PLAN NOTES
Oi REMOVE AND RELOCATE EXISTING DIFFUSER
�2 REMOVE AND CAP EXISTING RETURN GRILLE AND ASSOCIATED
DUCTWORK TO POINT INDICATED
�3 REMOVE AND RELOCATE EXISTING RETURN GRILLE
O4 REMOVE AND RELOCATE EXISTING FAN COIL UNIT
OREMOVE EXISTING RETURN DUCTWORK AS SHOWN
O6 REMOVE EXISTING SUPPLY DUCTWORK AS SHOWN
(7 REMOVE EXISTING SUPPLY DIFFUSER
( REMOVE AND RELOCATE EXISTING DUCT COIL
"'
I I
II �
IHI O
6
I I
O9 REMOVE AND RELOCATE EXISTING THERMOSTAT
10 REMOVE AND CAP EXISTING HWSSR AS SHOWN
PARTIAL HVAC DEMO PLANS
SCALE: 1/8" =1' -0"
PLAN NOTES
Ot RELOCATED SUPPLY DIFFUSER
0? RELOCATED RETURN GRILLE
03 • RELOCATED FAN COIL UNIT.
O4 RELOCATED DUCT COIL
OINSTALL 30 "X12" FIRE DAMPER IN EXISTING 30 "X12" DUCT
ORELOCATED THERMOSTAT
OCONNECT 1" HWS&R TO EXISTING 1 -1/2" HWS&R
PARTIAL HVAC PLANS
SCALE: 1/8"=l'-O"
PLAN NOTES PLAN NOTES
(D PIPE LOCATED UNDER SLAB U1 1 -1/2" W DROP, 1 -1/2" V RISE, 1/2" H&CW DROP TO RELOCATED
STAINLESS STEEL SINK. REUSE ALL FITTINGS AND TRIM
�2 REMOVE AND RELOCATE EXISTING STAINLESS STEEL SINK
O2 4" S DN, 2" V RISE, 1 -1/2" CW, 1/2" HW DROP
O REMOVE AND CAP EXISTING 1/2" H&CW
O PIPE LOCATED UNDER SLAB
4� REMOVE AND RELOCATE EXISTING MEDICAL GAS ALARM PANELS
O4 RELOCATED MEDICAL GAS ALARM PANELS
O REMOVE EXISTING 2' W AS SHOWN
O5 CONNECT 2' V TO EXISTING 2" V
G) REMOVE EXISTING 4" S AND CLEAN -OUT AS SHOWN
PARTIAL PLUMBING DEMO PLANS PARTIAL PLUMBING PLANS
SCALE 1/8 " =1' -0" SCALE: 1/8 " =1' -0"
W iii
aaw
zoz
) CFM
SPECIFICATIONS
HVAC
1. ALL WORK TO COMPLY WITH ALL APPLICABLE STATE AND LOCAL CODES.
2. ALL DUCTWORK TO BE G60 GALVANIZED STEEL AND CONSTRUCTED PER SMACNA STANDARDS.
ALL OTHER DUCTWORK TO BE CONSTRUCTED TO ti" PRESSURE CLASSIFICATION.
3. HYDRONIC PIPING TO BE TYPE L COPPER TUBING. FLUSH AND TEST PER ASME 831.9.
TEST AT 1.5 TIMES DESING PRESSURE FOR 10 MINUTES WITH NO LEAKS. INSULATION
SHALL BE 1" THICK FIBERGLASS WITH KRAFT REINFORCED FOIL VAPOR BARRIER SERVICE
JACKET. ALL JOINTS AND SEAMS TO BE SEALED. FLAME SPREAD SMOKE DEVELOPED RATING
OF 25/50 IN ACCORDANCE WITH ASTM E84.
4. ALL VALVES, PIPE, AND FITTINGS TO BE CLASS 125.
5. ALL SUPPLY AIR DUCTWORK TO BE INSULATED WITH 1.5" BLANKET GLASS FIBER INSULATION.
WITH KRAFT REINFORCED FOIL FACED VAPOR JACKET. FLAME SPREAD SMOKE DEVELOPED 25/50 IN ACCORDANCE NTH ASTM E84.
6. ALL DUCTWORK TO BE SEALED PER SMACNA STANDARDS.
PUAABNG
1. COMPLY WITH APPLICABLE PORTIONS OF THE UNIFORM PLUMING CODE PERTAINING TO
PLUMBING MATERIALS, CONSTRUCTION, AND INSTALLATION OF PRODUCTS.
2. PROVIDE DOMESTIC WATER PIPING TYPE L COPPER TUBING NTH WROUGHT COPPER FITTINGS
AND 95/5 SOLDER JOINTS. INSTALL DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE COUPLED
TOGETHER. CLEAN, FLUSH AND DISENFECT WATER PIPING IN ACCORDANCE NTH AWWA C601. TEST
DOMESTIC WATER SYSTEM AT A STATIC PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE
(125PSIG MINIMUM) AND MAINTAIN TEST PRESSURE FOR 4 HOURS NTH NO PRESSURE LOSS.
3. PROVIDE WASTE AND VENT PIPING 1 -1/2" OR LARGER OF NO HUB CAST IRON ASTM A74.
FITTINGS SHALL BE CAST IRON NO HUB CISPI 301. AT A HORIZONTAL GRADE ON NOT LESS THAN
1/8" PER FOOT. SLOPE VENT PIPING TO DRAIN CONDENSATION. TEST WASTE AND VENT NTH MINIMUM
10 FOOT OF HEAD FOR 10 HOURS NTH NO WATER LEAKS. CLEAN OUTS SHALL BE INSTALLED WHERE
WHERE SHOWN ON THE DRAWING AND AS REQUIRED BY THE PLUMBING CODE. ACCEPTABLE
MANUFACTURERS: ENFFIELD, ORION, AND R&G SLOANE.
4. PROVIDE SHUTOFF VALVES AS FOLLOWS:
BALL VALVE- THREADED END, 150 PSI, BRONZE BODY, STANDARD PORT, TFE SEATS WITH BRONZE
TRIM, NIBCO T -585. ACCEPTABLE MANUFACTURERS ARE NIBCO AND APOLLO.
5. WC- I
A. FIXTURE: AMERICAN STANDARD AFWALL EL 1.6 2257.103
WHITE VITREOUS CHINA WALL HUNG
SIPHON JET ELONGATED BOWL NTH TOP SPUD
B. TRIM: SLOAN 111 ROYAL FLUSH VALVE NTH VACUUM BREAKER
SCREW DRIVER STOP, AND QUIET EQUIPMENT
C. SEAT: BENEKE 527 SS SAN]- SHIELD FR, MITE SOLID PLASTIC
OPEN FRONT INTEGRAL CHECK SEAT LESS COVER
D. CARRIER: J.R. SMITH COMBINATION CARRIER FITTING SUPPORT
6. LAV -1:
1. FIXTURE: AMERICAN STANDARD LUCERNE 0356.015,
20" X 18" MITE VITREOUS CHINA HIGH BACK
BASIN FOR CONCEALED ARM BRACKET
2. FAUCET: CHICAGO FAUCET 786 -FC RIGID /SWING GOOSENECK
SUPPLY FITTING WITH 1.6 GPM INTEGRAL FLOW CONTROL AND
LAMINAR FLOW STREAM REGULATOR, AND WRIST BLADE HANDLES
3. TRIM: CHICAGO FAUCET 327 OPEN GRID STRAINER, MCGUIRE
8090 ADJUSTABLE CHROME PLATED CAST BRASS P -TRAP NTH
CLEANOUT, MCGUIRE 2127 WASTE NIPPLE WITH ESCUTCHEON,
CHICAGO FAUCET 1017 FLEXIBLE RISER LOOSE KEY STOP WALL
SUPPLIES
4. CARRIER: J.R. SMITH 700 KW SERIES SUITABLE FOR FIXTURE
r- ;'1��
1. SPRINKLER PIPING SYSTEM SHALL BE DESIGNED, FABRICATED, AND INSTALLED BY THE FIRE PROTECTION
CONTRACTOR TO MEET ALL REQUIREMENTS OF THE STATE FIRE MARSHALL AND THE LOCAL FIRE
PROTECTION AUTHORITY UTILIZING THE HYDRAULIC CALCULATION METHOD.
2. DESIGN SYSTEM TO PROVIDE A PENALTY FREE INSURANCE RATING AS DETERMINED BY THE
OWNER'S UNDERWRITER.
3. NFPA 13 SHALL BE A REFERENCED STANDARD.
4. ALL MATERIALS AND MANUFACTURERS SHALL HAVE FM APPROVAL.
5. ALL AREAS SHALL BE NFPA 13 LIGHT HAZARD.
6. SPRINKLER HEADS SHALL BE QUICK RESPONSE CONCEALED TYPE(VIKING B -1).
7. PIPING: ASTM 53 SCHEDULE 10 AND /OR 40 WITH ROLL GROOVED OR WELDED JOINTS;
ASTM 135 UL /FM APPROVED THREADABLE LIGHTWALL BLACK STEEL NTH THREADED JOINTS.
CALIBRATED BALANCING VALVE 2 -WAY MODULATING VALVE
BALL VALVE MANUAL AIR VENT
(TYPICAL) 2) PRESSURE &TEMPERATURE
Tr PLUG ( TYPICAL)
RETURN
UNION (TYPICAL)
i COIL
SUPPLY I
3/4" DRAIN W /HOSE
CONNECTION AND CAP
NOTES:
O1 PROVIDE BUTTERFLY VALVES IN LIEU OF BALL VALVES WHEN PIPE
SIZES ARE ABOVE 2', (TYPICAL).
O2 INSTALL AT LOWEST POINT IN PIPING.
OINSTALL MODULATING VALVE SO THAT STEM IS VERTICAL.
2 -WAY WATER
COIL PIPING DETAIL A
NO SCALE
2 --�
2"
loe 2"
� I I
EXIST (
2' V i -1/2"
+
WC-1 I
RELOCATED SINK
4"
A� V=1
4 FLOOR LINE
"
EXIST
4' S
SANITARY RISER DIAGRAM
NO SCALE
BSA DESIGN 6810 N SHADELAND AVE
INDIANAPOLIS INDIANA 46220.4287
317.849.7878 PH 317.849.2288 FX
O` q�4,,
l No. ' �.
* PE 60920307 .
= yt
s, STATE OFD
�'.N.a.1 At1P
rl ��i S� A ��►p�
i t, Ittt
ST. VINCENT
COMMUNITY
'NOWor
HEALTH NETWORK'
ST. VINCENT CARMEL HOSPITAL
13500 N. Meridian Street
P.O. Box 1903
Carmel, Indiana 46032
ER RENOVATION
PARTIAL HVAC
& PLUMBING
PLANS
SCALE AS NOTED CLIENT NO, 076000
DATE 13 JUNE 95 COMMISSION 076114
COORD DDF
DRAWN DDF
APPROVED BAB Hl