Through-penetration Firestop Systems System No. W -L-1049 September 24, 2004 F Ratings — 1 and 2 Hr (See Item 1B) T Rating — 0 H r L Rating At Ambient — Less Than 1 CFM/sq ft L Rating At 400 F — Less Than 1 CFM/sq ft 1. Wall A ssembly — The 1 or 2 hr fire-rated gypsum wallboard/stud w all assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series W all or Partition Design in the UL Fire R esistance D irectory and shall include the following construction features : A. Studs — W all framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 3-1/2 in. (89 mm) w ide and spaced m ax 24 in. (610 mm) OC. W hen steel studs are used and the d iam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the w all shall be 4 to 6 in. (102 to 152 mm) w ider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides. B. Gypsum B oard* — 5/8 in. (16 mm) thick, 4 ft (1.22 m ) w ide w ith square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance D irectory. M ax diam of opening is 26 in. (660 mm) for steel stud w alls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud w alls. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in w hich it is installed. 2. Through Penetrant — O ne metallic p ipe, conduit or tubing to be installed either concentrically or eccentrically w ithin the firestop system. P ipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between p ipe, conduit or tubing and periphery of opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to b e rigidly supported on both s ides of w all assembly. The following types and s izes of m etallic p ipes, conduits or tubing may be used: A. Steel P ipe — Nom 24 in. (610 mm) d iam (or smaller) Schedule 10 (or heavier) steel p ipe. B. Iron Pipe — Nom 24 in. (610 mm) d iam (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in. (102 mm) d iam (or smaller) steel electrical m etallic tubing, nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 1 in. (25 mm) d iam (or smaller) flexible steel conduit. D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe — Nom 6 in. (152 mm) d iam (or smaller) Regular (or heavier) copper p ipe. 3. Fill, V oid or C avity M aterial* — Sealant — Min 5/8 in. ((16 mm) thickness of fill material applied w ithin annulus, flush with both surfaces of wall. At the point contact location between through penetrant and gypsum board, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the gypsum board/through penetrant interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC — SpecSeal 100, 101, 102 or 105 Sealant *Bearing the UL Classification Mark Last Updated on 2004-09-24 Copyright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or p roduct in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be consid ered to be Listed and covered under UL's Follow-Up Service. Always look for the M ark on the product. UL permits the reproduction of the material contained in the Onlin e C ertification D irectory subject to the followin g conditions: 1 . The Guide Information, D esigns and/or Listings ( files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory w ith permission from Underwriters Laboratories Inc." must appear adjacent to th e extracted materia l. In addition, the reprinted m aterial must include a copyr ight notice in the following format: "Copyright © 2006 Underwriters Laborator ies Inc.®" Through-penetration Firestop Systems System No. F-C-2157 October 14, 2002 F Rating — 1 H r T R ating — 1 H r 1. Floor-Ceiling A ssembly — The 1 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series F loor-Ceiling D esigns in the UL F ire Resistance D irectory. The F R ating of the firestop system is equal to the ratings of the floor-ceiling and wall assemblies. The general construction features of the floor-ceiling assembly are summarized below: A. Flooring System — Lumber or p lywood subfloor w ith finish floor of lumber, p lywood or Floor Topping M ixture* as specified in the individual Floor-Ceiling Design. Diam of opening hole-sawed in flooring shall be max 1 in. larger than diam of branch p iping (Item 4). B. Wood Joists* — Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural W ood M embers* with bridging as required and with ends firestopped. C. Gypsum B oard* — Nom 4 ft. w ide by 5 /8 in. thick, attached as described in the individual F loor-Ceiling D esign. 2. Chase W all — The through-penetrant (Item 3) shall be routed through a 1 hr fire-rated s ingle, double or staggered w ood stud/gypsum w allboard chase w all constructed of the m aterials and in the manner specified in the individual U 300 Series W all and Partition D esigns in the UL Fire R esistance D irectory and shall include the following construction features: A. Studs — N om 2 by 6 in. or double nom 2 by 4 in. lumber studs. B. Sole Plate — N om 2 by 6 in. or parallel 2 by 4 in. lumber p lates, tightly butted. D iam of opening cut in sole p late shall be m ax 1 in. larger than d iam of through penetrant (Item 3). C. Top Plate — The double top p late shall cons ist of tw o nom 2 by 6 in. or two sets of p arallel 2 by 4 in. lumber p lates, tightly butted. D iam of opening cut in double top p late shall be m ax 1 in. larger than d iam of through penetrant (Item 3). D. Gypsum B oard* — Thickness, type, number of layers and fasteners shall be as specified in individual Wall or Partition D es ign. 3. Through Penetrant — One nonmetallic p ipe to be installed concentrically or eccentrically w ithin the firestop system. The annular space w ithin the opening shall be a m in 0 in. (point contact) to a m ax 1/2 in. P ipe m ay be installed in continuous point contact. The following types and s izes of nonmetallic p ipes may be used: A. Polyvinyl C hloride (PVC) Pipe — N om 4 in. d iam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or or vented (drain, w aste or vent) p iping system. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — N om 4 in. d iam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. C. Acrylonitrile B utadiene S tyrene (ABS) P ipe — Nom 4 in. d iam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) p iping sys tem. 4. Branch Piping — (Optional)— O ne nonmetallic pipe connected to through penetrant (Item 3) within concealed space above ceiling and installed w ithin opening in flooring. The annular space between the p ipe and the periphery of the opening shall be min 0 in. (point contact) to m ax 1/2 in. Pipe m ay be installed w ith continuous point contact. The follow ing types and sizes of nonmetallic p ipes may be used: A. Polyvinyl C hloride (PVC) Pipe — N om 4 in. d iam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, w aste or vent) p iping system. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — N om 4 in. d iam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system. C. Acrylonitrile B utadiene S tyrene — N om 4 in. d iam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, w aste or vent) p iping system. 5. Fill, V oid or C avity Material* — Sealant — M in 3/4 in. thickness of fill material applied w ithin annular space around perimeter of through penetrant (Item 3), flush w ith top surface of sole p late and flush w ith bottom surface of double top plate. Min 3/4 in. thickness of fill material applied w ithin annular space around branch p iping (Item 4), flush w ith top surface of flooring. At point contact locations within the chase wall assembly, apply m in 1/2 in. d iam bead of fill m aterial at nonmetallic pipe/wood p late interface on top and bottom surface of chase w all assembly. SPECIFIED TECHNOLOGIES INC — SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI Sealant *Bearing the UL Classification M ark Last Updated on 2002-10-14 Cop yright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or p roduct in this database does not in itself assure that products so identified have b een manufactured under UL's Follow-Up Service. Only those p rodu cts bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the M ark on the p roduct. UL permits the reproduction of the m aterial contained in the Onlin e C er tification D irectory subject to the following conditions: 1 . The Guide In formation, D esigns and/or Listings ( files) m ust be presented in their entirety and in a non-mis leading manner, w ithout any m anipulation of the data (or drawings). 2. The statement "Reprinted from the O nline Certifications Directory w ith permission from Underwr iters Laboratories Inc." must appear adjacent to th e extracted materia l. In addition, the repr inted m ater ial must include a copyright notice in the following format: "Cop yright © 2006 Underwriters Laborator ies Inc.®" Through-penetration Firestop Systems System N o. F-C-1010 December 11, 2001 F Ratings — 1 and 2 H r (See Item 1) T R atings — 1/2, 3/4, 1 and 1-1/2 H r (See Item 2) L Rating A t Ambient — Less Than 1 CFM/sq ft L Rating A t 400 F — Less Than 1 CFM/sq ft 1. Floor-Ceiling A ssembly — The 1 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the m anner specified in the individual L500 S eries F loor-Ceiling Des igns in the UL F ire R es istance D irectory. T he 2 hr fire-rated w ood joist floor-ceiling assembly shall be constructed of the materials and in the m anner specified in D es ign Nos. L505, L511 or L536 in the UL F ire Resistance D irectory. The F R ating of the firestop system is equal to the hourly fire rating of the floor-ceiling assembly. The general construction features of the floor-ceiling assembly are summarized below: A. Flooring System — Lumber or p lywood subfloor w ith finish floor of lumber, p lywood or Floor Topping M ixture* as specified in the individual Floor-Ceiling Design. Max diam of floor opening is 5 in. B. Wood Joists* — For 1 hr fire-rated floor-ceiling assemblies, nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural W ood Members* with bridging as required and w ith ends firestopped. For 2 hr fire-rated floor-ceiling assemblies, nom 2 by 10 in. lumber joists spaced 16 in. OC w ith nom 1 by 3 in. lumber bridging and w ith ends firestopped. C. Furring C hannels — (Not Shown) -In 2 hr fire-rated assemblies, resilient galv steel furring installed perpendicular to w ood jois ts between first and second layers of gypsum board (Item 1D ). Furring channels spaced max 24 in. OC. In 1 hr fire-rated assemblies, resilient g alv steel furring installed perpendicular to wood joists between gypsum board and w ood joists a s specified in the individual Floor-Ceiling D es ign. Furring channels spaced max 24 in. OC. D. Gypsum B oard* — N om 4 ft w ide by 5/8 in. thick as specified in the individual F loor-Ceiling D esign. F irst layer of gypsum board secured to w ood joists or furring channels as specified in the individual F loor-Ceiling Design. Second layer of gypsum board (2 hr firerated assembly) screw-attached to furring channels a s specified in the individual F loor-Ceiling Des ign. M ax diam of ceiling opening is 5 in. 2. Through Penetrants — One m etallic pipe, conduit or tube installed approxim ately midway betw een wood joists. Diam of openings holesawed through flooring sys tem and through gypsum board ceiling to be nom 1/2 in. greater than the outs ide diam of through-penetrant. F or 1 hr rated floor assemblies, through p enetrant to be installed either concentrically or eccentrically w ithin the opening with an annular space of 0 in. (point contact) to 1/2 in. F or 2 hr rated floor assemblies, through penetrant to b e centered in in the opening. P ipe, conduit or tube to be rigidly supported on both sides of floor-ceiling assembly. The following types and s izes of m eta llic p ipes, conduits or tubing m ay be used: A. Steel P ipe — N om 4 in. d iam (or smaller) Schedule 5 (or heavier) steel p ipe. B. Iron Pipe — Nom 4 in. diam (or smaller) cast or ductile iron pipe. C. Conduit — N om 4 in. d iam (or smaller) steel e lectrical metallic tubing or steel conduit. D. Copper Pipe — N om 4 in. d iam (or smaller) Regular (or heavier) copper p ipe. E. Copper Tubing — N om 4 in. d iam (or smaller) Type L (or heavier) copper tubing. The T Rating of the firestop system is dependent upon the hourly rating of the floor-ceiling assembly and type of through-penetrant used as shown in the table below: 3. Fill, V oid or C avity M aterial* — S ealant — F ill m aterial forced into annulus to fill space to max extent poss ible on top surface of floor and bottom surface of ceiling. M in 3/8 in. d iam bead of fill m aterial applied at point contact location on top surface of floor and on bottom surface of gypsum board ceiling. SPECIFIED TECHNOLOGIES INC — SpecSeal 100, 101, 102, 105, 120 or 129 Sealant *Bearing the UL Classification Mark Last Updated on 2001-12-11 Cop yright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so identified have b een manufa ctured under UL's Follow-Up S ervice. On ly those p roducts bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the M ark on the p roduct. UL perm its the reproduction of the m ater ial contained in the Onlin e Cer tification D irectory subject to the followin g conditions: 1 . The Guid e In formation, D esigns and/or L istings (files) must be presented in their entirety and in a non-mis lead ing m anner, w ithout any manipulation of the d a ta (or d rawings). 2 . The statement "Reprinted from the O n lin e C ertifications D irectory w ith permission from Und erwr iters Laborator ies In c." must appear adjacent to the extracted m ater ial. In addition, the reprinted m ateria l m ust in clude a copyr ight notice in the followin g format: "Copyr ight © 2006 Underwr iters Laboratories Inc.®" Through-penetration Firestop Systems System No. F-C-2204 December 07, 2001 F Rating — 1 Hr T Rating — 1/2 H r 1. Floor — C eiling A ssembly — The 1 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the m anner specified in the individual L500 Series Floor-Ceiling D es igns in theUL F ire Resistance Directory. The general construction features of the floor-ceiling assembly are summarized below: A. Flooring System — Lumber or p lywood subfloor w ith finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor-Ceiling D esign. R ectangular cutout in flooring to accommodate the bathtub drain piping (Item 2) to be m ax 8 in. by 12 in. Cutout to be patched on underside of subfloor using one layer of m in 3/4 in. thick plywood or m in 5/8 in. thick gypsum board (Item 1C) sized to lap m in 2 in. beyond each edge of rectangular cutout. Patch split into two p ieces at opening and hole-sawed for bathtub drain piping. Diam of opening hole sawed through patch to accommodate drain piping (Item 2) to be 1 in. larger than outside d iam of drain piping and positioned such that the annular space between drain p iping and periphery of opening is m in 0 in. (point contact) to m ax 1 in. Two pieces positioned around drain p iping, w ith cut edges tightly butted, and screw-attached to underside of subfloor w ith 1-1/4 in. long steel screws spaced max 6 in. OC. B. Wood Joists* — Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel jois ts, trusses or Structural W ood M embers* with bridging as required and w ith ends firestopped. C. Gypsum B oard* — Nom 5/8 in. thick, 4 ft w ide as specified in the individual F loor-Ceiling D esign. 2. Drain Piping — Nom 1-1/2 in. (or smaller) d iam Schedule 40 acrylonitrile butadiene styrene (ABS) or polyvinyl chloride (PVC) pipe and drain fittings cemented together and provided w ith ABS or PVC bathtub w aste/overflow fittings. Annular space shall be m in 0 in. (point contact) to m ax 1 in. 3. Fill V oid or Cavity M aterials* — Min 5/8 in. depth or fill m aterial applied w ithin the annulus, flush with both surfaces of plywood or gypsum board patch. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant *Bearing the UL Classification Mark Last Updated on 2001-12-07 Copyright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2006 Underwriters Laboratories Inc.®" Through-penetration Firestop Systems System No. W -L-2244 April 11, 2005 F R atings — 1 and 2 H r (See Item 1) T Ratings — 1 and 2 H r (See Item 1) L Rating at Ambient -Less Than 1 CFM/sq ft L R ating at 400 F -2 CFM/sq ft 1. Wall A ssembly — The 1 and 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the m aterials and in the manner described in the individual U 300, U 400 or V400 Series W all and Partition D es ign in the UL F ire Resistance D irectory and shall include the following construction features : A. Studs — W all framing shall consist of either w ood studs or steel channel studs. W ood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. S teel studs to be min 2-1/2 in. (64 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC. B. Gypsum B oard* — The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall b e as specified in the individual U 300, U 400 or V400 Series D esign in the UL F ire Resistance D irectory. Max diam of opening is 3 in. (76 mm). The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant — O ne nonmetallic p ipe, conduit or tubing installed either concentrically or eccentrically w ithin the firestop system. The annular space betw een p ipe and periphery of opening shall be min of 0 in. (point contact) to a max 5/8 in. .(16 mm). P ipe to be rigidly supported on both sides of wall assembly. T he following types and s izes of nonmetallic p ipes m ay be used: A. Polyvinyl C hloride (PVC) Pipe — N om 2 in. (51 mm) d iam (or smaller) cellu lar or solid core Schedule 40 (or heavier) p ipe for use in closed (process or supply) p iping systems. B. Chlorinated Polyvinyl C hloride (CPVC) — Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in closed (process or supply) piping systems. 3. Fill, Void or C avity M aterial* -Sealant — M in 5/8 in. (16 mm) thickness of fill m aterial applied within annulus, flush w ith both surfaces of wall. A t point contact location, a min 1/2 in. (13 mm) diam bead of fill material shall be applied to the wall/penetrant interface on both surfaces of the w all. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant *Bearing the UL Classification Mark Last Updated on 2005-04-11 Cop yright © 2006 Underwriters Laboratories Inc.® The appearance of a company 's name or p roduct in this database does not in itself assure that products so identified have been manufa ctured under UL's Follow-Up Service. Only those produ cts bearing the UL Mark should be consid ered to be Listed and covered under UL's Follow-Up Service. Always look for the M ark on the p roduct. UL perm its the reproduction of the m ater ial contained in the Onlin e Cer tification Directory subject to the followin g conditions: 1 . The Guid e In formation, D esigns and/or Listings ( files) m ust be p resented in their entirety and in a non-mis leading m anner, w ithout any m anipulation of th e data (or d rawings). 2 . The statement "Reprinted from the Online Certifications D irectory w ith permission from Underwr iters Laboratories Inc." must appear adjacent to the extracted materia l. In addition, th e repr inted material must include a copyr ight notice in the following format: "Copyright © 2006 Underwriters Laborator ies Inc.®" Through-penetration Firestop Systems System No. F-C-2242 July 23, 2002 F Rating — 1 Hr T Rating — 3/4 Hr 1. Floor-Ceiling A ssembly — The 1 hr fire-rated solid or trussed lumber joist Floor-Ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series F loor-Ceiling D esigns in the UL Fire Resistance Directory. The general construction features of the floor-ceiling assembly are summarized below: A. Floor System — Lumber or plywood sub floor with finish floor of lumber, plywood or Floor Topping M ixture* as specified in the individual Floor-Ceiling Design. Max diam of floor opening is 5-1/2 in. B. Wood Joints — Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural W ood Members* with bridging as required and ends firestopped. C. Gypsum Board* — Nom 4 ft wide by 5/8 in. thick as specified in the individual F loor-Ceiling Design. G ypsum board secured to wood joints or furring channels as specified in the individual F loor-Ceiling Design. 2. Chase W all — The through penetrants shall be routed through 1 fire-rated single, double or staggered wood stud/gypsum wallboard chase w all constructed of the materials and in the manner specified in the individual U 300 Series Wall and Partition Designs in the UL F ire Resistance D irectory and shall include the following construction features: A. Studs — Nom 2 by 6 in. lumber studs. B. Sole Plate — Nom 2 by 6 in. lumber plates. Max diam of floor opening is 5-1/2 in. C. Top Plate — The double top plate shall consist of two nom 2 by 6 in. lumber plates. Max diam of opening is 5-1/2 in. D. Gypsum B oard* — Thickness, type, number of layers and fasteners shall be as specified in individual Wall and Partition D esign. 3. Nonmetallic Penetrants — One nonmetallic pipe to be installed either concentrically or eccentrically w ithin the firestop system. The annular space between p ipe and periphery of opening shall be continuous contact, 0 in. (point contact) to max ¼ in. or 0 in. (point contact) to max 1 in. (See Item 4). Pipe to be rigidly supported on both sides of the floor-ceiling assembly. The following types and sizes of nonmetallic penetrants may be used: A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed (process or supply) or vented (drain, w aste or vent) p iping systems. B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 4 in. diam (or smaller) SDR13.5 CPVC pipe for used in closed (process or supply) piping systems. C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 4 in. diam (or smaller) Schedule 40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. 4. Fill, V oid or C avity Material* -Sealant — Min 1/2 in. thickness of fill material applied around through penetrant within the annulus on top surface of floor or sole p late of chase wall. M in 1/2 in. thickness of fill material applied within the annulus of the top plate flush w ith the bottom surface of the lower top plate. M in 1/2 in. bead of fill material applied at the penetrant/p late interfaces at point contact locations on both sides of assembly. W hen penetrants are installed at continuous contact or m in 0 in. to max ¼ in. annular spaces, a ½ in. bead of sealant shall be applied at the penetrant/plate interfaces and over ¼ in. annular space on the bottom side of the p lywood subfloor and lower top plate. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 606 Flexible F irestop Sealant *Bearing the UL Classification Mark Last Updated on 2002-07-23 Copyright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2006 Underwriters Laboratories Inc.®" Through-penetration Firestop Systems System No. F-C-2203 February 19, 2002 F Rating — 1 Hr T Rating — 1/2 Hr 1. Floor-Ceiling Assembly — The 1 hr fire-rated solid or trussed lumber joist floor-ceiling assembly shall be constructed of the materials and in the manner specified in the individual L500 Series Floor-Ceiling Designs in the UL Fire Resistance Directory. The general construction features of the floor-ceiling assembly are summarized below: A. Flooring System — Lumber or plywood subfloor with finish floor of lumber, plywood or Floor Topping Mixture* as specified in the individual Floor-Ceiling Design. Max diam diam of opening shall be 5 in. B. Wood Joist* — Nom 10 in. deep (or deeper) lumber, steel or combination lumber and steel joists, trusses or Structural Wood Members* with bridging as required and with ends firestopped. C. Gypsum Board* — Nom 5/8 in. thick, 4 ft wide as specified in the individual Floor-Ceiling Design. 2. Closet Flange — Acrylonitrile butadiene styrene (ABS) or polyvinyl chloride (PVC) closet stub sized to accommodate drain pipe. Closet flange installed over drain piping within floor opening with flange secured to plywood floor with steel screws. Diam of circular opening through flooring (Item 1A) to be max ½ in. larger than outside diam of closet flange. 3. Drain Piping — Nom 4 in. diam (on smaller) Schedule 40 acrylonitrile butadiene styrene (ABS) or polyvinyl chloride (PVC) drain pipe and 90 degree elbow for use in vented (drain, waste or vent) piping systems. Pipe installed concentrically within firestop system. 4. Fill, Void or Cavity Materials*—Sealant — Min 3/4 in. thickness of fill material applied within the annulus, flush with the bottom surface of floor. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant 5. Water Closet — (Not Shown)—Floor mounted vitreous china water closet. *Bearing the UL Classification Mark Last Updated on 2002-02-19 Copyright © 2006 Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product. UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2006 Underwriters Laboratories Inc.®"