HomeMy WebLinkAboutM5-1 - Mechanical Schedules and Details.pdf
ALL WORK SHALL CONFORM TO ALL APPLICABLE STATE, LOCAL, AND NATIONAL CODES. ALL WORK SHALL BE IN ACCORDANCE WITH CITY OF CARMEL BUILDING CODES. PROVIDE TESTS AND ARRANGE INSPECTIONS AS
REQUIRED. THE CODE SHALL BE FOLLOWED AT A MINIMUM. PROVIDE HIGHER GRADES OF MATERIAL AND WORKMANSHIP WHERE REQUIRED. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND INSPECTIONS
REQUIRED BY THE AUTHORITIES HAVING JURISDICTION. ANY PRODUCT MANUFACTURER NOT LISTED ON THE DRAWINGS BUT WISHING TO BID MUST BE SUBMITTED TO ENGINEER FOR APPROVAL NOT LESS THAN 7 DAYS
PRIOR TO BID DATE. SUBMIT SHOP DRAWINGS FOR APPROVAL PRIOR TO FABRICATION PURCHASE AND/OR INSTALLATION. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING DIFFUSER LOCATIONS WITH ARCHITECT'S
REFLECTED CEILING PLANS. DIFFUSER LOCATIONS ON SHOP DRAWINGS ARE SUBJECT TO APPROVAL BY THE ARCHITECT. SUBMIT FOR APPROVAL PRODUCT DATA FOR ALL EQUIPMENT LISTED ON THE MECHANICAL SCHEDULE
SHEET, AND FOR DUCT AND PIPE INSULATION, VALVES, FIRE-STOPPING AND FIRE DAMPERS. SUBMITTALS TO INCLUDE RATED CAPACITIES, FURNISHED SPECIALITIES, WIRING DIAGRAMS, ACCESSORIES, CERTIFIED
FAN-PERFORMANCE CURVES, CERTIFIED PUMPPERFORMANCE CURVES, AS PERTAINS TO THAT PIECE OF EQUIPMENT. DRAWINGS (PLANS, SCHEMATICS, AND DIAGRAMS) INDICATE GENERAL LOCATION AND ARRANGEMENT
OF PIPING, DUCTWORK, AND EQUIPMENT. THE LOCATION AND ARRANGEMENT TAKE INTO CONSIDERATION PIPE SIZING AND FRICTION LOSS, EXPANSION, AND OTHER DESIGN PARAMETERS. CLEARANCES ABOVE CEILINGS
IN CERTAIN AREAS ARE LIMITED AND MAY NECESSITATE ALTERNATE DUCTWORK AND/OR PIPING ROUTINGS. WHERE POSSIBLE, PIPING, DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AS INDICATED. CHANGES REQUIRED
TO MEET ARCHITECTURAL AND STRUCTURAL CONDITIONS ARE TO BE APPROVED BY THE ENGINEER. THE DRAWINGS AND SPECIFICATIONS ARE NOT INTENDED TO SHOW ALL DETAILS. THE CONTRACTOR SHALL SECURE
SATISFACTORY INFORMATION BEFORE SUBMITTING THEIR BID PROPOSAL AND INCLUDE IN THE PROPOSAL A SUM SUFFICIENT TO COVER ALL ITEMS OF LABOR AND MATERIAL REQUIRED FOR THE COMPLETE INSTALLATION
OF THE DEVICES AND SYSTEM DESCRIBED. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THAT OF ALL OTHER TRADES PRIOR TO FABRICATION AND INSTALLATION. ROOF PENETRATIONS REQUIRE COORDINATION
WITH GENERAL CONTRACTOR. APPROVE PENETRATION, FLASHING MATERIALS, AND CURBS WITH ROOFING CONTRACTOR RESPONSIBLE FOR ROOF WARRANTY, PRIOR TO INSTALLATION OF PENETRATIONS. M.C. IS RESPONSIBLE
FOR ALL SUPPLEMENTAL STEEL REQUIRED TO SUPPORT EQUIPMENT CURBS. ALL ROOFTOP MOUNTED EQUIPMENT SHALL BE INSTALLED LEVEL, PLUMB, AND FIRMLY ANCHORED IN LOCATIONS INDICATED. OBSERVE MANUFACTURER'S
INSTALLATION INSTRUCTIONS AND RECOGNIZED INDUSTRY PRACTICES TO INSURE THAT PRODUCTS SERVE THEIR INTENDED FUNCTION. ROOFTOP AIR HANDLING UNITS SHALL BE MANUFACTURED BY TRANE, YORK OR
CARRIER. ALL SHEET METAL DUCTWORK SHALL BE G-60 COATED GALVANIZED STEEL CONFORMING TO ASTM A653 AND A924 STANDARDS OF GAUGE AND REINFORCEMENT COMPLYING WITH CURRENT ADDITIONS OF SMACNA
STANDARDS. DUCTWORK SHALL BE AIRTIGHT (5% LEAKAGE). ALL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS SHALL BE SEALED. FABRICATE ELBOWS WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES THE DUCT
WIDTH IN THE PLANE OF THE TURN; AND FABRICATE TO INCLUDE FACTORY MANUFACTURED TURNING VANES IN ELBOWS WHERE SHORTER RADIUS IS NECESSARY. LIMIT ANGULAR TAPERS TO 30 DEGREES AND 20 DEGREES
FOR EXPANDING TAPERS. MAXIMUM STRAIGHT LENGTH OF FLEX DUCT SHALL BE 4 FEET. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS. TAKE-OFFS SHALL NOT BE PLACED CLOSER THAN 12" FROM THE
END OF A TRUNK OR LESS THAN 24" DOWNSTREAM FROM AN ELBOW. PROVIDE AND INSTALL DUCT TRANSITIONS TO ALL TERMINAL DEVICES FOR CONNECTIONS TO EITHER SIDE AS REQUIRED. SEE PLANS FOR DUCT
SIZES AND REFER TO TERMINAL UNIT SCHEDULE FOR RECOMMENDED INLET AND OUTLET SIZE. MANUAL VOLUME DAMPERS ARE TO BE PROVIDED IN ALL DUCT RUN OUTS FOR SUPPLY DIFFUSERS AND EXHAUST GRILLES.
PROVIDE SQUARE-TO-ROUND AND ROUND-TOROUND DUCT TRANSITIONS AT SUPPLY DIFFUSERS AS REQUIRED FOR PROPER CONNECTION. DUCT LAYOUT IS DIAGRAMATIC IN NATURE. ADJUST TO FIELD CONDITIONS. ADD
OFFSETS WHERE NEEDED. ALL RECTANGULAR SUPPLY DUCT SHALL BE LINED WITH 1/2" LINER. LAMINATE LINER TO INTERNAL SURFACES IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. DUCT DIMENSIONS
ARE "FREE AREA" AND SHALL NOT BE REDUCED. ALL ROUND SUPPLY AIR DUCT SHALL BE WRAPPED EXTERNALLY WITH 1 1/2" THICK FLEXIBLE FIBERGLASS INSULATION. EXHAUST DUCT NEED NOT BE INSULATED OR
LINED EXCEPT TO PROVIDE LINING FOR 5 FT. UPSTREAM OF EXHAUST FAN FOR ACOUSTICAL REASONS.NO DUCT LINER SHALL BE INSTALLED 10 FT. DOWNSTREAM OF HUMIDIFIER MANIFOLDS. ALL ROUND DUCTWORK
SHALL BE EXTERNALLY INSULATED. THIS INSULATION SHALL ACHIEVE A 25/50 FLAME-SPREAD AND SMOKE-DEVELOPED RATING IN ACCORDANCE WITH NFPA 255. THE SMOKE DEVELOPMENT RATING FOR PIPE INSULATION
SHALL NOT EXCEED 150. INSTALL INSULATION PRODUCTS ON SPECIFIED DUCTWORK, PIPING, AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH RECOGNIZED
INDUSTRY PRACTICES TO INSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. MATERIALS EXPOSED WITHIN DUCTS OR OR PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED
RATING OF NOT MORE THAN 50 IN ACCORDANCE WITH SECTION 102 (A), IMC (675 IAC 18-1). ANY PLASTIC PIPING, ROUTED IN SUCH LOCATION SHALL BE COVERED WITH INSULATION AS REQUIRED TO COMPLY
WITH ABOVE INDICATED FLAME-SPREAD AND SMOKE-DEVELOPED RATING. AIR SMOKE DETECTORS FOR AIR HANDLING UNIT SHUTDOWN AND FOR SMOKE DAMPER CONTROL WILL BE PROVIDED AS PART OF THE FIRE ALARM
SYSTEM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING THE DETECTORS AND FOR PREPARING THE DUCTWORK FOR MOUNTING THE DETECTORS. CONTRACTOR SHALL INSTALL CONSTRUCTION FILTERS ON ALL
AIR DISTRIBUTION EQUIPMENT SERVING NEW TO INSURE THAT COILS AND INTERNAL COMPONENTS ARE PROTECTED. BY COMPLETION OF THE PROJECT THE M.C. SHALL REPLACE CONSTRUCTION FILTERS WITH NEW FILTERS.
ALL BACKDRAFT DAMPERS SHALL BE RUSKIN MODEL CBD4 OR PRE-APPROVED EQUAL. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL TEMPERATURE CONTROL WIRING, THERMOSTATS, RELAYS, AND INTERLOCKS
ETC. AS REQUIRED. INSTALL PLASTIC PIPE MARKERS ON ALL PIPING, AND INCLUDE ARROWS TO SHOW NORMAL DIRECTION OF FLOW. PROVIDE A VALVE TAG ON EVERY VALVE, COCK AND CONTROL DEVICE IN EACH
PIPING SYSTEM. EXCLUDE CHECK VALVES, VALVES FROM FACTORY-FABRICATED EQUIPMENT UNITS, PLUMBING FIXTURE FAUCETS, HOSE-BIBS, HVAC TERMINAL DEVICES, AND SIMILAR ROUGH-IN CONNECTIONS OF END-USE
FIXTURES AND UNITS. ALL ABOVE GRADE CONDENSATE DRAIN PIPING SHALL BE COVERED WITH 1/2" PRE-FORMED ELASTOMERIC FOAM INSULATION. ALL CONNECTIONS BETWEEN DISSIMILAR PIPING MATERIAL SHALL
BE MADE WITH "EPCO" FITTINGS TO PREVENT GALVANIC ACTION. INSTALL CHROME-PLATED PIPE ESCUTCHEONS ON EACH PIPE PENETRATION THROUGH FLOORS, WALLS, PARTITIONS, AND CEILINGS WHERE PENETRATION
IS EXPOSED TO VIEW. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE. ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO
BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL PIPING HANGER AND SUPPORTS SHALL BE UL OR FM APPROVED. UNIONS AND VALVES SHALL BE PROVIDED AT CONNECTIONS TO ALL EQUIPMENT.
INSTALL VALVES WHERE REQUIRED FOR PROPER OPERATION OF PIPING AND ISOLATION OF EACH PIECE OF EQUIPMENT. IN ADDITION INSTALL SECTIONAL VALVES ON EACH BRANCH AND RISER, CLOSE TO MAIN, AND
WHERE BRANCH OR RISER SERVES TWO OR MORE PIECES OF MECHANICAL EQUIPMENT OR FIXTURES. LOCATE VALVES SO AS TO BE ACCESSIBLE AND SO THAT SEPARATE SUPPORT CAN BE PROVIDED WHEN NECESSARY.
INSTALL VALVES WITH STEMS POINTED UP IN VERTICAL POSITION WHERE POSSIBLE, BUT IN NO CASE WITH STEMS POINTED DOWNWARD FROM HORIZONTAL PLANE. WHERE INSULATION IS INDICATED, INSTALL EXTENDED
STEM VALVES, ARRANGED IN PROPER MANNER TO RECEIVE INSULATION. REFRIGERANT PIPING SHALL BE TYPE ACR DRAWN COPPER TUBING WITH WROUGHT COPPER FITTINGS AND BRAZED JOINTS ABOVE GROUND WITHIN
BUILDING. USE TYPE K, ANNEALED TEMPER COPPER TUBING FOR 2 INCH AND SMALLER WITHOUT JOINTS BELOW GROUND AND WITHIN SLABS. MECHANICAL FITTINGS (CRIMP OR FLAIR) ARE NOT PERMITTED. REFRIGERANT
SUCTION LINES SHALL BE INSULATED WITH 1 INCH ELASTOMERIC INSULATION. ANY INSULATION LOCATED OUTSIDE SHALL BE COVERED WITH 2 COATS OF ULTRAVIOLET RESISTANT PAINT. HANGING OF PIPING SHALL
BE ON NOT MORE THAN 10'-0" CENTERS WITH 3/8" RODS. ACCEPTABLE MANUFACTURERS FOR AIR GRILLES INCLUDE: CARNES; HART & COOLEY; KRUEGER INDUSTRIES; PRICE; TITUS; TUTTLE & BAILEY. VOLTAGE
FOR ALL EQUIPMENT IS TO BE VERIFIED BY THE MECHANICAL CONTRACTOR. ALL FINAL POWER (LINE VOLTAGE) WIRING OF ALL EQUIPMENT WILL BE EXECUTED BY THE ELECTRICAL CONTRACTOR. ALL THERMOSTATS
SHALL BE MOUNTED NEAR DOORS OR CORNERS OF WALLS UNLESS SHOWN OTHERWISE. ALL THERMOSTATS TO BE MOUNTED AT 48" A.F.F. COMPLY WITH MANUFACTURER'S WRITTEN INSTRUCTIONS FOR INSTALLATION OF
VIBRATION CONTROL ON ALL MECHANICAL EQUIPMENT. ADJUST TO ENSURE THAT UNITS HAVE EQUAL DEFLECTION, DO NOT BOTTOM OUT UNDER LOADING, AND ARE NOT SHORT-CIRCUITED BY OTHER CONTACTS OR BEARING
POINTS. A COMPLETE AIR TEST AND BALANCE SHALL BE PERFORMED IN COMPLETE ACCORDANCE WITH NEBB OR AABC NATIONAL STANDARDS FOR FIELD MEASUREMENTS AND INSTRUMENTATION. MECHANICAL CONTRACTOR
SHALL CHANGE BELTS AND SHEAVES ON AIR HANDLING EQUIPMENT AS DIRECTED BY BALANCING CONTRACTOR, IF REQUIRED, TO ACHIEVE DESIGN PARAMETERS WITH NO EXTRA COST TO THE OWNER. THE CONTRACTOR
SHALL PROVIDE A COMPETENT OPERATING TECHNICIAN TO INSTRUCT THE OWNER IN THE OPERATION AND MAINTENANCE REQUIREMENTS OF THE INSTALLED EQUIPMENT. THE CONTRACTOR SHALL ASSEMBLE AND SUBMIT
THREE COPIES OF PRINTED INSTRUCTIONS, INCLUDING EQUIPMENT CUTS AND WIRING DIAGRAMS FOR THE OPERATION AND MAINTENANCE OF EACH ITEM OF INSTALLED EQUIPMENT. THE CONTRACTOR SHALL GUARANTEE
ALL WORK AND MATERIALS FOR ONE YEAR AFTER DATE OF ACCEPTANCE AGAINST ALL DEFECTS OF MATERIALS, EQUIPMENT AND WORKMANSHIP. INSTALL ENGRAVED PLASTIC LAMINATE SIGN OR PLASTIC EQUIPMENT
MARKER ON OR NEAR EACH MAJOR ITEM OF MECHANICAL EQUIPMENT. RETURN DUCT DAMPERS SHALL BE BALANCED TO THEIR RESPECTIVE SPACE CUMALATIVE SUPPLY AIR TOTALS. DURING CONSTRUCTION, WHEN ROOFTOP
UNITS ARE OPERATING, INSTALL MERV-8 FILTERS. JUST PRIOR TO OCCUPANCY, INSTALL MERV-13 FILTERS. AFTER THE FLUSH OUT PERIOD, INSTALL NEW MERV-13 FILTERS FOR EACH UNIT. SEE SPECIFICATIONS
FOR FLUSHOUT PROCEDURE. FOR LEED REQUIREMENTS AND COMMISSIONING DETAILS, SEE SPECIFICATIONS. ROUND TO ROUND 10" AND LARGER ROUND TO ROUND 8" AND SMALLER RECTANGULAR TO ROUND 10" AND
LARGER RECTANGULAR TO ROUND 8" AND LESS RECTANGULAR TO RECTANGULAR ROUND DUCT RECTANGULAR DUCT RECTANGULAR DUCT ROUND DUCT RECTANGULAR DUCT 45° TAKEOFF BOOT TO BE SIZED TO MATCH 1/2"
FIBERGLASS DUCT LINER RETURN GRILLE DIMENSIONS. RETURN GRILLE NOTE: W 1 1/2 W (MINIMUM) 2W ACOUSTICAL CEILING DIFFUSER FLEXIBLE DUCT RIGID DUCT 4'-0" MAX. IF BRANCH DUCT IS LARGER THAN
INLET TO DIFFUSER, PROVIDE TRANSITION AT THIS POINT RIGID DUCT ELBOW CENTER LINE RADIUS = 1.5 NECK DIA. VD VD VD * * S SLIP OR U OPTIONAL ALL SUCH CONNECTIONS TO BE SEALED W H W H R
ACCU AIR COOLED CONDENSING UNIT A.F.F. ABOVE FINISHED FLOOR AHU-AIR HANDLER UNIT ATV AIR TUNING VANE BDD BACK DRAFT DAMPER CAL-COMBUSTION COMBUSTION AIR LOUVER CH-CABINET HEATER EAL-EXHAUST
AIR LOUVER EAT ENTERING AIR TEMPERATURE EAV-EXHAUST AIR VENTILATOR EDB ENTERING DRY BULB EF-EXHAUST FAN EG-EXHAUST GRILLE ESP EXTERNAL STATIC PRESSURE EWB ENTERING WET BULB FCU FAN COIL
UNIT FD FIRE DAMPER FTR FINNED TUBE RADIATION GPM GALLONS PER MINUTE HP HEAT PUMP HVAC-HTG, VENT, & AC UNIT L-LOUVER LAT LEAVING AIR TEMP LDB LEAVING DRY BULB LWB LEAVING WET BULB MAT
MIXED AIR TEMP MD MANUAL DAMPER MOD MOTOR OPERATED DAMPER MUA MAKE-UP AIR UNIT OAD OUTSIDE AIR DAMPER OAI OUTSIDE AIR INTAKE OAL OUTSIDE AIR LOUVER RAD-RELIEF AIR DAMPER RAL-RELIEF AIR
LOUVER RHP RADIANT HEATING PANEL RTU-ROOFTOP UNIT RV RELIEF VENT SD SPLITTER DAMPER SF SUPPLY FAN SFD SMOKE FIRE DAMPER TB-TERMINAL BOX TG-TRANSFER GRILLE TSP TOTAL STATIC PRESSURE UH-UNIT
HEATER VAV-VARIABLE AIR VOLUME BOX NOTE: SOME SYMBOLS MAY NOT BE USED VAC A HWS HWR CHWS CHWR FP LPS LPR MPS MPR HPWS HPWR D HG RS RL CWS CWR VACUUM PIPING AIR PIPING HOT WATER SUPPLY
HOT WATER RETURN CHILLED WATER SUPPLY CHILLED WATER RETURN FIRE PROTECTION PIPING LOW PRESSURE STEAM SUPPLY CONDENSATE STEAM RETURN MED. PRESSURE STEAM SUPPLY MED. PRESSURE STEAM RETURN
HEAT PUMP WATER SUPPLY HEAT PUMP WATER RETURN CONDENSATE DRAIN REFRIGERANT HOT GAS REFRIGERANT SUCTION REFRIGERANT LIQUID CONDENSER WATER SUPPLY CONDENSER WATER RETURN THPSS TSENSOR
SWITCH THERMOMETER THERMOMETER CONNECT NEW TO EXISTING HUMIDISTAT THERMOSTAT THERMOSTAT W/GUARD ASPIRATING THERMOSTAT TT GA F SMOKE DETECTOR VOLUME DAMPER BACK WATER VALVE FLEX DUCT
RECTANGULAR DIFFUSER ROUND DIFFUSER SLOT DIFFUSER RETURN GRILLE/DIFFUSER EXHAUST GRILLE/DIFFUSER FLOW SETTER TEMP WELL METER CAP LINE PRESSURE SENSOR 3-WAY CONTROL VALVLE 2-WAY CONTROL
VALVE LINE STRAINER HORIZONTAL FIRE DAMPER VERTICAL FIRE DAMPER CHECK VALVE BUTTERFLY VALVE BALL VALVE GATE VALVE DOUBLE BACKFLOW PREVENTER GAS COCK EQUIP/PIPING TO BE DEMOLISHED EXISTING
EQUIPMENT TO REMAIN M FCU-1 DUCTLESS SPLIT SYSTEM -SERVER ROOM A. MITSUBISHI ELECTRIC MODEL #MS-A09WA "MR. SLIM" INDOOR DUCTLESS AIR CONDITIONER. 9,500 BTU/HR, SEER 13.0, 115V, 1.2 MCA,
15A BREAKER, B. MU-A09WA OUTDOOR CONDENSING UNIT. SINGLE ROTARY COMPRESSOR, 14A MCA, R410A REFRIGERANT, LOW AMBIENT CONTROLLER (0 DEGREES). C. WIRELESS WALL-MOUNTED REMOTE CONTROLLER.
UH-1 CEILING-RECESSED UNIT HEATER -ENTRANCE VESTIBULE A. REZNOR MODEL #ECR, SIZE "2", 2 KW, 450 CFM, 208 V, T-STAT B. SUPPORT WITH RUBBER/SPRING ISOLATORS. GR-1, GR-2, GR-3 GRAVITY RELIEF
HOOD A. COOK MODEL 20-PR. 1,500 CFM AT 0.05" SP. B. FURNISH WITH CURB AND BIRDSCREEN. C. COUNTER-BALANCED BACKDRAFT DAMPER. D. PROVIDE SHEET METAL DRIP PAN UNDERNEATH UNIT. 1. FURNISH
AND INSTALL OUTDOOR AIR MONITORING (FLOW MEASURING DEVICE AT EACH RTU WITH SIGNAL OUTPUT FOR ALARM, SEE SEQUENCE OF OPERATIONS. 2. FURNISH AND INSTALL BUILDING AUTOMATED CONTROLLER FOR
MONITORING, SCHEDULING, AND CONTROLLING OF HVAC EQUIPMENT. SEE SEQUENCE OF OPERATIONS. 3. FURNISH AND INSTALL CO2 SENSORS IN CONFERENCE ROOM 112, CONFERENCE ROOM 140, AND PUBLIC MEETING
ROOM 106. SEE SEQUENCE OF OPERATIONS. AFM: OUTDOOR AIRFLOW MONITOR A. EBTRON, ADVANTAGE GOLD MODEL GTX-116-PC B. INSTALL IN 12" SHEET METAL SLEEVE BETWEEN RTU AND RTU OUTSIDE INTAKE
HOOD. C. OUTPUT: 0-10 V, INPUT: 24 V. PACKAGED ROOFTOP UNITS UNITS SHALL BE CONTROLLED THERMOSTATICALLY, (1) PER ZONE (EXCEPTION: RTU-3 HAS (2) THERMOSTATS WHICH SHALL BE AVERAGED).
EACH THERMOSTAT SHALL HAVE AN OCCUPANCY OVERRIDE -3 HOUR INTERVAL. OCCUPIED COOLING: CONSTANT SPEED FAN SHALL RUN CONTINUOUSLY WITH CYCLING DX COMPRESSOR TO SATISFY SETPOINT. COMPRESSOR
SHALL HAVE ANTI-SHORT CYCLE TIMER. UNIT SHALL BE SET FOR MINIMUM VENTILATION REQUIREMENT. WHEN CONDITIONS ARE MET, UNIT SHALL GO TO 100% ECONOMIZER AND POWERED EXHAUST SHALL ENERGIZE.
HEATING SHALL BE DISABLED. OCCUPIED HEATING: THE GAS HEAT SHALL CYCLE BETWEEN STAGES TO SATISFY HEATING SETPOINT. COOLING SHALL BE DISABLED. UNOCCUPIED COOLING/HEATING: UNIT FAN AND
COILS SHALL CYCLE AS REQUIRED TO SATISFY REDUCED SETPOINT. ECONOMIZER DISABLED. HUMIDIFIERS UNITS SHALL MODULATE AS REQUIRED TO MAINTAIN A MINIMUM 30% RELATIVE RELATIVE HUMIDITY IN THE
SPACES SERVED, AS MEASURED BY HUMIDISTAT LOCATED IN RETURN AIR OF TO EACH RTU. EXHAUST FAN EXHAUST FAN SHALL RUN CONTINUOUSLY DURING EXTENDED OCCUPIED HOURS, "OFF" DURING UNOCCUPIED
HOURS. EXHAUST FAN OCCUPANCY HOURS SCHEDULE IS SET AT THE LIGHTING PANEL (BY E.C.). BASEBOARD HEATERS UNITS SHALL CYCLE AS REQUIRED TO MEET SETPOINT, AS SET BY LOCAL THERMOSTAT. UNITS
ARE INTERLOCKED WITH ROOM THERMOSTAT SUCH THAT UNIT CANNOT BE ENERGIZED FOR HEATING IF CORRESPONDING RTU IS IN COOLING MODE. ELECTRIC HEATER -VESTIBULE UNIT SHALL CYCLE AS REQUIRED TO
MEET SETPOINT VIA LOCAL THERMOSTAT. ELECTRIC WATER HEATER UNIT SHALL MAINTAIN A DOMESTIC HOT WATER TEMPERATURE OF 110 DEG F. A HOT WATER RETURN RECIRCULATING PUMP SHALL BE CONTROLLED
VIA AQUASTAT, SET TO "ON" AT 100 DEGREES, "OFF" AT 108 DEGREES. ALTERNATE M1 BUILDING AUTOMATION CONTROLLER A. CONTROLLER SHALL ACCEPT MONITORING INPUTS FROM PACKAGED ROOFTOP UNITS,
RTU AIRFLOW MONITORS, EXHAUST FAN, HUMIDIFIERS, AND FAN COIL UNIT. CONTROLLER SHALL HAVE AN ONBOARD GRAPHIC OUTPUT AND REMOTE ACCESS MONITORING CAPABILITY. B. CONTROLLER SHALL MONITOR
OUTDOOR AIR DELIVERY. WHEN OUTDOOR AIR INTAKE IS 15% UNDER MINIMUM VENTILATION REQUIREMENT, AN ALARM DISPLAY AND SOUND SHALL BE GIVEN. C. WHEN THE CO2 SENSOR MEASURES ABOVE SPACE CO2
LIMIT, THE CONTROLLER SHALL SIGNAL THE CORRESPONDING RTU TO OVERRIDE AND ECONOMIZE TO 100% UNTIL THE SENSOR SIGNALS THAT THE SPACE CO2 THRESHOLD IS MET. D. EXHAUST FAN SCHEDULE/CONTROL
SHALL BE SWITCH FROM THE LIGHTING CONTROLLER TO THIS CONTROLLER. MICHAEL D. NICHT I ENGINEER REGISTERED 890360 STATE OF I I ND A AN No. PROFESSONAL ER * * COMMISSION NUMBER DATE SHEET
NUMBER SHEET TITLE The concepts, ideas, designs, plans, and details as shown on this document are the sole property of MSKTD & Associates, Inc., and were created, developed and presented
for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any person, firm, or corporation for any purpose whatsoever, without the expressed
written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE,
IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190 fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN
CERTIFICATION MSKTD 5629 BUILD 65076 CONSTRUCTION SET 3-21-11 3/18/2011 4:48:36 PM 100 W 96th St Indianapolis, Indiana 46290 M5.1 2-11-11 Indianapolis North Mechanical Schedules and
DetailsLake City Bank AIR HANDLING UNIT SCHEDULE MARK MANUFACTURER MODEL SIZE TOTAL CFM OA CFM ELECTRICAL SUPPLY FAN DX COOLING COIL GAS HEATING COIL ESP FAN HP EDB EWB LDB LWB OA AMB
SENS MBH TOTAL MBH STAGES MBH NOTES RTU-1 YORK D2NY 024 800 110 208/3/60 0.6 0.50 80 67 59.2 57.6 95 18.0 23.8 2 36.0 1-4 RTU-2 YORK D2NY 036 1200 200 208/3/60 0.6 0.75 80 67 59.6 58.0
95 26.5 34.3 2 36.0 1-4 RTU-3 YORK D2NY 036 1200 165 208/3/60 0.6 0.75 80 67 59.6 58.0 95 26.5 34.3 2 36.0 1-4 RTU-4 YORK D2NY 060 1800 345 208/3/60 0.6 1.00 80 67 58.2 56.4 95 42.4
59.8 2 65.0 1-4 RTU-5 YORK D2NY 036 1200 150 208/3/60 0.6 0.75 80 67 59.6 58.0 95 26.5 34.3 2 36.0 1-4 RTU-6 YORK D2NY 024 800 75 208/3/60 0.6 0.50 80 67 59.2 57.6 95 18.0 23.8 2 36.0
1-4 RTU-7 YORK D2NY 036 1200 155 208/3/60 0.6 0.75 80 67 59.6 58.0 95 26.5 34.3 2 36.0 1-4 RTU-8 YORK D2NY 060 1800 75 208/3/60 0.6 1.00 80 67 58.2 56.4 95 42.4 59.8 2 65.0 1-4 General
Mechanical Specifications: Not to Scale HVAC Isometric -For Reference EXHAUST FAN SCHEDULE TAG MANUFACTURER MODEL CFM ESP IN. WC ELECTRICAL HP MOUNTING STYLE DRIVE SONES SERVICE NOTES
EF-1 COOK 100C2B 600 0.8 115/1/60 1/6 ROOF DOWNBLAST BELT 10.1 RESTROOMS 1 Typical Duct Take Off Detail Return Grille and Sound Boot Detail Diffuser/Duct Connection Detail Typ. Divided
Flow Branch Connection Typ. Duct Elbow Detail Mechanical Engineering Symbols Mechanical Schedule 1. FURNISH WITH BIRDSCREEN, ROOF CURB, INTEGRAL DISCONNECT, AND BELT TENSIONER. 2. ON/OFF
OPERATION BY LIGHTING CONTROLLER (BY E.C.). DIFFUSER, GRILLE AND REGISTER SCHEDULE TAG MANUFACTURER MODEL SIZE (IN) INLET (IN) MATERIAL COLOR PATTERN MOUNTING NOTES EG-1 PRICE 80F-NT
12x12 10x10 ALUMINUM WHITE EGG CRATE LAY-IN EG-2 PRICE 80F-NT 24x24 22x22 ALUMINUM WHITE EGG CRATE LAY-IN EG-3 PRICE 80F-NT 12x12 10x10 ALUMINUM WHITE EGG CRATE LAY-IN 3 RG-1 PRICE 80F-NT
12x12 10x10 ALUMINUM WHITE EGG CRATE LAY-IN 3 SD-1 PRICE SPD 24x24 6 STEEL WHITE SQUARE PLAQUE LAY-IN SD-2 PRICE SPD 24x24 8 STEEL WHITE SQUARE PLAQUE LAY-IN SG-1 STEELCREST CUSTOM 12x10
12x10 STEEL WHITE 1/2" SQUARE SURFACE 1,2 1. FURNISH WITH CONCEALMENT LOUVERS AND PATTERN STYLE "MISSION".. 2. SUPPLY GRILLE SHALL BE FABRICATED TO MATCH THE CURVATURE OF THE WALL (ALONG
THE 12" DIMENSION) -18 FOOT RADIUS. 3. BORDER IS 24"x24". 1. FURNISH WITH BAROMETRIC RELIEF. 2. FURNISH WITH STRION AIR A130 MERV13 FILTERS OR APPROVED LOW-PRESSURE DROP MERV13 MEDIA.
3. FURNISH WITH MANUFACTURER-PROVIDED PROGRAMMABLE THERMOSTAT. 4. SEPERATE DISCONNECT BY E.C. Alternate M1 Sequence of Operations Revisions: Date: By: