Loading...
HomeMy WebLinkAboutE5-1 - Details & Schedules.pdf PANEL 'MDP' PANEL 'P1' PANEL 'P2' UTILITY TRANS. RISER DIAGRAM NTS CT CABINET BY UTILITY CO. INST. BY E.C. 2 -3" C, 4-350MCM, 1 -#2 GND IN EACH 600A. M.B. 100A. M.L.O. 100A. M.L.O. PANEL 'L' 100A. M.L.O. 1-1/4" C, 4#3AWG, 1#8GND PAD BY E.C. PER UTILITY COMPANY STANDARDS PANEL 'EM' 100A. M.C.B. BUILDING STEEL CONCRETE ENCASED GROUNDING ELECTRODE IN FOUNDATION WATER MAIN #3/0 #3/0 #3/0 N E C WP GENERATOR RECEPTACLE VERIFY EXACT NEMA CONFIGURATION TVSS 2 -3" C, 4-350MCM, 1 -#2 GND IN EACH 1-1/4" C, 4#3AWG, 1#8GND 1-1/4" C, 4#3AWG, 1#8GND 1-1/4" C, 4#3AWG, 1#8GND 1-1/4" C, 4#3AWG, 1#8GND 1-1/4" C, 4#3AWG, 1#8GND F H 35 E G 4 OPEN OFFICE 120 WOMEN 132 MEN 131 TABLE/CHAIR STORAGE 109 SERVER 129 ELECT 108 WORKROOM 128 BREAKROOM 133 HALLWAY 121 HALLWAY 130 33 +44" MOUNT BELOW CEILING IN SERVER ROOM AND TRANSITION TO 6" ABOVE CEILING IN WORKROOM AND HALLWAY. END END PROVIDE B-LINE SERIES 148 P, 9" WIDTH OR APPROVED EQUAL COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE The concepts, ideas, designs, plans, and details details as shown on this document are the sole property of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN CERTIFICATION MSKTD 5629 BUILD 65076 CONSTRUCTION SET 3-21-11 3/18/2011 3:17:01 PM 100 W 96th St Indianapolis, Indiana 46290 E5.12-11-11 Indianapolis North Details & Schedules Lake City Bank COMMUNICATIONS WIRING SCHEDULE Drop ID Data Drops Phone Drops Coax Drops Fiber Drops Comments 1 1 0 0 106A 3 1 0 0 106B 3 1 0 0 106C 2 0 0 0 106D 106D 2 0 0 0 Provide 2 -3/4" C up to projector 110A 3 1 0 0 110B 1 0 1 0 112A 3 1 0 0 112B 3 1 0 0 113C 1 1 0 0 115A 1 1 0 0 116A 1 1 0 0 117A 1 1 0 0 118A 1 1 0 0 119A 1 1 0 0 120A 2 1 0 0 120B 2 1 0 0 120C 2 1 0 0 120D 2 1 0 0 120E 2 1 0 0 120F 2 1 0 0 120G 2 1 0 0 122A 1 1 0 0 123A 1 1 0 0 124A 1 1 0 0 125A 1 1 0 0 126A 1 1 0 0 127A 1 1 0 0 128A 1 1 0 0 128B 1 1 0 0 128C 1 1 0 0 128D 1 1 0 0 128E 0 1 0 0 128F 1 1 0 0 132A 0 1 0 0 135A 2 2 0 0 136A 2 2 0 0 136B 2 2 0 0 136C 1 1 0 0 136D 1 1 0 0 136E 1 1 0 0 139A 1 1 0 0 139B 1 1 0 0 139C 1 0 1 0 139D 1 0 1 0 140A 1 1 0 0 140B 0 1 0 0 141A 1 1 0 0 142A 1 1 0 0 143A 1 1 0 0 144A 1 1 0 0 Panel Modifications: Total Amps: 565 A 545 A 559 A Total Load: 67816 VA 65368 VA 67082 VA 41 ------14120 3632 ------42 39 ------10080 3960 ------40 37 P1 100 A 3 12630 5210 3 100 A EM 38 35 ------12434 10660 ------36 33 ------12687 9155 ------34 31 L 100 A 3 11755 8735 3 100 A P2 32 29 30 27 ------1000 2250 ------28 25 UH-1 20 A 2 1000 2250 2 30 A EW-1 26 23 ------3480 3948 ------24 21 ------3480 3948 ------22 19 RTU-7 35 A 3 3480 3948 3 40 A RTU-8 20 17 ------3480 2200 ------18 15 ------3480 2200 ------16 13 RTU-5 35 A 3 3480 2200 3 25 A RTU-6 14 11 ------3480 3948 ------12 9 ------3480 3948 ------10 7 RTU-3 35 A 3 3480 3948 3 40 A RTU-4 8 5 ------2220 3480 ------6 3 ------2220 3480 ------4 1 RTU-1 25 A 3 2220 3480 3 35 A RTU-2 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Manufacturer: Square D Model: NF Enclosure: Type 1 MCB Rating: 600 A Mounting: Surface Wires: 4 Mains Rating: 600 A Supply From: Phases: 3 Mains Type: MB Location: ELECT 108 Volts: 120/208 Wye A.I.C. Rating: 42K AIC Branch Panel: MDP Panel Modifications: Total Amps: 105 A 84 A 118 A Total Load: 12630 VA 10080 VA 14120 VA 41 Spare 20 A 1 0 VA 3800 ------42 39 Spare 20 A 1 0 VA 3800 2 50 A HUM-8 40 37 ------3800 0 VA 1 20 A Spare 38 35 HUM-4 50 A 2 3800 0 VA 1 20 A Spare 36 33 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 34 31 Power TELLER WORKROOM 20 A 1 360 VA 0 VA 1 20 A Spare 32 29 Exterior Receptacle 20 A 1 180 VA 180 VA 1 20 A Power BREAKROOM 132 30 27 ------750 VA 180 VA 1 20 A Exterior Receptacle 28 25 Heating BREAKROOM 132 20 A 2 750 VA 500 VA 1 20 A EF-1 26 23 Power DISPOSAL 20 A 1 1200 720 VA 1 20 A Power OFFICE 142 24 21 Rooftop Receptacles 20 A 1 360 VA 720 VA 1 20 A Power OFFICE 141 22 19 Power OFFICE 143 20 A 1 900 VA 720 VA 1 20 A Power OFFICE 140 20 17 Power BREAKROOM 132 20 A 1 360 VA 1000 1 20 A Power DISHWASHER 18 15 Power BREAKROOM 132 20 A 1 1000 750 VA 1 20 A Power REFRIGERATOR 16 13 Power VISITING OFFICE 20 A 1 720 VA 1280 1 20 A Power HALLWAY 129 14 11 Power OFFICE 123 20 A 1 720 VA 720 VA 1 20 A Power VISITING OFFICE 12 9 Power OFFICE 122 20 A 1 720 VA 720 VA 1 20 A Power OFFICE 125 10 7 Power OFFICE 119 20 A 1 900 VA 900 VA 1 20 A Power OFFICE 124 8 5 Power OFFICE 115 20 A 1 720 VA 720 VA 1 20 A Power OFFICE 118 6 3 Power CONFERENCE 113 20 A 1 360 VA 720 VA 1 20 A Power OFFICE 117 4 1 Power CONFERENCE 113 20 A 1 900 VA 900 VA 1 20 A Power OFFICE 116 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Manufacturer: Model: Enclosure: Type 1 MCB Rating: Mounting: Surface Wires: 4 Mains Rating: 100 A Supply From: MDP Phases: 3 Mains Type: MLO Location: ELECT 108 Volts: 120/208 Wye A.I.C. Rating: Branch Panel: P1 Panel Modifications: Total Amps: 73 A 76 A 89 A Total Load: 8735 VA 9155 VA 10660 VA 41 ------2000 1000 ------42 39 Heating LOBBY 101 20 A 2 2000 1000 2 20 A Heating WAITING 111 40 37 ------2500 0 VA 1 20 A Spare 38 35 Heating LOBBY 101 30 A 2 2500 0 VA 1 20 A Spare 36 33 Spare 20 A 1 0 VA 1375 ------34 31 Spare 20 A 1 0 VA 1375 2 20 A Heating LOBBY 101 32 29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30 27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28 25 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 26 23 Exterior Receptacle 20 A 1 180 VA 180 VA 1 20 A Power Large Printer 24 21 Power BANKING LOBBY 138 20 A 1 180 VA 1180 1 20 A Power MEN 130 22 19 Power PUBLIC MEETING 20 A 1 1080 900 VA 1 20 A Power LOBBY 101 20 17 Power WORKROOM 128 20 A 1 540 VA 720 VA 1 20 A A Power WORKROOM 128 18 15 Power HALLWAY 107 20 A 1 720 VA 540 VA 1 20 A Power WORKROOM 128 16 13 Power CONFERENCE RM 139 20 A 1 1080 540 VA 1 20 A Power BANKING LOBBY 138 14 11 Power WOMEN 104 20 A 1 1280 1540 1 20 A Power PUBLIC MEETING 12 9 Power WAITING 111 20 A 1 1260 180 VA 1 20 A Power PUBLIC MEETING 10 7 Power OPEN OFFICE 120 20 A 1 360 VA 180 VA 1 20 A Power PUBLIC MEETING 8 5 Power OPEN OFFICE 120 20 A 1 360 VA 360 VA 1 20 A Power OPEN OFFICE 120 6 3 Power OPEN OFFICE 120 20 A 1 360 VA 360 VA 1 20 A Power OPEN OFFICE 120 4 1 Power OPEN OFFICE 120 20 A 1 360 VA 360 VA 1 20 A Power OPEN OFFICE 120 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Manufacturer: Model: Enclosure: Type 1 MCB Rating: Mounting: Surface Wires: 4 Mains Rating: 100 A Supply From: MDP Phases: 3 Mains Type: MLO Location: ELECT 108 Volts: 120/208 Wye A.I.C. Rating: Branch Panel: P2 Panel Modifications: Total Amps: 43 A 33 A 30 A Total Load: 5210 VA 3960 VA 3632 VA 23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 Restroom Lighting 20 A 1 332 VA 1080 1 20 A Driveup Lighting 18 15 FCU-1 20 A 1 500 VA 600 VA 1 20 A Power 16 13 Night Lights & Exits 20 A 1 630 VA 1680 1 20 A CU-1 14 11 Driveup Lane 2 Power 20 A 1 1000 500 VA 1 20 A Fire Panel 12 9 Driveup Teller Power 20 A 1 360 VA 1000 1 20 A Driveup Lane 1 Power 10 7 Power SERVER 109 20 A 1 360 VA 1080 1 20 A Power TELLER AREA 136 8 5 Power SERVER 109 20 A 1 360 VA 360 VA 1 20 A Power SERVER 109 6 3 Driveup Area Printer Power 20 A 1 1000 500 VA 1 20 A Security Panel 4 1 ATM Power & Night Dep. Light 20 A 1 1100 360 VA 1 20 A Power TELLER WORKROOM 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Manufacturer: Model: Enclosure: Type 1 MCB Rating: Mounting: Surface Wires: 4 Mains Rating: 100 A Supply From: MDP Phases: 3 Mains Type: MLO Location: ELECT 108 Volts: 120/208 Wye A.I.C. Rating: Branch Panel: EM Cable Tray Detail Panel Modifications: Total Amps: 98 A 106 A 104 A Total Load: 11755 VA 12687 VA 12434 VA 41 Space ----0 VA 0 VA ----Space 42 39 Space ----0 VA 0 VA ----Space 40 37 Space ----0 VA 0 VA ----Space 38 35 ------1654 1654 ------36 33 HUM-6 20 A 2 1654 1654 2 20 A HUM-7 34 31 ------1654 1654 ------32 29 HUM-3 20 A 2 1654 1654 2 20 A HUM-5 30 27 ------1654 1654 ------28 25 HUM-1 20 A 2 1654 1654 2 20 A HUM-2 26 23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24 21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22 19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20 17 ------1150 690 VA ------18 15 Parking Lot Lighting 20 A 2 1150 690 VA 2 20 A Parking Lot Lighting 16 13 Sign Light -East 20 A 1 500 VA 500 VA 1 20 A Sign Light -North 14 11 Sign Light -South 20 A 1 500 VA 1548 1 20 A Bollard Lighting 12 9 Teller Work & Break Rms + 127 20 A 1 904 VA 756 VA 1 20 A Lighting WAITING 111 10 7 Lighting 20 A 1 710 VA 1271 1 20 A SW Conf Rm and Open Ofc Ltg. 8 5 Lighting LOBBY 101 20 A 1 780 VA 1152 1 20 A Lighting BANKING LOBBY 138 6 3 Lighting 20 A 1 1412 1161 1 20 A Lighting -Teller & East Ofcs. 4 1 Lighting -North Private Offices 20 A 1 1080 1080 1 20 A Lighting -West Private Offices 2 CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT Manufacturer: Model: Enclosure: Type 1 MCB Rating: Mounting: Surface Wires: 4 Mains Rating: 100 A Supply From: MDP Phases: 3 Mains Type: MLO Location: ELECT 108 Volts: 120/208 Wye A.I.C. Rating: Branch Panel: L Floor Box Schedule Type Mark Manufacturer Model Comments FB-1 Wiremold 880CS2-1 FB-2 Wiremold 880CS2-1 Revisions: Date: By: