zz REFER TO DRAWINGS P2.1, P2.9 AND P2.14 FOR REWORK OF EXISTING STORM AND SANITARY SEWERS LOCATED UNDER THE
NEW BUILDING FOOTPRINT.
FOR CONTINUATION SEE DRAWING P2.2.
2 FIRE PUMP TEST HEADER_
25 NEW FIRE HYDRANT LOCATION. THIS HYDRANT IS TO BE INSTALLED AND ON LINE PRIOR TO REMOVAL OF EXISTING FIRE
HYDRANT BEING RELOCATED. INSTALL PER LOCAL UTILITY AND FIRE DEPARTMENT REQUIREMENTS. REFER TO SPECIFICATION
SECTION 15417 AND HYDRANT DETAIL ON THIS SHEET FOR FURTHER INFORMATION.
(2 EXISTING GAS METERS TO BE REWORKED TO ACCOMMODATE THE NEW FRESHMAN CENTER GAS LOADS.
REMOVE PIPING COMPLETE
SITE PLUMBING PLAN NOTES (BY PLUMBING CONTRACTOR)
"Holey Moley" says,
"DON'T DIG BLIND"
Colt Monday through Fridoy- 7 AM to 6 PRA
1 800 1 -800
382 -5544 428-5200
Within Indiana Outside Indiana
CHS FRESHMAN CENTER
2011 05.00