HomeMy WebLinkAboutDrainage Calculations Drainage
Calculations
PROJECT:
DRAINAGE REPORT for
RANGELINE COMMERCIAL
PREPARED FOR:
I.E. INVESTMENTS, LLC
DATE:
04/22/09
JOB NUMBER:
7310.002
The Schneider Corporation
8901 Otis Avenue
Indianapolis, Indiana 46216
b 5 iksr�•° j k ��n'
317- 826 -7100
317- 826 -7300 Fax
Schn
11 12 AM
9
tt LV
M 0 24 w
T: \7k \7310 \002 \drainage \4580001 drainrep.doc �b s 1�
Ad
eat.
t.
TABLE OF CONTENTS
A. Drainage Narrative Al A4
B. Site Maps
USGS Quadrangle Map B1
Soils Map B2
C. Existing Conditions
Watershed Plan 01
Site Hydrologic Groups C2
Curve Number C3
Existing Time of Concentration C4
Existing Basin Input C5
Existing Basin Peak Discharge C6
D. Detention Analysis
Watershed Plan 01
Nodal Diagram D2
Storm Sewer Rational Design D3
Storm Sewer Pipe Design D4
Time of Concentration D5
ICPR Input report
Basin Input D6
Node Input D7
Pipe Input D8
Rainfall Chart D9
CN value table D10
Basin Results Comparisons D11
Results (node max. Condition) D12
Composite "c" Values D13
Runoff Coefficient D14
h
a RECEIVED
M J
co
DOGS
cb
T:\7k\7310\002\drainage\4580001drainrep.doc 40` �1 it 00
co
-A- RECEIVED 1
N APR 2 4 2009
DRAINAGE NARRATIV DOCS
"fr
DESIGN CRITERIA t 1 01' 4
These drainage calculations are based on given data and design criteria as
follows:
Site location:
The site is located at the northeast corner of Rangeline Road and 4 Street,
Carmel, Hamilton County, Indiana.
Terrain and existing ground condition:
The site is currently 3 lots of a previously platted subdivision containing 3 existing
homes. Two homes are slated to be removed, and 1 existing home will remain.
Adjoining land conditions:
North: residential /commercial
South: residential /commercial
East: residential /commercial
West: residential /commercial
Soil types:
Soils maps from the United States Department of Agriculture Soil Conservation
Service identify Crosby and Miami Silt Loam soils on the subject tract.
Crosby (CrA silt loam) The main soil features that adversely affect engineering
uses of this soil are a seasonal high water table, high potential frost action,
moderate shrink -swell potential and moderate permeability. This soil has severe
limitations for building sites. The site needs to be artificially drained to prevent
wetness from becoming a problem. Dwellings with basements should not be
constructed on this soil. This soil has severe limitations for local roads and
streets because of seasonal high water table and high potential frost action. The
base material for roads and streets should be replaced or strengthened with
suitable material.
T:\7k\7310\002\drainage\4580001drainrep.doc
Miami (MmB2 silt loam) The main soil features that adversely affect
engineering uses of this soil are moderate potential frost action, moderate
shrink -swell potential, moderate permeability and low strength. In addition,
erosion is a hazard during construction. This soil is suitable for building sites, but
slope, clayey texture, shrinking and swelling, and low strength are moderate
limitations that need to be overcome. This soil has severe limitations for local
roads and streets because of low strength. The base material for roads and
streets should be replaced or strengthened with suitable material.
Design storm frequency:
The storm sewers are designed for a 10 -year storm event. The detention areas
are designed for the 100 -year, 10 -year, and 2 year 24 hour storm events with the
SCS -II hydrograph. The applicable rainfall amounts for the 2yr, 10yr, and 100yr
frequencies of the 24 hour storm duration are derived from the Technical Paper
No. 40 of the National Weather Service provided from the State of Indiana
Department of Natural Resources Division of Water.
REFERENCES
Design and data methods are based on the following references:
1. City of Carmel Stormwater Technical Standards Manual
2. Hamilton County Soils Survey
OVERALL WATERSHED
Morrow Follett Legal Drain
UNDEVELOPED SITE DATA
The existing site contains three existing homes. There are mature trees and
established grass. The overall existing watershed drains in three directions.
West into Rangeline Road, east to an alleyway and rearyards of existing homes,
and then south into 4 Street. There are no existing storm sewers directly within
the vicinity of the site.
The existing watershed is approximately: EX -W 0.48 acres, EX -E 0.17 acres,
and EX -S 0.14. The site has roughly 2.5 feet of fall across the site from the
middle to the west and east.
The following is a summary of the peak discharge rates:
BASIN 2 -Year 10 -Year 100 -Year
T:\7k\7310\002\drainage\4580001drainrep.doc
EX -W 0.53 cfs 1.04 cfs 2.31 cfs
EX -E 0.21 cfs 0.41 cfs 0.92 cfs
EX -S 0.12 cfs 0.24 cfs 0.51 cfs
DEVELOPED SITE DATA
The proposed development will encompass renovating the existing home on the
southwest corner of the property, relocated 1 historic home to the southeast
corner, and then adding 3 mixed -use office /retail and residential buildings. A
parking lot will be constructed in the middle to serve the mixed -use buildings and
will utilize the existing curb cuts on Rangeline Road and 4 Street.
There will be thre proposed watersheds for the development. One basin is
defined as "602" (storm inlet structure number) and is located in the middle of the
parking lot. All runoff from this watershed will be directed to this inlet where a 6"
PVC pipe will serve as a reducer in the 12" RCP pipe. This reducer will allow
water to stage in the inlet structure itself allow for detention on site. Stormwater
quality for the parking lot impervious areas will be handled through a "treatment"
train of pervious pavement and a Snout Catch Basin Insert, prior to leaving the
site.
The remaining two proposed watersheds will maintain the existing discharge
locations to the south and west. The runoff from these direct basins will be
through established grass acting as a filtering device and slowing velocity, via
sheet flow.
The following is a summary of the peak discharge rates:
NODE 2 -Year 10 -Year 100 -Year
PR-W 0.27 cfs 0.52 cfs 1.15 cfs
PR -S 0.12 cfs 0.24 cfs 0.51 cfs
602 1.47 cfs 2.13 cfs 3.61 cfs
600 0.51 cfs 1.01 cfs 2.25 cfs
FACILITY DESIGN
The storm sewer facilities are designed to collect stormwater runoff and detain
the release such that the peak discharge rates from the site are Tess than the
allowable rate as discussed in the above topic of "Design storm frequency
This is to be accomplished with a 6" reducer in the outfall pipe to stage water in
the inlet structure. Below is a summation of this and their performance in the
100 year storm event.
T:\7k\7310\002\drainage\4580001drainrep.doc
Inlet Summary INVERT 100 yr Casting. Elevation
Structure 602 830.00 ft 834.43 ft 834.00 ft
SUMMARY
The detention system is designed to release the developed site's storm runoff at
as much of a reduced peak flow rate possible with a 6" reducer pipe at the inlet
structure where the bulk of the impervious surface areas are located..
Node "602" EX -E
Post Developed Rate (cfs) Pre Developed Rate (cfs)
100 year 1.99 cfs 0.92 cfs
10 year 1.86 cfs 0.41 cfs
2 year 1.34 cfs 0.21 cfs
PR -W EX -W
Post Developed Rate (cfs) Pre Developed Rate (cfs)
100 year 1.15 cfs 2.31 cfs
10 year 0.52 cfs 1.04 cfs
2 year 0.27 cfs 0.53 cfs
PR -S EX -S
Post Developed Rate (cfs) Pre Developed Rate (cfs)
100 year 0.51 cfs 0.51 cfs
10 year 0.24 cfs 0.24 cfs
2 year 0.12 cfs 0.12 cfs
T: \7k \7310 \002 \drainage \4580001 drainrep.doc