HomeMy WebLinkAboutMDATUM ELEVATION 1. See civil drawings for USGS elevation of first floor. SaEdEBAL 1. Concrete contractor is responsible for stability of excavations required to complete the work of their contract. Systems used to stabilize excavations shall be adequate to resist the force of the soil, any surcharge due to construction activities and the fords imposed on the excavation during construction activities due to wind or seismic forces. FOUNDATIONS 1. A soils report was not provided for this project. The contractor is responsible for contacting a qualified Geotechnical Engineer to verify that the existing sub - surface conditions and other soils related items are adequate for the design requirements listed below. 2. Exterior footings shall bear a minimum of 3' -0" below finish grade. 3. Foundations have been designed for the following net soil pressures: Isolated Spread Footings: 2,000 psf Continuous Wall Footings: 2,000 psf 4. Foundation excavations shall be made to plan elevations. The soil conditions beneath foundations shall then be inspected by a qualified Geotechnical Engineer. N the soils under the foundations are unacceptable, Use one of the following procedures: A Remove the unacceptable soil and bockfill with engineered fill compacted to 100% standard proctor density and in accordance with the geotechnical report or inspecting Engineer. B. Lower the footing to an acceptable soil. 5. Excavations for spread footings, combined footings, continuous footings and /or mat foundations shall be cleaned and hand tamped to a uniform surface. Footing excavations shall have the sides and bottoms temporarily lined with 6 mil visqueen N placement of concrete does not occur within 24 hours of the excavation of the footing. 6. Soils under the slab -on -grade shall be compacted per the geotechnical report. Soils work shall be inspected by a material testing lab. 7. Foundation conditions noted during construction, which differ from those described in the geotechnical repot shall be reported to the Structural Engineer, Geotechnical Engineer and construction manager before further construction is attempted. CONCRETE 1. Reinforced concrete has been designed in accordance with the 'Building Code Requirements for Structural Concrete' (ACI 318 -95) and Commentary (ACI 31811-95). 2. Mixing, transporting, and placing of concrete shall conform to the latest edition of the "Specifications for Structural Concrete for Buildings" (ACI 301). 3. Concrete in the following areas shall consist of natural sand fine aggregates and normal weight coarse aggregates conforming to ASTM C33, Type I Portland cement conforming to ASTM C150, and shall have the following compressive strength (F'c) at 28 days: 3,000 psi: Footings, pilasters, pedestals, and slabs on grade 4,000 psi with 6% +/- 1 -1/2% entrained air by volume: Retaining, knee and foundation walls, Curtis, sidewalks and other Concrete exposed to de -icers or freeze /thaw conditions 4. Adjustment of slump by adding water to the mix at the job site shall occur as follows. Adjustment shall be made one time only with a maximum of 2 gallons of water per cubic yard such that the specified slumps and water /cement ratios are not exceeded. The concrete shall be mixed after the addition of water one minute per cubic yard to a maximum of 5 minutes. 5. Protect the concrete surface between finishing operations on hot, dry days or any time plastic shrinkage cracks could develop by using wet burlap, plastic membranes or fogging. Protect concrete surfaces at all times from rain, hail or other injurious effects. 6. Horizontal joints will not be permitted in concrete construction except as shown on the contract documents. Vertical joints shall occur at locations approved by the Structural Engineer. CONCRETE SLABS ON GRADE 1. Slabs on grade shall be constructed in accordance with the latest edition of the "Guide for Concrete Floor and Slab Construction" (ACI 302.1R). 2. In addition to the specifications noted elsewhere, concrete for interior flatwork shall conform to the following: 470 lbs. of cement per cubic yoM of concrete, minimum 0.47 maximum water cement ratio 3 inch maximum slump prior to addition of plasticizers 5 inch maximum slump if plasticizers are not used Midrange or highronge water reducing admixture required 3. In addition to the specifications noted elsewhere, concrete for exterior flatwork curbs and walls exposed to freeze /thaw shall conform to the following: 564 lbs. of cement per cubic yard, minimum 0.45 maximum water cement ratio by weight 3 inch maximum slump prior to addition of plasticizers 5 inch maximum slump if plasticizers are not used Midrange or highronge water reducing admixture required 4. Place concrete in a manner so as to prevent segregation of the mix. Delay floating and troweling operations until the concrete has lost surface water sheen or all free water. Do not sprinkle free cement on the slab surface. 5. Provide curing of concrete slabs immediately after finishing using a sprayed on liquid curing compound. Other methods may be used with approval by structural engineer. 6. Slabs on grade shall receive a smooth trowel finish, and be placed to achieve the following minimum tolerances: Overall values: FF = 35, FL = 25 Local values: FF = 25, FL = 15 CONCRETE and MASONRY REINFORCEMENT 1. Reinforcing steel shall be deformed bars of new billet steel conforming to ASTM A615 -90 with a minimum yield strength of 60,000 psi. 2. Reinforcing steel, which is to be welded, shall conform to ASTM A706 'Low -Alloy Steel Deformed Bars for Concrete Reinforcement 3. Reinforcing bar detailing, fabricating, and placing shall conform to the latest edition of "Specifications for Structural Concrete for Buildings' (ACI 301). 4. Provide standard bar chairs and spacers as required to maintain specified concrete protection. 5. Reinforcement bars shall not be tack welded, welded, heated or cut unless indicated on the contract documents or approved by the Stnactural Engineer. 6. Unless otherwise shown or noted, splicing of reinforcing bars shall conform to ACI 318 -95. Where the length of lap is not shown or noted, provide a Class 'B' lap at splices. 7. Horizontal bars in walls or grade beams shall be bent at corners and intersections in a way that continuity is provided through the joint. Separate comer bars of the some size and spacing as the horizontal reinforcing may be substituted for the bent bars. 8. Unless noted otherwise, provide 2 - 15 bars (one each face) around unframed openings in concrete walls and grade beams. Place bars parallel to sides of the opening and extend 24' beyond comers. 9. Provide galvanized steel wire joint reinforcement in all masonry construction. Reinforcement shall be continuous and be lapped sixteen inches at splices. Cut reinforcement at all control and expansion joints. Space reinforcement at 8' on center for stack bond construction, parapets and below building floor elevation. Elsewhere space reinforcement at 16 inches on center. MASON� 1. Concrete masonry has been designed in accordance with the latest edition of the 'Building Code Requirements for Concrete Masonry Structures' (ACI 530). 2. Concrete masonry construction shall conform to the latest edition of the "Spec cation for Concrete Masonry Construction" (ACI 530.1). 3. Concrete masonry constriction shall be inspected as required by the 1Specif�cation for Concrete Masonry Construction' (ACI 530.1). 4. Concrete masonry construction shall have a minimum compressive strength (f'm) of 2,000 psi at 28 days. 5. Mortar shall be type M below grade and type M or S above grade proportioned in accordance with the latest edition of ASTM C270 or C476. 6. Unless otherwise noted, reinforced masonry cores, cores specified to be filled on the drawings, and bond beams shall be filled with concrete with a minimum 2,800 psi compressive strength at 28 days, 314' maximum aggregate and 7" maximum slump. 7. Unless otherwise noted, provide two 1/2' diameter x 1' -2" hooked anchor bolts at beam bearings shown on framing plans. Space at beam gage. 8. Beams, lintels, joists, etc. shall bear on bond beams or hollow masonry units with cores filled solid with grout. See drawings for minimum requirements. EXPANSION and SLEEVE ANCHORS 1. Expansion and sleeve anchors shall be carbon steel anchors as manufactured by HiIU Fastening Systems or approved equal. Install anchors in conformance with the manufacturer's recommendations and the contract documents. 2. Masonry cores receiving 3/4' diameter anchors shall be filled with coarse grout conforming to ASTM C476 with a minimum compressive strength of 2,000 psi at 28 days. Do not install anchors in mortar joint. 3. Do not install expansion anchors in concrete until concrete has attained the specified 28-day compressive strength• 4. Test expansion, sleeve and epoxy anchors prior to connecting steel to anchors. NON - SHRINK GROUT 1. Grout shall be a prepackaged, non- metallic and non - gaseous. ft shall be non -shrink when tested in accordance with ASTM -01107 Grade B or C at a fluid consistency (flow cone) of 20 to 30 seconds. Thirty - minute -old grout shall flow through the flow cone after slight agitation, in temperatures of 40 degrees F to 90 degrees F. Grout shall be bleed free and attain 5,000 -psi compressive strength in 28 days at fluid consistency. 2. Grout compressive strength tests shall be performed in accordance with the latest edition of ASTM C109. PLYWOOD 1. Plywood panels shall be detailed, fabricated and erected in accordance with the latest criteria established by the American Plywood Association (APA) including their latest edition of the PLvwood Design Specification (and its Supplements). 2. Plywood panels shall be identified with the appropriate trademark of the APA and shall meet the requirements of the latest edition of the U.S. Product Standard PS 1 for Construction and Industrial Plywood [or the APA PRP -108 Performance Standards and Policies for Structural -Use Panels]. 3. Roof panels shall be installed with the long dimension (face grain) across the supports with panels continuous over 2 or more supports (minimum 3 span condition). 4. Stagger panel end joints. End joints shall only occur over a support. Unless recommended otherwise by the panel manufacturer, provide a 1/8" gap between panel ends and edges. Panel edges shall be tongue- and - groove or supported on 2" (nominal) lumber blocking installed between joists. 5. Panels shall be fastened to their supports as follows: Roof panels: 6" o.c. along supported panel edges and 12" o.c. at intermediate supports Use 8d galvanized common nails for panels 1/2" thick and less and 8d galvanized common nails for panels of greater thickness. WOOl2 TRUSSES 1. Prefabricated wood trusses shall be detailed, fabricated and erected in accordance with the latest editions of the Timber Construction Manual by the American Institute of Timber Construction (AITC), the National Design Specification for Wood Construction by the National Forest Products Association (NFPA) and in accordance with the latest criteria established by the Truss Plate Institute (TPI). 2. Temporary and permanent bracing of wood trusses shall be in accordance with the latest edition of Bracing Wood Trusses: Commentary and Recommendations BWT by the TPI. 3. Wood trusses shall be designed to support the loads shown in the design data in addition to the weight of the trusses. 4. Wood roof trusses shall be designed using the following allowable stress increase factors: Dead Load + Live Load: 1.15 Dead Load + Wind Load: 1.33 Dead Load + Live Load +Wind Load: 1.15 5. Deflection due to live load shall be limited to 1/360 of the truss span. For truss cantilevers, the deflection due to live load at the end of the cantilever shall be limited to 1/180 of the cantilever dimension. 6. Truss plates shall be galvanized steel and shall be applied to both faces of the members being connected. 7. Trusses shall conform to the geometry shown on the architectural drawings. 8. The Truss Manufacturer shall prepare detailed working or shop drawings and shall submit one reproducible copy and one blue line copy to the Architect for review prior to fabrication. The approval drawings shall show the design forces in truss members, the sizes of truss plates; the lumber species, commercial grade and normal duration design values; required bracing and details necessary to enable fabrication, erection and construct of all parts of the work in accordance with the detail drawings and specifications. These shop drawings will be reviewed for design features only. The Truss Manufacturer shall be responsible for all dimensions, accuracy, and fit of work. Allow time in schedule for shop drawings to be in engineer's office five working days for review. All shop drawings shall be prepared and certified by a structural engineer licensed in the some state where the project is located. 9. THE CONTRACTOR SHALL INSTALL ALL TEMPORARY AND PERMANENT TRUSS BRACING AS SHOWN ON THE TRUSS MANUFACTURER'S SHOP DRAWINGS. LUMBER 1. Structural lumber shall be detailed, fabricated and erected in accordance with the latest editions of the Timber Construction Manual by the American Institute of Timber Construction (AITC) and the National Design Specification for Wood Construction by the National Forest Products Association (NFPA). 2. Lumber shall be No. 2 Southern Pine, kiln dried, with a maximum moisture content of 15%, or approved equal (unless noted otherwise). 3. Lumber for top plates supporting roof trusses shall be No. 2 Southem Pine Select Structural, kiln dried, with a maximum moisture content of 15%, or approved equal. 4. Lumber used for blocking and other non - stress related uses shall be No. 2 Southern Pine, surface dry, with a maximum moisture content of 19%. 5. Unless otherwise shown or noted, bolts and lag screws in connections of wood members shall be made with material conforming to ASTM A307. Standard cut washers shall be used between the wood and bolt head and the wood and nut. 6. Joist hangers and connection plates shall be manufactured by Simpson Company or approved equal. 7. Nails and other wood fastenings, unless otherwise noted, shall conform to the latest edition of the National Design SgMcffication for Wood Construction by the NFPA. 8. Rough sawn timbers shall be treated and finished as required by the specifications. Weather exposed members shall be treated with CCA. RE -BAR LAP SPLICE SCHEDULE FOR CONCRETE CONSTRUCTION BAR SIZE ARCH. CLASS A CLASS B COMPRESSION #3 1' -4" 1' -10" 1' -0" #4 1' -10" 2' -4" i' °3" #5 2' -3" 3' -0" 1' -7" #6 2' -9" 3' -8" 1' -11" #7 4' -0" 5' -2" 2' -3" #8 4' -8" 6' -0" 2' -6" #9 5' -2" 6' -8" 2' -10" 1. P" DE M ES AS %M ABM UNLESS LOWER LAPS ARE INDICATED ON DRAWINGS. 2. PROVIDE CLASS B SPUCE UNLESS CLASS A OR SPLICE • �r / DETAILS. APPLICABLE CODES AND DESIGN DATA THE BUILDING STRUCTURE IS TO BE DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, 2008 EDITION AND THE FOLLOWING CRITERIA ROOF DESIGN LOADS: TOP CHORD LIVE LOAD .......................... 20 PSF TOP CHORD DEAD LOAD .........................10 PSF BOTTOM CHORD LIVE LOAD ....................10 PSF BOTTOM CHORD DEAD LOAD ..................10 PSF ROOF SNOW LOADS: FLAT ROOF SNOW LOAD (Pf) ............... N/A SNOW EXPOSURE FACTOR (Ce) ............1 SNOW LOAD IMPORTANCE FACTOR (I)...1 THERMAL FACTOR (Ct) ..........................1 WIND LOAD DESIGN DATA BASIC WIND SPEED (3 SECOND GUST) ..... 90 MPH WIND LOAD IMPORTANCE FACTOR (1).........1.0 WIND EXPOSURE ........... ..............................0 OCCUPANCY CATEGORY .............................. II INTERNAL PREESURE COOEFFICIENT (GCpi) ............... +0.18, -0.18 COMPONENTS AND CLADDING DESIGN PRESSURE ..... 15 PSF SEISMIC DESIGN DATA SEISMIC IMPORTANCE FACTOR (I) .............1.0 SEISMIC DESIGN CATEGORY ........................ B SPECTRAL RESPONSE COEFFICIENTS do ACCELERATIONS Sds ..........18.1 % Ss .......... 0.170 Sd 1 ..........12.2% S1 .......... 0.076 SITE CLASS .................. ............................... D DESIGN BASE SHEAR .. ............................... 3 KIPS SEISMIC RESPONSE COEFFICIENT (Cs) ...... 0.18 RESPONSE MODIFICATION FACTOR (R) ....... 6.5 BASIC SEISMIC RESISTING SYSTEM LIGHT FRAME WITH STRUCTURAL WOOD PANELS (R =6 1/2) ANALYSIS PROCEDURE UTILIZED EQUIVALENT LATERAL FORCE PROCEDURE CONSTRUCTION INSPECTION REOUIREMENTS THE BUILDING CODE REQUIRES A SPECIAL INSPECTOR TO OBSERVE THE WORK ASSIGNED FOR CONFORMANCE TO THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS. THESE INSPECTIONS ARE IN ADDITION TO INSPECTIONS SPECIFIED ELSEWHERE. AJ & ASSOCIATES, P.C. DOES NOT PROVIDE THESE INSPECTIONS. THE OWNER SHALL RETAIN THE SERVICES OF A MATERIAL TESTING AGENCY TO MAKE AVAILABLE A SPECIAL INSPECTOR WHO SHALL PROVIDE INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED BELOW. CONCRETE CONSTRUCTION: ACI 318 CONCRETE MASONRY CONSTRUCTION: ACI 530, ACI 530.1 STRUCTURAL STEEL CONSTRUCTION: AISC ASD, AISC LRFD, ASTM A6, ASTM A588, AWS ABBREVIATIONS A.B. ANCHOR BOLT ARCH. ARCHITECTURAL B.L. BUILDING LINE B /BM BOTTOM OF BEAM B/F BOTTOM OF FOOTING BLDG. BUILDING BM. BEAM BRG. BEARING C.J. CONTROL OR P.C. CONSTRUCTION JOINT CLR. CLEAR CMU CONCRETE MASONRY UNIT CONC. CONCRETE CONNX CONNECTION CONST. CONSTRUCTION CONT. CONTINUOUS CONTR. CONTRACTOR D.L. DEAD LOAD DET. DETAIL DU. DIAMETER DWG. DRAWING DWL. DOWEL E.E. EACH END E.F. EACH FACE E.W. EACH WAY EA. EACH E.J. EXPANSION JOINT EQ. EQUAL EXIST. EXISTING EXP. EXPANSION EXPAN. EXPANSION F.D. FLOOR DRAIN FlN. FINISH F.S. FAR SIDE OSF OUTSIDE FACE FDN. FOUNDATION OPP. OPPOSITE FIG. FOOTING P.EM.B. PRE- ENGINEERED FT. FOOT OR FEET METAL BUILDING GA. GAGE P.C. PRECAST CONCRETE GAIN. GALVANIZED PL PLATE GRAN. GRANULAR PSF POUNDS /SQUARE FT. GYP. BD. GYPSUM BOARD R.D. ROOF DRAIN H. HORIZONTAL REINF. REINFORCING OR HK. HOOK REINFORCED HORIZ. HORIZONTAL REQ'D. REQUIRED ISF INSIDE FACE REV. REVISION OR REVISED IN. INCH SECT. SECTION INSUL INSULATION SHT. SHEET J/B JOIST BEARING SAM. SIMILAR JST. JOIST SPA. SPACES OR SPACING JT. JOINT SPECS SPECIFICATIONS LB. /LBS. POUND /POUNDS STL STEEL LL LIVE LOAD STD STANDARD LLH LONG LEG HORIZ. T&B TOP AND BOTTOM LLV LONG LEG VERTICAL T/B TOP OF BEAM OR LT. WT. LIGHT WEIGHT TRUSS BEARING M.O. MASONRY OPENING T/F TOP OF FOOTING MAT'L MATERIAL TEMP. TEMPORARY OR MAX. MAXIMUM TEMPERATURE MIN. MINIMUM TYP. TYPICAL AISC. MISCELLANEOUS U.N.O. UNLESS NOTED OTHERWISE N.I.C. NOT IN CONTRACT V. VERTICAL N.S. NEAR SIDE VERT. VERTICAL N.T.S. NOT TO SCALE W.W.R. MELDED WIRE REINFORCING NO. NUMBER W/ WITH O.C. ON CENTER O.D. OVERFLOW DRAIN PLAN NOTES LIDIA LOCKWOOD DESIGN ASSOCIATES, LLC • ARCHITECTS • 10610 N. PARK AVENUE, INDIANAPOLIS, INDIANA 46280 (317) 844 -1315 • (317) 844 -1758 fax DRAWN BY: ��11111111///� D. L. LOGKWOOD ��0�����SG s ER CHECKED BY: - �� For D. I- LOGKWOOID NO. DATE: 26 JANUARY 201.2 OF PROJECT NO.: �� HI''" 11002 1 A NEM'/WOO G SHP GAC EL T Y REH OOWAT TOO N FOR: THE FAMILY CHURCH 1005400 JESSUP BOUILEWARDD, WDOANAPOLOS, [I MANA AM2B0 SHEET NAME: STRUCTURAL NOTES REVISIONS: DESCRIPTION: DATE: SHEET NUMBER: S 0 OF: THREE 0 ® COP"KHT 2011. LOOCNOOD OESIGN ASSOCNTES, LLC (LM LLC). ALL DROMM. REPORTS. PUNS, SPECMTCATIONS, CUFLRER FILES. FIELD DATA NOTES AMID OTHER MAIIENFS AND 06fRlM OM PREPARED BY ILK LLC AS INSIRlAIENTS OF SERNCE RD" THE PROPERTY OF LID, LLC, LD, LLC SHALL RETAIN ALL CdYON I AIM, STATUTORY AND OTHER RESERVED RIGHTS NCLA10Nf THE COPYRIGHT THERETO. ANY USE OR REPRODUCTION Or THE DOCAIM WITHOUT WRITTEN! PEIMSSION RiOM t k LLC IS N VIOLATION OF FEDERM COPYRIGHT LAW S