HomeMy WebLinkAboutP2-1 - Plumbing Domestic Water, Gas and Fire Floor Plan.pdf
T inot cepoC ithgry702 A D F H 23 I J K L 578 10 11 X B E G 46 Y 9 3/4"ø 3/4"ø 1 1/2"ø 1"ø 1"ø 3/4"ø 3/4"ø 1"ø 1 1/2"ø 3/4"ø3/4"ø 3/4"ø 3/4"ø 2"ø 3/4"ø 2"ø 3/4"ø 3/4"ø 1 1/4"ø 3/4"ø
3/4"ø 2"ø 3/4"ø 3/4"ø 1"ø S-1 S-2 L-1H L-1H L-1H L-1H WC-1H WC-1H WC-1H WC-1H L-1H WC-1H EWC-1 U-1H L-1H WC-1H U-1H S-2 MB-1 EWC-1 FD-1FD-1 FD-1 FD-1 FD-1 1"ø RCP-1 CITY WATER METER
FIRE PROTECTION RISER, VALVE TRAIN, SEE DETAILS 3/4"ø 3/4"ø TO REFRIGERATOR ICEMAKER TO DISHWASHER TO FREEZEPROOF SILCOCK 3/4"ø 2"ø 3/4"ø 1"ø OFFICE 122 OFFICE 123 OFFICE 124 OFFICE
125 VISITING OFFICE 126 VISITING OFFICE 127 BREAKROOM 133 TELLER WORKROOM 136 SAFE DEPOSIT 138 TELLER AREA 137 BANKING LOBBY 139 CONFERENCE RM 140 OFFICE 119 OFFICE 118 OFFICE 117 OFFICE
116 OFFICE 115 CONFERENCE 112 WAITING 110 COATROOM 111 OPEN OFFICE 120 HALLWAY 114 HALLWAY 121 WORKROOM 128 SERVER 129 ELECT 108 HALLWAY 107 HALLWAY 102 PUBLIC MEETING ROOM 106 LOBBY
101 VESTIBULE 100 OFFICE 144 OFFICE 143 OFFICE 142 OFFICE 141 HALLWAY 130 MEN 131 HALLWAY 103 WOMEN 104 MEN 105 WOMEN 132 TABLE/CHAIR STORAGE 109 1"ø G UP TO ROOF FD-2 2"ø HUM-4 HUM-8
9 P5.1 FD-2 FD-2 HUMIDIFIERS CW HW HW CW HWCW CW HW CW CW CW HW CWHW HW CW HWCW G G HWR HWR HWR HWR BACKFLOW PREVENTER, SEE DETAILS OUTDOOR GAS METER UP FROM UNDERGROUND 4 1 2 1 4 4
4 4 5 4 3 5 HUMIDIFIER CW SUPPLY 3/4"ø 1"ø 1"ø 1 1/4"ø 1 1/4"ø EWH-1 UNDERGROUND CW/FIRE PIPED 5' OUTSIDE BUILDING BY THIS CONTRACTOR 5 6 7 8 6 8 9 WATER SHOCK ABSORBER REC REC 9 9 10
11 AFTER WATER METER, ROUTE 1"Ø CW TO SUBMETER AND RPZ, THEN 5' OUTSIDE BUILDING FOR IRRIGATION. SEE DETAIL. 3/4"ø 12 12 HB-1 HB-1 MICHAEL D. NICHT I ENGINEER REGISTERED 890360 STATE
OF I I ND A AN No. PROFESSONAL ER * * COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE The concepts, ideas, designs, plans, and details as shown on this document are the sole property
of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any
person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information
and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190
fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN CERTIFICATION MSKTD 5629 BUILD 65076 CONSTRUCTION SET 3-21-11 3/18/2011 4:48:58 PM 100 W 96th St Indianapolis,
Indiana 46290 P2.12-11-11 Indianapolis North Plumbing Domestic Water, Gas and Fire Floor Plan Lake City Bank 1/8" = 1'-0" Plumbing First Floor Domestic Water, Gas and Sprinkler Plan
P2.1 CONSTRUCTION NOTES 1 HUMIDIFIER LOCATIONS AS SHOWN AND PER SECTION ON SHEET P5.1. REFER TO DETAIL ON SHEET P5.1 FOR INSTRUCTIONS, ELEVATIONS, ETC. STEAM PIPING NOT SHOWN. USE AS
FEW 90° ELBOWS AS POSSIBLE. 2 FURNISH AND INSTALL TRAP PRIMER DISTRIBUTION UNIT TO SERVE THESE TWO FLOOR DRAINS IN ROOM 109. 3 PROVIDE REGULATOR TO GAS LINE SERVING WATER HEATER. VENT
REGULATOR THROUGH ROOF. 4 FURNISH INLINE TRAP PRIMER TO SERVE ADJACENT FLOOR DRAIN. 5 PAINT EXPOSED PORTIONS OF GAS PIPE TO MATCH EXTERIOR OF BUILDING. 6 EXTEND 1/2" CW LINE WITH BALL
VALVE, STRAINER TO EACH HUMIDIFIER. FOLLOW MANUFACTURER'S RECOMMENDATIONS. 7 SPRINKLER MAIN TO SERVE BUILDING. PROVIDE A FULLY WET SYSTEM PER NFPA 13 REQUIREMENTS. CONTRACTOR TO DEVELOP
DRAWINGS AND SUBMIT TO STATE. 8 FURNISH AND INSTALL HOT WATER RETURN BALANCE VALVE. SET TO 0.5 GPM. 9 TOILET FLUSH HANDLES SHALL BE OPPOSITE THE CLOSEST STALL WALL. 10 SPRINKLER LINE
FOR LOBBY 101 SHALL ENTER ROOM TIGHT TO UNDERSIDE OF BEAM AND SHALL RISE BETWEEN COLUMN AND WINDOW MULLION. PAINT TO MATCH STEEL COLUMN. 11 SPRINKLER LINE FOR VESTIBULE 100 SHALL DROP
BETWEEN COLUMN AND WINDOW MULLION. PAINT TO MATCH STEEL COLUMN. 12 ROUTE 1/2" CW LINE DOWN WALL TO SERVE COUNTERTOP COFFEE MACHINE. FURNISH ESCUTCHEON PLATE AT WALL PENETRATION. Revisions:
Date: By: