MATERIALS:
A.
APPLICATION:
SANITARY SEWER SYSTEMS
The work within these specifications include all sanitary sewers, manholes, catch basins cleanouts, and related items,
including excavating and backfilling, necessary to complete the work shown on the drawings, starting five feet outside
the building walls. The ends of sewers shall be tightly plugged or capped at the terminal points, adjacent to buildings,
pending the connecting of all such lines to the building drain as specified in the plumbing specifications and
architectural drawings,
Sanitary Sewers:
1. All gravity plastic sewer pipe and fittings shall conform to ASTM D3034, SDR -35. The minimum cell classification
for P,V.C• and P.V.C. truss pipe shall be 12454 -B or 12454-C.
2, All force main sewer shall be PVC ASTM D 1785 Schedule 40. 80 or 120; POLYETHYLENE 160p.s.1, SDR 7 in 3 /4- -inch,
1 inch and 1-1/4-inch diameters only PVC ASTM -D 2241 SDR 13.5, 17, 21 or 26; ABS ASTM -D 1527 Schedule 40, 80 or
ASTM -D 2282 SDR 13.5, 17, 21 or 26. Compression fittings must be use in crossing situations with potable water lines.
3. ABS Sewer Pipe and fittings shall conform to ASTM D2680 latest revision, if using truss pipe, joints shall be
gasket type.
4. The flow channels for the sanitary sewer manholes shall be u- shaped with the benchwalls extending to the crown of
the incoming and outgoing pipes.
5. Joints for P.V.C. and P.V.C. truss pipe shall be compression type flexible gasketed joints,
8: Manholes:
1. Precast reinforced concrete manhole sections shall conform to ASTM C -478 latest revision.
2. Castings shall be of uniform quality, free from blow holes, porosity, hard spots, shrinkage distortion or other
defects. They shall be smooth and well cleaned by shot blasting or some other approved method, They shall be
coated with asphalt paint which shall result in a smooth coating, tough and tenacious when cold, not tacky or
brittle.
3. All castings shall be manufactued In accordance with ASTM A-48-83 Class 358 having a minimum tensile strength of
35,000 psi, and be true to pattern; component parts shall fit together in a satisfactory manner, Round frames and
covers shall be of non rocking design or shall have machined horizontal bearing surfaces to prevent rocking and
rattling under traffic. All castings shall be fully interchangeable.
4. All weights shall not deviate from the tolerances permitted by ASTM A48 -83 "Standard Specifications for Gray Iron
Castings
5. Sanitary sewer frames and covers shall be type Neenah R1642 A
6. Joints manhole sections shall be jointed with sealed "o rings. The "o rings shall meet ASTM C-433 latest
revisions.
A. Permits and Codes: The intent of this section of the specifications is that the contractors bid on the work
covered herein shall be based upon the drawings and specifications but that the work shall comply with all
applicable codes and regulations as amended by any waivers, Contractor shall furnish all bonds necessary to get
permits for cuts and connections to existing sewers.
B, Local Standards; The term "Local Standards" as used herein means the standards of design and construction of the
respective municipal department or utility company,
C, Existing Improvements; Maintain in operating condition all active utilities, sewers and other drains encountered
in the sewer installation. Repair to the satisfaction of the owner any damage to existing active improvements.
D. Workmanship: To conform to all local, state and national codes and to be approved by all local and state agencies
having jurisdiction.
E. Trenching: Lay all pipe in open trenches, except when the local authority gives written permission for tunneling.
Open the trench sufficiently ahead of pipe- laying to reveal any obstructions. The width of the trench shall be
the inside pipe diameter plus 24 inches for 12 inches above the pipe. Sheet and brace trench as necessary to
protect workmen and adjacent structures. All trenching to comply with Occupational Safety° and Health
Administration Standards. Keep trenches free from water while construction is in progress. Under no
circumstances lay pipe or appurtenances in standing water. Conduct the discharge from trench dewatering to
drains or natural drainage channels,
F. Special Supports: Whenever, in the opinion of the Engineer, the soil at or below the pipe grade is unsuitable for
supporting sewers and appurtenances specified in this section, such special support, in addition to those shown or
specified, shall be provided as the Engineer may direct and the contract will be adjusted,
0, Backfilling: For a depth of at least 12 inches above the top of the pipe, backfill with granular material free
from large stones, rock fragments, roots or sod. Compact this backfill thoroughly, taking care not to disturb the
pipe. For the remaining trench depth, backfill with earth or granular material containing stones or rocks not
larger than 4 inches, Backfill under walks, parking areas, driveways and streets shall be granular material only,
thoroughly compacted, by approved methods. Trenches parallel to and within 5 feet of paved roadways shall be
constructed the same.
H, Manhole inverts: Construct manhole flow channels of concrete or sewer pipe, smoothed and semi-
circular section conforming to the inside diameter of the connecting sewers, Make changes in size or grade
gradually and changes in direction by true curves. Provide such channels for all connecting sewers at each
manhole.
I. Infiltration: Furnish necessary equipment to test sewers for infiltration. Infiltration rates shall not exceed
the local standards, All sanitary sewer lines upon completion will be required to pass a low pressure air test,
unless otherwise directed by the City of Carmel Utilities. Infiltration under test shall not
exceed 100 gallons per inch on inside diameter of sewer pipe per mile of sewer in 24 hours and inclusive of all
appurtenances within the section being tested such as manholes, house connections, etc.
J. Flushing Sewers: Flush all sanitary sewers except building sewers with water to obtain free flow through each
line. Remove all silt and trash from appurtenances just prior to acceptance of work.
K.. Plastic Sewer Pipe Installation: Plastic sewer pipe shall be installed in accordance with ASTM D232I per latest
revision, and no plastic pipe shall exceed a deflection of 5 Contractor shall be responsible for performing
mandrel -type deflection testing, with supervision of designated County inspector.
L. Storm Water Connections: No roof drains, footing drains and /or surface water drains may be connected to the
sanitary sewer systems, including temporary connections during construction.
M. Waterline Crossing; Where water lines and sanitary sewers cross and water lines cannot be placed above the sewer
with a minimum of 18 inches vertical clearance, the sewer must be constructed of water works grade ductile iron
pipe with mechanical joints within 10 feet of the water line.
N. Utilities: It shall be the responsibility of each contractor to verify all existing utilities and conditions
pertaining to his phase of the work. It shall also be the contractors responsibility to contact the owners of the
various utilities before work is started. The contractor shall notify in writing the owners or the engineer of
any changes, errors or omissions found on these plans or in the field before work is started or resumed.
0, Service Laterals: Individual lot service lines shall be 6" in diameter and of material equal to the specified in
A -2 of this section. Service lines shall be connected to the main sewer by a wye at locations generally shown
within these plans. Service lines shall be extended and capped at a point 5 feet beyond the right -of -way line or
one pipe length for those services on the same side of the street as the main.
P. New Sanitary Sewer Main Construction: Contractor to record dimensions of each service line stub from nearest
downstream manhole measured along the sanitary sewer main. The locations of manholes and service lines along with
any other construction changes are to be incorporated on the original construction drawings and "Record Drawing
prints submitted to the City of Indianapolis and the engineer as soon after completion of construction as
N. T. S.
30 1/2" O.D.
24" I.D.
1/4" (TYP)
PLAN VIEW
1/4" (TYP) -•r--
5/8
30 1/8" O.D. •0-I
SECTION A —A
ADJUST/NG RING DETAIL
NOTE: CONCRETE APRON AND CASTING SHALL BE
INSTALLED SO THAT THEY DO NOT
CONTACT THE LATERAL OR LATERAL CAP.
36" x 36" x 8" CONCRETE
APRON WITH FIBERMESH
REINFORCEMENT.
PLACE MINIMUM 10" DIA. HDPE
PIPE AROUND LATERAL PRIOR
TO BACKFILLING. HOPE PIPE TO
EXTEND INTO CONCRETE.
EDGE OF PAVEMENT, CURB,
GUTTER OR SIMILAR STRUCTURE
IN THE PUBLIC RIGHT OF WAY
B OUTSIDE DIAMETER
D INSIDE DIAMETER
d DEPTH OF BEDDING
MATERIAL BELOW PIPE
63'
8 -12"
1 /2"
GREATER THAN 5'
"B "BORROW OR EQUIV.
GRANULAR MATERIAL
COMPACTED TO 90%
STANDARD PROCTOR
DENSITY
RISER RING THICKNESS
8" -12"
OUTSIDE DIA. 34" OR 36"
EAST JORDAN IRONWORKS MODEL
1755 CASTING, LETTERED "SEWER"
6" PVC CAP
JOINT DETAIL
2" LETTERS, RECESSED,
FLUSH WITH SURFACE
EXPANSION JOINT
AROUND LATERAL
FINAL GRADE
,ii„
#8 STONE BELOW CONCRETE
APRON TO PREVENT
SETTLING. EXTEND TO
UNDISTURBED EARTH.
CLEANOUT TYPE 2
(HARDSCAPE SURFACES AND ALL OTHER INSTALLATIONS
BEYOND THREE FEET OF BUILDING)
NOTE: TOP OF CASTING OR
CAP SHALL EXTEND 0.20' MIN.
ABOVE FINISHED GRADE UNLESS
CONSTRUCTED WITHIN PEDESTRIAN
OR VEHICULAR TRAFFIC WAY.
N. T. S.
1.25 B MIN.
REGULAR BACKFILL
WET GROUT BED
A
6" SEWER LATERAL
PRECAST CONC.
ADJUSTING RING
OR FLANGE OF
CASTING
MIN. 6" TOPSOIL
TO ENSURE GRASS
GROWTH IF NOT
UNDER PAVEMENT
PIPE BEDDING SECTION
(NO SCALE)
GREATER THAN 5' FROM EDGE OF PVMT.
id 0 Oh,
O D 0 ODD
"SELF- SEALING"
APPLICATION
r 22 3/4"
(STANDARD MANHOLE)
(NO SCALE)
6" PIPE
6" 1/8 BEND
45' (6" X 6
MINIMUM 4" CONCRETE CAP FROM
THE SPRING LINE TO 6" OVER PIPE,
NOT TO EXTEND BEYOND FIRST PIPE
JOINT OF WYE. MINIMUM CONCRETE
STRENGTH OF 3500 PSI, 28 DAY
COMPRESSIVE STRENGTH.
NOTE:
ALL CLEANOUT PIPE AND FITTINGS TO BE PVC SCHEDULE 40
OR SDR 35 WHEN SHALLOWER THAN 12 FEET. AT DEPTHS
GREATER THAN 12 FEET MATERIAL OF CONSTRUCTION WILL BE
DETERMINED BY ENGINEER.
TYPICAL CLEANOUT DETAILS
VOTE: AL_ STORY SEW
I \STALLED U \D -R PAVEIV
S ALL BE BACK iLLED, P
T DETAIL A \D DCAM S
NOTE:
ALL BEDDING INITIAL BACKFILL
SHALL BE INSTALLED IN 6" TO 12"
BALANCED LIFTS.
MIN. 9" OF CLEARANCE SHALL
1 /6Bc BE PROVIDED ON EACH SIDE OF
THE INSTALLED PIPE.
NEENAH R- 1077 -A COVER
WITH NEENAH R- 1712 -8 -SP
FRAME WITH SELF SEALING
APPLICATION OR EQUAL
PER SECTION 5.04 (a)
2 CONCEALED
PICKHOLES 180'
(W9204-A OR CITY EQUAL)
MACHINE BEARING
SURFACE
SANITARY SEWER MANHOLE
FRAME AND COVER
6" PVC CAP
FiNAL GRADE
6" PVC PIPE
6" 1/8 BEND
45' (6" X 6
6" SEWER LATERAL
CLEANOUT TYPE 1
(ONLY LANDSCAPED SURFACES WITHIN
THREE FEET OF BUILDING)
ER
ENT
ER
PECS.
5' (MiN
18 (MIN)
WATER LINE
CONCRETE ENCASEMENT
SECTION VIEW
5'(MIN)
B OUTSIDE DIAMETER
D INSIDE DIAMETER
d DEPTH OF BEDDING f;
MATERIAL BELOW PIPE
NOTE:
ALL BEDDING INITIAL BACKFILL
SHALL BE INSTALLED IN 6"
TO 12" BALANCED LIFTS
MIN. 9" OF CLEARANCE SHALL
BE PROVIDED ON EACH SIDE
OF THE INSTALLED PIPE
REVISIONS
PRE -BID SET
ISSUE DATE
POST BID SET
ISSUE DATE
DATE DESCRIPTION
12/12 CHANGE CASTING
GD
z
Q
SHEET
Ld
w
U
L 012.4.
c
N
d
N
C -604
0
U V
o
N d i
(0 co Q)
o rnf E
Lo 0
1 'NS
CN
0
0 x .0
W
CSI PROJ. 00 --113
NOTES:
MANHOLE TO CONFORM
TO ASTM C -478
LIFT HOLES TO BE FILLED
WITH NON-SHRINK MORTAR
PREFORMED BITUMEN SEALS,
KENT SEAL OR EAQUAL, MAY
BE USED BETWEEN ADJUSTING
RINGS iN LIEU OF MORTAR
BED BASE SECTION IN 4 "(MIN.) CLASS "B"
CONC. OR COMPACTED GRANULAR BEDDING MATERIAL
CONFORMING INDOT 903.02, SIZE NO. 8
MUST EXTEND TO
UNDISTURBED SOIL
6
END VIEW
WATER LINE— SEWER CROSSING
RUBBER GASKET JOINTS
TO CONFORM
TO ASTM C- 443
(NO SCALE)
PAVEMENT SUB -GRADE
1.25 B 12" (MIN.)
"B" BORROW OR EQUIV.
GRANULAR MATERIAL
COMPACTED TO 95%
STANDARD PROCTOR DENSITY
#8 CRUSHED STONE OR
APPROVED EQUIV. CLASS MIN. 12"
BEDDING MATERIAL HAND
TAMPED OR WALKED INTO
PLACE
PIPE BEDDING SECTION
(NO SCALE)
WITHIN 5' OF EDGE OF PAVEMENT
NOTE:
SEAL MUST BE ABLE TO PASS AIR PRESSURE
TESTS REQUIRED FOR SEWER MAIN
PRECAST CONCRETE
ADJUSTER RING
8"M/N- 12 "MAX
Aro
I,
SANITARY SEWER MANHOLE DETAIL
(NO SCALE)
I
.32"
16"
32"
OR
48"
I�
8
12 "MAX
4" IN.
FRAME AND COVER
r SEE SPECS THIS SHEET
CEMENT MORTAR
4' DIAMETER
FILL WITH CONCRETE
CLASS "A"
48" 1/2 /FOO T(MiN)
SLOPE
FLOW
NOTE:
IF MANHOLE HAS ONLY ONE INFLUENT PIPE WHICH iS APPROXIMATELY
90 DEGREES TO EFFLUENT PIPE, THEN CONTRACTOR SHALL MAINTAIN
A RADIUSED CHANNEL OF SAME WIDTH AS INFLUENT PIPE.
FLOW CHANNEL DETAIL
N.T.S.
ECCENTRIC CONE SECTION
PVC GASKETED OR SOLVENT
WELDED CAP (FOR PVC PIPE)
D.I. PUSH ON OR M.J. CAP
(FOR D.I. PIPE)
AS —BUILT LOCATION AND INVERT
ELEVATION REQUIRED IF STUB
IS LONGER THAN 20 FEET
1 LINE OF .24"
NOTE:
MANHOLE STEPS SHALL BE POLYPROPYLENE,
POLYPROPYLENE COATED STEEL REINFORCING OR
AN APPROVED NON CORROSIVE FIBERGLASS MATERIAL.
THE COPOLYMER POLYPROPYLENE SHALL MEET THE
REQUIREMENTS OF ASTM 0 -4101 REINFORCED WITH
DEFORMED 3/8 INCH.(MIN) DIAMETER REINFORCING
STEEL CONFORMING TO THE REQUIRMENTS OF
ASTM A-615, GRADE 60
PRECAST CONCRETE SECTIONS
0 -RING GASKET BETWEEN
ALL RISER AND CONE
SECTIONS, PLUS 1/2"
EXTRUDABLE GASKET
(KENT SEAL OR EQUAL)
BARS -12" 0.C. BOTH WAYS
3 "MIN.
WATERTIGHT FLEXIBLE JOINTS SHALL BE
RES -SEAL (PRICE BROS.), LOCK JOINT
P (INTERPACE
EQUAL O.. KOR -N -SEAL (US CONC.
8" MIN. FROM OUTER EDGE
OF RESILENT CONNECTORS.
A
A likf
3500 PSI CONCRETE
BLOCKING (FOR GASKETED
FITTINGS ONLY)
UNDISTURBED
EARTH
SEWER STUB CAPPING DETAIL
NOTE:
IF SEPARATION IS BETWEEN
8" AND 20 THEN
ADDITIONAL
REINFORCEMENT (REBAR OR
MESH AREA) SHALL BE
INCREASED AS DEEMED
NECESSARY BY SAMCO
ENGINEER