HomeMy WebLinkAboutCorrespondenceMARK SWANSON ASSOCIATES INC. 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 October 14, 2004 Gary R. Duncan, Jr., P.E. (./~. Mr. Assistant City Engineer City of Carmel L~' L~, ~,) -~ © C? Department of Engineering One Civic Square Carmel, Indiana 46032 Re: Engineered Cooling Systems Plant Expansion - Crossroad Engineers Review Dear Mr. Duncan: We have the following comments to Crossroad Engineers 5-25-04, project review letter. Our comments follow Crossroad Engineers Review Checklist headings. Drainage Approval (City or County) OK. Detention Required - 100 yr. flood On 4-06-04, a storm drainage report developed by Mid-States Engineering was submitted to your office for review. The report analyzed the impact of the proposed addition including the additional parking. The report indicated a 0.005 cfs increase in the 100-year peak discharge and an increase of 0.07 feet in the 100-year water surface elevation. The existing 100oyear water surface elevation is 824.93. Increasing it by 0.07 ft raises the 100-year water surface elevation to 825.00 ,ff. The drawings indicate the emergency spillway elevation to be 826.00 ft. The new 100-year water surface elevation is Ift below the emergency spillway elevation. The drainage report concluded that. due to the small increases of the approved data, no improvements on any existing storm water structures are proposed. Drainage Calculations OK Pipe Design - 10 yr flood OK Pipe Slopes / Velocities OK Adequate Lot Drainage OK Surface drainage shown Sheet C-2, SITE GRADING PLAN, indicates drainage pattems on the new parking areas with directional arrows. The arrows indicate drainage sheet flows to inlets located and identified on the drawing. The minimum pavement slope is N" per ft. Adequate Easement Widths OK Grading Elevations Shown Sheet C-2, SITE GRADING PLAN, shows a sedes of existing elevation spot grades, new top of curb spot grades and new paving spot grades along with. sections that descdbe the profile of the ditch, top of bank, new curbs and paving and existing paving that sufficiently describes the new construction. The new 100-year water surface elevation is established at 825 ft. (see above comments) and the emergency spillway elevation is set at 826 ft. The proposed pavement and curb along the existing pond has been held behind elevation contour 827, and does not encroach into the storage area. Structures Numbers / Corresponding to Previous Sections OK Pipe Sizes OK Overflow Location Shown OK Off-Site information OK Existinq sewers and structures .... OK Please forward a copy of our comments to Crossroad Engineers as you have with previously submitted correspondence. Sincerely, M IA~'~INC. Dennis L. Lockwooo Project Architect Cc: Jon Dobosiewicz, DOCS John Duffy, Carmel Utilities Paul Pace, Carmel Utilities Jim Haag, Carmel Utilities Greg Hoyes, Hamilton County Surveyor's Office John South, Hamilton County Soil & Water Conservation District September 30, 2004 C JAMES BRMNARD, MAYOR L Mr. Dennis L. Lockwood Mark Swanson Associates, Inc. 10610 North Park Avenue Indianapolis, IN 46280 RE: Engineered Cooling Systems Plant Expansion-Project Review #2 Dear Mr. Lockwood: The City has received your comment letter and revised drawings dated May 11, 2004 based on the City review of April 16, 2004. The comments from the City have been satisfactorily addressed. However, we are not able to determine that you have addressed the drainage review comments from Crossroad Engineers. A copy of these comments was sent to you on May 25, 2004 and another copy is included with this letter. If you have not yet responded to those, please do so at this time. If you have previously responded to the drainage review comments, please send us a copy of the responses. The above comments are based on the Engineering Department's second review. If you have questions, please contact me at 571-2441. Sincer. d~ ~ // ineer cc: Joff Dobosiewicz, Department of Community Services John Duffy, Carmel Utilities Paul Pace, Carmel Utilities Jim I-:Iaag, Carmel Utilities Greg Hoyes, Hamilton County Surveyor's Office John South, Hamilton County Soil & Water Conservation District Greg Ilko, Crossroad Engineers S:WROJREV03\ENGCOOLSYSEXPANSION - REVIEW 2 DEPARTMENT OF ENGINEERING ONE CIVIC SQ15kRE, CAIL\IEL, IN 46032 OFFICE 317.571.2441 E.xmk engineering@ci.carmel.in.us FAX 317.571.2439 tolT5 .]'.~MES BR_-U×.-U~,.D? I¥1'~YOR May 25, 2004 Mr. Dennis L. Lockwood Mark Swanson & Associates, Inc. 10610 North Park Avenue Indianapolis, IN' 46280 RE: Crossroad Engineer's Drainage Review-Engineered Cooling System Dear Mr. Lockwood: We have engaged Crossroad Engineers, PC, to review storm drainage plans and drainage calculations for all projects submitted to the Department of Engineering for review/comments. I am sending copies of the Crossroad reviews for the follow/ng: ' · Engineered Cooling Systems Plant Expansion Please respond to all issues raised in these reviews. Sincerely, Dick Hill, Assistant Director Department of Engineering Enclosures Cc~ Mike McBride 'P.E., City Engineer Gary Duncan P.E., Assistant Cit-),' Engineer Greg Hoyes, Han'filton County Surveyor's Office S:XJ'ROJP. EV04 .,CROSSRDENGENGiNEEREDCOOL Civic Sc,~':x~i. C..:!:.:I!tl. IN -i6r).~,2 t)~'~I'~-!' 317.571.2441 t:,xx 317.571.2-539 Technical Advisory Committee Engineering Review Checklist for Commercial Designs Project Name' Engineered Coolin$ System Plant Expansion _ Owner' Engineered Cooling Systems Location: 201 W. Carmel Drive Section(s)' Date Received: April 22, 2004 Review Date: May 18, 2004 T.A.C. Date: [---] PrimaD' [-~ 1st Review Construction T.A.C. Review Drainage Drainage Approval (City or County) The Engineered Cooling Systems Plant Exflansion is under the jurisdiction of the CiO' of Carmel. Drainage Calculations Drainage calculations have been submitted Detention Required - 100yr flood Detention has been accommodated within a previously improved plan; however, it apflears that the proposed Rarking is impacting the existing storage volume. Please provide data for the stage/storage of the pond in proposed conditions. This stage/storage, ~d~ferent than existing, should be reflected in the detention analysis calculations included in thc Drainage Report. . '~.',.:.7 ;~ 2-. '' t"t ' RECEIVED '"-... ENGINEER "' '~'~.~ ..... Pipe Design- 10 yr flood. :V/A Pipe Slopes / Velocities A7,4 Adequate Lot Drainage It appears that the drainage is adequate off the lot and to the detention area. Surface drainage shown · Existing drainage patterns are shown, but the new parking drainage is not clearly indicated. Please show bi,' drainc:ge arrows, percent slopes, etc. the sheet flow off of the proposed pavement. Adequate Easement Widths N/A - Grading Elevations Shown There is not a sufficient amount of proposed grades or existing contours shown on the plan. The actual impact of the new c~trb to the bank of Ha'wkins ditch cannot be determined without existing ~ontours and proposed top of curb grades. Please supply sufficient i~ormation on the construction plans. It appears that the proposed pavement adjacent to the existing pond encroaches into the storage area. Proposed grades of 82Z O0 are seen overlapping the limits of the detention area, which per the drainage report are at an elevation of 826.00. Please explain/show how the proposed grading is going to be accomplished without reducing the storage volume of the existing pond. Structures Numbers / Corresponding to Previous Sections N/A _Pipe Sizes N/A Overflow Location Shown The existing overflow location is indicated on the plan Off-Site information (i.e. tying into sewers in existing sections or preparing for future sections) The existing storm sewer which is being used to route storm water to the existing detention is shown on the plans. Existing sewers and structures labeled and./or drawn as such, including as-built elevations -drainage calculations based upon as-built situation, not original plans. It ctppears thr~t the existing in~'erts are from c~ recent topogrctphical st~r~'e)'. Additional Questions / Comments None. MARK SWANSON ASSOCIATES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 LETTER OF TRANSMITTAL To: Department of Community Services One Civic Square Carmel, Indiana 46032 A Regarding: 2004 )na Hancock ECS Plant Exp. Docket No.: 04030046 DP Amend/ADLS Amend We are sending you: Under Separate Cover I Attached FI Presentation Dwgs. F1 Preliminary Plans O Specifications [~ Copy of Letter Shop Drawings Clarification dwg. Samples Documents Fl Change Order [} Construction doc. E] Reproducibles Fl For approval 0 Review and Comment E} Approved as submitted 1'] For your use Fl Correct and Resubmit {~ Approved as noted D For distribution For your files As Requested Copies/Sets Number Description 1 copy Petitioner's Affidavit of Notice of Public Hearing. 1 copy Hamilton County Auditor's Adjoiner list 1 copy Hamilton County Auditor's Adjoiner Affidavit. 2 copies Publisher's Affidavit. 1 copy each U.S. Postal Service certified mail receipts. 1 copy each Certified mail green signature cards. Remarks: Copies to: . Signed: ~.MAY 13 '04 12:02PM jJ P.1/2 .'Kenton C. 'U/ard, Sumeyol' (I'f1O"" (3 T7) 776-84';15 'FII.\' (;17) 776-9/hS Suit" 188 Olle .7{t1Jl1illo/t COl/nty SIf/JiJl'~ .7'fobbllille, [lIdi11110 4606(\-,Zj.Jtl May 12; 2004 Mark Swanson Associates, Inc. A TTN: Dennis Lockwood 10610 North Park Avenue Indianapolis, IN 46280 VIA FACSIMILE: 844-1758 Re:Engineer Cool Systems Dear Mr. Lockwood: This letter is to follow-up on the discussion and requirement that were determined at the meeting in our office on May 11, 2004. The meeting was attended by the owner of Engineered Cooling Systems, Mark Swanson and you, along with Kent Ward and me, The following requirements were determined: 1. This office will require a new non-enforcement agreement for the parking lot that will referenoe the 5' previous agreed parking encroaclunent and the survey done that establishes the top of bank.. This will need to be submitted to our office and approved by the Hamilton County Drainage Board. 2. Engineered Cooling Systems will remove or trim any trees that will interfere with the new proposed parking area being installed. This should only affect tree along the natural top of bank and will be at the discretion of Engineered Cooling Systems. 3. The Hamilton County Surveyor's Office will require the removal of the under- canopy, any trees that lean and could fall into the channel, or any dead tree on the eastern bank of the open ditch. Also any brush or debris will need to be removed from the bank to ensure it does not float downstream and get caught in a structure. causing a flooding event. :i' MRY 13 '04 12:03PM .. P.2/2 4. An on-site meeting should be scheduled when the clearing/clean-up is to begin to determine what is the Wlder-canopy and what large trees that can be left in place. Please give me a call before this begins to schedule the on-site meeting. 5. Please submit the latest construction plans that address all the T AC comments. 6. Please note that further comments may be necessary at a later date. Should you have any questions~ I can be reached at 317-776-8495. Sincerely. ~ fItr~ Greg Hayes Plan Reviewer ~~ on Dobosiewicz - Carmel DOCD~~>-~ fflhn-8outh---HC weD Dick Hill - Carmel Engineering Scott Brewer - City of Cannel MARK SWANSON ASSOCIA TES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA' 46280 317-844-1315 FAX 844-1 758 May 10, 2004 Mr. Jon Dobosiewicz Planning Administrator City of Carmel Department of Community Services One Civic Square Carmel, Indiana 46032 :>OD 4lt ~O o Dear Jon: Re: 10 Engineered Cooling Systems Plant Expansion ~ tt i\ tjA1E~~IV!D (v'Or -' DOCS Please find attached documents responding to issues that ca meeting. 1. Revised Sheets: C-1, Existinq Site Conditions Plan C-2, Site Gradinq Plan/Erosion Control Plan C-3, Site Development Plan L-1, Landscape Plan 2. Comments from Greg Hoyes, Hamilton County Surveyor's Office dated 4-29- 04, regarding Hawkins Ditch along west property line. 3. Letter from Mid-States Engineering dated 4-29-04, responding to comments in Hamilton County Surveyor's Office letter dated 4-19-04. 4. Mark Swanson Associates letter dated 5-10-04, responding to comments from Dick Hill, City of Carmel, Department of Engineering in letter dated 4-16-04. 5. Mark Swanson Associates letter dated 5-10-04, responding to comments from John South, Hamilton County Soil and Water Conservation District in letter dated 4-26-04. 6. Photo of proposed bulk storage silo. Silo for ECS will not have a funnel base as shown in the photo but will have straight sides, This is the closest photo the manufacturer could provide for what will be built 7. Photo of existing cooling tower. t,'Jewtower to be similW and placed due north of existing as shown on drawings, . .' ...... - .,..-. Sincerely, MARK SWANSON ASSOCIATES, INC. LljJ~ Dennis L. Lockwood Project Architect Ene, MARK SWANSON ASSOCIATES INC. ARCH ITECTU RE 10610 NORTH PA,.RK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 May 10, 2004 Mr. Dick Hill, Assistant Director City of Carmel Department of Engineering One Civic Square Carmel, Indiana 46032 Re: Engineered Cooling Systems Plant Expansion - Project Review #1 Dear Mr. Hill: We have the following comments to your 4-16-04, project review letter. They are numbered to correspond with your numbered comments. 11. OK. 12. We have included an Erosion Control Plan on our Sheet C-2, Site GradinQ Plan/Erosion Control Plan, and is attached for your review. 13. First Item: The inlet and lift station are not being proposed and do not currently exist. The information appeared on a previous CAD base sheet and was mistakenly left on the plan. Second Item: The new paved areas are curbed. We have more clearly identified this on the attached Sheet C-3, Site Development Plan. Third Item: We have indicated the drainage pattern and outlet for the paved area west of the warehouse addition on the attached Sheet C-2, Site GradinQ Plan/Erosion Control Plan. Fourth Item: The paved area does not encroach into the detention area. As with the inlet and lift station, our CAD drawing registration inadvertently shifted and we have corrected this on the attached Sheet C-3, Site Development Plan. Fifth Item: There is currently an existing paved drive that is not curbed along the south side of this building. We have more clearly identified it on the attached Sheet C-1, ExistinQ Site Conditions Plan. Sincerely, MARK SWANSON ASSOCIATES, INC. ~/I~ Dennis L. Lockwood Project Architect Ene. Cc: Jon Dobosiewicz MARK SWANSON ASSOCIA TES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 May 10, 2004 Mr. John B. South, P. E. Hamilton County Soil and Water Conservation District 1108 South 91h Street Noblesville, Indiana 46060 Re: Engineered Cooling Systems Plant Expansion Dear Mr. South: With regard to your comments on the subject project in a letter dated 4-26-04, please find attached the following sheets for clarification: Sheet C-2, Site Gradinq Plan/Erosion Control Plan, for the location of silt fence along disturbed areas. Sheet L-1, Landscape Plan, indicating re-vegetation. Sincerely, MARK SWANSON ASSOCIATES, INC. L/~ Dennis L. Lockwood Project Architect Enc. Cc: Jon Dobosiewicz 8 I t-.GHi'lM MCHAL E 5177,68857 !<l4rZS<"!<l4 11: 46am P. 008 0<'., Ii Mid-State! II ----- EnGInEERinG I 9iO Logan Street, Suite 202 NQblesviile, IN 46060 (317) 775-8665 Phone 1317) 775.8666 FAX wIVw.mic -stateseng ;com April 29, 2004 Mr. Greg Hoyes Hamilton County Surveyor's Office One Hamilton Square Suile 1'88 NoblesviUe, IN 46060 RE: Engineered Cooling Systems Addition Carmel, IN Dear Greg: Thank you for taking the time c-ut of your busy schedule to meet with Chadi Karam and me regarding the drainage report that was prepared and filed with your office for the above-referenced project. The outcome of the meeting was that you were satisfied that the proposed building and parking additions had negliglb~e impact on the existing storm drainage system. In short, the incre2se in the site discharge was 0.01 cfs and ihe detention basin staged an additional 0.07 feet. We also discusse::l some of the issues ra~sed in your comment letter dated April 19. 2004. We would like to respond to your comments in writmg as follows: 1. We are aware that the project falls within the city limits of Carmel. They were also provided 8 copy of the drainage reporl 2. We are aware of Carmel's mapped Wellhead Prolection Zones and realize that the Droject does not fall within these designated areas, 3. We are aware of the J. W. Hawkins lega! draln and the impact that the regulated drain easemenl has on the project site. 4. We aie aware that the J. W. Hawkins regulated drain empties Into the W.R. Fertig legal dra1n, We are also aWare of the allowable release rate of 0.24 ds per acre for the Fertig legal drain, as we have designed several projects within this watershed. 5. We are aware that the City of CarmE:i has the jurisdiction over the on"site storm sewer system prior to its outlet into the J. W. Hawkins legal drain. We are aware that the County Surveyor's Office has jurisdiction over all legal drains within Hamilton County. 6, We are aware that you had an on-site meeting with the project's designers to discuss the issue of potential grade changes to the top of the bank of the J. W. Hawkins legai drain, 7 An encroachment agreement is already in place for this site. A recorded copy of said agreement has been forwarded to you by t~e project's designer. Aviation Engineermg Llnd5C3p~ Arc/lite<:/ufe Site Engineering Surveying Tra,1sportatiOl1 E~gtne=ring B I NGHPM f"Ct-'ALE 3177758657 l2l4/Z'3/~ 12: 1!:pm P. euz .. Mr. Greg Hoyes April 29, 2004 Page:2 of2 8, We are 3\Nare that there was an on-site meeting with you, the project's designer and Carmel's Urban Forester to discuss the scope of ditch maintenance to be performed as part of the scope of work for Ih is project. Resolution of th at issue rests with you and the Urban Forester and is beyond our control. Final decisions on this matter should be relayed to the project's desig,')sr. 9. As discussed in our mee~ing, the increased runoff rate for this site is negligible. The draii1age calculations that were p:-ovided prove that the peak runoff rate of 4.0 cfs that was previously appio'ied will be maintained after the completion ofthe proposed impro\iements 10. The 100-year elevation d the detention basin is 826.00. All site work around the pond occurs at an elevation of 827.00 or above. Therefore, L~e parking does not encroach into the previously designed detention basin. 11. We are of the understanding that all the issues regarding the design of the storm sewer system and its outlet into the J.W. Hawkins regulated drain have been addressed and that you are satisfied that the proposed project will f10t adversely affect downstream conditions. We do realize that you are still working with the project's designer on items 6 and 8, but the outcome of those issues will net affect the calculations that have been submitted. Should you have any questions please feei free to contact either Chadi or myself at 776-8665, Thank you for your input regard;ng this submittal. Respectfuily submitted, MID-STATES ENGINEERING, LLC G!:Z/:~7 Director, Hamilton County Office \\HamC)Srv~HamCD]les\F'ROJECTS\122..o21 O\Do~\SuC"/e~or Res!,D~se Letter.ooc Mark Swanson and Associates From: Sent: To: Cc: Subject: Greg Hayes [grh@co.hamilton.in.us] Thursday, April 29, 20042:51 PM den nis@markswanson.com JDobosiewicz@ci.carmel.in.us; SBrewer@ci.carmel.in.us; Jerry Liston Engineer Cooling System Dennis After the site meeting on Friday April 23, 2004, Jerry Liston and I talked with the Hamilton County Surveyor and showed him the revised plans. He gave us the following direction: 1.) Since the location of the ditch or flow-line has moved from the 2 different submitted set of plans, the physical property line must be staked in the field to determine where the ditch lays in relationship to the property. 2.) Clearing must be done on the property owned by Engineer Cooling Systems per Hamilton County Ordinance 4-26-99-C(4). 3.) The actual location of the top of bank must be surveyed and showed on the construction plans. 4.) Should the elevation of top af bank af the J.W. Hawkins Regulated Drain be disturb in any way, it will require a HEC-2 study to be done to determine that the 100 flood elevation will not come out of the top of bank of the ditch. 5.) A cross section of the proposed parking in relationship to the top of bank will need to be submitted to this office. Should a retaining wall be needed, a non-enforcement request for the encroachment in the regulated drain easement must be submitted to this office. Favorable recommendation will not be given to the drainage board on the retaining wall, as this will cause future maintenance access issues. 6.) The parking will not be allowed to encroach any closer the 5' (per the previous approved non-enforcement agreement) from what is determine to be the top of bank. A very defined top of bank exist in this situation and a surveyor should have no problem picking it up to show on the drawings. 7.) Please call1his office when the property line is staked (suggested a stake every 25' due to the heavy vegetation) and another on-site meeting can be held to discuss the clearing process. Should you have any questions, I can be reached at 776-8495. Thank You, Greg Hayes Plan Reviewer Hamilton County Surveyor's Office One Hamilton County Square, Suite 188 Noblesville, IN 46060 Phone: (317) 776-8495 Fax: (317) 776-9628 1 From: Sent: To: Subject: Brewer, Scott I Thursday, April 29, 2004 4:45 PM Butler, Angelina V; Dobosiewicz, Jon C ~_~) FW: Engineer Cooling System (¥,~1,r~,-~ ~ ~') (---- ¥'"- ....,~-- ..... Original Message ..... From: Greg Hoyes [mailto:grh@co.hamilton.in.us] Sent: Thursday, April 29, 2004 2:51 PM To: dennis@markswanson.com Cc: JDobosiewicz@ci.carmel.in.us; SBrewer@ci.carmel.in.us; Jerry Liston Subject: Engineer Cooling System Dennis After the site meeting on Friday April 23, 2004, Jerry Liston and I talked with the Hamilton County Surveyor and showed him the revised plans. He gave us the following direction: 1.) Since the location of the ditch or flow-line has moved from the 2 different submitted set of plans, the physical property line must be staked in the field to determine where the ditch lays in relationship to the property. 2.) Clearing must be done on the property owned by Engineer Cooling Systems per Hamilton County Ordinance 4-26-99-C(4). 3.) The actual location of the top of bank must be surveyed and showed on the construction plans. 4.) Should the elevation of top of bank of the J.W. Hawkins Regulated Drain be disturb in any way, it will require a HEC-2 study to be done to determine that the 100 flood elevation will not come out of the top of bank of the ditch. 5.) A cross section of the proposed parking in relationship to the top of bank will need to be submitted to this office. Should a retaining wall be needed, a non-enforcement request for the encroachment in the regulated drain easement must be submitted to this office. Favorable recommendation will not be given to the drainage board on the retaining wall, as this will cause future maintenance access issues. 6.) The parking will not be allowed to encroach any closer the 5' (per the previous approved non-enforcement agreement) from what is determine to be the top of bank. A very defined top of bank exist in this situation and a surveyor should have no problem picking it up to show on the drawings. 7.) Please call this office when the property line is staked (suggested a stake every 25' due to the heavy vegetation) and another on-site meeting can be held to discuss the clearing process. Should you have any questions, I can be reached at 776-8495. Thank You, Greg Hoyes Plan Reviewer Hamilton County Surveyor's Office One Hamilton County Square, Suite 188 NATURAL RESOURCES PLAN REVIEW AND COMMENT Hamilton County Soil and Water Conservation District ll08 South 9lh Street, Noblesville IN 46060 Ph- 317-773-1432 or Email at john-south@iaswcd.org Project Name- Engineered Cooling Systems- Plant Expansion Location- S. Side of Carmel Drive, Y4 mile west of Rangeline Road Acreage- lac Owner/Developer- Engineered Cooling Systems 201 West Carmel Drive Carmel, IN 46032 Engineer- Mark Swanson 10610 North Park Avenue Indianapolis, IN 46280-1020 Plan Review Date: April 26, 2004 Soils blformation: Prior disturbed I have reviewed the plans for this project aod have the following comments: ,. The disturbed area for this project is less than 1 acre and will not require a Rule 5 NOr. . Silt fence is recommended along the perimeter of the disturbed area and a revegetation plan is needed. Should you have questions concerning these comments, please contact me. Submitted By: John B. South P.E. Certified Professional in Erosion and Sediment Control Cc: Jon Dobosiewicz, Carmel DOCS Greg Hayes, County Surveyor File NATURAL RESOURCES PLAN REVIEW AND COMMENT Hamilton County Soil and Water Conservation District 1108 South 9th Street, NoblesviUe IN 46060 Ph- 317-773-1432 or Email at .iohn-south(iV,iaswcd.of2 Project Name- Engineered Cooling Systems- Plant Expansion Location- S. Side of Cannel Drive, Y4 mile west of Rangeline Road Acreage- lac Owner/Developer- Engineered Cooling Systems 201 West Carmel Drive Cannel, IN 46032 Engineer- Mark Swanson 10610 North Park Avenue Indianapolis, IN 46280-1020 Plan Review Date: April 26, 2004 Soils Information: Prior disturbed I have reviewed the plans for this project and have the following comments: ,. All issues have been addressed. Should you have questions concerning these comments, please contact me. Submitted By: John B. South P.E. Cerlifkd Professional in Erosion and Sediment Control Cc: Jon Dobosiewicz, Cannel DOCS Greg Hoyes, County Surveyor File MARK SWANSON ASSOCIATES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX E~.~.-1758 TRANSMITTAL Date: To: Hamilton County Auditor Attention: Mr. ~aul Pace, Water Distribution Supervisor Mr. Jim Haag, Sewer collections Supervisor / I ......... ~ ..... iii i Project: tiCS Plant Expansion R~: T^¢ eomment~ Illl I Page: 1 of 2 Fax: 571-2653 Dear Mr. Pace and Mr. Haag' Thank you for your comments on the subject project. As a matter of clarification, the proposed addition does not require any sewer or water connection. The water and sewer lines shown on the drawings are existing water and sewer lines. This addition does not add any additional capacity to the existing system. If you have any questions, please call me at 844-1315. Sincerely, Kenton C. Ward, Surveyor Pr;one (SI7) 776-$4~5 Fax C3 z7) 776?628 April 19, 2004 Mark Swanson Associates, Inc. ATTN: Dennis Lockwood 10610 North Park Avenue Indianapolis, IN 46280 VIA FACSIMILE: 844-1758 Re: Engineer Cool Systems Suite x88' One .7./imilton County Square ~oblesville, Indiana 46ot;o.223o Dear Mr. Lockwood: We have reviewed the construction plans submitted to the Hamilton County Surveyor's Office on April 7, 2004, 2004 for this project and have the following comments: 1. The proposed project falls in the jurisdiction of the City of Carmel. 2. The proposed project DOES NOT fall in a Carmel Wellhead Protection Zone. 3. The J.W. Hawkins Regulated Drain passes directly on the western property line of this site. , . , , The project falls in the J.W. Hawkins Regulated Drain Watershed. This watershed is part of the W.R. Fertig Watershed that has an allowable release rate set at 0.24 cfs per acre. Please coordinate the storm sewer design with both the City of Carmel and this office. The existing Top of Bank on the J.W. Hawkins regulated drain cannot be filled or moved to accommodate the new proposed parking. Please submit a Non-enforcement Agreemem of Individual Tracts to this office for the encroachment of the new parking area into the regulated drainage easement. The form is available on our website at www.co.hamilton.in, us, click on Department Directory, then Surveyor's Office. Per Hamilton County Ordinance 4-26-99-C(3), debris and obstruction removal, tree cleaning, and stream bank erosion will need to be completed from bank to bank of the open ditch. Please schedule an on-site meeting with engineer, developer, contractor, and this office to determine the scope of work. 9. The watershed restriction rate would allow this site to discharge approximately 1.5 cfs, which is currently being exceeded. The original outlet permit was granted for a 4.0 cfs discharge rate for the site. This proposed site must retain up to the 100 year storm event and discharge at the original rate of 4.0 cfs. Please provide drainage calculation to prove this is being accomplished with the existing and proposed conditions. 10. The proposed parking appears to encroach into the detention basin. Any decrease in storage from this basin will need to be provided elsewhere on-site to maintain the site release rate. 11. Please note that further comments may be necessary at a later date. Should you have any questions, I can be reached at 31%776-8495. Sincerely, Greg Hoyes Plan Reviewer CC: Jon Dobosiewicz - Carmel DOCD John South- HCSWCD Dick Hill - Carmel Engineering MARK SWANSON ASSOCIATES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-8~ ~1315 FAX 844-t 758 FAX TRANSMITTAL Date: " ....... ~'20-2004 To: DOCS Attention: Ms. Angle Butler Page: 1 of 4 Fax: 571-2426 .... ~ .... m Project: ECS Plant Expansion IIII ... Im III# Re: TAC responses Dear ^ngie: Please find attached our correspondence to Carmel Water-Wastewater Utilities and Carmel Fire Department responding to their comments for the subject project. We are reviewing comments from the Hamilton County Surveyor's Office that were received today, April 20, 2004, and will be able to comment on them at our TAC meeting tomorrow. We also received responses from Hamilton County Highway Department, Carmel Police Department and Panhandle Eastern Pipeline Company. Each of these agencies either had no comments, was not in their jurisdiction or their facilities were not affected by this project. If you have any questions, please call me at 844-1315. Sincerely, City of Carmel Fire Department Headquarters 2 CIVIC 8QIJARE CARMEL, INDIANA 46032 Voice [31 ?) 57t-2600 Fax (.317) 571-2615 Fire Prevention Bureau Denrlie Lockwooct Mark Swanson Associates 106'10 No~h Perk Avenue !ndianapoti~. IN 46280 R~: EngJneered Cooling Expmnstor~ LETTER OF APPROVAL The underalgned has reviewed the propased plane for Engineered Cooling Expansion ind his approved the plans subject to the following: 1, Il the proposecl ad¢ition to the building to be spr~nklered? Yes , , Whet Is t~e height of the adcli~ion and will the eddi[ion have a basement? Building height -- 25'-0" ~nere is no basement;, We are requesting that a Kr~ox Box be ipstailed on the building for fire departme~! emergency acoess, An existing Knox Box is located at the main entrance. , 6~ Pteate ralpond to Re above holed condition(s) in writing and suDmit to our office mrlor to the scheciuled Technical Advisory Meeting for this proJe~. Date: APril 8. ?O0~ . By: Gary Hoyt. Fire Marshal Cam'tel Fire Depadment ZITY OF RMEL /ATE R-WASTEWATER UTILITIES 130 ]ST AVE. SW · (';ARMI',t,, INI)tANA 4~11 ~.! April 13,200,~ Mark Swanson Associates, Inc. 10610 North Park Avenue Indianapolis, IN 46280 RE: ECS Plant Expansion Dean' Mark Swanson Associates, Inc.: We have reviewed thc prints for ECS Plant Expansion and have some corrections to your plans listed below. Also, listed are our standard specifications we the City Utility require, As-builts, which include both sewer collection and water service measurements are to be turned into the distribution and collection office at the time the water is due to be turned on. Please send those as-builts to the following address: ! 30 ! u Ave. S.W. Use a 6' piece of PVC pipe to mark the water service stub. We will need 2 sets of paper/hard copy as-builts as well as 2 copies of electronic us-builts on a CD. These CD drawings must include streets, lots, water mains, valves, sewer mains, manholes, laterals and service lines. Posi- Caps or the equivalent is now required on all water valve installations- You will need to call for an on site meet with the inspector. You will also need to have an approved stamped set of prints before starting any construction, Tracer wire must be installed with all water main laid in Carmel. Warning tape must be installed 12" to 18" above the water main. We also need a detail sheet that includes a restraint joint chart. Sewer Corrections: I. Please send sanitary sewer print details. Water Corrections: 1. Please send water print details, Should you have any questions or would like :o schedule a joint meet, please fee} free to contact us at 571-2648. Sincerely, Sincerely, Paul Pace Water Distribution Supervisor April 16, 2003 Mr. Dennis L. Lockwood Mark Swanson Associates, Inc. 10610 North Park Avenue Indianapolis, IN 46280 RE: Engineered Cooling Systems Plant Expansion-Project Review #1 Dear Mr. Lockwood: We have reviewed the drawings submitted for this project for the April 21, 2004 Technical Advisory Committee meeting. We offer the following comments: GENERAL INFORMATION 1. The project site is located within current City of Carmel Corporate Limits. The following jurisdictions will apply. 2. Jurisdictions: · Street and Right of Way - City of Carmel (Carmel Drive) · Water and Sanitary Sewer - City of Carmel Utilities · Storm Sewer - City of Carmel and Hamilton County Surveyor's Office regarding discharge to the Hawkins regulated drain. 3. Board of Public Works and Safety Approval Requirements: · Additional Water and Sanitary Sewer Availability if applicable. I am enclosing a schedule for Board of Public Works and Safety meeting dates and agenda deadlines for your use. Please use the Engineering Department deadlines for submissions to the Board. Any submission to the Board requires prior final approval by the Carmel Clay Plan Commission and/or the Board of Zoning Appeals and completion of review by the Technical Advisory Comntittee. All written requests to be place on the Board's agenda must include the appropriate Docket Numbers and the date (or dates) of approval by the Plan Commission and/or BZA. 4. Water and Sanitary Sewer Availability (acreage) and Connection Fees Carmel Utilities will determine if this expansion will result in additional Water and Sanitary Sewer Connection Fees. 5. TAC Review/Drawings submitted for approval: We request that all comments and comment letters generated by this office be answered in writing and be accompanied by a drawing reflecting requested revisions. Final drawings will not be approved for construction until all issues have been resolved. The design engineer must certify all drawings submitted for final approval. This office will require a minimum of five-sets of approved drawings after all issues have been resolved and the construction drawings have been approved. The drawings will be stamped approved and signed by the City Engineer and by the Director of Carmel Utilities. The Developer/Owner will receive one-set which is to be maintained on the construction site at all times. Carmel Utilities will receive two-sets, our Construction Manager (Inspector) will receive one- set and one-set will be maintained in the Department of Engineering. If more than the minimum five- sets are requested to be approved, the additional sets (maximum total of two additional) must be submitted with the five required sets. ])}~t~AI~TME_NT 0t: }'~N(;1NEERING CIvIc SQt!ARE, C:x.I~M~I.. IN 46032 O}:}:~c~.; 317.571.2441 t~MAII, kwccsc ?¢ ('i.carmel.in. us F^x 317.571.2439 Mr. Dennis L. Lockwood April 16, 2004 Page 2 6. Please be advised that any installation of signs, walls, irrigation systems, etc. within dedicated right of way and/or dedicated easements will require a Consent to Encroach Agreement between the Owner/Developer and the City of Carmel. This Agreement requires Board of Public Works and Safety approval. 7. Carmel Utilities does not subscribe to "Holey Moley" and should be contracted directly for all water and sanitary sewer main locations. 8. Carmel Utilities will provide a separate review of this project for water and sanitary sewer issues. 9. I am including copies of the following with this correspondence: · Commercial Project Approval Procedures. Permit Data, Contacts, etc. · Commercial Permitting Procedures. I will send a copy of our Residential Subdivision and Commercial Irrigation System Requirements upon request. BONDING REQUIREMENTS 10. Upon initial review, it appears the following bonding requirements may apply to this project: Performance Guarantees There are no Performance Guarantees required. Street Cut/Right of Way Permit and Bonding Requirements Any work in the dedicated right of way of Carmel Drive not included or covered by a Performance Guarantee will require a Right of Way Permit and a License and Permit Bond. The bond amount will be determined by the number of instances of work in the right of way @ $2,000.00 per instance. Open pavement cuts in dedicated streets require approval by our Board o[Public Works and Sa[eO:. It does not appear that a Right of Way Permit will be required. If this does become applicable, please contact Fred Glaser, Department of Engineering Right of Way Inspector/Manager for details regarding this issue. PROJECT COMMENTS-CONSTRUCTION PLANS 11. Please be advised that we have engaged Crossroad Engineers for review of drainage issues and drainage calculations. We will share these comments when they are received. 12. What are the plans for erosion control on this site during construction? This has not been addressed on the plans. 13. Sheet C-1 · What is the prop(osed) inlet and lift station at the south end of the existing warehouse? Is this an interior inlet? What is the inlet an outlet for? · The new paved areas must be curbed. Not really apparent if they are planned to be curbed. · What is the drainage pattern and outlet for the paved area west of the warehouse addition? · It appears this new paved area encroaches into the detention area. · Is the area adjacent to the new paving and adjacent to the grass along the south side of the building up to the gates currently paved and/or curbed? If so, please indicate on the plans. We reserve the right to provide additional comments upon further review by the City Engineer and upon receipt of the drainage revie~v by Crossroad Engineers. Mr. Dennis L. Lockwood April 16, 2004 Page 3 The above comments are based upon the Engineering Department's initial review. Please provide our office with a follow up letter regarding this review and revised plans, indicating, all revisions. A second review will focus only on detailed construction plans. It is critical that our office be made aware of all modifications made on the plans being re-submitted, particularly if any such changes are considered "new" or fall outside of our initial review. If you have questions, please contact Mike McBride or me at 571- 2441. Sincerely, Dick Hill, Assistant Director Department of Engineering Enclosures cc: Mike McBride, City Engineer (w.o. encl.) Jon Dobosiewicz, Department of Community Services (w.o. encl.) John Duffy, Carmel Utilities (w.o. encl.) Paul Pace, Carmel Utilities (w.o. encl.) Jim Haag, Carmel Utilities (w.o. encl.) Greg Hoyes, Hamilton County Surveyor's Office (fax/w.o. encl.) John South, Hamilton County Soil & Water Conservation District (fax/w.o. encl.) Greg Ilko, Crossroad Engineers SSPROJREV03\ENGCOOLSYSEXPANSION HAMILTON COUNTY HIGHWAY DEPAR T ENT April 12, 2004 Mr. Dennis L. Lockwood Mark Swanson Associates INC. 10610 North Park Avenue Indianapolis, IN 46280 VIA FACSIMILE RE: ECS Plant Expansion TAC Submission N of 116th Street'/W of Rangellne Road Clay Township Dear Mr. Lockwood: This letter serves to acknowledge receipt of a transmittal containing the plans for the above-mentioned project. After reviewing the plans the Highway Department has the followihg comments; 1, It appears that this project lies entirely within the limits of the City of Carmel, Therefore, all future comments should be directed toward the City, If you have any questions or comments concerning this letter, please feel free to contact me at anytime, Sincerely, Staff Engineer cc: Jon Dobosiewicz Grog Hoyes G:~US ER$\Sg~O4tac~04-12-04ECSplant,doc 1700 South !0'~ Street www.co.hamllton,in,us 017) ?73-?770 Fax-(317) 776~9814 April 8, 2004 Dennis L. Lockwood Mark Swanson Associates, INC. 10610 North Park Avenue Indianapolis, IN 46280 RE: ECS Plant Exp. TAC submission Dear Mr. Lockwood: I have received and reviewed the information for the above-mentioned project. At the present time, I see nothing in the plans that would hamper law enforcement efforts. If we can be of any further assistance to you, please contact us. Respectfully Michael D. Fogarty ' Chief of Police MDF:vb cc: Dept. of Community Services (517) 571-2500 A Nationally Accredit~.'~!~forcement Agency F.~ (317) 571-2512 City of Carmel Fire Department Headquarters 2 CIVIC SQUARE CARMEL, INDIANA 46032 Voice (317) 571-2600 Fax (317) 571-2615 Fire Prevention Bureau Dennis Lockwood Mark Swanson Associates 10610 North Park Avenue Indianapolis, IN 46280 RE: Engineered Cooling Expansion LETTER OF APPROVAL The undersigned has reviewed the proposed plans for Engineered Cooling Expansion and has approved the plans subject to the following: 1. Is the proposed addition to the building to be sprinklered? 2. What is the height of the addition and will the addition have a basement? , , We are requesting that a Knox Box be installed on the building for fire department emergency access. . . Please respond to the above noted condition(s) in writing and submit to our office prior to the scheduled Technical Advisory Meeting for this project. Date: April 8, 2004 By: Gary Hoyt, Fire Marshal Carmel Fire Department City of Carmel Fire Department Headquarters 2 CIVIC SQUARE CARMEL, INDIANA 46032 Voice (317) 571-2600 Fax (317) 571-2615 Fire Prevention Bureau Dennis Lockwood Mark Swanson Associates 10610 North Park Avenue Indianapolis, IN 46280 RE: Engineered Cooling Expansion LETTER OF APPROVAL The undersigned has reviewed the proposed plans for Engineered Cooling Expansion and has approved the plans subject to the following: 1. Is the proposed addition to the building to be sprinklered? 2. What is the height of the addition and will the addition have a basement? , . We are requesting that a Knox Box be installed on the building for fire department emergency access. o . Please respond to the above noted condition(s) in writing and submit to our office prior to the scheduled Technical Advisory Meeting for this project. Date: April 8, 2004 By: Gary Hoyt, Fire Marshal Carmel Fire Department MARK SWANSON ASSOCIATES INC. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 LETTER OF TRANSMITTAL To: Carmel Dept. of Community Services Date: 04-06-2004 One Civic Square Attention: Angie Butler Carmel, Indiana 46032 Regarding: ECS Plant Exp. TAC submission We are sending you: Under Separate Cover I Attached FI Presentation Dwgs. FI Shop Drawings FI Change Order Preliminary Plans FI Clarification dwg. FI Construction"doc. FI Specifications FI Samples FI Copy of Letter F1 FI For approval B Review and Comment FI For your use FI Correct and Resubmit E) Rep ~ro~ci bJ.~ 'D~ For distribution FI For your files FI Approved as submitted FI Approved as noted FI As Requested Copies/Sets Number Description 1 copy each T-01 Title Sheet. C-01 Site Development Plan. L-01 Landscape Plan. Remarks: Drawings submitted for Carmel/Clay Technical Advisory Committee Members project review. Storm Drainage Reports submitted to Hamilton Co. Surveyor, Hamilton Co. Soil & Water Conservation & City of Carmel Dept. of Engineering. Copies to: . Signed: Fro m: Sent: To: Subject: Babbitt, Pamela A Monday, March 22, 2004 8:36 AM Brewer, Scott I; Butler, Angelina V; Dobosiewicz, Jon C; Hollibaugh, Mike P; Keeling, Adrienne M; Pattyn, Dawn E ,~,'¥1L .~ ~I/ newi ~. L{~)--~,¢.~ ~ ~ ~]-~W4 # ~/ .~r"t/ Engineered Cooling Systems, Inc. 201 West Carmel Drive DP/ADLS Amend c¥. "' ~;~ Mark Swanson 844-1315 844-1758 fax +%;Z / /czp ( t c. pz,.~,_:~ lb-- o q" "5~- LETTER OF TRANSMITTAL To: Department of Community Services Date: 03-19-2004 One Civic Square Carmel, Indiana 46032 MARK SWANSON ASSOCIATES INC. We are sending you: At~te..ntion: John Dobosiewicz ,,~,,~~'~~,.ECS Plant exp. //~ ,.._ ~ ;Xt~/ADLS FiUnderS~.rate~ove~~~~/ached FI Shop Dra~Change Order FI Clarification dwg. FI Construction doc. ARCHITECTURE 10610 NORTH PARK AVENUE INDIANAPOLIS INDIANA 46280 317-844-1315 FAX 844-1758 Presentation Dwgs. Preliminary Plans Specifications FI Samples FI Reproducibles Copy of Letter Applications For approval Review and Comment Approved as submitted For your use Correct and Resubmit Approved as noted FI For distribution 0 For your files FI As Requested Copies/Sets Number 2 copies 2 copies 2 copies C-01 Description DP Application. ADLS Application. Site Development Plan. Remarks: ,,, Copies to: Siqned: