MSKTD & Associates D. Nicholas Slater Kyle Hardie 317.917.1190 Loftus Engineering, Inc. Joyce Jones-Myers Mark Jackson Brenda Bradley 260.432.9337 1. Portions of the building shall be
occupied during construction. Contractors shall comply with the following life safety issues. Failure to list all life safety issues does not relieve the contractors from complying with
federal, state and local codes, the contractural agreement between the contractor and the owner,and the other governing bodies which have jursidiction on this project. The following
are interim life safety code issues which are specific to this project and must be addressed. A. Insure all exits provide free and unobstructed egress. B. Smoking shall be prohibited
in all areas of the building. Campus is smoke free environment. C. Develop and enforce storage, housekeeping and debris removal procedures that reduce the flammable and combustible fire
load to the lowest level necessary for daily operations. D. Secure all tools and construction materials during breaks and non-construction hours. E. IOSHA requires material safety data
sheets (MSDS) for all materials being used or stored on this project be made available to all workers on this jobsite. 2. The contractors shall be responsible for informing the owner
in writing on a bi-weekly basis, the construction schedule for the approaching two weeks construction period. Any storage materials access or egress problems, traffic flow or normal
owner operations which are to be affected must be protected and/or agreed upon by owner. All costs shall be incurred by the general contractor. 3. Any services which must be temporarily
shut off must be coordinated with the owner. 4. All construction areas, removal traffic pattern areas and associated work areas shall be kept clean of debris by the contractors daily.
5. Fire rated wall and ceiling penetrations must comply with E-814. 6. The general contractor shall provide all necessary fire treated wood blocking for all trades. Continuous blocking
required for all wall hung shelving, casework, grab bars and handrails. Brace walls with wall hung items to deck as by printed stud mfg. recommendations. 7. Dimensions are to face of
stud or masonry, unless otherwise noted. 8. Existing surfaces shall be prepared to accept new finishes, per finish material manufacturer recommendations. This preperation of substrate
shall be the responsibility of the particular finish contractor. If no preperation work is done to surfaces, the contractor accepts the conditions as they are, and is responsible for
the performance of the material. 9. "Construction Limits" generally illustrate areas of new construction. Other work may be required for demolition or replacement of the other systems
including the MEP. 10. Contractor to provide ten-day notice with owner-supplied forms for all system shut-downs to facilities. Minimal exceptions will be made in cases of emergency or
schedule conflicts on an owner-determined basis. 1. These demolition notes shall serve to aid the contractor in the evaluation of the extent of demolition; but shall not be held to be
all inclusive. 2. Contractors shall be responsible for all demolition required for the installation of new construction, whether or not it is specifically shown or noted in these documents.
3. Remove all damaged gypsum board, or concrete from existing surfaces an repair to match adjacent construction. 4. Selective electrical, mechanical, and fireprotection demolition will
result in various wall/floor/ceiling openings. Contractor to repair these areas as necessary in accordance with specifications. 5. "Construction Limits" generally illustrate areas of
demolition. Other work may be required for demolition or replacement of the other systems including MEP above ceiling items. 6. All demolition material becomes the property of the contractor
and is to be removed from hospital property, in a legal manner. The owner reserves the right to claim items whether or not those items were specifically noted "to be relocated" or "to
be returned to owner." 7. The contractor is responsible for salvaging all items in good condition for owners re-use: lights, ceiling tiles, doors, windows, plumbing fixtures, toilet
accessories, etc. 8. Refer to Clarian's "Mandatory Contractor's Orientation Requirements" (MCOR) for additional requirements. 9. Contractor to provide ten-day notice with owner-supplied
forms for all system shut-downs to facilities. Minimal exceptions will be amde in cases of emergency or schedule conflicts on an owner determined basis. 10. All mobilization and deliveries
shall use only Hospital Service Elevator No. 10 and Lower Level's Loading Dock. All deliveries shall be before 7:00 A.M. or after 4:00 P.M. ROOM NAME 101 1 A101 SIM 1i 1t 1 A 101A A101
1 SIM DETAIL NUMBER SHEET NUMBER DETAIL NUMBER SHEET NUMBER X XX.X X SHEET NUMBER DETAIL NUMBER NEW DOOR AND FRAME SPECIFIC CONSTRUCTION NOTES ROOM NAME AND NUMBER INTERIOR ELEVATION
SYMBOL PLAN DETAIL EXISTING COLUMN LINE SECTION ELEVATION SYMBOL PARTITION TYPE WINDOW ELEVATION SYMBOL TOILET ACCESSORY A SPECIFIC DEMOLITION NOTES 1.5B EXTEND TO DECK ABOVE 1.5E EXTEND
TO 8" A.F.C. 1-HR FIRE RESISTANT ASSEMBLY EXTEND TO DECK ABOVE 1.5C LEAD SHIELDING (REFER TO SPECIFICATIONS) 1.5D 5/8" GYPSUM BOARD (BOTH SIDES) 3 1/2" SOUND ATTENUATION BLANKET 3 5/8"
20 GA. METAL STUD FRAMING (@16" o.c.) 5/8" TYPE X GYPSUM BOARD (BOTH SIDES) SOUND ATTENUATION BLANKET 3 5/8" 20 GA. METAL STUD FRAMING (@16" o.c.) 5/8" GYPSUM BOARD (BOTH SIDES) SOUND
ATTENUATION BLANKET 3 5/8" 20 GA. METAL STUD FRAMING (@16" o.c.) 5/8" GYPSUM BOARD 3 1/2" SOUND ATTENUATION BLANKET 3 5/8" 20 GA. METAL STUD FRAMING (@16" o.c.) 1/16" LEAD SHIELDING
(IMAGING SIDE ONLY -TO 8'-0" A.F.F.) 1. All work located outside of construction separation walls shall be coordinated with the owner/architect. 2. All work located in Control Room B133,
Imaging B133A, and Work B133B shall be performed from 6 PM to 7 AM. 3. All work associated with Doors 128B, 132A, and 133B shall be performed after the construction completion and start
of operation of CT #2. Tentative schedule for work is August 30 -September 2, 2010. 4. Alternate No. 1: Replace doors one at a time. Contractor must maintain access for general public
into Waiting B120. 5. Alternate No. 2: Work associated within Transitions K120 to be coordinated with owner/architect. All work to be performed as-soon-as -possible with minimal shutdowns.
Coordinate with door delivery. 6. All Unistrut framework to be designed and installed by manufactuer for owner-supplied equipment. Coordinate lay-out within plenum space. Refer to MEP
and Philips drawings. 7. Contractor is responsible for providing floor support and anchoring for owner-supplied equipment. Refer to Philips drawings. COMMISSION NUMBER DATE SHEET NUMBER
SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates, Inc., and were created, developed and
presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation for any purpose whatsoever, without
the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection with this project. 1715 MAGNAVOX WAY
FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR
DESIGN !" !4/16/2010 2:59:42 PM 11700 North Meridian Street, Carmel, Indiana 46032 -! !" #Clarian North Medical Center CT #2 Build Out 11700 North Meridian Street, Carmel, Indiana
46032 Consultants Partition Types General Demolition Notes Drawing Index General Construction Notes EQ101 Philips Equipment EQ102 Philips Equipment EQ103 Philips Equipment EQ104 Philips
Equipment EQ105 Philips Equipment EQ106 Philips Equipment EQ107 Philips Equipment EQ108 Philips Equipment EQ109 Philips Equipment EQ110 Philips Equipment EQ111 Philips Equipment E000
Electrical Symbols E101 Lower Level Electrical Electrical Demolition Plan E111 First Floor Electrical Demolition Plan E211 First Floor Lighting Plan E301 Lower Level Electrical Plan
E311 Electrical Equipment and Raceway Layout E312 First Floor Power Plan E313 First Floor Systems Plan E601 Electrical One-Line Diagram E602 Brilliance CT Incoming Power Schematic E701
Electrical Schedules MP001 Symbols and Abbreviations M101 Lower Level HVAC Demolition Plan M111 First Floor HVAC Demolition Plan M201 Lower Level HVAC Plan M211 First Floor HVAC Plan
M500 Schedules M501 Details P201 Lower Level Plumbing Plan P211 First Floor Plumbing Plan P212 First Floor Medical Gas Plan T001 Title Sheet A101 First Floor Demo Plan A200 Lower Level
Plan A201 First Floor Plan A300 Lower Level Reflected Ceiling Plan A301 First Floor Reflected Ceiling Plan A400 Casework Elevations Architectural: Architectural: Engineering: Specific
Notes Graphic Symbols Mechanical: Electrical: Philips Equipment: Plumbing: Revisions: Date: By:
6 6 6 2 2 2 2 3 4 5 4 11.3 12 13 JK 14 H 10 11 CONSTRUCTION LIMITS -BASE BID CONSTRUCTION LIMITS -BASE BIDALTERNATE No. 1 MRI IMAGING 1 B132 LOCKERS B132 CT IMAGING 1 B128 TLT PAT B130A
DRESS B130B IMAGING WORK B133A B133B STAIR B3-1 OFFICE B145 OFFICE B146 OFFICE B147 OFFICE B148 OFFICE B144 ES CLOSET B142 CORRIDOR B044D CORRIDOR B1C16 CONSULT B121 RECEPT B120A DRESS
B123A WORK B120B OFFICE B113 CORRIDOR B1C17 LAB C129 WAITING B120 CORRIDOR B1C01 CORRIDOR B1C14 MRI SHELL B134 CONTROL B133 CORRIDOR B1C15 FS T FS T 9.7 L 2 1 1 1 1 7 8 9 9 1 1 10 10
2 11 12 TYP. COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD &
Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm,
or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference
in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236
http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:29 PM 11700 North Meridian Street, Carmel, Indiana 46032 !" #1/8" = 1'-0" First Floor Demo Plan First
Floor Key Plan Specific Demolition Notes 1 (INFECTIOUS CONTROL) CONSTRUCTION AND DUST SEPARATION WALL. 6" METAL STUD w/5/8" VINYL FACES GYPSUM BOARD AND SOUND ATTENUATION BLANKET. EXTEND
TO CEILING. TAPE SEAMS. REFER TO CLARIAN'S MANDATORY CONTRACTOR'S ORIENTATION REQUIREMENTS AND SPECIFICATION SECTION. MAINTAIN A MINIMUM OF 5'-0" AT EXISTING CORRIDORS AND OWNER OCCUPIED
SPACES FOR EGRESS. CONTRACTOR IS RESPONSIBLE FOR SUPPLYING AND DETERMINING WALL LOCATIONS AND NUMBER AND SIZE OF CONSTRUCTION DOORS WITHIN SEPARATION WALL. REPAIR FLOOR AND WALLS AS
NEEDED AFTER REMOVAL OF WALLS. 2 REMOVE PORTION OF WALL FOR NEW DOOR AND FRAME. 3 REMOVE PORTION OF WALL FOR NEW WINDOW. 4 REMOVE WALL ASSEMBLY. 5 REMOVE CARPET TILE. 6 REMOVE DOOR AND
FRAME. 7 RELOCATE FIRE ALARM STROBE LIGHT. REFER TO ELECTRICAL DRAWINGS. 8 RELOCATE THERMOSTAT. REFER TO MECHANICAL DRAWINGS. 9 REMOVE PORTION OF HANDRAIL/BUMPRAIL. 10 ALTERNATE No.
1 -REMOVE DOOR AND FRAME/ENTRY SYSTEM. 11 ALTERNATE No. 1 -RELOCATE FIRE ALARM STROBE LIGHT, THERMOSTAT, AND LIGHT SWITCH FOR NEW DOOR. 12 REFER TO ELECTRICAL AND PHILIPS DRAWINGS FOR
RECESSED FLOOR ROUGH-INS AND ANCHORING POINTS. Revisions: Date: By:
11.3 12 13 J K 14 H 10 11 TRASH RM B040 LINEN SERV B039 CORRIDOR B0C13 CORRIDOR B0C12 ELEV LOBBY B0C16 TELECOM B041 ELEVATOR 10 ELEVATOR 11 CONSTRUCTION LIMITS -BASE BID CORRIDOR C0C15
CORRIDOR B0C11 STAIR B3-LL CARTS C042 CORRIDOR C0C16 STORAGE C041 RECEIVING DOC C039 RECEIVING C033D CENTRAL PROCESSING C033 TRASH C040 CLASS C043 9.7 L CONSTRUCTION LIMITS -BASE BID
12 5' -0" 16' -0" 24 27 FIELD VERIFY 7' -6" COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are
the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall
be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies
for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice
317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:30 PM 11700 North Meridian Street, Carmel, Indiana 46032 $% !" #1/8"
= 1'-0" Lower Level Floor Plan Specific Plan Notes 1 INFILL WALL, FLOOR, AND CEILING OPENING. INFILL TO BE FLUSH AND LEVEL WITH EXISTING ADJACENT CONSTRUCTION. PREPARE TO RECEIVE NEW
FINISHES. 2 INFILL WALL ASSEMBLY. INFILL TO BE FLUSH AND LEVEL WITH EXISTING ADJACENT CONSTRUCTION. INFILL TO HAVE LEAD LINING. 3 DOOR TO RECEIVE AUTO OPERATOR. PROVIDE ROUGH-IN. 4 PROVIDE
CARD READER ROUGH-IN. REFER TO ELECTRICAL DRAWINGS FOR COORDINATION. 6 "NURSE CALL -AUDIO STATION" DISPLAY. (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DWGS. FOR ROUGH-IN
AND CONDUIT SPECIFICATIONS. 7 "NURSE CALL -PULL SWITCH" DISPLAY. (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DWGS. FOR ROUGH-IN AND CONDUIT SPECIFICATIONS. 8 "PHILIPS
-CIRS RECON /COM CABINET". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 9 "PHILIPS -OPERATORS CONSOLE". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL
DRAWINGS. 10 "PHILIPS -TRIPP LITE UPS". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 11 "PHILIPS -TEAL ISOTRAN POWER UNIT". (OWNER FURNISHED AND OWNER INSTALLED).
REFER TO ELECTRICAL DRAWINGS. 12 ISOCENTER. "PHILIPS -BRILLIANCE GANTRY AND TABLE". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 13 RECESSED 10" x 10" x 4" JUNCTION
BOX FOR PHILIPS EQUIPMENT. REFER TO ELECTRICAL DRAWINGS. 14 "PHILIPS -GANTRY MAIN SERVICE DISCOUNT." (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 16 EXISTING
MEDICAL GAS ZONE VALVE. 17 15" DEEP LAMINATE (PL-2) COUNTER TOP w/(2) GROMMET LOCATIONS. LENGTH OF 6'-0". MOUNT AT 2'-10" AFF w/CONTINUOUS BLOCKING AND STRUCTURAL SUPPORTS. CENTER BELOW
WINDOW. CORNERS TO HAVE A 6" RADIUS. 18 MEDICAL GAS LOCATIONS. REFER TO ELEVATION 3/A400 AND PLUMBING DRAWINGS. 19 CHAIR RAIL. REFER TO FINISH SCHEDULE GENERAL NOTES. 20 PROVIDE BLOCKING
IN WALL FOR TV MOUNT FROM 6'-8" TO 8'-10" AFF. CENTER BETWEEN DOORS. 21 PROVIDE BLOCKING IN WALL FOR LEAD APRON RACK FROM 3'-6" TO 5'-6" AFF. 22 PROVIDE BLOCKING IN WALL FOR PATIENT
SLIDER RACK FROM 6'-4" TO 7'-8" AFF. 23 PREP EXISTING DOOR AND FRAME TO RECEIVE MAGLOCK OR ELECTRIC STRIKE. 24 NEW UPS SYSTEM. REFER TO ELECTRICAL DRAWINGS. 25 EXISTING WALL ASSEMBLY
w/LEAD LINING. PROTECT AS POSSIBLE. PATCH AND REPAIR TO MATCH EXISTING CONSTRUCTION WHERE NEW ARCHITECTURAL AND MEP ITEMS ARE REQUIRED TO BE INSTALLED. PREP ENTIRE WALL FOR NEW FINISHES.
26 EXTEND EXISTING WALL CONSTRUCTION TO DECK. EXISTING WALL CONSTRUCTION IS APPROXIMATELY 8'-0" AFF AND EXISTING SECOND FLOOR IS 16'-0" AFF. NEW WALL ASSEMBLY IS 1-HOUR FIRE RATED. APPLY
5/8" TYPE-X GYPSUM BOARD ON ENTIRE WALL FACE OF MRI SHELL 27 STANDARD CHAIN LINK FENCE AND 3'-0" w. SWING GATE. HEIGHT TO BE 8'-0" AFF w/TOP AND BOTTOM RAILS. PROVIDE LATCHING FROM BOTH
SIDES w/INTEGRAL EYE OPENINGS FOR PADLOCKING. CORE DRILL AND GROUT FOR POST. 2" DIA. POSTS. FIELD VERIFY EXACT LOCATION w/OWNER. Lower Level Key Plan Revisions: Date: By:
MRI SHELL B134 CONTROL B133 CORRIDOR B1C14 CORRIDOR B1C15 135B 135BA 135AA 129B 135A 129A 134A TLT PAT B135A DRESS B135B 129C CR CR CT IMAGING 2 B129 WAITING B135 A400 1 1 1 * 1-HR 4
4 11.3 12 13 JK 14 H 10 11 WAITING B120 CORRIDOR B1C01 120A 120B A300 1 MRI IMAGING 1 B132 LOCKERS B132 CT IMAGING 1 B128 TLT PAT B130A DRESS B130B IMAGING B133A WORK B133B STAIR B3-1
OFFICE B145 OFFICE B146 OFFICE B147 OFFICE B148 OFFICE B144 ES CLOSET B142 CORRIDOR B044D CORRIDOR B1C16 CONSULT B121 RECEPT B120A DRESS B123A WORK B120B OFFICE B113 CORRIDOR B1C17 LAB
C129 CONSTRUCTION LIMITS -BASE BID CONSTRUCTION LIMITS -BASE BIDALTERNATE No. 1 A A400 5 NC NC NC 67 7 12' -0" 20' -0" 30' -0" 6' -7" 5' -0" 10' -5" 6' -7" 8 9 10 11 1213 14 A400 3 16
16 AO AO AO 17 18 19 19 2 20 19 21 22 9.7 L CR 4 CR4 CR4 128B 132A 133B 23 23 23 3 3 3 3 25 25 25 1.5C 1.5B 1.5B 1.5E 1.5D 26 IMAGING C176 PROCEDURE C178 AO 3 AO 2 1.5D 1. LEAD SHIELDED
GLASS AND FRAME. 2. 1/4" FULLY-TEMPERED, CLEAR GLASS w/FROST FILM (DUSTED CRYSTAL). REFER TO SPECIFICATION APPENDIX FOR FILM PATTERN. 1. ALTERNATE No. 1: DOOR AND FRAME ASSEMBLY. 2.
DOOR TO BE POSITIVE LATCHING. 3. DOOR TO RECEIVE AUTO OPERATOR. 4. DOOR TO RECEIVE SECURITY CARD READER. 5. LEAD LINED DOOR AND FRAME. 6. DOOR TO BE DUAL-SWING w/SET PIVOTS. 7. GLAZING
TO HAVE SAFETY IDENTIFICATION LABEL PER INDIANA BUILDING CODE 2406.2. 8. ALTERNATE No. 2: CLOSET AT TRANSITION No. K120. F F1 1' -0" 6" DOOR HEIGHT 6" 6" DOOR WIDTH 1' -6" 4' -0" DOOR
HEIGHT F2 2 1 2 DUAL-SWING DOOR FRAME A LEAD LINED WINDOW TO RECEIVE STANDARD MINI-BLINDS. 5' -8" 3' -4" 3' -10" 3 ALTERNATE No. 1 1 2" LEAD LINED METAL FRAME 3/A201 6/A201 DOOR WIDTH
9' -8" (FIELD VERIFY EXISTING OPENING) 2 1' -0" REFER TO PARTITION TYPE FOR WALL CONSTRUCTION (EXTRA LAYER OF 1/2" GYP. BOARD) DOUBLE 3 5/8" METAL STUD FRAMING CONTINUOUS SEALANT (BOTH
SIDES) HOLLOW MTL. DOOR FRAME SEE SCHEDULE 2" REFER TO PARTITION TYPE FOR WALL CONSTRUCTION DOUBLE 3 5/8" METAL STUD FRAMING CONTINUOUS SEALANT (BOTH SIDES) HOLLOW MTL. DOOR FRAME SEE
SCHEDULE 2" REFER TO PARTITION TYPE FOR WALL CONSTRUCTION (EXTRA LAYER OF 1/2" GYP. BOARD) DOUBLE 3 5/8" MTL. STUD FRAMING CONTINUOUS SEALANT (BOTH SIDES) HOLLOW MTL. DOOR FRAME 5 3/8"
REFER TO PARTITION TYPE FOR WALL CONSTRUCTION DOUBLE 3 5/8" MTL. STUD FRAMING CONTINUOUS SEALANT (BOTH SIDES) HOLLOW MTL. DOOR FRAME REFER TO PARTITION TYPE FOR WALL CONSTRUCTION HOLLOW
MTL. FRAME (LEAD LINED) CONTINUOUS SEALANT (BOTH SIDES) LEAD SHIELDED GLASS REFER TO PARTITION TYPE FOR WALL CONSTRUCTION DOUBLE 3 5/8" MTL. STUD FRAMING CONTINUOUS SEALANT (BOTH SIDES)
HOLLOW METAL FRAME (LEAD LINED) DC 120C TRANSITION CLASSROOM K120 ALTERNATE No. 2 1.5B 1.5B +/-5' -0" ALIGN w/CEILING GRID PAINT WALLS. PROVIDE RUBBER BASE. NEW CEILING GRID. +/-8' -4"
DUST SEPARATION WALLS. REFER TO NOTE 1/A101. COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document
are the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details
shall be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain
copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204
voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:31 PM 11700 North Meridian Street, Carmel, Indiana 46032 !" #1/8"
= 1'-0" First Floor Plan First Floor Key Plan Specific Plan Notes 1 INFILL WALL, FLOOR, AND CEILING OPENING. INFILL TO BE FLUSH AND LEVEL WITH EXISTING ADJACENT CONSTRUCTION. PREPARE
TO RECEIVE NEW FINISHES. 2 INFILL WALL ASSEMBLY. INFILL TO BE FLUSH AND LEVEL WITH EXISTING ADJACENT CONSTRUCTION. INFILL TO HAVE LEAD LINING. 3 DOOR TO RECEIVE AUTO OPERATOR. PROVIDE
ROUGH-IN. 4 PROVIDE CARD READER ROUGH-IN. REFER TO ELECTRICAL DRAWINGS FOR COORDINATION. 6 "NURSE CALL -AUDIO STATION" DISPLAY. (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL
DWGS. FOR ROUGH-IN AND CONDUIT SPECIFICATIONS. 7 "NURSE CALL -PULL SWITCH" DISPLAY. (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DWGS. FOR ROUGH-IN AND CONDUIT SPECIFICATIONS.
8 "PHILIPS -CIRS RECON /COM CABINET". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 9 "PHILIPS -OPERATORS CONSOLE". (OWNER FURNISHED AND OWNER INSTALLED). REFER
TO ELECTRICAL DRAWINGS. 10 "PHILIPS -TRIPP LITE UPS". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 11 "PHILIPS -TEAL ISOTRAN POWER UNIT". (OWNER FURNISHED AND
OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 12 ISOCENTER. "PHILIPS -BRILLIANCE GANTRY AND TABLE". (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL DRAWINGS. 13 RECESSED
10" x 10" x 4" JUNCTION BOX FOR PHILIPS EQUIPMENT. REFER TO ELECTRICAL DRAWINGS. 14 "PHILIPS -GANTRY MAIN SERVICE DISCOUNT." (OWNER FURNISHED AND OWNER INSTALLED). REFER TO ELECTRICAL
DRAWINGS. 16 EXISTING MEDICAL GAS ZONE VALVE. 17 15" DEEP LAMINATE (PL-2) COUNTER TOP w/(2) GROMMET LOCATIONS. LENGTH OF 6'-0". MOUNT AT 2'-10" AFF w/CONTINUOUS BLOCKING AND STRUCTURAL
SUPPORTS. CENTER BELOW WINDOW. CORNERS TO HAVE A 6" RADIUS. 18 MEDICAL GAS LOCATIONS. REFER TO ELEVATION 3/A400 AND PLUMBING DRAWINGS. 19 CHAIR RAIL. REFER TO FINISH SCHEDULE GENERAL
NOTES. 20 PROVIDE BLOCKING IN WALL FOR TV MOUNT FROM 6'-8" TO 8'-10" AFF. CENTER BETWEEN DOORS. 21 PROVIDE BLOCKING IN WALL FOR LEAD APRON RACK FROM 3'-6" TO 5'-6" AFF. 22 PROVIDE BLOCKING
IN WALL FOR PATIENT SLIDER RACK FROM 6'-4" TO 7'-8" AFF. 23 PREP EXISTING DOOR AND FRAME TO RECEIVE MAGLOCK OR ELECTRIC STRIKE. 24 NEW UPS SYSTEM. REFER TO ELECTRICAL DRAWINGS. 25 EXISTING
WALL ASSEMBLY w/LEAD LINING. PROTECT AS POSSIBLE. PATCH AND REPAIR TO MATCH EXISTING CONSTRUCTION WHERE NEW ARCHITECTURAL AND MEP ITEMS ARE REQUIRED TO BE INSTALLED. PREP ENTIRE WALL
FOR NEW FINISHES. 26 EXTEND EXISTING WALL CONSTRUCTION TO DECK. EXISTING WALL CONSTRUCTION IS APPROXIMATELY 8'-0" AFF AND EXISTING SECOND FLOOR IS 16'-0" AFF. NEW WALL ASSEMBLY IS 1-HOUR
FIRE RATED. APPLY 5/8" TYPE-X GYPSUM BOARD ON ENTIRE WALL FACE OF MRI SHELL 27 STANDARD CHAIN LINK FENCE AND 3'-0" w. SWING GATE. HEIGHT TO BE 8'-0" AFF w/TOP AND BOTTOM RAILS. PROVIDE
LATCHING FROM BOTH SIDES w/INTEGRAL EYE OPENINGS FOR PADLOCKING. CORE DRILL AND GROUT FOR POST. 2" DIA. POSTS. FIELD VERIFY EXACT LOCATION w/OWNER. Glazing Schedule Door Remarks Door
Elevations Frame ElevationsDOOR AND OPENING SCHEDULE Opening No. Door Frame Details Label Door Glass Hdw. Size Mat. Ele. Mat. Ele. Head Jamb Set Remarks First Floor Slab 120A 4'-0" x
7'-0" x 1 3/4" WD F1 HM 3 1/A201 4/A201 ---2 ---1, 2, 3, 7 120B 4'-0" x 7'-0" x 1 3/4" WD F HM 1 1/A201 4/A201 ---------1, 2, 3, 7 120C (1) 4'-0" x 7'-0" x 1-3/4" and (1) 1'-6" x 7'-0"
x 1-3/4" WD F2 HM 1 2/A201 5/A201 ---------8 129A 3'-0" x 7'-0" x 1 3/4" WD F HM 1 2/A201 5/A201 LEAD LINED ------5 129B (1) 4'-0" x 7'-0" x x 1-3/4" and (1) 1'-6" x 7'-0" x 1-3/4" WD
F2 HM 1 1/A201 4/A201 LEAD LINED ------2, 4, 5 129C 4'-0" x 7'-0" x 1 3/4" WD F HM 1 2/A201 5/A201 LEAD LINED ------5 134A 4'-0" x 7'-0" x 1 3/4" WD F HM 1 1/A201 4/A201 45 MIN. ------2
135A 4'-0" x 7'-0" x 1 3/4" WD F HM 1 1/A201 4/A201 ---------2, 4 135AA 4'-0" x 7'-0" x 1 3/4" WD F HM 2 2/A201 5/A201 ---------6 135B 3'-0" x 7'-0" x 1 3/4" WD F HM 1 2/A201 5/A201
---------135BA 3'-0" x 7'-0" x 1 3/4" WD F HM 2 2/A201 5/A201 ---------6 1 1/2" = 1'-0" 1 Head Detail 1 1/2" = 1'-0" 2 Head Detail 1 1/2" = 1'-0" 4 Jamb Detail 1 1/2" = 1'-0" 5 Jamb
Detail 1 1/2" = 1'-0" 3 Head /Sill Detail 1 1/2" = 1'-0" 6 Jamb Detail NOTE: REFER TO PLAN NOTE No. 23 ON FIRST FLOOR PLAN FOR WORK TO BE PERFORMED ON EXISTING DOOR AND FRAME Nos. B128B,132A,
AND B133B. DOORS TO RECEIVE STOREROOM LOCKSET. 1/8" = 1'-0" First Floor Plan (Partial) -Alternate No. 2 Revisions: Date: By:
11.3 12 13 J K 14 H 10 11 CONSTRUCTION LIMITS -BASE BID 9.7 TRASH RM B040 LINEN SERV B039 CORRIDOR B0C13 CORRIDOR B0C12 ELEV LOBBY B0C16 TELECOM B041 ELEVATOR 10 ELEVATOR 11 CORRIDOR
C0C15 CORRIDOR B0C11 STAIR B3-LL CARTS CORRIDOR C042 C0C16 STORAGE RECEIVING DOC C041 C039 RECEIVING C033D CENTRAL PROCESSING C033 TRASH C040 CLASS C043 CONSTRUCTION LIMITS -BASE BID
L 7 9 TYP. 88 SMOKE PARTITION SMOKE BARRIER WALL -1-HOUR (20 MIN. OPENING) 1-HOUR RATED FIREWALL (45 MIN. OPENING) 2-HOUR RATED FIREWALL (90 MIN. OPENING) A400 1 A400 4 11.3 12 K 11
15 8 439 6 2 9 TLT PAT B135A DRESS B135B 135BA 135AA A400 3 2 CT IMAGING 2 B129 WAITING B135 129B 135A 129A (2) 9 (2) 9 7 8 5 10 11 12 12 12 13 14 15 1' -7 3/4" +/-5' -7 1/4" 9' -4"
1' -1" 16 ALIGN 1.5D 1.5B 1.5B 1.5E 17" MIN. 2'-10" MAX. 2'-3" MIN. 8" 6" 9" 2'-5" MIN. 6" 12" MIN. 24" MIN. 1' -6" 33" -36" 17" -19" 15" MIN. WATER CLOSET SIDE WALL WATER CLOSET BACK
WALL TOILET PAPER MOUNTING AREA LAVATORY OR VANITY SINK 54" MIN. 42" MIN. 12" MAX. MIN. 1 1/2" 15" MIN. 8" 36" MIN. TO OPERATOR 4' -2 15/32" MAX. SOAP DISPENSER TO OPERATOR 48" MAX.
MIRROR PAPER TOWEL DISPENSER ABOVE LAVATORIES, SINKS, OR COUNTERS 40" MAX. DIMENSION IS TO BOTTOM OF REFLECTIVE SURFACE 1. ACCESSORY PROVIDED AND INSTALLED BY CONTRACTOR. 2. ACCESSORY
PROVIDED AND INSTALLED BY OWNER. BLOCKING BY CONTRACTOR. VERIFY LOCATION WITH OWNER. COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans,
and details as shown on this document are the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts,
ideas, designs, plans, and details shall be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The
Owner shall be permitted to retain copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930
NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:33 PM 11700 North Meridian
Street, Carmel, Indiana 46032 $%&'#( !" #1/8" = 1'-0" Lower Level Reflected Ceiling Plan Specific Reflected Ceiling Plan Notes 1 GPYSUM BOARD BULKHEAD AT 7'-2" AFF. PAINT BOTTOM SIDE
OF BULKHEAD (P-1). 2 FRAME AND TOP-OUT EXISTING WALL FROM 8'-0" AFF TO DECK. WALL ASSEMBLY TO BE 1-HR FIRE RESISTANT. APPLY 5/8" TYPE-X GYPSUM BOARD ON ENTIRE WALL FACE OF MRI SHELL.
3 CONTRACTOR TO PROVIDE AND INSTALL UNISTRUT FRAMEWORK AND HARDWARE FOR OWNER FURNISHED MEDICAL EQUIPMENT (MEDRAD INJECTOR) AND MOUNTING PLATE. CONTRACTOR TO INSTALL MOUNTING PLATE.
REFER TO PHILIPS EQUIPMENT DRAWING SD-3 FOR SPECIFICATIONS AND DETAIL. 4 CONTRACTOR TO PROVIDE AND INSTALL UNISTRUT FRAMEWORK AND HARDWARE FOR OWNER FURNISHED AND INSTALLED MEDICAL EQUIPMENT
(CONTINUOUS CT) AND MOUNTING PLATE. CONTRACTOR TO INSTALL MOUNTING PLATE. REFER TO PHILIPS EQUIPMENT DRAWING SD-4 FOR SPECIFICATIONS AND DETAIL. 5 CEILING MOUNTED "NURSE CALL -DOME LIGHT
w/A & B" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED). CENTER OVER CORRESPONDING DOOR. REFER TO ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION. 6 WALL MOUNTED "NURSE
CALL -DOME LIGHT" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED). CENTER OVER CORRESPONDING DOOR AT 8'-0" AFF. REFER TO ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION.
7 ISOCENTER. "PHILIPS -BRILLIANCE GANTRY AND TABLE. 8 REMOVE EXISTING PORTION OF LAY-IN CEILING FOR INSTALLATION OF ELECTRICAL CONDUIT RUNS AS NEEDED. REINSTALL TILE AND GRID. PROTECT.
(HATCHED AREA). 9 EXISTING PLASTER SOFFIT w/CONTROL JOINTS AT 10'-0" o.c. CEILING HAS EXISTING ACCESS PANELS FOR ACCESSIBILITY TO UNDERSIDE OF FIRST FLOOR. 10 WALL MOUNTED "X-RAY IN-USE"
INDICATION LIGHT (CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED). CENTER OVER CORRESPONDING DOOR. REFER TO ELECTRICAL DWGS. NOTE: ALL CEILING HEIGHTS TO BE 8'-10" AFF, UNLESS OTHERWISE
NOTED. Wall Assembly Legend Lower Level Key Plan 1/4" = 1'-0" 1 Enlarged Floor Plan Standard Mounting Heights TOILET ACCESSORIES SCHEDULE NOTE: Manufacturer's numbers refer to "Bobrick
Co." unless noted otherwise, and are used for quality control only. They are not intended to limit bidding to one manufacturer. Item Accessory Description MFG'S # Remarks 1 SINGLE WALL
GRAB BAR -42" B-6806x42 1 2 SINGLE WALL GRAB BAR -36" B-6806x36 1 3 SINGLE VERTICAL GRAB BAR -18" B-6806x18 1 4 MULTI-ROLL TOILET TISSUE DISPENSER B-2740 1 5 SURFACE MOUNTED SOAP DISPENSER
STERIS SDS
2 6 24" x 36" MIRROR B-165 2436 1 7 24" x 72" MIRROR B-165 2472 1 8 SURFACE MOUNTED PAPER TOWEL DISPENSER Georgia-Pacific enMotion 2 9 ROBE HOOK B-76717 1 10 LEAD APRON RACK HOLDER RayShield/AADCO
R-513B 1 11 PATIENT MOVER HANGER AADCO N-537 2 12 HAND SANITIZER DISPENSER Purell Instant 2 13 SHARPS DISPOSAL CONTAINER Daniels 2 14 GLOVE BOX HOLDER Medline BOWGW055 2 15 SEAT COVER
DISPENSER B-4221 1 16 RECESSED SANITARY NAPKIN RECEPTACLE B-353 1 Revisions: Date: By:
CONSTRUCTION LIMITS -BASE BID A.F.F. 9' -0" 1 1 2 11.3 12 13 JK 14 H 10 116' -7 1/2" 6' -7" 1' -2" 4' -5" 6' -11" CONSTRUCTION LIMITS -BASE BID ALTERNATE No. 1 3 4 5 6 6 440 SF CT IMAGING
2 B129 66 SF DRESS B135B 67 SF TLT PAT B135A 190 SF WAITING B135 CONTROL B133 MRI SHELL B134 WAITING B120 9.7 L 5 10 10 10 8 8 8 SMOKE PARTITION SMOKE BARRIER WALL -1-HOUR (20 MIN. OPENING)
1-HOUR RATED FIREWALL (45 MIN. OPENING) 2-HOUR RATED FIREWALL (90 MIN. OPENING) 11.3 12 JK H 10 11 SV-2 SV-1 SV-2 SV-1 SV-2 SV-2 SV-2 SV-2 SV-1 SV-1 SV-1 SV-1 EXIST (INFILL) (INFILL)
EXIST SV-1 PT-1 CPT-1 CPT-1 CPT-1 DRESS B135B TLT PAT B135A WAITING B135 CT IMAGING 2 B129 SV-1/SV-2 CPT-1 CG EXIST (INFILL) (INFILL) EXIST INFILL RAIL/BASE AS REQUIRED FOR CONTINUOUS
BUMPER AND RAIL. PATCH WALL w/VINYL WALLCOVERING (VW-C1) MRI IMAGING 1 B132 LOCKERS B132 CT IMAGING 1 B128 TLT PAT B130A DRESS B130B WORK B133B CORRIDOR B1C16 CONSULT B121 RECEPT B120A
DRESS B123A WORK B120B CONSTRUCTION LIMITS -BASE BID CONSTRUCTION LIMITS -BASE BIDALTERNATE No. 1 WAITING B120 CONTROL B133 MRI SHELL B134 EXIST CPT-1 EXIST CPT-2 EXIST CPT-2 EXIST CPT-1
INFILL CARPET INFILL CARPET INFILL RAIL/BASE AS REQUIRED FOR CONTINUOUS BUMPER AND RAIL. PATCH WALL w/VINYL WALLCOVERING (VW-C1). CHAIR RAIL CHAIR RAILCHAIR RAIL REFINISH WALL AND PAINT.
9.7 L CORRIDOR B1C14 CORRIDOR B1C15 CORRIDOR B1C01 FLOORS CARPET CPT-1 -INTERFACE. ZEN (1 m VINYL BACK TILE) #1666109700. COLOR: #2098 WILLOW. CPT-2 -LEES. DESIGN CONNECT #DG163. COLOR:
#502 BRICK. PORCELAIN TILE PT-1 -CROSSVILLE. EMPIRE SERIES 14" x 14". COLOR: VS81 PALAIS TAUPE. SHEET VINYL SV-1 -TEKNOFLOR. 52202. COLOR: HARVEST CHERRY. SV-2 -TEKNOFLOR. 52207. COLOR:
LIGHT MAPLE. BASES PORCELAIN BASE TILE PBT-1 -CROSSVILLE. EMPIRE SERIES 6" x 14" COVE BASE. COLOR: VS81 PALAIS TAUPE. RUBBER BASE RB-1 -JOHNSONITE. 4" HIGH COVED #29. COLOR: MOON ROCK.
WALLS CERAMIC TILE CT-1 -AMERICAN OLEAN. 6"x6" WALL TILE. #51 MATTE VANILLA. CT-2 -CROSSVILLE -QUESTTECH METALS -3/4" x 12" TRIM NUMBER 042-055-001. GLASS TILE GT-1 -HAKATAI GLASS MOSAIC
TILE -AVENTURINE LUX SERIES KS33 ARCHIPELAGO. WALLS (...continued) PAINTP-1 -SHERWIN WILLIAMS. #SW6378. COLOR: CRISP LINEN. P-2 -SHERWIN WILLIAMS. #SW6113. COLOR: INTERACTIVE CREAM.
P-3 -SHERWIN WILLIAMS. #SW6191. COLOR: CONTENTED. VINYL WALLCOVERING VW-C1 -MDC WALLCOVERING -STYLE: VYCON OASIS #449150A -COLOR: GRASSCLOTH. VW-C2 -JM LYNNE -STYLE: ZOONI #ZOON-005
-COLOR: GALLINO. CEILINGS ACCOUSTICAL TILE ACT-1 -ARMSTRONG. "DUNE, FINE TEXTURED." 24" x 24" #1772 -COLOR: WHITE CASEWORK SOLID SURFACE SS-1 -CORIAN -COUNTER TOPS, 3/4" THICK MATERIAL,
COLOR: FOSSIL. PLASTIC LAMINATE PL-1 -PIONITE -SUEDE #WC431-S, COLOR: MILLWORK CHERRY. PL-2 -FORMICA -MATTE FINISH #7698-58, COLOR: ASHEN CERAMIC. -INDICATES NEW BUMP RAIL /GUARD RAIL
(REFER TO DETAIL 7/A400). -INDICATES NEW CHAIR RAIL (REFER TO REMARKS NOTE No. 9). 1. ALL BULKHEADS AND DRYWALL CEILINGS SHALL BE PAINTED (P-1) UNLESS OTHERWISE NOTED. 2. ALL METAL DOOR
FRAMES SHALL BE (P-2). 3. ALL FLOORING METERIAL TRANSITIONS SHALL BE CENTERED UNDER THE DOOR JAMB. 4. TRANSITION BETWEEN CARPET AND SHEET VINYL TO BE SCHULTER SCHIENE #YPE AS-80 ANODIZED
ALUMINUM. 5. ALL CARPET TILE TO BE INSTALLED AT 45 DEGREE ANGLE. QUARTER TURN AS RECOMMENDED MY MANFACTURER. 6. ALL GROUT TO BE XT SANDED GROUT. -FLOOR GROUT TO BE TEC COLOR 915 LIGHT
SMOKE, AND WALL GROUT TO BE TEC COLOR 902 IVORY. 7. 2" w. CORNER GUARD (CG): 12 ga. STAINLESS STEEL w/RADIUSED CORNER AND EDGES. HEIGHT TO BE 6'-8". SILICONE APPLIED. 8. SHEET VINYL
TO BE INSTALLED WITH WOOD GRAIN RUNNING IN NORTH/SOUTH DIRECTION. 9. CHAIR RAIL TO BE CHERRY HARDWOOD w/#WM 430 PROFILE (9/16" x 4 1/4"). STAIN TO MATCH DOOR. COUNTERSINK FASTNERS w/PLUGS
TO MATCH RAIL. MOUNT AT 2'-8 1/2" AFF -CENTER. 1. TOILET ROOM PORCELAIN FLOOR TILE TO BE INSTALLED AT 45 DEGREE ANGLE. 2. REFER TO 6/A400 FOR TOILET ROOM ELEVATION. DETAIL OCCURS ON
ALL WALLS. 3. DECORATIVE WALL MIRROR AT SINGLE SINK. OVERALL DIMENSION OF MIRROR IS 24"x36". PROVIDE FRAME IN 2" WIDTH. CENTER MIRROR OVER SINK. MOUNT BOTTOM AT 3'-2" AFF. -FRAME TO
BE ROMA #35033085 IN TOILET ROOMS. 4. FINISH TOUCH UP REQUIRED (WALL, FLOOR, OR CEILING). MATCH NEW FINISH TO EXISTING. REPAIR ANY AREAS DAMAGED DURING CONSTRUCTION. 5. REPAIR, PATCH,
OR INFILL EXISTING FINISHES FOLLOWING NEW DOOR AND FRAME OR NEW INFILL. COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details
as shown on this document are the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas,
designs, plans, and details shall be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner
shall be permitted to retain copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH
MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/19/2010 7:32:06 AM 11700 North Meridian Street,
Carmel, Indiana 46032 !"#$ 1/8" = 1'-0" First Floor Reflected Ceiling Plan First Floor Key Plan Specific Reflected Ceiling Plan Notes 1 GPYSUM BOARD BULKHEAD AT 7'-2" AFF. PAINT BOTTOM
SIDE OF BULKHEAD (P-1). 2 FRAME AND TOP-OUT EXISTING WALL FROM 8'-0" AFF TO DECK. WALL ASSEMBLY TO BE 1-HR FIRE RESISTANT. APPLY 5/8" TYPE-X GYPSUM BOARD ON ENTIRE WALL FACE OF MRI SHELL.
3 CONTRACTOR TO PROVIDE AND INSTALL UNISTRUT FRAMEWORK AND HARDWARE FOR OWNER FURNISHED MEDICAL EQUIPMENT (MEDRAD INJECTOR) AND MOUNTING PLATE. CONTRACTOR TO INSTALL MOUNTING PLATE.
REFER TO PHILIPS EQUIPMENT DRAWING SD-3 FOR SPECIFICATIONS AND DETAIL. 4 CONTRACTOR TO PROVIDE AND INSTALL UNISTRUT FRAMEWORK AND HARDWARE FOR OWNER FURNISHED AND INSTALLED MEDICAL EQUIPMENT
(CONTINUOUS CT) AND MOUNTING PLATE. CONTRACTOR TO INSTALL MOUNTING PLATE. REFER TO PHILIPS EQUIPMENT DRAWING SD-4 FOR SPECIFICATIONS AND DETAIL. 5 CEILING MOUNTED "NURSE CALL -DOME LIGHT
w/A & B" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED). CENTER OVER CORRESPONDING DOOR. REFER TO ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION. 6 WALL MOUNTED "NURSE
CALL -DOME LIGHT" INDICATION LIGHT (OWNER FURNISHED AND OWNER INSTALLED). CENTER OVER CORRESPONDING DOOR AT 8'-0" AFF. REFER TO ELECTRICAL DWGS FOR ROUGH-IN AND CONDUIT INFORMATION.
7 ISOCENTER. "PHILIPS -BRILLIANCE GANTRY AND TABLE. 8 REMOVE EXISTING PORTION OF LAY-IN CEILING FOR INSTALLATION OF ELECTRICAL CONDUIT RUNS AS NEEDED. REINSTALL TILE AND GRID. PROTECT.
(HATCHED AREA). 9 EXISTING PLASTER SOFFIT w/CONTROL JOINTS AT 10'-0" o.c. CEILING HAS EXISTING ACCESS PANELS FOR ACCESSIBILITY TO UNDERSIDE OF FIRST FLOOR. 10 WALL MOUNTED "X-RAY IN-USE"
INDICATION LIGHT (CONTRACTOR FURNISHED AND CONTRACTOR INSTALLED). CENTER OVER CORRESPONDING DOOR. REFER TO ELECTRICAL DWGS. Wall Assembly Legend ROOM FINISH SCHEDULE Room No. Name Floor
Base Walls N E S W Ceiling Remarks B1C01 CORRIDOR CPT-1/CPT-2 RB-1 ---VWC-1 ---VWC-1 GYP. BD. 4, 5 (PATCH AND REPAIR) ALTERNATE No. 1 B1C14 CORRIDOR CPT-1 RB-1 ---VWC-1 ---VWC-1 ACT-1
4, 5 (PATCH AND REPAIR) ALTERNATE No. 1 B1C15 CORRIDOR CPT-1 RB-1 ---VWC-1 ---VWC-1 ACT-1 4, 5 (PATCH, REPAIR, AND INFILL) B041 TELECOM VCT-1 RB-1 P-1 P-1 P-1 P-1 DECK 4 (PATCH AND REPAIR)
B120 WAITING CPT-1/CPT-2 RB-1 ---VWC-2 ---VWC-2 ACT-1 4, 5 (PATCH, REPAIR, AND INFILL) ALTERNATE No. 1 B129 CT IMAGING 2 SV-1 /SV-2 RB-1 VWC-2 VWC-2 VWC-2 VWC-2 ACT-1 B133 CONTROL CPT-1
RB-1 ---P-1 ---P-1 ACT-1 4, 5 (PATCH, REPAIR, AND INFILL) B134 MRI SHELL NO FLOOR ------------------B135 WAITING CPT-1 RB-1 VWC-1 VWC-1 VWC-1 VWC-1 ACT-1 4, 5 B135A TLT PAT PT-1 PBT-1
CT-1 /P-3 CT-1 /P-3 CT-1 /P-3 CT-1 /P-3 ACT-1 1, 2, 3 B135B DRESS CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1 1/8" = 1'-0" 3 First Floor Finish Plan Material Legend General Finish Remarks Specific
Finish Remarks NOTE: ALL CEILING HEIGHTS TO BE 8'-10" AFF, UNLESS OTHERWISE NOTED. Revisions: Date: By:
BULKHEAD 7' -0" 2" 1' -6" FLIP TOP BENCH 24" DEEP 24" DEEP REVEAL CONTINUOUS HINGE 2' -0" 4' -0" 7' -0" (5) ADJUSTABLE SHELVES 8 A400 BULKHEAD SINK REMOVABLE PANEL REVEAL 14" DEEP BACKSPLASH
24" DEEP 24" DEEP 24" DEEP 33" CLEAR SPACE BULKHEAD 2' -0" 2' -0" 14" DEEP 9 A400 1" 2' -0" 2' -0" 2' -0" 3' -0" A 3' -6" 3' -8" 7' -2" WINDOW TO RECEIVE MINI-BLINDS. 129B A O V S WAG
B NO 4' -6" 11' -0" 4' -6" (2) COAT HOOKS LEAD APRON RACK 2' -10" 2' -1" STAINLESS STEEL SINKBOWL REFER TO PLUMBING DRAWINGS. SOLID-SURFACE TURN-DOWN (SS-1) LINE OF WALL BEYOND 4" SOLID-SURFACE
BACKSPLASH (SS-1) AT ALL WALL SURFACES. PROVIDE 1 1/2" RADIUS AT ENDS. 3/4" LAMINATE APRON 3/4" LAMINATE ACCESS PANEL ON Z-CLIPS. CONCEAL FASTNERS. (2) 3/4" LAMINATE END PANEL -BOTH
SIDES. (MAINTAIN 30" CLEAR DIMENSION -33" OVERALL). 2' -5" 6" 1/2" RADIUS RUBBER BASE. LINE OF WALL BEYOND CHERRY HARDWOOD BUMP RAIL w/CLEAR FINISH AND 1/4" RADIUS EDGES. ANCHOR AT 4'-0"
o.c. MAX. COUNTERSINK FASTNERS w/PLASTIC PLUGS TO MATCH RAIL. RUBBER BASE 2x6 FIRE TREATED WOOD BLOCKING BETWEEN STUDS OR 16 ga. 6" WIDE ANCHOR STRIPS. 1' -0" 1' -10" 8" 2" 4" 2" 6"
2" 2" 2" CHERRY HARDWOOD BUMP RAIL w/CLEAR FINISH AND 1/4" RADIUS EDGES. ANCHOR AT 4'-0" o.c. MAX. COUNTERSINK FASTNERS w/PLASTIC PLUGS TO MATCH RAIL. 2x6 FIRE TREATED WOOD BLOCKING
BETWEEN STUDS OR 16 ga. 6" WIDE ANCHOR STRIPS. 1' -6" 2' -0" CONTINUOUS HINGE 3/4" PLASTIC LAMINATE PLYWOOD (ALL EXPOSED SIDES AND INTERIOR) RUBBER BASE BULKHEAD 24" DEEP 24" DEEP REVEAL
2' -0" 3' -0" 2' -0" 1" 7' -0" 2" 1' -10" 3" 4' -5" (PBT-1) 3" x 14" (CT-1) 6" x 6" (CT-2) 3/4" x 12" (GT-1) -4 ROWS OF MOSAICS (CT-2) 3/4" x 12" P-X 1. CONTRACTOR SHALL PROVIDE WOOD
BLOCKING AS REQUIRED FOR INSTALLATION OF ALL UPPER AND LOWER UNITS AND STRSUUCPTPUORRATLS . 2. ALL CASEWORK SHALL BE CONSTRUCTED PER SPECIFICATIONS. 3. CABINET MFG. SHALL COORDINATE
WITH OWNER ALL LOCATIONS FOR "GROMMETS." PROVIDE APPROXIMATELY ONE GROMMET PEFRE 3E TL IONEFAL COUNTERTOP. 4. PLASTIC LAMINATE SHALL BE APPLIED TO ALL EXPOSED CASEWORK SURFACES ON BOTH
NEW AND EXISTING RELOCATED UNITS RFEIQNIUSIHREINDG S URFACES. 5. APPLY 1 1/2" RADIUS ON ALL OUTSIDE CORNERS OF COUNTERTOPS UNLESS OTHERWISE NOTED. 6. ALL END PANEL SUPPORT SHALL BE CONSTRUCTED
WITH 1 1/2" LAMINATED PARTICLE BOARD. 7. ALL COUNTER TOPS SHALL EXTEND 1" BEYOND BASE CABINET. 8. ALL BASE CABINET DEPTH SHALL BE 24" UNLESS NOTED OTHERWISE. 9. ALL UPPER CABINET DEPTH
SHALL BE 14" UNLESS NOTED OTHERWISE. 10. APPLY 4" HIGH BACKSPLASH AT PERIMETER OF ALL COUNTER TOPS. 11. APPLY (1) ADJUSTABLE SHELF IN ALL BASE UNITS, AND (2) ADJUSTABLE SHELVES IN ALL
UPPER UNITS WITH EXCEPTION OF SINK BASE UNITS, UNLESS NOTED OTHERWISE. 12. ALL BASE UNITS SHALL HAVE A 4" h. x 3" d. TOE SPACE WITH RUBBER BASE BY FLOORING CONTRACTOR. 13. REFER TO FLOOR
PLAN FOR ALL WALL PARTITION TYPES. 14. ALL COUNTERTOPS WITH SINKS TO BE SOLID SURFACE. ALL OTHERS TO BE PLASTIC LAMINATE WRAPPED PARTICLE BOARD UNLESS NOTED OTHERWISE. 15. REFER TO SPECIFICATIONS
FOR DRAWERS AND DOOR HANDLES. 16. ALL HINGES SHALL BE 5-KNUCKLE EXPOSED. 17. P = PAPER TOWEL DISPENSER LOCATED AT EVERY SINK. SUPPLIED BY OWNER, INSTALLED BY GENERAL CONTRACTOR. 18.
L = DOOR TO BE LOCKED WITH KEY CYLINDER. COORDINATE WITH OWNER ON KEYING REQUIREMENTS. 19. UL = UNDER UPPER CABINET LIGHT. APPLY 2" LAMINATED APRON. 20. S = PLASTIC LAMINATED STRUCTURAL
SUPPORT SUPPORT FOR COUNTER AND/OR RECEPTION DESK. PROVIDED SUPPORT AT 40" o.c. 21. AP = REMOVABLE ACCESS PANEL. PROVIDE COUNTERSUNK ANCHORS. 22. G = GROMMETS, VERIFY LOCATION WITH OWNER.
(PROVIDE 1 PER 4 LINEAL FT. OF COUNTER). COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are
the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall
be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies
copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204
voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:36 PM 11700 North Meridian Street, Carmel, Indiana 46032 $) *%
!" #1/2" = 1'-0" 4 Casework Elevation 1/2" = 1'-0" 1 Casework Elevation 1/2" = 1'-0" 5 Interior Elevation 1/2" = 1'-0" 3 Interior Elevation 1 1/2" = 1'-0" 9 Casework Detail 1 1/2" =
1'-0" 7 Bump Rail Detail 1 1/2" = 1'-0" 8 Casework Detail 1/2" = 1'-0" 2 Interior Elevation 1/2" = 1'-0" 6 Typical Toilet Elevation General Casework Notes CIRS OPERATORS CONSOLE TRIPP
LITE UPS EPO PATIENT SLIDER HANGER UL AP Revisions: Date: By:
NOTE: ALL SYMBOL DESCRIPTIONS ARE SUBJECT TO MODIFICATION ON THE DRAWINGS. ALL SYMBOLS ARE NOT NECESSARILY USED ON THIS PROJECT DUCTWORK: VALVES: SUPPLY DIFFUSER: RETURN /EXHAUST GRILLE:
LINEAR SLOT DIFFUSER: FITTINGS & MISCELLANEOUS ACCESSORIES: GENERAL SYMBOLS: PIPING: MECHANICAL /PLUMBING ABBREVIATIONS: GENERAL MECHANICAL /PLUMBING NOTES: EQUIPMENT: I OFTUS E INC.
REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian Street, Carmel, IN 46032
2009-059 CT #2 Lab Build Out 04-19-10 Symbols and Abbreviations MP001
LOWER LEVEL HVAC DEMOLITION PLAN I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center
11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 Lower Level HVAC Demolition Plan M101 13 J 14 H KEY PLAN PLAN NOTES:
FIRST FLOOR HVAC DEMOLITION PLAN PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North
Medical Center 11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 First Floor HVAC Demolition Plan M111 13 J 14 H KEY PLAN
LOWER LEVEL HVAC PLAN PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical
Center 11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 Lower Level HVAC PlanM201 13 J 14 H KEY PLAN
FIRST FLOOR HVAC PLAN PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical
Center 11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 First Floor HVAC PlanM211 13 J 14 H KEY PLAN
AIR TERMINAL UNIT SCHEDULE GRILLE/REGISTER AND DIFFUSER SCHEDULE HUMIDIFIER SCHEDULE I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233
M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 Schedules M500
STEAM TRAP DETAIL 1 DIRECT STEAM INJECTION HUMIDIFER DETAIL 2 2-WAY WATER COIL PIPING DETAIL 3 SUPPLY DIFFUSER DETAIL 8 RETURN/EXHAUST GRILLE DETAIL 4 AIR TERMINAL UNIT DETAIL 7 ROUND
DUCT TAKE-OFF DETAIL 5 BRANCH DUCT TAKE-OFF DETAIL 6 AIR TERMINAL CONTROL DIAGRAM 9 HUMIDIFIER CONTROL DIAGRAM 10 I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX:
(317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 Details M501
PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian
Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 Lower Level Plumbing Plan P201 13 J 14 H KEY PLAN Lower Level Plumbing Plan GENERAL NOTE:
PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian
Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 First Floor Plumbing Plan P211 13 J 14 H KEY PLAN First Floor Plumbing Plan WASTE PLUMBING FIXTURE ROUGH-IN SCHEDULE DESCRIPTION
ROUGH-IN CONNECTIONS HW CW VENT GENERAL NOTE:
PLAN NOTES: I OFTUS E INC. REA STREET SUITE 700 INDIANAPOLIS, NDIANA 46225 FAX: (317) 352-5821 NGINEERING, 233 M TEL: (317) 352-5822 L CC Clarian North Medical Center 11700 North Meridian
Street, Carmel, IN 46032 2009-059 CT #2 Lab Build Out 04-19-10 First Floor Medical Gas Plan P212 13 J 14 H First Floor Medical Gas Plan KEY PLAN
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:36 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:37 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:37 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:38 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:38 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:39 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:39 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:40 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:40 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:41 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By:
COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE CERTIFICATION The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates,
Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation
for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection
with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com
ARCHITECTURE ENGINEERING INTERIOR DESIGN !" !4/16/2010 2:59:41 PM 11700 North Meridian Street, Carmel, Indiana 46032 !+*,+ !" #Revisions: Date: By: