HomeMy WebLinkAbout0110-SU1.1.pdfGENERAL SITE UTILITY PLAN NOTES 1. THE PLANS SHOW THE LOCATION OF UTILITIES LOCATED WITHIN THE LIMITS OF THE CONTRACT ACCORDING TO INFORMATION PROVIDED BY THE VARIOUS UTILITY COMPANIES, PREVIOUS CONSTRUCTION PLANS AND AS EVIDENCED BY OBSERVATION OF ABOVE GROUND CONDITIONS BY THE SURVEYOR. THE ACCURACY OF THE INFORMATION IS NOT GUARANTEED. 2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY AND COORDINATE CONSTRUCTION WITH ALL RESPECTIVE UTILITIES. 3. EXCAVATIONS EXCEEDING TWENTY (20) FEET IN DEPTH REQUIRE THE DESIGN OF A TRENCH SAFETY SYSTEM BY A REGISTERED PROFESSIONAL ENGINEER. 4. SEE PLUMBING DRAWINGS FOR CONTINUATION OF UTILITIES INTO BUILDING. 5. SEE DETAILS ON SU2.1 FOR PIPE BEDDING AND BACKFILL DETAILS. 6. ALL PAVEMENT CUT DUE TO UTILITY INSTALLATION SHALL BE PATCHED WITH A PAVEMENT SECTION WHICH MEETS OR EXCEEDS THE EXISTING PAVEMENT. 7. CONTRACTOR SHALL SLEEVE ALL PIPING AT FOOTINGS AND SLEEVES SHALL BE WATER TIGHT. 8. WHERE WATER LINES AND SEWERS CROSS AND THE WATER LINE CANNOT BE PLACED ABOVE OR BELOW THE SEWER WITH A MINIMUM OF 18" VERTICAL CLEARANCE, THE SEWER MUST BE CONSTRUCTED OF WATER WORKS GRADE DUCTILE IRON PIPE WITH MECHANICAL JOINTS WHEN WITHIN 10' OF THE WATER LINE. THE WATER LINES SHALL BE INSTALLED ABOVE THE SEWER WHERE EVER POSSIBLE. 9. WHERE WATER LINES AND SEWERS RUN PARALLEL AND A MINIMUM SEPARATION DISTANCE OF 10' CANNOT BE MAINTAINED, THE SEWER MUST BE CONSTRUCTED OF WATER WORKS GRADE DUCTILE IRON PIPE WITH MECHANICAL JOINTS. 10. SEE SITE ELECTRICAL FOR SITE LIGHTING CIRCUITS AND SITE ELECTRICAL LAYOUT. 11. BENCHMARK (PROVIDED BY SURVEYOR) - HAM G-26 ELEVATION - 802.61' (NGVD29) A ISHC DISK AT THE SOUTH END OF WEST CURB OF SOUTHBOUND LANE BRIDGE ON SR431 OVER COOL CREEK. 17.7 FEET NORTH OF THE SOUTH END OF BRIDGE AND 0.4 MILES NORTH OF MAIN STREET. 12. ALL STORM SEWER CASTINGS SHALL CONTAIN A MESSAGE AT THE TOP OF THE CASTING STATING "DUMP NO WASTE-DRAINS TO WATERWAY." 13. FIELD VERIFY PIPE INVERT ELEVATIONS OF EXISTING STRUCTURES TO BE MODIFIED OR CONNECTED INTO PRIOR TO STARTING INSTALLATION OF NEW STORM SEWERS. NOTIFY ARCHITECT- ENGINEER OF ANY DISCREPANCY 14. SEE MEP PLANS FOR LOCATION OF NEW FIRE PROTECTION LINES, PIVs OR FDCs. 20 0 20 40 60 KEYNOTES 1. SANITARY PIPE TO BE ASTM-D3034, SDR-35 PVC. 2. ALL SANITARY SEWERS SHALL BE TESTED IN ACCORDANCE WITH CARMEL UTILITIES STANDARD SPECIFICATIONS. 3. CONTRACTOR SHALL PROVIDE 95% MODIFIED PROCTOR COMPACTION OF SUITABLE FILL IN SIX (6) INCH LIFTS FOR ALL PORTIONS OF SANITARY SEWER INFRASTRUCTURE. 4. MANHOLE OR CLEAN-OUT CASTINGS MAY NEED TO BE ELEVATED AFTER FINAL GRADING TO ENSURE DRAINAGE AWAY FROM STRUCTURES. CLEANOUTS IN SIDEWALKS OR PAVED AREAS SHALL BE FLUSH WITH PAVEMENT. 5. ALL ROUGH GRADING MUST BE FINISHED TO WITHIN 1 FOOT OF FINAL GRADE PRIOR TO THE START OF CONSTRUCTION OF THE SANITARY SEWER INFRASTRUCTURE 6. AT THE INSPECTOR'S DISCRETION, A CONCRETE CRADLE MAY BE REQUIRED FOR ALL LATERAL OR UTILITY CROSSINGS. 7. ALL BENCH WALLS SHALL EXTEND TO THE CROWN OF THE HIGHEST INFLUENT PIPE. 8. DRAIN PIPE SHALL INCLUDE ALL ELBOWS, WYES, FITTINGS AND MATERIAL NECESSARY TO CONNECT DOWNSPOUTS TO DRAIN. INDIVIDUAL DOWNSPOUT CONNECTIONS SHALL BE A MINIMUM OF 8". PVC SHALL BE ASTM D3034 SDR35. 9. CONTRACTOR SHALL CONTACT STEVE COOK WITH CARMEL WATER AT 733-2855 FOR ALL INSTALLATION AND INSPECTION REQUIREMENTS RELATED TO THE WATER LINE WORK. PROPOSED BUILDING ADDITION FFE = 832.94 SANITARY NOTES 1 2 3 4 5 6 9 10 11 7 LEGEND WATER SANITARY SEWER STORM SEWER MANHOLE EXISTING PROPOSED NOTE: SEE SURVEY FOR ADDITIONAL LEGEND INFORMATION SANITARY PIPE STORM PIPE CLEANOUT co GAS LINE WATER LINE 13 14 GAS LINE AND VALVE TO BE RELOCATED AROUND NEW CONSTRUCTION. COORDINATE WITH GAS CO. SEE MEP PLANS 15 JOINT RESTRAINT PER CITY OF CARMEL REQUIREMENTS, SEE TABLE 5/SU2.2 NEW FIRE HYDRANT AND VALVE, SEE DETAIL 4/SU2.2 REMOVE EXISTING WATER LINE FUTURE BUILDING LINE REMOVE EXISTING FIRE HYDRANT AND VALVE REMOVE EXISTING FIRE DEPARTMENT CONNECTION REMOVE EXISTING POST INDICATOR VALVE RECONNECT TO EXISTING EXISTING CONCRETE CURB AND SIDEWALK EXISTING SCHOOL BUILDING SEE ENLARGED EXISTING FIRE WATER SERVICE PLAN THIS SHEET ENLARGED EXISTING FIRE WATER SERVICE PLAN SCALE: 1" = 10' CONNECT TO EXISTING WATER LINE EXISTING CONCRETE CURB RECONNECT REROUTED WATER MAIN REMOVE EXISTING WATER LINE REMOVE EXISTING WATER LINE I.E.=826.25 2 3 3 24 6 7 24X24 IN CONCRETE BOX STRUCTURE, SEE DETAIL 3/SU2.1 T. RIM ELEV. = 828.00 INV. ELEV. = 825.25 SUMP INV. ELEV. = 822.00 INV. ELEV. 4" ORIFICE = 827.50 8 79 FT OF 6 IN SCH. 40 PVC SANITARY SEWER LATERAL LINE (MIN. 1.04% SLOPE). CONNECT TO BUILDING AT 829.94 AND TIE INTO EXISTING 8" 6$1,7$5<$7(/(9 “6(('(7$,/668 AND 2 & 3/SU2.2 SEWER CLEANOUT TYPE 2, SEE DETAIL 1/SU2.2 12 8 IN DUCTILE IRON WATER LINE (MATCH EXISTING), PER CARMEL UTILITIES STANDARDS AND DETAILS 6 & 7/SU2.2 12 12 12 NOT USED 110 L.F. OF 12" PVC STORM SEWER@ 2.89% SLOPE, SEE DETAIL 2/SU2.1 (SEE NOTE 25 FOR ADDITIONAL INFORMATION CONCERNING PIPE MATERIAIL) STORM CLEANOUT TYPE 2, SEE DETAIL 1/SU2.2 WYE INTO EXISTING 8" SANITARY, SEE DETAIL 2/SU2.2 & 3/SU2.2 CAST IN PLACE CONCRETE HEADWALL, SEE DETAIL 5/SU2.1 COBBLESTONE AT END SECTION, SEE DETAIL 6/SU2.1 14 20 14 15 RAIN GARDEN BMP AREA, SEE DETAIL 1/SU2.1 AND LANDSCAPE PLAN. 16 16 22 L.F. OF 12" DUCTILE IRON @ 2.89% SLOPE WITH 18" FULL CONCRETE ENCASEMENT 5 FEET FROM STAIRS ON BOTH SIDES, SEE DETAIL 2/SU2.1 17 10" STORM OUT OF BUILDING. COORDINATE WITH PLUMBING PLANS 18 20 EXISTING LIGHT POLE AND BASE TO REMAIN. ELECTRICAL SERVICE LINES WILL NEED TO BE RE-ROUTED TO PROVIDE AND MAINTAIN SERVICE. 21 PROTECT EXISTING GAS LINE. RE-ROUTE EXISTING LINE AS NECESSARY FOR NEW CONSTRUCTION. 22 EXISTING STORM INLET TO BE CLEANED AND DEBRIS REMOVED FROM INLET AND DISCHARGE PIPE. IF STORM LINE CONFLICTS WITH NEW CONSTRUCTION, RE-ROUTE LINE TO PROVIDE POSITIVE DRAINAGE. REMOVE ABANDONED WATER LINE PAVEMENT PATCH (APPROX. LIMITS), MATCH EXISTING PAVEMENT SECTION WITH REPAIRS 21 14 22 21 15 8 14 9 13 20 21 21 19 14 14 9 11 18 4 10 9 13 VALVE FIRE HYDRANT EXISTING BUILDING 19 EXISTING 15" STORM LINE INLETS, VALVES, AND MARKS MADE UPON THE GROUND BY ALSO BE OTHER EXISTING UNDERGROUND UTILITIES FOR WHICH THERE IS NO ABOVE GROUND EVIDENCE OR FOR EXACT LOCATIONS OF EXISTING UNDERGROUND UTILITIES SHALL BE VERIFIED BY CONTRACTOR PRIOR TO ANY AND WHICH NO ABOVE GROUND EVIDENCE WAS OBSERVED. THE OTHERS) AND ARE SPECULATIVE IN NATURE. THERE MAY ALL CONSTRUCTION. THE LOCATIONS OF ALL EXISTING UNDERGROUND UTILITIES EVIDENCE (INCLUDING, BUT NOT LIMITED TO, MANHOLES, SHOWN ON THE PLAN ARE BASED UPON ABOVE GROUND CAUTION !! Know what's R Call 811 or 1-800-382-5544 Before You Begin Any Digging Project. Call 48 hours or 2 working days before you dig. It's Fast, It's Easy and It's the Law in the state of Indiana! REMOVE EXISTING WATER LINE REMOVE EXISTING WATER LINE NOTE: COORDINATE FIRE PROTECTION SYSTEM REMOVALS AT THE BUILDING WITH MEP PLAN. INFORMATION SHOWN FOR REFERENCE ONLY. 14 8 23 ADS TRENCH DRAIN, PER DETAIL 8/SU2.1 LENGTH = 16 FEET RIM ELEV. (E) = 828.75 INV. ELEV. (E) = 828.25 RIM. ELEV. (W) = 828.75 INV. ELEV. (W) = 827.75 23 24 24 L.F. OF 6" PVC STORM SEWER @ 6.27% SLOPE WITH GALVANIZED ANIMAL GUARD. CONNECT TO TRENCH DRAIN AT ELEV. = 827.75, SEE DETAIL 2/SU2.1 I.E.=827.80 PAVEMENT SAW CUT LINE PAVEMENT SAW CUT LINE I.E.=826.30 (12" DOUBLE WYE) 17 I.E.=829.44 I.E.=829.94 5 DRAINAGE OVERFLOW PATH LEGEND DRAINAGE AREA AREA (SF) 2 YEAR Q (CFS) 10 YEAR Q (CFS) 100 YEAR Q (CFS) CURRENT (CN=98) 18,600 1.32 1.91 PROPOSED (CN=97) 18,600 1.89 3.23 REQUIRED (CF) PROVIDED (CF) DETENTION VOLUME [10 PROPOSED - 2 CURRENT] 1,625 1,695 DETENTION VOLUME [100 PROPOSED - 10 CURRENT] 3,859 1,894 DETENTION SUMMARY