1. ALL WORK SHALL CONFORM TO STATE AND LOCAL PLUMBING AND BACKFLOW PREVENTION CODES, AND THE REQUIREMENTS OF THE LOCAL WATER UTILITY. 2. VACUUM BREAKERS MUST BE INSTALLED ON ALL PROPOSED
HOSE THREAD FITTINGS, INCLUDING BUT NOT LIMITED TO HOSE BIBBS, WALL/YARD HYDRANTS, MOP/SERVICE SINKS. 3. A CROSS-CONNECTION CONTROL DEVICES INSPECTOR SHALL TEST ALL BACKFLOW DEVICES
AT THE TIME OF INSTALLATION AND SUBMIT REPORTS TO THE LOCAL WATER UTILITY AS REQUIRED. 4. COORDINATE EXACT LOCATION OF ROOF DRAINS WITH ARCHITECTURAL AND STRUCTURAL PLANS. 5. ALL MATERIALS
INSTALLED WITH PLENUM SHALL HAVE FLAME SPREAD RATING OF NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING NOT EXCEEDING 50 IN ACCORDANCE WITH STATE CODES. 6. THIS CONTRACTOR SHALL PROVIDE
ALL EQUIPMENT, MATERIALS AND LABOR FOR CORE DRILLING AS REQUIRED FOR INSTALLATION OF PIPING PENETRATING BUILDING CONSTRUCTION. 7. ALL EQUIPMENT USING NATURAL GAS SHALL HAVE A GAS COCK
AND DIRT LEG FOR EACH PIECE OF EQUIPMENT. 8. REFERENCE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS, TYPICAL. 9. ALL NATURAL GAS PIPING SERVING RTU'S ARE LOCATED ON ROOF. SEE SHEET M2.2.
10. CONNECT PLUMBING FIXTURES TO PIPING INDICATED PER THE PLUMBING FIXTURE/EQUIPMENT CONNECTION SCHEDULE AND/OR AS NOTED. REFER TO PIPING ISOMETRICS FOR ADDITIONAL PIPING REQUIREMENTS.
11. COORDINATE MECHANICAL PENETRATIONS OF/WITH OTHER WORK TO AVOID INTERFERENCES, SEAL PENETRATIONS AS NOTED AND/OR SPECIFIED. 12. PIPING INVERTS AND/OR ELEVATIONS INDICATED ARE PRELIMINARY
IN NATURE AND ARE FOR COORDINATION ONLY. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING AND ESTABLISHING FINAL INVERTS AND/OR ELEVATIONS. INDICATE FINAL INSERTS AND/OR ELEVATIONS
ON RECORD DOCUMENTS. 13. REFER TO ARCHITECTURAL PLANS FOR WALL TYPES IN WHICH PLUMBING IS TO BE INSTALLED. COORDINATE PLUMBING INSTALLATION WITH OTHER WORK. 14. STORM PIPING SHALL BE
SCHEDULE 40 STEEL OR PVC, INSULATED WITH 1/2" ELASTOMERIC OR OTHER PLENUM-RATED INSULATION COVERING. 15. STEAM PIPING SHALL BE TYPE L COPPER WITH 1-1/2" FIBER INSULATION. 16. ANY PVC
USED AS WASTE/VENT PIPING ABOVE GROUND SHALL BE COVERED IN A PLENUM-RATED MATERIAL. CO-1 CLEANOUT -FLOOR ZURN Z-1400-NL "LEVEL-TROL" ADJUSTABLE FLOOR CLEANOUT. DURA-COATED CAST IRON.
SIZE PER LOCAL PLUMBING CODE. (JOSAM 58360 IS APPROVED EQUAL.) CO-2 CLEANOUT -WALL ZURN Z-1441 WALL CLEANOUT WITH ROUND STAINLESS STEEL ACCESS COVER. SIZE PER LOCAL PLUMBING CODE. (JOSAM
58910 W/58600 IS APPROVED EQUAL.) CO-3 CLEANOUT -OVERHEAD JOSAM 58900 SERIES COATED CAST IRON CLEANOUT FERRULE, NO-HUB CONNECTION, BRONZE COUNTERSUNK PLUG. SIZE PER LOCAL PLUMBING CODE.
FD-1 FLOOR DRAIN -ROUND WITH CLEANOUT -6", 2" CONNECTION JOSAM #30500-A SERIES CAST IRON COMBINATION FLOOR DRAIN AND INTEGRAL DEEP DRUM "P" TRAP WITH DOUBLE DRAINAGE FLANGE, WEEP HOLES,
SIDE OUTLET SPIGOT CONNECTION, NIKALOY INTEGRAL FLUSH-WITH-FLOOR CLEANOUT AND ADJUSTABLE SATIN NIKALOY 6" ROUND STRAINER. FD-2 FLOOR DRAIN -ROUND WITH CLEANOUT -8", 3" CONNECTION JOSAM
#30500-A SERIES CAST IRON COMBINATION FLOOR DRAIN AND INTEGRAL DEEP DRUM "P" TRAP WITH DOUBLE DRAINAGE FLANGE, WEEP HOLES, SIDE OUTLET SPIGOT CONNECTION, NIKALOY INTEGRAL FLUSH-WITH-FLOOR
CLEANOUT AND ADJUSTABLE SATIN NIKALOY 8" ROUND STRAINER. ALL FLOOR DRAINS SHALL HAVE DEEP SEAL TRAPS. WHERE ANY TYPE FLOOR DRAIN IS NOT SPECIFIED FOR A GIVEN LOCATION, IT SHALL BE THE
SAME AS USED ELSEWHERE IN SIMILAR LOCATIONS AND/OR SIMILAR USAGE. RD-1 ROOF DRAIN ZURN #ZC100 15" DIAMETER DURA-COATED CAST IRON BODY, COMBINATION MEMBRANE FLASHING CLAMP/GRAVEL GUARD
AND LOW SIHOUETTE CAST IRON DOME. (JOSAM #21500-AE SERIES IS AN APPROVED EQUAL.) ORD-1 OVERFLOW ROOF DRAIN ZURN #ZC100-W2 15" DIAMETER DURA-COATED CAST IRON BODY, COMBINATION MEMBRANE
FLASHING CLAMP/GRAVEL GUARD, LOW SIHOUETTE CAST IRON DOME, 2" INTERNAL WATER DAM. (JOSAM #21500-AE-16 SERIES IS AN APPROVED EQUAL.) L-1H LAVATORY -WALL MOUNTED, ADA A. AMERICAN STANDARD
#0495.300 "OVALYN" VITREOUS CHINA, UNDERCOUNTER LAVATORY WITH 4" FAUCET CENTERS, 17"x14"x5-1/2" DEEP, ROUND, WHITE. B. ZURN Z6915 "AQUASENSE" LAVATORY FAUCET WITH 0.5 GPM AERATOR. HARDWIRED.
C. 1 1/4" POLISHED CHROME, CAST BRASS, ADJUSTABLE "P" TRAP, CLEANOUT PLUG, TAPPED OUTLET FOR I.P. D. 3/8" I.P.S. ANGLE SUPPLIES WITH LOOSE KEY STOPS AND ANNEALED VERTICAL TUBES. E. LAVATORY
TO BE MOUNTED AT 34" TO RIM (COUNTERTOP). F. OFFSET DRAIN ASSEMBLY FOR WHEELCHAIRS. G. TRUEBRO MODEL #103 HANDI LAV-GUARD INSULATION KIT. WC-1 WATER CLOSET -WALL HUNG, FLUSH VALVE A.
AMERICAN STANDARD "AFWALL" FLOWISE EL ADA1.1/1.6 GPF HIGH EFFICIENCY TOILET SYSTEM, ELONGATED BOWL, WALL MOUNTED AT 15" TO RIM, 1 1/2" TOP SPUD, 2-1/8" FULLY GLAZED TRAPWAY WITH SIPHON
JET ACTION. B. ZURN MODEL #P6000-M-ADA-DF HIGH EFFICIENCY DUAL-FLUSH FLUSHOMETER VALVE. C. JOSAM SERIES #12674-HS, 12684-HS, 12694-HS CAST IRON CLOSET CARRIER -ADJUSTABLE CLOSET CONNECTION,
ADJUSTABLE FEET, CHROME PLATED TRIM AND COATED ACCESSORIES FOR USE WITH TOILET SPECIFIED WITH TEST CAP. (J.R. SMITH IS APPROVED EQUAL) D. ELONGATED OPEN FRONT SEAT WITH STAINLESS STEEL
CHECK HINGE. (OLSONITE AND CHURCH ARE APPROVED.) WC-1H WATER CLOSET -WALL HUNG, FLUSH VALVE, ADA A. AMERICAN STANDARD "AFWALL" FLOWISE EL ADA1.1/1.6 GPF HIGH EFFICIENCY TOILET SYSTEM,
ELONGATED BOWL, WALL MOUNTED AT 17" TO RIM, 1 1/2" TOP SPUD, 2-1/8" FULLY GLAZED TRAPWAY WITH SIPHON JET ACTION. B. ZURN MODEL #P6000-M-ADA-DF HIGH EFFICIENCY DUAL-FLUSH FLUSHOMETER
VALVE. C. JOSAM SERIES #12674-HS, 12684-HS, 12694-HS CAST IRON CLOSET CARRIER -ADJUSTABLE CLOSET CONNECTION, ADJUSTABLE FEET, CHROME PLATED TRIM AND COATED ACCESSORIES FOR USE WITH TOILET
SPECIFIED WITH TEST CAP. (J.R. SMITH IS APPROVED EQUAL) D. ELONGATED OPEN FRONT SEAT WITH STAINLESS STEEL CHECK HINGE. (OLSONITE AND CHURCH ARE APPROVED.) U-1H URINALS -AUTO FLUSH, ADA
COMPLIANT A. ZURN MODEL #Z5738.205.00 "THE SMALL PINT" 1/8 GPF ECO-VANTAGE ULTRA LOW CONSUMPTION BATTERY POWERED URINAL SYSTEM. 3/4" TOP SPUD WITH MANUAL OVERRIDE BUTTON. B. JOSAM URINAL
CARRIER #17560-UR, COMPLETE WITH BLOCK FEET AND POSITIONING FRAME. (OR ZURN #Z-1222, AND J.R. SMITH ARE APPROVED EQUALS.) RETROFIT BRACKET AS REQUIRED. C. MOUNT AT 17" TO RIM. SC-1 SILCOCK
-FREEZING AREAS A. B&K INDUSTRIES MODEL #104-559HC FROST-FREE SILCOCK B. 3/4" HOSE OUTLET C. CHROME-PLATED LEAD-FREE SILVER SOLDER CONSTRUCTION EWC-1H ELECTRIC WATER COOLER -SPLIT-LEVEL
A. HALSEY TAYLOR #HTHB-HAC8BL "HAC", 3.7 AMPS, 325 W, 115/60/1, WALL MOUNTED, 8 GPH @50~F. INCLUDES "HYDROBOOST" BOTTLE FILLING STATION MOUNTED ON TOP. B. STAINLESS STEEL FINISH. C.
MOUNT AT 34.5" TO LOWER BUBBLER OUTLET. D. ZURN Z-1225 PLATE TYPE SYSTEM WATER COOLER SUPPORT WITH DURA-COATED STEEL UPRIGHTS, ADJUSTABLE SUPPORT PLATES AND MOUNTING. (JOSAM 17560-WCBL
EQUAL) S-1 SINK -SINGLE COMPARTMENT A. ELKAY #LRAD2219, BOWL: 18"x14"x6" DEEP, 18 GA. STAINLESS STEEL SELF-RIMMING SINGLE COMPARTMENT SINK WITH 3 FAUCET HOLES @4" CENTERS. B. ELKAY #LKLFD2439
DUAL HANDLE LOW-FLOW KITCHEN FAUCET, 3-4" CENTERS, WRISTBLADE HANDLES, 1.5 GPM AERATOR. C. #LK-35 BASKET STRAINER WITH NEOPRENE STOPPER AND TAILPIECE. D. P-TRAP, CHROME-PLATED CAST BODY
WITH CLEANOUT, ESCHUCHEON. E. SOLID BRASS ANGLES STOPS, CHROME PLATED, LOOSE KEY, CHROME-PLATED RISERS AND EXTENSION TUBES. F. FURNISH TEMPLATE TO COUNTER TOP SUPPLIER. S-2 SINK -SINGLE
COMPARTMENT A. ELKAY #LRAD1918, BOWLS: 16"x11-1/2"x6" DEEP, 18 GA. STAINLESS STEEL SELF-RIMMING SINGLE COMPARTMENT SINK WITH 3 FAUCET HOLES @4" CENTERS. B. ELKAY #LKD2438BH DUAL HANDLE
LOW-FLOW KITCHEN FAUCET, 3-4" CENTERS, WRISTBLADE HANDLES, 1.0 GPM AERATOR. C. #LK-35 BASKET STRAINER WITH NEOPRENE STOPPER AND TAILPIECE. D. P-TRAP, CHROME-PLATED CAST BODY WITH CLEANOUT,
ESCHUCHEON. E. SOLID BRASS ANGLES STOPS, CHROME PLATED, LOOSE KEY, CHROME-PLATED RISERS AND EXTENSION TUBES. F. FURNISH TEMPLATE TO COUNTER TOP SUPPLIER. MB-1 MOP BASIN -SHEET MOLDING
COMPOUND A. FIAT #MSB-2424 24"x24", 10" HIGH WALLS. B. FIAT #830AA FAUCET SET. C. FIAT #832AA HOSE AND HOSE BRACKET. D. FIAT #833AA SILICON SEALANT. E. INCLUDE 2" P-TRAP. F. FIAT#889-CC
MOP BRACKET 24"x3" WIDE STAINLESS STEEL WITH THREE RUBBER GRIPS. RCP-1 RECIRCULATION PUMP -DOMESTIC HOT WATER A. GRUNDFOS MAGNA 25-60N, 1/12 HP; 115/1/60 B. 1 GPM, 20 FT. HEAD C. CAST
BRONZE PUMP BODY D. STAINLESS STEEL FACE PLATE E. 30% GLASS FILLED NORYL IMPELLOR F. SOLID HIGH-STRENGTH ALLOY STEEL SHAFT G CARBON/SILICON CARBIDE SEAL SYSTEM H. PERMANENTLY LUBRICTED
SEALED BEARINGS I. AQUASTAT BFP-1 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER A. WILKINS MODEL #975XL; 2" B. CAST BRONZE (ASTM B 854) MAIN VALVE BODY AND ACCESS COVER C. STAINLESS
STEEL (300 SERIES) SPRINGS AND FASTENERS D. SILICONE SEAT DISC; NSF LISTED NORYL SEAT RING AND INTERNAL POLYMERS E. THE FIRST AND SECOND CHECKS SHALL BE ACCESSIBLE FOR MAINENTANCE WITHOUT
REMOVING THE RELIEF VALVE OR THE ENTIRE DEVICE FROM THE LINE F. INCLUDE AIR GAP ET-1 EXPANSION TANK -POTABLE HOT WATER AMTROL "THERM-X-TROL" ASME MODEL # ST-5-C, 2.1 GAL TOTAL VOLUME,
0.9 GAL MAX MAXIMUM ACCEPTANCE, 3/4" NPT CONNECTION EWH-1 WATER HEATER A. A.O.SMITH MODEL ECL-30 PROMAX LOWBOY B. HEATER STORAGE: 30 GAL C. INPUT: 4500 W AT 240 V, ENERGY FACTOR 0.93
D. HEATER RECOVERY: 21 GPH @90 DEGREE RISE DSP-1 KITCHEN SINK DISPOSAL A. INSINKERATOR "BADGER 5" SINK DISPOSAL B. B. 1/2 HP, 120V/1/60, 1725 RPM, 6.9 AVERAGE AMP. GWHPVRDHBEWCLSSA SHTMSDFFDEWH
VTR MBMV-**-*H WCPRVPCOUSOFT SOFTENED WATER G WASTE PIPING ELECTRIC WATER COOLER HOSE BIB STORM WATER PRESSURE REDUCING VALVE HOSE BIB MOP BASIN AUTOMATIC PLUMBING VENT GAS WATER HEATER
THERMOMETER INDICATES DIRECTION OF FLOW ROOF DRAIN SINK SHOCK ABSORBER URINAL DRINKING FOUNTAIN FLOOR DRAIN FOLLOW ADA GUIDELINES LAVATORY ELECTRIC WATER HEATER WASTE/STORM PIPING (UNDERGROUND)
WATER CLOSET SHOWER PUMP VENT THROUGH ROOF CLEAN OUT MOP SINK MIXING VALVE COLD WATER GATE VALVE RISER UP (TEE) RISER UP (ELBOW) RISER DOWN (ELBOW) RISER DOWN (TEE) HOT WATER DOUBLE
BACK FLOW PREVENTER UNDERGROUND UTILITY SERVICE TEE UNION CHECK VALVE BALL VALVE RECIRCULATING HOT WATER GAS COCK BUTTERFLY VALVE VENT PIPING OXYGEN DEIONIZED WATER CONNECT NEW TO EXISTING
GAS PIPING METER THERMOMETER PRESSURE GAUGE ST DE MNOTE: SOME SYMBOLS MAY NOT BE USED O SAN PLUMBING ROUGH-INS FIXTURE WASTE VENT HOT COLD SH-* 2" 3/4" 3/4" L-* S-* EWC-* ---1/2" 1/2"
1/2" 1/2" ---1/2" ---1/2" ------3" 3" WC-* U-* 3/4" 1" 3/4" 1 1/2" 1 1/2" ---2" 1 1/2" 1 1/2" 1 1/2" ---MB-* HB-* FD-* ------2" 4" ---1/2" 1 1/2" 1 1/2" ---FINISHED FLOOR COVER ADJUSTING
COLLAR RISER 1/8 BEND FULL SIZE, 4" MAX. CLEANOUT PLUG AND BODY. SEE SPECIFICATIONS PLUG IF END OF LINE FLOW DOMESTIC WATER METER BY LOCAL UTILITY. PAID FOR UNDER THIS CONTRACT 2" INCOMING
SERVICE TYP. BALL VALVE TEST COCK TYP., 1/4 TURN BALL VALVE TYP. STRAINER AIR GAP FUNNEL PROVIDED BY RPBP MFG. AS REQUIRED TO FLOOR DRAIN SIZE PER AIR GAP STATE APPROVED REDUCED PRESSURE
BACKFLOW PREVENTER ASSEMBLY TYP. FLANGED CONNECTION 60" MAX. 12" MIN. 1 1/2" BYPASS PEAK GPM = 40 AVG. GPM = 20 SUB-METER FOR IRRIGATION RPZ FOR IRRIGATION ROUTE UNDERGROUND TO 5' OUTSIDE
BUILDING FOR IRRIGATION 1" 2" CW TO BUILDING SERVICE TO FLOOR DRAIN SIZE PER AIR GAP REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLIES TO BE LOCATED BOTTOM MIN. 12" A.F.F., TOP MAX 60"
A.F.F. COLD WATER FEED TO OTHER FIXTURES TRAP PRIMER VALVE UNIT, PPP-PR500 OR SIMILAR 12" MINIMUM TO HORIZONTAL RUN OF PIPE P-TRAP FLOOR DRAIN TRAP PRIMER DISTRIBUTION UNIT, PPP DU-U
OR SIMILAR SPLIT PIPE CLAMP GRININEL 3138 OR EQUAL BLACK IRON GAS PIPE INSTALL PIPE LEVEL PIPE NIPPLE COORDINATE HEIGHTS 12x12 20 GAUGE GALV. PLATE ON ROOFING. NO GRAVEL UNDER PLATE
CLAMP SIZE 3" 2" 1 1/2" 1" FLANGE SIZE 1/2" 1/4" 1/4" 1/4" GAS SIZE 2" -2 1/2" 1 1/2" 1" -1 1/4" 1/2" -3/4" PATE STEPPED POLYVINYL CHLORIDE BOOT PATE SPUN ALUMINUM BASE ROOF MEMBRANE
PATE STAINLESS ADJUSTABLE CLAMPS INSULATION ROOF DECK PIPEFirst Floor Slab 100' -0" F G S2.1 Foundation Plan First Floor Slab 100' -0" HUM-5 HUM-6 HUM-7 ROUTE DRAIN LINES FROM HUM-1
HUM-2 HUM-3 HUMIDIFIERS ALONG WALL TO ADJACENT FD-2, TYP. ROUTE STEAM SUPPLY/CONDENSATE RETURN TO APPROPRIATE DISPERSION MANIFOLD PER MANUFACTURER'S RECOMMENDED SLOPE/ROUTING INSTRUCTIONS
(TYP.) HUMIDIFIER MARK NUMBERS CORRESPOND TO THE RTU SERVED (HUM-1 TO RTU-1, ETC.) FD-2 3' -6" 7' -0" 115V ELECTRIC ALARM BELL CHECK VALVE FIRE DEPARTMENT CONNECTION BALL DRIP 115V TAMPER
SWITCH 115V WATER FLOW INDICATOR TEE CONNECTION WATER GAUGE TEE CONNECTION MAIN DRAIN VALVE MAIN DRAIN (FLOW TEST LINE) DOUBLE CHECK VALVE ASSEMBLY (APPROVED FOR WILKINS BRAND ONLY)
RISER FROM MAIN WATER SUPPLY (6"Ø LEAD-IN) DRAIN PAN H = (1" FOR EACH 1" OF MAXIMUM NEGATIVE STATIC PRESSURE) + 1" J = H/2 L = H + J + PIPE DIAMETER + INSULATION L J H NOTES: 1. AHU
COMPONENT PRESSURE DROPS ARE BASED UPON THE SCHEDULED EQUIPMENT. CONTRACTOR TO INCREASE TRAP DEPTH (AND HOUSEKEEPING PAD HEIGHT) AS NECESSARY PER INSTALLED EQUIPMENT. 2. FILTER PRESSURE
DROP BASED UPON DIRTY FILTERS 3. APPLIES TO DRAW-THROUGH AIR HANDLING UNITS ONLY ET DRAIN VALVE HWR RECIRC. PUMP AQUASTAT STRAINER FLOOR DRAIN THERMOMETER ELECTRIC WATER HEATER BALL
VALVE PRESSURE & TEMPERATURE ASME RELIEF VALVE KUNKLE MODEL 912 LINE SIZE T & P RELIEF VALVE CHECK VALVE ON @100 OFF @108 HOT WATER CW D 110° F 110° F MOUNT APPROX. 6'-0" A.F.F, SUPPORT
AS REQUIRED FOR FULL OPERATING WEIGHT THIS CONTRACTOR SHALL INSTALL SPRINKLER SYSTEM THROUGHOUT THE ENTIRE NEW BUILDING PER NFPA 13. FIRE PROTECTION CONTRACTOR SHALL DEVELOP DRAWINGS
WITH LISTED EQUIPMENT AS REQUIRED, AND SUBMIT DRAWINGS TO THE STATE FOR APPROVAL. THIS CONTRACTOR MUST BE REGULARLY ENGAGED IN FIRE PROTECTION INSTALLATION. SPRINKLER HEADS SHALL BE
UPRIGHT, OR PENDANT WITH RECESSED ESCUTCHEON AS MANUFACTURED BY GRINNEL, VIKING, FIKE, OR AUTOMATIC. RECESSED HEADS SHALL BE OF THE BEST QUALITY CHROME PLATED, AND SHALL BE CENTERED
IN CEILING TILE. IN DRYWALL CEILINGS USE CONCEALED HEADS, HORIZON MIRAGE BY VIKING OR APPROVED EQUAL. IN ALL OTHER AREAS USE SEMI-RECESSED HEAD, MODEL M BY VIKING OR APPROVED EQUAL.
SYSTEM SHALL COMPLY WITH ALL LOCAL, STATE AND NFPA CODES AND OWNER INSURANCE AGENCY. ALL AREAS SHALL BE DESIGNED FOR LIGHT HAZARD. MICHAEL D. NICHT I ENGINEER REGISTERED 890360 STATE
OF I I ND A AN No. PROFESSONAL ER * * COMMISSION NUMBER DATE SHEET NUMBER SHEET TITLE The concepts, ideas, designs, plans, and details as shown on this document are the sole property
of MSKTD & Associates, Inc., and were created, developed and presented for use on this specific project. None of the concepts, ideas, designs, plans, and details shall be used by any
person, firm, or corporation for any purpose whatsoever, without the expressed written consent of MSKTD & Associates, Inc. The Owner shall be permitted to retain copies for information
and reference in connection with this project. 1715 MAGNAVOX WAY FORT WAYNE, IN 46804 voice 260.432.9337 fax 260.436.2402 930 NORTH MERIDIAN INDIANAPOLIS, IN 46204 voice 317.917.1190
fax 317.822.6236 http://www.msktd.com ARCHITECTURE ENGINEERING INTERIOR DESIGN CERTIFICATION MSKTD 5629 BUILD 65076 CONSTRUCTION SET 3-21-11 3/18/2011 4:50:52 PM 100 W 96th St Indianapolis,
Indiana 46290 P5.12-11-11 Indianapolis North Plumbing Schedules and Details Lake City Bank General Plumbing Notes: Plumbing Fixture Schedule: Plumbing Engineering Symbols Floor Cleanout
Detail Water Meter Backflow Preventer Detail Automatic Trap Primer Detail Not to Scale Natural Gas Pipe Support Not to Scale Pate Pipe Seal Detail Humidifier Wall Locations HUMIDIFIER
SCHEDULE MARK MANUFACTURER MODEL/SIZE ZONE SERVED STEAM CAP (LBS/HR) ADJ. RANGE MIN ELECTRICAL BREAKER SIZE NOTES HUM-1 Nortec NHTC-010 RTU-1 10 20% 208/1/60 25 1,2 HUM-2 Nortec NHTC-010
RTU-2 10 20% 208/1/60 25 1,2 HUM-3 Nortec NHTC-010 RTU-3 10 20% 208/1/60 25 1,2 HUM-4 Nortec NHTC-020 RTU-4 20 20% 208/3/60 30 1,2 HUM-5 Nortec NHTC-010 RTU-5 10 20% 208/1/60 25 1,2
HUM-6 Nortec NHTC-010 RTU-6 10 20% 208/1/60 25 1,2 HUM-7 Nortec NHTC-010 RTU-7 10 20% 208/1/60 25 1,2 HUM-8 Nortec NHTC-020 RTU-8 20 20% 208/3/60 30 1,2 1. FURNISH WITH CONDENSATE/BLOWDOWN
COOLER OPTION. 2. FURNISH WITH SHORT ABSORPTION MANIFOLD (SAM) FOR DISPERSION AT DUCTWORK (SIZED PER EACH DUCT, SEE SHEET M2.1). Not to Scale Wet Pipe Vertical Sprinkler Riser Condensate
Trap Detail Electric Water Heater w/Recirc. Detail Fire Protection Specification Revisions: Date: By: