CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on: January 31. 2005
Indiana Department of Fire and
BU Iding Services
PLANREVIEW DIVISION ~"~' S UUUU
office of the State Building Commissioner ~""
402 W Washington St Room E245
lad anap ia, tana 2 4 PP
TO: Owner lArch tact Eng near SU ORT HOOS E~SAFET
PAUL I CPJPE INC nd aha State Emergency
Management
FREDRICK J GREEN 00001 Department of Fire and Bulldir
7172 GRAHAM ROAD Services
~IAPOLIB IN 46250 Public Safety and Training
institute
Construction type Occupancy classification
[~-B. SPK E. ADD, RE~vl
ARCH ELEC FDN MECH
PLUM STR
Standar¢
Project name
SMOKY ROW ~_~ARY ADD~ON AND RENOVATION
Street address
900 WEST 13STH STREET
County
HAMILTON
null and void, if th~
t is determined to be issued in error, ir
~hall expire by lin'Aation, and become
as wellas a
THIS PROJECT HAS BEEN REV IEWIE~ UNDEr{ THE 2003 INDIA NA BUILDING CODE.
Detailed plans and specifications of the fire Suppression system shall be filed with the required
application and appropriate fees in accordance with 675 lAC 12-6-3(a) and 675 lAC 13~1-8, (N.F.P.A. 13)
3B0907A1 The fire alarm system shall be designed as specified in Section 907, IFC (675 lAC 22-2.3) and N.F.P.A.
72 (675 lAC 22-2.2-17) in accordance with Section 907, IBC (675 lAC 13-2.4).
3B1003J Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or
mere shall not be provided with a latch or lock unless it is panic hardware, in accordance with Section
1003.3.1,9, IBC (675 lAC 13-2.4).
Please be advised that if an ad~nistratrve rev~w of this action ~s desired, a w r~ten petition for review must be filed at the above address w Ifh the
Fire Prevention and Building Safety Corc,3ission iden ifyiog the trotter for w hich a revhgw is sought no ieter than eighteen (18) days from the above
-stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in w hich the Department of Fire
and Building Services is closed during normal business hours, ~n the latter Case, the filing deadline w ill be the first working day thereafter, if you
choose to petition, and the before-mentiol3ed procedures are follow ed, your petition for review W ill be granted, and an administrative proceeding
w ill be conducted by an administrative law judge of the Fire Prevention and Buildieg Safety Derra~ission. If a petition for review is not filed~ this
Order w iii be final, and you rnus[ comp~ with its requiremems