HomeMy WebLinkAboutNNEW METER 2 AND
WEATHER HEAD
rcli
D
2 -12
x
Is
LIGHTING GENERAL NOTES:
1. ALL WORK SHALL COMPLY WITH ALL NATIONAL. STATE AND LOCAL
CODES AND ORDINANCES PERTAINING TO THE WORK IN THIS
PROJECT.
2. WIRING SYSTEM SHALL BE CONDUIT AND COPPER WIRE.
3. REFER TO THE MECHANICAL PLAN FOR THE D(ACT LOCATION OF
ALL LIGHTING.
2 -14
POWER GENERAL NOTES:
1. ALL WORK SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL
CODES AND ORDINANCES PERTAINING TO THE WORK IN THIS
PROJECT.
2. WONG SYSTEM SHALL BE CONDUIT AND WIRE, MINIMUM WIRE
SIZE SHALL BE NO. 12 AWG /SOLID CONDUCTOR N0. 10 AWG.
AND UP, STRANDED IN LARGE SIZES.
3. E.C. SHALL WIRE COMPLETE ALL EQUIPI►NENT FURNISHED BY
OTHERS CORRDINATE LOCATIONS AND REQUIREMENTS WITH ALL
TRADES AND PLANS.
4. E.C. SHALL PROVIDE ALL POWER AND CONTROL WIRING INCLUDING
HVAC CONTROL WIRING.
5. M.C. SHALL SUPPLY CONTROL DEVICES AND WIRING DIAGRAMS IN
LADDER FORM TO THE E.C. FOR COMPLETE INSTALLATIONS.
6. CONTRACTOR SHALL COORDINATE AND VERIFY ALL ASPECTS OF
THE INCOMING SERVICES WITH THE UMAY COMPANY PRIOR TO
RMING AND INCLUDE ALL UTILITY COST IN THIS BID.
NEW METER 1 AND
WEATHER HEAD
2 -14
ELECTRICAL PANEL 1
MAIN BREAKER
200A 10 120/230V
LOAD DESIGNATION
�,1
Q
CKT.
BKR
CKT.
NO
KW
CONN
CKT.
NO
CKT.
BKR
'Ooh
Fs
LOAD DESIGNATION
PHASE A
PHASE B
HP 41
2
60
1
8.6
8.6
2
60
2
# HP 42
HP ul
-
40
3
-
-
4
40
-
HP 42
SANCTUARY LITES
1
20
5
1.0
.8
6
20
1
SANCTUARY LITES
CELING FANS
1
20
l
.3
1.0
8
20
1
ATTIC FANS
PULPIT LITE
1
20
9
.I
.3
10
20
1
CORRIDOR LITES
OUTLETS
1
20
II
.6
.8
12
20
1
OUTLETS
EXIT LITES
1
20
13
.1
.1
14
20
1
EMERGENCY LITES
BAPTISTRY PUMP
1
20
15
1.0
1.0
Ib
20
1
OUTLETS
SPARE
1
20
11
1.0
1.0
18
20
1
OUTLETS
SPARE
1
20
19
1.0
1.0
20
20
1
SPARE
TOTAL CONNECT LOAD (KW)
13.1
14.4
28.3 KW 144-1 AMPS
3 Ito WIRES IN 11/4" CONDUIT
�r 3 x4 /0 IWRE IN 2" CONDUIT
ELECTRICAL PANEL 2
MAIN BREAKER 120A 10 120/230V >�
LOAD DESIGNATION
O��y
Q
CKT.
BKR
CKT.
NO
KW
COON
CKT.
NO
CKT.
BKR
'00:
Fs
LOAD DESIGNATION
PHASE A
PHASE B
HP 43
2
1 40
1
1.3
1
2
20
1
SPARE
HP 83
-
40
3
-
1
4
20
1
SPARE
FURNACE
1
20
5
1.5
A
L
20
1 1
LOBBY t CLASS RMS
MECH t DRESS RMS
1
20
1
.2
.6
8
20
1
RE5TRM LITES t EX FANS
OUTLETS
I
1 20
9
1.0
.8
10
20
1
HALLS
LOBBY OUTLETS
1
20
11
.6
.2
12
20
1
FRONT DOOR LT
MECH RM OUTLETS
1
20
13
5
.6
14
20
1
EXTERIOR LITES
WATER COOLER
1
20
15
.5
1
16
20
1
SPARE
SPARE
1
20
11
18
20
1
SPARE
SPARE 7-71-23
19
20
20 1
1
SPARE
TOTAL CONNECT LOAD (KW)
N.L
5.4
11.5 KW 18.3AMPS
3 #4 M5 IN 11/4' CONDUIT
* 3 $2 WIRES IN 11/4" CONDUIT
LEGEND
A 2'X4' LENS TROFFER - MAGNETIC BALLAST - 4
LAMPS - 120V
B 2'X4' LENS TROFFER - MAGNETIC BALLAST - 2
LAMPS - 120V
VANDAL RESISTANT LITHONIA VRI -IOOA WHITE 120V
® EXITS - EXIT SIGN LITHONIA LOMSW3ELN - RED
SINGLE FACE WITH BATTERY
SWITCH
$3 3 WAY SWITCH
SURFACE MOUNTED PORCELAN IOOW LAMP
OUTLET
O EMERGENCY LIGHTS - LITHONIA ELM - WHITE
u QUANTON THERMOPLASTIC - 90MIN - 120V - SAW
M FAN UNIT
ELECTRICAL PLAN
1/4" =1' -O"
8' 01 4 2' 0'
LIDIA
LOCKWOOD DESIGN ASSOCIATES, LLC
• ARCHITECTS o
10610 N. PARK AVENUE, INDIANAPOLIS, INDIANA 46280
(317) 844 -1315 • (317) 844 -1758 fax
DRAWN BY: •
M. SHAW �rI'► :`o�ot�oMt��
CHECKED BY: r7` N0. 1249 9
H. MEIER @ T S
DATE: I * #Alt*
10 NOVEMBER 2011 '�, k I.T �G
PROJECT NO.:
11002
FOR:
THE FAMILY CHURCH
10"0 J ESSUP BOULEVARD, ONDRANA OLDS, 0900haNA O
SHEET NAME:
ELECTRICAL PLAN
REVISIONS:
SHEET NUMBER:
DESCRIPTION: DATE:
wool
OF:
�.
®
uo, anta '�0 uc Mt use &. awryvaRrs aAxs canx am
ar n� ooc 40 . AU °tea' u� swwoRr Nn M �rs n� t�v nr n ro �xr ux at "MM U'C aa�ton R" Wk uc IS M
VRON of FOM c WMW UMM