Loading...
HomeMy WebLinkAbout283101 - ADDRESSABLE FIRE-ALARM SYSTEM.pdfMatt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 1 of 17 March 23, 2012 Section 283101 Addressable Fire�Alarm System PART 1 � GENERAL A. Section Includes: 1. System smoke detectors. 2. Notification appliances. 1.02 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. B. Section 23 33 00 �Ductwork Accessories. C. Section 26 05 00 � Basic Electrical Requirements. D. Section 26 05 30 – Conduit. E. Section 26 05 29 � Supporting Devices. F. Section 26 05 53 – Identification for Electrical Systems G. Section 28 05 00 – Electronic Safety and Security System Electrical Requirements. H. Section 28 05 01 – Basic Electronic Safety and Security System Requirements. 1.03 REFERENCES A. Review the Drawings and all sections of the Specifications for equipment furnished by other Contractors and the Owner throughout the entire project. B. See references noted in Specification Section 26 05 00, Paragraph 1.03. C. EIA RS�232C. D. 675 IAC 13�2.3�131 � 1998 Indiana Building Code, Chapter 11 � Accessibility. E. NFPA 70 � National Electrical Code, Article 760. F. NFPA 72 � National Fire Alarm Code. G. NFPA 90A � Air Conditioning and Ventilating Systems. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 2 of 17 March 23, 2012 1.04 REGULATORY REQUIREMENTS A. All items of the fire alarm system shall be listed as a product of a single fire alarm system manufacturer under the appropriate category by the Underwriters' Laboratories, Inc. (UL), and shall bear the UL label. All control equipment shall be listed under UL category UOJZ as a single control unit. Partial listing shall not be acceptable. B. In addition to the UL�UOJZ requirement listed above, the system controls shall be UL listed for power�limited applications per NFPA 70, Article 760. All circuits must be marked in accordance with NFPA 70, Article 760.23. 1.05 DEFINITIONS A. LED: Light�emitting diode. B. NICET: National Institute for Certification in Engineering Technologies. 1.06 SUBMITTALS A. Submit shop drawings and product data under provisions of Division 01 and Section 26 05 00. B. Submit complete descriptive data indicating UL listing for all system components. C. Submit complete sequence of operations of system. D. Submit rough�in drawings containing 1/8" = 1'�0" scale drawings of Architect's building floor plans indicating all conduit sizes and runs, quantity and types of cables, equipment locations, visual device strobe output candela rating for each device, system riser diagram, and any other special details required to coordinate the work. E. These rough�in drawings shall be separate from general power and light, or other shop drawing, and are to show symbols, wiring, details and notes applicable only to the fire alarm system. F. All drawings shall be revised to “As�Built” status at the project completion. All drawings must be drawn on a CAD system. Hand drawn or scanned copies of drawings are not acceptable. Drawings must be submitted as electronic drawing files in AutoCAD 2000 format on CD�ROM. File that are not editable (DWF, etc.) or in other formats (DXF, etc.) are not acceptable. Each project drawing shall be submitted as a separate drawing file. Zipped files containing multiple drawings are not acceptable. G. General Submittal Requirements: 1. Shop Drawings shall be prepared by persons with the following qualifications: a. Trained and certified by manufacturer in fire�alarm system design. b. NICET�certified fire�alarm technician, Level III minimum. c. Licensed or certified by authorities having jurisdiction. H. Product Data: For each type of product indicated. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 3 of 17 March 23, 2012 I. Shop Drawings: For fire�alarm system. Include plans, elevations, sections, details, and attachments to other work. 1. Comply with recommendations in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA 72. 2. Include voltage drop calculations for notification appliance circuits. 3. Include battery�size calculations. 4. Include performance parameters and installation details for each detector, verifying that each detector is listed for complete range of air velocity, temperature, and humidity possible when air�handling system is operating. 5. Include plans, sections, and elevations of heating, ventilating, and air�conditioning ducts, drawn to scale and coordinating installation of duct smoke detectors and access to them. Show critical dimensions that relate to placement and support of sampling tubes, detector housing, and remote status and alarm indicators. Locate detectors according to manufacturer's written recommendations. 6. Include voice/alarm signaling�service equipment rack or console layout, grounding schematic, amplifier power calculation, and single�line connection diagram. 7. Include 1/8” = 1’� 0” scale floor plans to indicate final outlet locations showing address of each addressable device. Show size and route of cable and conduits. J. Qualification Data: For qualified Installer. 1. Technicians shall be factory�authorized technicians. 2. Technicians shall be NICET certified. 3. Installer shall have not less than 5 years experience with the manufacturer’s product line, and not less than 5 years experience in projects of similar scope to this project. K. Field quality�control reports. L. Operation and Maintenance Data: For fire�alarm systems and components to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 01 Section "Operation and Maintenance Data," include the following: 1. Comply with the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72. 2. Provide "Record of Completion Documents" according to NFPA 72 article "Permanent Records" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter. 3. Record copy of site�specific software. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 4 of 17 March 23, 2012 4. Provide "Maintenance, Inspection and Testing Records" according to NFPA 72 article of the same name and include the following: a. Frequency of testing of installed components. b. Frequency of inspection of installed components. c. Requirements and recommendations related to results of maintenance. d. Manufacturer's user training manuals. 5. Manufacturer's required maintenance related to system warranty requirements. 6. Abbreviated operating instructions for mounting at fire�alarm control unit. 1.07 SCOPE OF WORK A. Extension of Existing Fire Alarm System: 1. Extend the existing fire alarm system. Extend all features and functions of the existing system to the new and renovated areas of the building. 2. Provide all necessary material and labor to furnish, install, and leave the system in first class operating condition. 3. Assure that all new equipment connected to the existing system is compatible and will operate properly with the existing fire alarm system. 4. Keep the existing fire alarm system operational at all times during the project, except for approved shutdowns required for the indicated Work: a. Notify the local fire department prior to any disruption. b. Make all system changes or shutdowns so as to provide minimum of interference with the operation of facility. Notify the Owner not less than 24 hours in advance of a shutdown/changeover and obtain approval from the Owner and Architect/Construction Manager. 5. The extension of the existing system shall include, but is not limited to, the following: a. Automatic fire detectors. b. Audio/visual units. c. Visual only units. d. All wiring, connections to devices, outlet boxes, and all other necessary material for a complete operating system. B. Noncoded UL�Listed addressable system, with automatic sensitivity control of certain smoke detectors and multiplexed signal transmission, dedicated to fire�alarm service only. 1.08 SYSTEM DESCRIPTION A. Connection to kitchen hood fire�suppression system for system alarm initiation. The kitchen hood fire�suppression systems shall shut down any gas supply for cooking. B. Connection and operation under system alarm condition to shut�off valves for gas and fuel oil supplies that serve or pass through student�occupied spaces. The system shall not shut Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 5 of 17 March 23, 2012 off gas supplies serving emergency power sources. The kitchen hood fire�suppression systems shall shut down any gas supply for cooking. 1.09 SYSTEM ALARM OPERATION A. Alarm Activation: The system alarm operation subsequent to the alarm activation of any manual station, or automatic detection device , or sprinkler flow switch activation shall be as follows: 1. Signal Synchronization: a. All audible alarm indicating appliances shall sound in a synchronized temporal pattern alarm signal until silenced by the alarm silence switch at the control panel or at the remote annunciator. b. All visual alarm strobes shall operate in a continuous and synchronized pattern until extinguished by total system reset. All visual alarm strobes shall be synchronized as one pattern throughout the building. 2. Activation of alarm silence shall not extinguish visual alarms. All visual alarms shall remain operating when audible alarms are silenced. 3. The audible alarms shall be automatically silenced after 15 minutes of alarm operation. 4. Shut down building air handling systems in the zone affected. Upon total reset of the fire alarm control panel, the air handling units shall sequentially start up to minimize power demand. Coordinate with Temperature Control Trades and provide separate contact closure from fire alarm system to building automation system to signal total reset of the fire alarm system control panel. 5. Activate a digital alarm communicator transmitter (DACT) for notification of alarm and trouble conditions to the designated monitoring service. B. Subsequent Alarm: Any subsequent alarm activation shall reactivate the alarm indicating appliances as specified above. C. Identify alarm at fire�alarm control unit and remote annunciators. 1.10 QUALITY ASSURANCE A. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project. B. Installer Qualifications: Installation shall be by personnel certified by NICET as fire�alarm Level II technician. C. Source Limitations for Fire�Alarm System and Components: Obtain fire�alarm system from single source from single manufacturer. Components shall be compatible with, and operate as, an extension of existing system. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 6 of 17 March 23, 2012 D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 1.11 PROJECT CONDITIONS A. Interruption of Existing Fire�Alarm Service: Do not interrupt fire�alarm service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary guard service according to requirements indicated: 1. Notify Architect no fewer than two days in advance of proposed interruption of fire�alarm service. 2. Do not proceed with interruption of fire�alarm service without Architect's written permission. B. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project. 1.12 SEQUENCING AND SCHEDULING A. Existing Fire�Alarm Equipment: Maintain existing equipment fully operational until new equipment has been tested and accepted. As new equipment is installed, label it "NOT IN SERVICE" until it is accepted. Remove labels from new equipment when put into service and label existing fire�alarm equipment "NOT IN SERVICE" until removed from the building. 1.13 WARRANTY A. Provide warranty under the provisions of Division 01. PART 2 � PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Match existing. 2.02 NOTIFICATION APPLIANCE CIRCUIT (NAC) EXTENDER PANELS A. Provide notification appliance circuit extender panels or remote booster power supply panels as needed to serve all fire alarm system audible and visual notification appliances. Provide panels with battery back�up. B. Panel Power and Battery Back�Up. 1. Normal Power: Panel shall operate from 120 VAC power circuit under normal conditions. 2. Battery Back�Up: Upon loss of the 120 VAC power circuit for the panel, the panel shall automatically transfer to and operate from integral standby battery supply. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 7 of 17 March 23, 2012 Provide sealed type rechargeable battery supply for the panel with sufficient additional capacity to operate the entire system, including all panels, detectors, remote annunciators, and accessories, in a normal supervisory mode for a period of 24 hours with at least 5 minutes of alarm operation at the end of this period. The system shall automatically transfer to the standby batteries upon power failure. All battery charging and recharging operations shall be integral and automatic. 2.03 ADDRESSABLE PERIPHERAL DEVICES A. Area Detectors: 1. Sensors: The sensors shall be of the heat or photoelectric smoke type and shall communicate actual chamber values to the system control panel. The smoke sensors and bases shall be listed to UL Standard 268 and documented compatible with the control equipment to which they are connected. The sensors shall be listed for both ceiling and wall mount applications. There shall be no limit to number of sensors, stations or zone adaptor modules that may be activated or "in Alarm" simultaneously. 2. Photoelectric Smoke Sensor Head: a. The sensor shall be of the solid�state photoelectric type, shall operate on the light scattering, photodiode principle, and shall contain no radioactive material. The sensor shall use a pulsed infrared LED light source designed to ignore invisible particles or smoke densities that are below the factory set point, and be sealed against rear airflow entry. To minimize nuisance alarms, detectors shall have a built�in insect screen. b. The photoelectric type sensor shall be a plug�in unit that mounts to a twist�lock base that is common with both the photoelectric smoke and heat type sensor and shall be compatible with other addressable detectors, addressable manual stations, and addressable zone adaptor modules on the same circuit. 3. Addressable Sensor Bases: Sensor bases shall be compatible with all sensors. Each base shall be capable of communicating sensor values to the panel if a "wrong device type" trouble condition is present. The panel shall continue to monitor for alarms and troubles using the default setting for the wrong device until the proper type is installed or the program is changed. Each sensor base shall contain a LED (if not part of the sensor head) that will flash each time it is scanned by the control panel (about once every 4 seconds). When the control panel determines that a sensor is in the alarm or trouble condition, the control panel shall command the LED on that sensor's base to turn on steady indicating the abnormal condition. Each sensor base shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location. a. Base: Unless otherwise indicated, the sensor base shall provide connections for sensor and annunciate power�on, alarm and trouble conditions locally at the base. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 8 of 17 March 23, 2012 b. Base With Supervised Relay: Where indicated, the sensor base shall be provided with a control relay for programmable operation. The relay shall not take any additional addressable device capacity. B. Duct Smoke Detector: Each duct detector shall be a complete package that includes a solid�state photoelectric type sensor, a sensor base, a compact air duct sensor housing with supervised output for multiple remote relays, a set of sampling tubes, a remote relay, and a duct detector remote test station: 1. Detector and Housing: Housing and sensor shall obtain operating power from the supervisory current in the fire alarm detection loop. 2. Sampling Tubes: Provide each duct detector with sampling tubes in accordance with the detector manufacturer’s recommendations and instructions. 3. Remote Relays: Provide each duct detector with remote relay contacts for the functions listed below. Relay shall operate on 24 VDC power and provide at least one normally�open and one normally�closed set of contacts. a. Provide each duct detector with a remote relay for shutdown of the associated air handling unit motor starter or motor drive control circuit and dampers as specified in this Section and in Division 23. b. Provide each duct detector with a remote relay for signaling the building automation system as specified in this Section and in Division 23. 4. Remote Test Station: Provide each duct detector with one remote test station. Station shall include alarm indicator light and key test switch. Install the station on the nearest adjacent wall to the duct detector. C. Addressable Input/Output Modules: Modules shall be designed for flush mounting in standard electrical outlet box and to operate on 24 VDC: 1. Monitor Module: a. Module shall provide supervised monitor circuit(s) capable of reporting normal, alarm and/or trouble conditions: b. Provide monitor modules as required for conventional initiating device circuits of the system for items such as dry contacts and direct connected detectors. 2. Tamper Switch and Waterflow Switch Monitor Module: a. Module shall provide supervised Class B monitoring of normally open, dry contacts. Provide a monitor module for each sprinkler system flow switch and each supervised control valve, including wall indicating valves and post indicating valves. 3. Control Relay Module: a. Module shall provide double pole/double throw contacts for control of external appliances such as fans and dampers. b. Provide control modules for air handling units, fans and dampers as necessary to meet all requirements specified in the Contract Documents. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 9 of 17 March 23, 2012 c. Provide control modules for each elevator control panel for elevator capture. d. Provide each module with trim plate for outlet box mounting. 4. Signal Module: a. Module shall provide supervised signal circuits capable of activating audio and visual alarm signaling devices and reporting trouble conditions. Each signal module circuit shall be individually fused at 2 amperes. b. Provide signal modules as required to operate all audio/visual signal devices. 2.04 SYSTEM SMOKE DETECTORS A. General Requirements for System Smoke Detectors: 1. Comply with UL 268; operating at 24�V dc, nominal. 2. Detectors shall be two�wire intelligent�type. 3. Integral Addressable Module (Intelligent Electronics): Arranged to communicate detector status (normal, alarm, or trouble) to fire�alarm control unit. 4. Base Mounting: Detector and associated electronic components shall be mounted in a twist�lock module that connects to a fixed base. Provide terminals in the fixed base for connection to building wiring. 5. Self�Restoring: Detectors do not require resetting or readjustment after actuation to restore them to normal operation. 6. Integral Visual�Indicating Light: LED type indicating detector has operated and communication status. 7. Remote Control: Unless otherwise indicated, detectors shall be analog�addressable type, individually monitored at fire�alarm control unit for calibration, sensitivity, and alarm condition and individually adjustable for sensitivity by fire�alarm control unit. a. Rate�of�rise temperature characteristic shall be selectable at fire�alarm control unit for 15 or 20 deg F per minute. b. Fixed�temperature sensing shall be independent of rate�of�rise sensing and shall be settable at fire�alarm control unit to operate at 135 or 155 deg F. c. Provide multiple levels of detection sensitivity for each sensor. B. Photoelectric Smoke Detectors: 1. Detector address shall be accessible from fire�alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 10 of 17 March 23, 2012 2. An operator at fire�alarm control unit, having the designated access level, shall be able to manually access the following for each detector: a. Primary status. b. Device type. c. Present average value. d. Present sensitivity selected. e. Sensor range (normal, dirty, etc.). C. Duct Smoke Detectors: Photoelectric type complying with UL 268A. 1. Detector address shall be accessible from fire�alarm control unit and shall be able to identify the detector's location within the system and its sensitivity setting. 2. An operator at fire�alarm control unit, having the designated access level, shall be able to manually access the following for each detector: a. Primary status. b. Device type. c. Present average value. d. Present sensitivity selected. e. Sensor range (normal, dirty, etc.). 3. Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with the supplied detector. 4. Each sensor shall have multiple levels of detection sensitivity. 5. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific duct size, air velocity, and installation conditions where applied. 6. Relay Fan Shutdown: Rated to interrupt fan motor�control circuit. 2.05 SIGNAL NOTIFICATION APPLIANCES AND ACCESSORIES A. General Requirements for Notification Appliances: Connected to notification appliance signal circuits, zoned as indicated, equipped for mounting as indicated and with screw terminals for system connections. B. Audio/Visual Units. 1. Units shall meet minimum requirements of Americans with Disabilities Act (ADA). Units shall operate from 24 VDC, polarized. Visual units shall utilize a Xenon strobe with a light intensity meeting ADA requirements. Unit housing shall be red and have the word "FIRE" in readily visible in white lettering. 2. Units shall include separate wire leads for in/out wiring of the signal circuit(s) and have the ability of the control panel silencing the audio alarm portion of the unit and the visual portion of the unit remain flashing. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 11 of 17 March 23, 2012 3. Indoor Units: a. Units shall have a minimum SPL level of 82 dBA (synchronized temporal pattern) under UL 464 reverberant chamber test. b. Units shall have the ability for the horns and visual strobes to be operated in a synchronized pattern so that all strobes flash at the same time. c. Units shall have selectable strobe outputs of 15, 30, 75 and 110 candelas. d. Units shall be Simplex Model 4906�9127, GE Security/EST Model G1RF Series, Notifier Model P1224MC, or approved equal. C. Visual Units: 1. Unit shall meet minimum requirements of Americans with Disabilities Act (ADA). Unit shall operate from 24 VDC, polarized, and utilize a Xenon strobe. Unit housing shall be red and have the word "FIRE" in readily visible in white lettering. 2. Units shall include separate wire leads for in/out wiring of the signal circuit(s) and have the ability of the control panel silencing the audio alarm signals while visual units remain flashing. 3. Indoor Units: a. Units shall have the ability for the strobes to be operated in a synchronized pattern so that all strobes flash at the same time. b. Units shall have selectable strobe outputs of 15, 30, 75 and 110 candelas. D. Synchronizing Modules: Provide synchronizing modules as required to synchronize the horns and the strobes of all audio/visual units and visual units. Module shall be as manufactured by specified acceptable manufacturer. E. Appliances shall comply with UL 1480 and shall be listed and labeled by an NRTL. 2.06 FIRE ALARM CABLE A. All wiring shall be power�limited cable unless other types are required by system manufacturer or applicable codes. B. All wiring shall meet the requirements of the National Electrical Code and all other applicable national, state, and local codes. C. Plenum Rated Cabling: Where system cabling is installed without conduit or other enclosed raceways, <or in open cable tray> in supply and return air ducts, air plenums such as above accessible ceiling, or in risers, system cabling shall be plenum�rated. D. Communications Wiring: Twisted and shielded #18 AWG two�conductor cable or other cabling as recommended by the fire alarm system manufacturer. Minimum conductor size shall be #18 AWG. E. Notification Appliance Signal Wiring: Wiring to signaling devices, such as fire alarm audio and visual units, shall be solid or stranded, two�conductor cable. Minimum conductor size shall be< #16 AWG.>< #14 AWG.>. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 12 of 17 March 23, 2012 F. All 24 volt power wiring from control panels to zone addressable modules shall be two�conductor cable or other cabling as recommended by the fire alarm system manufacturer. Minimum conductor size shall be #14 AWG. PART 3 � EXECUTION 3.01 GENERAL A. Provide the system as indicated and in accordance with all applicable codes and the manufacturer's recommendations. All wiring shall be installed in strict compliance with all the provisions of NFPA 70 � Article 760, Power�Limited Protective Signaling Circuits. B. All equipment and wiring shall be installed as directed by the manufacturer's instructions and diagrams. C. The manufacturer's authorized representative shall provide on�site supervision of installation. D. Coordinate the installation of equipment and devices that pertain to the work of other Trades on the project with the appropriate Trade. 3.02 SYSTEM INSTALLATION A. Comply with NFPA 72 for installation of fire�alarm equipment. B. All equipment shall be installed at the locations and heights indicated. C. 120 VAC Power: Provide 120 VAC power from dedicated circuits to the control panel and any required Notification Appliance Circuit (NAC) extender panels whether or not indicated on the Drawings. D. Mounting Heights: 1. Mount fire alarm audio/visual units, visual units, and audible only units at 84" (7’�0”) above finish floor to the top (80” to the bottom) or 6” below finished ceilings, whichever is lower, to the top of the outlet boxes unless otherwise noted. E. Area Detectors: 1. Provide area detectors at all indicated locations. 2. Notification Appliance Circuit (NAC) Extender Panels: Provide an area smoke detector at each Notification Appliance Circuit (NAC) extender panel location whether or not indicated on the Drawings. F. Duct Smoke Detectors: 1. Detectors: Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 13 of 17 March 23, 2012 a. Provide duct smoke detectors in all new fan systems that are in excess of 2,000 cubic feet per minute in accordance with NFPA 90A. b. Provide each duct detector with sampling tubes in accordance with the detector manufacturer’s recommendations and instructions. c. Connect the detectors so that if smoke of sufficient concentration appears, they will activate the fire alarm system in the same manner as manual stations, area detectors, or other initiating device. d. In return air ducts, install the detectors ahead of any fresh�air inlet. e. In return air ducts, install the detectors ahead of any fresh�air inlet. 2. Remote Relays: a. Provide each duct detector with a remote relay for shutdown of the associated air handling unit motor starter or motor drive control circuit and dampers as specified in this Section and in Division 23. Locate the relay within 3 feet of the device being controlled in accordance with NPFA 72. The Temperature Control Trade shall wire from the contacts of each detector’s associated remote relay to the associated air handling unit motor starter or motor drive control circuit for shutdown of the fan. This Contractor shall furnish and install all other detector wiring for power, alarm, trouble, etc. b. Provide each duct detector with a remote relay for signaling the building automation system as specified in this Section and in Division 23. Locate the relay within 3 feet of the device being controlled in accordance with NPFA 72. The Building Automation System contractor shall wire from contacts of each detector’s associated remote relay to the associated air handling unit building automation system control panel. 3. Remote Test Station: Provide each duct detector with one remote test station. Install the station on the nearest adjacent wall to the duct detector at a height of 48 inches above the finished floor. Provide printed label on each station indicating associated air handler and associated detector (supply or return). 4. This Contractor shall furnish and install all other detector wiring for power, alarm, trouble, etc. G. Audio/Visual Units and Visual Units. 1. Set the strobe output levels to 75�candela for all rooms up to a maximum dimension of 40’ x 40’ where in compliance with applicable codes. 2. The strobe output levels may be set to 15�candela in the following rooms if their usage meets all 1998 Indiana Building Code, Chapter 11 – Accessibility (675 IAC 13�2.3�131) requirements for strobe brightness and coverage: a. Small toilet rooms. b. Small internal office suite hallways. c. Small mechanical rooms. 3. Set the strobe output levels to 110�candela strobe in all rooms exceeding 50 feet in any direction or where required for provide coverage required by applicable codes. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 14 of 17 March 23, 2012 This shall include, but not be limited to, cafeterias, gymnasiums, field houses, and auditoriums. I. Kitchen Hood: Connect the fire alarm system to the kitchen hood fire�suppression system for system alarm initiation. The kitchen hood fire�suppression systems shall shut down any gas supply for cooking. J. Gas and Fuel Shut�Off Valves: Connect the system to shut�off valves for gas and fuel oil supplies that serve or pass through student�occupied spaces for alarm condition shut down. 3.03 CONDUIT, RACEWAYS AND WIRE AND CABLE INSTLLATION A. All wiring shall meet the requirements of the National Electrical Code, and all national, state, and local codes. B. Install all fire alarm system cables as follows: 1. General: Install all system cabling in conduit, boxes, and other enclosed raceways for system equipment and outlets unless specifically otherwise noted. 2. Above Finished Ceilings: a. Install cables without conduit only in areas specifically indicated in the Contract Documents and when routed concealed above accessible ceilings. In all other locations install cables in conduit or other enclosed raceways. b. Where cables are installed without conduit or other enclosed raceway or in open cable tray 1) Route cables parallel or perpendicular to building lines. 2) Arrange cable runs to maintain headroom above ceiling and present neat appearance. 3) Bundle cable runs together by system type and secure the cables to the building structure utilizing bridle rings or cable ties of at least 30 pounds tensile strength. 4) Secure and support all cables at intervals not more than six feet (6’�0”) and such that cables do not sag more than seven (7) inches from any point of support. 5) Provide clearances of at least 10 feet from electrical bus duct, six (6) feet from large motors and transformers, 12 inches from conduit and cables used for electrical power distribution, and 6 inches from lighting fixtures that utilized ballasts (fluorescent, high intensity discharge, etc.) to minimize electromagnetic interference. C. All fire alarm system cabling within building perimeters are to be installed above the building finished floor line. D. Provide all wiring, conduit, pull boxes, outlets, and mounting boxes required for the installation and operation of a complete fire alarm system, as specified and described. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 15 of 17 March 23, 2012 E. Provide all outlets and mounting boxes required as a part of the mounting arrangement for stations, control cabinets, and signals. These shall be in accordance with the manufacturer's specifications. F. This Contractor shall provide power from a dedicated 1P�20 ampere, 120�volt circuit for fire alarm system control panel and all notification appliance circuit (NAC) extender panels. Wiring for 120 VAC power wiring shall be #12 AWG installed in conduit. G. Audio/visual and Visual Only Unit Cabling. 1. A single pair of conductors can be used for indicating appliance circuits where the system provides the capability to silence audio devices without interrupting visual/strobe operation. 2. Where audio units cannot be silenced without interrupting visual/strobe operation provide separate pairs of conductors on indicating appliance circuits for the audio and the visual signals as required to allow the audio units to be silenced while the visual units remain activated. 3.04 CLEANING A. Clean all dirt and debris from the inside and the outside of the fire alarm equipment after completion of system installation. 3.05 PROGRAMING AND LABELING A. Program the system to display the Owner's room numbers for each system addressable device. Do not use the Architect’s room numbers. B. System labeling shall utilize the Owner's room numbers. 3.06 TESTING A. The completed fire alarm system shall be fully tested in accordance with NFPA�72 by the Contractor in the presence of the Owner's representative, the Engineer, the Architect and the local authority having jurisdiction, and the manufacturer's technical representative. Upon completion of a successful test, the contractor shall so certify in writing to the Owner, Engineer, Architect, and all authorities having jurisdiction 3.07 WARRANTY A. Provide warranty under the provisions of Division 01. B. The equipment manufacturer shall make available to the Owner a maintenance contract proposal to provide a minimum of two inspections and tests per year in compliance with NFPA 72 guidelines. Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 16 of 17 March 23, 2012 3.08 CLOSE OUT MANUALS A. At the completion of the project and before final payment the Electrical Contractor shall turn over to the Owner all system keys, spare parts, manuals, as�built drawings, etc., required by these Specifications, and certify in writing that the Fire Alarm System has been installed in conformance with all applicable codes and is operating properly. 3.09 CONNECTIONS A. For fire�protection systems related to doors in fire�rated walls and partitions and to doors in smoke partitions, comply with requirements in Division 08 Section "Door Hardware." Connect hardware and devices to fire�alarm system. 1. Verify that hardware and devices are NRTL listed for use with fire�alarm system in this Section before making connections. B. Make addressable connections with a supervised interface device to the following devices and systems. Install the interface device less than 3 feet from the device controlled. Make an addressable confirmation connection when such feedback is available at the device or system being controlled. 1. Alarm�initiating connection to activate emergency shutoffs for gas and fuel supplies. 3.10 IDENTIFICATION A. Identify system components, wiring, cabling, and terminals. Comply with requirements for identification specified in Division 26 Section "Identification for Electrical Systems." B. Install framed instructions in a location visible from fire�alarm control unit. 3.11 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory�authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. B. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory�authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. C. Tests and Inspections: 1. Visual Inspection: Conduct visual inspection prior to testing. a. Inspection shall be based on completed Record Drawings and system documentation that is required by NFPA 72 in its "Completion Documents, Matt the Miller’s Carmel, In L’Acquis Number: 12056 Section 283101 Addressable Fire�Alarm System Page 17 of 17 March 23, 2012 Preparation" Table in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter. b. Comply with "Visual Inspection Frequencies" Table in the "Inspection" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72; retain the "Initial/Reacceptance" column and list only the installed components. 2. System Testing: Comply with "Test Methods" Table in the "Testing" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72. 3. Test audible appliances for the public operating mode according to manufacturer's written instructions. Perform the test using a portable sound�level meter complying with Type 2 requirements in ANSI S1.4. 4. Test audible appliances for the private operating mode according to manufacturer's written instructions. 5. Test visible appliances for the public operating mode according to manufacturer's written instructions. 6. Factory�authorized service representative shall prepare the "Fire Alarm System Record of Completion" in the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA 72 and the "Inspection and Testing Form" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in NFPA 72. D. Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or replaced devices and appliances. E. Fire�alarm system will be considered defective if it does not pass tests and inspections. F. Prepare test and inspection reports. G. Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly, quarterly, and semiannual periods. Use forms developed for initial tests and inspections. 1. Provide pricing to the Owner after commissioning. H. Annual Test and Inspection: One year after date of Substantial Completion, test fire�alarm system complying with visual and testing inspection requirements in NFPA 72. Use forms developed for initial tests and inspections. 1. Provide pricing to the Owner after commissioning. END OF SECTION 283111