Loading...
HomeMy WebLinkAbout04070007 C702 Water Details and SpecificationsPRESSURE PIPE JOINT RESTRAINT TABLE Length Of Pipe To Be Restrained In Each Direction From 1/4 Of Bend Based On 150 PSI Test Pressure Degree Of Bend 6" 8" 10" 12" 14" 16" 18" 20" 24" 30" 90; Tees Plugs 27' 35' 42' 50' 58' 65' 73' 80' 95' 115' 45° 7' 9' 11' 13' 15' 17' 19' 21' 24' 29' 22 -1/2' 3' 4' 5' 6' 7' 8' 9' 10' 12' 14' 11 -1/4° 2' 2' 3' 3' 4' 4' 4' 5' 6' 7' DATE: 7/2/04 PROJECT NO.: 1238.9007 DRAWN BY: BET CHECKED BY: SHEET TITLE: WATER DETAILS AND SPECIFICATIONS DRAWING FILES: N: \1238 \9007 \DWGS \C702.DWG SHEET NO.: C702 BLOCKING FOR PLUGS BENDS BLOCKING FOR TEES WYES PIPE SIZE OUTSIDE FACE AREA (SQ. FT. SIZE OF RUN SIZE OF BRANCH OUTSIDE FACE AREA (SQ. FT.) PLUG 90' BEND 45" BEND 22 1/2" 11 1/4" 20" 16 25 14 7 4 20" OR 16" 16" 12 16" 12 16 9 5 3 6 12" 7 9 5 3 2 g 5 10" 4 7 4 2 1 12" OR LESS 12" 7 8" 3 5 3 2 1 10" 6 8" 4 6" 2 3 2 1 1 6" 2 4" 2 3 2 1 1 4" 2 1. SCOPE OF WORK: A. The work required under this section includes all cold water distribution lines, valves, hydrants, and related items including excavating and backfilling necessary to complete the work shown on the drawings. The ends of water service lines shall be tightly plugged or capped at the terminal points pending the connecting to all such lines of the building piping as specified in the plumbing specifications and architectural drawings. 2. MATERIALS: WATER MAINS A. Cast Iron Pipe: Cast iron pipe shall meet AWWA Specification C -106 with push —on joints meeting AWWA Specification C -111. Wall thickness shall be determined from Table 6.4 in AWWA C -106. Ductile iron pipe shall meet AWWA C -150 and C -151 Specifications. Pipe to be cement lines per AWWA C -104. B. Copper Tubing: Shall be seamless, "K" copper tubing complying with Federal Specification WW —T -799. Fittings shall be wrought copper with compression fitttings or cast bronze. C. Fire Hydrants: Shall comply with AWWA Specification C -502 and shall meet local standards and requirements, particularly as to nozzle diameters and threads, direction of opening and dimensions of operating and cap nuts. Fire Hydrants shall have one pumper and two hose nozzles. A valve opening not less than 5 inches and a 6 inch inlet connection. The length of the hydrant barrel shall be determined by the specified depth of cover over the pipe. D. Valves: All valves and stops shall have ends suited or adapters shall be provided for the proper installation in the lines in which they are located. Valves shall meet local standards or in the absence of such standards, the following requirements: 1. Valves in cast iron pipe shall be iron body, bronze mounted, disc gate valves conforming to AWWA Specification C -500. They shall open in the same direction as those used in the local waterworks system. Valve stems shall terminate in 2 inch wrench nuts. Furnish two (2) keys. 2. Valves in copper pipe shall be standard brass body, round —way, ground —key stops with T heads. Furnish two (2) keys. E. Valve Boxes: Shall meet local standards or in the absence of such, shall comply with the following requirements: 1. For iron body valves, boxes shall be approved standard buffalo —type, cast iron, adjustable shaft boxes, having a minimum shaft diameter of 5 -1/4 inches. 2. For brass body valves (stops) boxes shall be approved standard cast iron extension service boxes, having a minimum diameter of 2 -1/2 inches and having lid held in place by a brass or bronze bolt. The castings shall be coated with two coats of coal —tar pitch varnish. Furnish two (2) keys for bolt in lids. F. Stops: Stop shall be those manufactured by Ford or Mueller Corporation with AWWA taper thread, and with copper compression type fitting on outlet, or equal. G. Blow —off Valves: Blow —off valves shall be those manufactured by Muller Corporation (H -10283 or H- 10291), or equal. H. Angle Valves: Angle valves at the end of water service stub are to be copper compression type fitting also, and ore to be protected with plastic bag over the valve. I. Taps: 3/4" taps in lines smaller than 4 inches shall be only by tapped tee or tapping saddle. Water service lines should be marked on curbs with a stamped "W placed while pouring curbs. 3. APPLICATION: A. Permits and Codes: The intent of this section is the specifications if that the contractor's bid on the work covered herein shall be based upon the drawings and specifications but that the work shall comply with all applicable codes and regulations. Contractor shall furnish all necessary bonds to get permits for cuts and connections. B. Existing Improvements: Maintain in operating condition all active utilities and sewers and other pipe system that may be encountered. C. Trenching: Lay all pipe in open trenches, except when local authority gives written permission for tunneling. Provide a separate trench for the water line at least 10 feet horizontally from any sanitary sewer. In locations where separate trenches for sewer and water lines are impracticable, lay the water pipe on a solid shelf at least 18 inches above the top of the sewer. D. Width of Trench: Excavate trenches minimum of pipe diameter plus 12 E. Sheeting and bracing: Sheet and brace trenches as necessary to protect workmen and adjacent structures. All trenching shall comply with the Occupational Safety and Health Administration Standards. F. Water Removal: Keep trenches free from water while construction therein is in progress. Under no circumstances lay pipe or appurtenances in standing water. Conduct the discharge from trench dewatering to drains or natural drainage channels. G. Grading Trench Bottoms: The bottom quadrant of the pipe shall be fully and uniformly supported. The full load shall rest on the barrel of the pipe. The trench may be excavated to a depth of 4 inches or more below final grade with sand, crushed stone or grovel backfill to bring it back to pipe laying grade. For a depth of at least 12 inches above the top of the pipe backfill with earth or granular material free from large stones, roots or frozen clogs. Tamp this backfill thoroughly taking care not to disturb the pipe. Backfill under walks, parking areas, driveways and streets with granular material only and tamp thoroughly, by approved methods. Trenches parallel to and within 10 feet of paved roadways shall be constructed the same. H. Tests: Before joints are covered, fill the piping with water, opening hydrants or at least two hours at a pressure of 100 pounds per square inch. Inspect all joints for leakage and remedy any leaks. Upon completion of the water distribution mains, flush out the system until the water runs clear. As soon as the system has been flushed out, it shall be sterilized in accordance with the requirements of City of Carmel. I. If a horizontal distance of 10 feet cannot be maintained between the water line and and a sanitary sewer line, one of the following shall be done. a. Water line laid in a separate trench and 18" above sewer. b. Water line laid in same trench on a bench of undisturbed earth and sewer at least 18" below bottom of water line. J. Utilities: It shall be the responsibility of each contractor to verify all existing utilities and conditions pertaining to his phase of the work. It shall also be the contractors responsibility to contact the owners of the various utilities before work is started. The contractor shall notify in writing the owners or the engineer of any changes, errors or omissions found on these plans on in the field before work is started or resumed. K. New Water Main Construction: Contractor to record dimension of each water stub and valves from nearest fire hydrant measured along water main. The locations of hydrants and water valves, along with any other construction changes are to be incorporated on the original construction drawings and "Record Drawing" prints submitted to Engineer's Office as soon after completion of construction as possible. Pipe Tracing Tape A. All pipe shall be traced with "Terra Tape" by Reef Industries, Inc., P.O. Box 33248, Houston, Texas 77033 or equal. tape shall be "Detectable" type imprinted with "Caution Buried Water Line Below Gate Valves Where water lines and sewers cross and the water lime cannot be placed above the sewer with a minimum of 18" vertical clearance, the sewer must be constructed of water works grade cost iron pipe with mechanical joints within 10 feet of the water line. A. All gate valves shall be iron body, bronze mounted, double disc, parallel seat type gate valves, conforming to AWWA Standard Specifications C500. They shall open in a counter clockwise direction. Valves placed in a valve box shall terminate in 2 inch square operating nut and have non rising stems. One valve wrench shall be supplied to the Owner for this project. Gate valves shall be as made by Kennedy Valve Manufacturing Co., Inc., Elmira, New York, Mueller or equal. Valve Boxes A. Valve boxes shall be a three —piece cast iron type (base, center section, and sliding type adjustable extension) toge +her with a "stay —put" cover marked "WATER The base shall be of the size recommended by the manufacturer for the size valve with which it is to be used. Wall thickness of the base and vertical sections shall not be less than 3/16 inch, and each valve box shall have a minimum shaft diameter of 5-1/4 inches. BACKFILL WITH EXCAVATED MATERIAL 0.D. OF WATERMAIN /.A. MINIMUM O.D. 1'— TYPICAL WATER MAIN INSTALLATION FITTING TO SUIT MECHANICAL JOINT r CONNECTION TO EXISTING MAIN OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR 22 1/2' 11 1/4* BENDS. 3/4 "x18" ANCHOR BOLTS (4 REQ'D) PLAN 5" DIAM. WASHER, 1" THICK ANCHOR BLOCK TO BE OF CLASS "B" CONCRETE STRAP IRON ANCHORS 2" WIDE x 1/2" THICK DOWNWARD BEND DIG OUT EACH JOINT. PIPE TO REST ON FIRM EARTH USE TAPPING SLEEVE "ALV E FOR CONNECTIONS UNDER PRESSURE 1 EXISTING MAIN I OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR 90' 45" BENDS. PLAN OUTSIDE FACE AREA AS NOTED IN TABLE. SECTION "C —C" NOTE: ALL CONCRETE BLOCKING TO CONSIST OF CLASS "B" CONCRETE POURED AGAINST FIRM GROUND. Ii, ,Il, GAS MAIN SANITARY SEWER SET TOP FLUSH WITH FINISHED GRADE POSI —CAP OR EQUIVALENT TO BE INSTALLED ON ALL VALVES BRANCH PLUG 12" OUTSIDE FACE AREA NOT LESS THAN VALUES GIVEN IN TABLE FOR TEES WYES. FOR PLUGS. PLAN -1 11 -1 I I -1 11 -1 I ICI SECTION "D —D" DETAIL CONCRETE BLOCKING TYPICAL UTILITY CROSSING GATE VALVE AND BOX WATER MAIN lo 4, 4 4 1 ADJUSTABLE VALVE BOX Restrained Joints Shall Be Mechanical Joint With Retainer Glands, US Pipe TR Flex Joint System, US Pipe Field LOK Gasket System, Or Equal. NOTE.' THE ABOVE RESTRAINED JOINT LENGTHS ARE MINIMUM LENGTHS THE DESIGN ENGINEER SHALL DETERMINE IF LONGER LENGTHS ARE REQUIRED. CITY OF CARMEL STANDARD DETAILS Date: March 2001 Scale: Not To Scale TfTL JOINT RESTRAINT TABLE Drawn By: Jones Henry Engineers. Inc. Drawing Name: CW10 Existing Water Main Tapping Sleeve Notes. Varies Bend As Required Water Main Note: All Joints Shall Be Restrained Except In Run Of Tee. Notes: 1) Megalug flanges shall be used for all mechanical joints. 2) Bell end pieces of pipe 4 ft. and smoller shall be considered scrap, and shall not be installed into system. L h Service Saddle Must Be Omitted For Services 1" And Smaller And Direct Taps Made To Ductile Iron Pipe, Class 350 Or Greater. (Verify With Owner For Pressure Class DIP.) Valve Varies PLAN 9 New Water Main Tee Curb Box With Cover Double Strap Service Saddle Lenath Varies Copper Service Line 1. At High Points Along Main Water Line Where Indicated On Drawings, Anchoring Tee Shall Be Set At 45° Angle Upwards And Connected To 6" 45° Bend. Main Water Line Shall Be Lowered To Provide Sufficient Cover As Specified. 2. All Joints Shall Be Restrained Except In Run Of Tee. 3. Hydrants Shall Be Set At 500' Max. Horizontal Distance, Or Less As Specified By Fire Department 4. All valves must include Posi —Cap or equivalent New Pipe Shall Be Installed Under The Existing Water Main Curb Stop Date: March 2001 Corporation Stop Mueller H-15008, Or Equal Water Main Length And Fittings ,4s Required Date: March 01 12" Min. CITY OF CARMEL STANDARD DETAILS Concrete Block (Verify) 1 vvvvvvvvvvv vvvvvvvvvv•- vvvvvvvvvvv •vvvvvvvvvv•/ vvvvv7vvvvv vvvv vvv g3�+ vvvv vvv vvv vvv \.vvv vvvv vvvv•••vvvv Scale: Not To Scale CITY OF CARMEL STANDARD DETAILS Date: March 2001 I Scale: Not To Scale Ea t Mueller Centurion A -423, Or Equal Painted 'Safety Ye %w" 5. Hydrant Valves must be restrained to the tee with either all thread, or an anchoring tee. CITY OF CARMEL STAN DAR D DETAILS 1 -0" Min. Bedding Material Conforming To INDOT 903.02, Size No. 8 One 8 "x8 "x16" Solid Conc. Block Or 6"Min. Class "8" Concrete Base On Undisturbed ground. Scale: Not To Scale SECTION See Trench Detail For Backfill Requirements Bed Pipe In Specified Granular Bedding Material Hand Tamped In 6" Layers To Pipe Centerline Bedding Material Shall Conform To INDOT 903.02, Size No. 8 WATER MAIN CONNECTION DETAIL Drawn Henry Engineers. Inc. NOTE. 1) 1" Or Smaller Service Line Shall Be Direct Tap Unless Approved By Carmel Utilities. 2) Corporation Stop Shall Be Brand And Model Approved By Carmel Utilities. 3) Service Line Top Shall Be Installed With A Min. Horz. Seperation Of 24': 4) 2 inch taps and smaller shall not be installed within 18 inches of machanical joints and be /s. Jones Henry En 'veers. Inc. Drawn By: Jones Henry Engineers. Inc. Existing Water Main New Water Main Drawing Noah: CW5 WATER SERVICE DETAIL 1 Dmwing Nome: CW4 ARE HYDRANT ASSEMBLY Drawing Nome: CW8 LLJ DATE: 7/02/04 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF THE SCHNEIDER CORPORATION, AND ARE NOT TO BE USED OR REPRODUCED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF THE SCHNEIDER CORPORATION. COPYRIGHTED BY THE SCHNEIDER CORP. (2004) Schneider THE SCHNEIDER CORPORATION 12821 E. New Market Street Suite 100 Carmel, IN 46032 Telephone: 317.569.8112 Fax: 317.826.6410 www.schneidercorp.com Architecture Civil Engineering Environmental Engineering Geotechnical Services GIS LIS Home Builder Services Interior Design Land Surveying Landscape Architecture Transportation Engineering