1. All mechanical work shall conform to the latest edition of the BOCA Plumbing and
Uniform Mechanical Codes as ,adopted by the State of Indiana and all local codes as they
may apply.
Obtain all permits and pay all fees required by this work.
3. Do all excavation and backfill as required in accordance with the general conditions.
4. Sanitary sewer shall be piped from all plumbing fixtures, floor drains, cleanouts and other
pieces of equipment requiring waste connections to a point five feet outside the building as
shown on the plans.
5. Vent piping shall be piped froin all plumbing fixtures and other pieces of equipment or
connections requiring vent, collected together, and extended up through the roof in a 4"
minimum vent stack, not less than 12 inches.
6. All sanitary and vent piping in the building shall be PVC Schedule #40 ASTM -D -2665,
with solvent cement joints ASTM -13-2564.
7. Furnish and install all outside underground sanitary sewers, including the pre -cast concrete
grease trap, and extended to a connection with the sanitary sewer to be furnished and
installed by others, including grade cleanouts at all turns and all final connections.
8. All sanitary sewer piping outside the building shall be PVC SDR -35 ASTM -D -3034.
All water domestic piping above grade shall be copper type "L" hard, with lead -free
soldered fittings, all underground water piping shall be type "K" copper, no joints below
grade permitted.
10. Each fixture and piece of equipment shall be connected with stop valves and air chambers
full pipe size at least 18" long.
11. All cold, hot water and hot water return piping above grade shall be insulated with 1/2"
foamed plastic, 25 -50 fire rated.
s supports, c rriers faucets
12. Furnish and install all plumbing fixtures and accessories, a ,
strainers, trim, chronic plated tail pieces and traps, stop valves, cleanouts, hose bibbs, as
scheduled on the plans.
13. Furnish and install all the water heaters, complete with ASME relief valve piped to spill
above the adjacent floor drain, or mop basin adjustable thermostat, glass lined tank,
insulated metal jacket with baked enamel finish, drain valve, cold and hot water valved
connections, gas burner or electric heating elements, suitable for 240 volts, single phase,
electric service, as shown, sized and scheduled on the plans.
14. Furnish and install a 120 volt, all bronze, in -line recirculating pumps in the hot water
return lines, complete with aquastat inserted in the hot water return pipe and isolated with
b all valves, tom maintain a uniform quantity of of w at er in the piping system.
15. Furnish and install a new g is service into the building, and make all necessary
arrangements with the local g, ,s company for this service and meter and pay all costs
involved with this new service.
16. Furnish and install all gas piping in the building as required to extend gars from the new gas
meter to all the furnaces, gas :cater heater and food service cooking equipment requiring
gas connections, with schedule 440 black steel piping with 150# malleable iron fittings,
through unions, dirt legs and stop valves at each piece of equipment.
17. All sheet metal ductwork shall be furnished and installed in accordance with NFPA #96
and the ASHRAE Guide and HVAC Duct Construction Standards as published by
SMACNA. Ducts shall be constructed of galvanized sheet metal, including turning vanes,
air extractors, back draft dampers, flexible canvas connections, manual dampers.
18. All duct joints shall be sealed with mastic material in accordance with HVAC Duct
Construction Standards as published by SMACNA, Duct Sealing Requirements Table 12.
Range hood ductwork shall be 16 gauge carbon steel with all seams and joints liquid tight
continuous external welded from the stub collar on the hood to the wall exhaust fan.
19. Water heater vent piping shall be type "B" double wall vent piping equal to Metalbestos-
QC.
20, insulate all ductwork above the ceiling in the unconditioned attic spaces with 2" minimum
flexible fiberglass duct insulation complete with a vapor barrier jacket, sealed and taped as
recommended by the manufacturer.
21. Furnish and install all grilles, registers, diffusers as sized and scheduled on the plans.
0
Balance air system within 10% of design air flow and submit test report to engineer.
22. Flue inlet and discharge stacks shall be 2" and /or 3" PVC or CPVC Schedule #40 piping,
terminating above the roof Aith the proper termination device as furnished by the
equipment supplier.
23. Outside air intake and discharge louvers, including inside birdscreens, will be furnished
and installed by the general contractor.
24. Furnish and install the ceiling fans as shown on the plans, equal to Leading Edge Model
HI TECH 11 56, with 56" diameter fan blades, 94 watt, 120 volt fan motor, variable speed
fan switch with on -off feature, safety cable, 25,500 maximum CFNI, solid state motor
speed controls, aluminum blades, die cast aluminum housing, finished with a corrosion
resistant white epoxy enamel, electrostatically applied epoxy powder primer.
25. Furnish and install all the exhaust fans as shown and scheduled on the plans, including the
wall mounted range hood exhaust fan, and the two packaged cabinet exhaust fans for the
toilet rooms, equal to Penn Large Capacity Zephyrs, in -line type, with insulated housing,
120 volt direct drive fan motor with variable speed switch, galvanized steel housing,
integral back -draft damper, vibration isolators on the fan motors, centrifugal type fan
blades.
26. Furnish and install all supply fans as shown and scheduled on the plans, including the roof
mounted range hood supply fan, and the four packaged cabinet supply fans to supply
outside air to all the furnaces. The range hood supply fan shall be mounted on a level
insulated curb extended from the sloping roof deck, and be mounted in a galvanized steel
housing with a black baked enamel finish, and include a downblast belt - driven centrifugal
fan, and four (4) 16" x 25" intake filters, motor operated damper, and ce mounted level on
the curb.
27. The range hood itself will be furnished and installed by the kitchen equipment supplier.
28. Furnish and install a complete winter and summer air conditioning system as shown and
scheduled on the plans, with condensing type high efficiency gas fired up -flow furnaces,
direct expansion evaporator type cooling coils, direct or belt drive fan motors, a complete
set of throw -away filters, remote outdoor condensing units with cc*anpressor, high -low
pressure cutouts, starting capacitor and relay, 2 pole contactor, crankcase heater,
ELECTRICAL SPECIFICATIONS
PLUMBING FIXTURE SCHEDULE
temperature switch and tinier, low ambient operating capability down to 0 degrees F., and
Remarks
WC- I
pre - charged refrigerant lines.
1.
29.
Space temperature for each zone shall be controlled with a wall mounted temperature
527 -SS white open front seat with self - sustaining check hinge, flush valve and supply
O
sensor located on the wall of each zone as shown on the plans, through a remote control
2.
Water closet shall be floor mounted, tank type, white vitreous china, water - saver, elongated,
station located on the wall of Conference Room 104. These remote control stations shall
3,
include a 7 -day program for occupied and unoccupied times for each day, emergency
4.
pipe assembly.
override and battery backup, hEA "r- AUTO - COOL -OFF system switch, AUTO -ON fan
Water closet shall be floor mounted, tank type, floor outlet, white vitreous u-hina, siphon jet
1
switch, LED readout of space temperature, occupied heating set point, occupied cooling
5.
with Beneke 323 -5 white open front scat with self - sustaining check hinge or approved equal,
set point, unoccupied heating set point, unoccupied cooling set point and a key pad for
white, bolt caps, and wall supply tike assembly.
L -1
inserting and changing all parameters. [wring occupied cycle, the furnace fan shall run
6.
17 ", oval, American Standard "Aqualyn ", #0476.028 or approved equal, with "Reliant"
constantly, and the burner and condensing unit shall cycle to maintain space temperature.
7.
During the unoccupied cycle, furnace fan shall cycle on and off with the burner to maintain
L -2
Lavatory shall be wall hung, white vitreous china, front overflow, 20" x 18 ", self draining deck,
space temperature, and the condensing units shall be locked out. All remote stations shall
8.
be carefully labeled as to the space controlled with bakelite nameplates with 1/8" high
approved equal, with grid drain, supply pipes & valves, & offset "P" trap. Provide concealed
white letters.
9.
30.
Do all cutting and patching involved in the installation of this work. Special attention shall
L -3
Lavatory shall be counter mounted, white vitreous china, front overflow, self - rimming, 20" x
be taken for roof penetrations. All flashing shall be performed by persons qualified in
10.
roofing. Roofing will be subject to Architect's approval.
11.
31.
Remove all items related to this work that interfere with the new construction and patch
12.
surfaces as required and leave in a safe condition for other trades.
13.
32.
Remove all debris and surplus material from the premises as progress of the work dictates.
14.
33.
Clean all fixtures inside and outside and leave all equipment ready for painting by others.
15.
PLUMBING FIXTURE SCHEDULE
Symbol
Remarks
WC- I
Water closet shall be floor mounted, t.nk type, white vitreous china, water- saver, elongated,
siphon jet action, American Standard Elongated Cadet No. 2812.053 or approved equal, with
1leneke
527 -SS white open front seat with self - sustaining check hinge, flush valve and supply
O
ripe assembly.
WC -2
Water closet shall be floor mounted, tank type, white vitreous china, water - saver, elongated,
O
m
siphon jet action, approved equal to American Standard Elongated Cadet No. 2108.408 -18"
high, with Beneke 527 -SS white seat with self - sustaining check hinge, flush valve and supply
pipe assembly.
WC -3
Water closet shall be floor mounted, tank type, floor outlet, white vitreous u-hina, siphon jet
1
action, round front bowl, American Standard "Baby Devoro" No. 2162.100 or approved equal,
with Beneke 323 -5 white open front scat with self - sustaining check hinge or approved equal,
bm
O
white, bolt caps, and wall supply tike assembly.
L -1
Lavatory shall be counter mounted, white vitreous china, front overflow, self - rimming, 20" x
M
O
17 ", oval, American Standard "Aqualyn ", #0476.028 or approved equal, with "Reliant"
C
#2385.003 single lever trim faucet with high temperature safety stop, with grid drain, supply
end adjustable "P" trap. Mounting height 31" to rim.
L -2
Lavatory shall be wall hung, white vitreous china, front overflow, 20" x 18 ", self draining deck,
Z%
backsplash, American Standard "Lucerne" 0355.012 or approved equal, with centerset single
lever trim American Standard "Reliant" #2385.003 with high temperature safety stop or
approved equal, with grid drain, supply pipes & valves, & offset "P" trap. Provide concealed
arm carrier Josam 17100 floor mountcd. Provide "P" -trap & supply insulation kit, equal to
Truebro handi -lav- uard.
L -3
Lavatory shall be counter mounted, white vitreous china, front overflow, self - rimming, 20" x
r
17 ", oval, American Standard "Aqualyn ", #0476.028 or approved equal, with "Reliant"
#2385.003 single lever trim faucet with Nigh temperature safety stop, with grid drain, supply
and adjustable "P" trap. Mountirib, height 30" to rim.
L -4
Lavatory shall be counter mounted, white vitreous china, front overflow, self - rimming, 20" x
17 ", oval, American Standard "Aqualyn ", #0476.028 or approved equal, with "Reliant"
#2385.003 single lever trim faucet with high temperature safety stop, with grid drain, supply
F nd adjustable "P" trap. Mounting height 24" to rim.
L -5
Lavatory shall be counter mounted• white vitreous china, front overflow, sell- rimming, 20" x
17 ", oval, American Standard "Aqualyn ", #0476.028 or approved equal, with Sloan "Optima"
model #ETF -80 sensor operated faucet with transformer & solenoid. Provide grid drain,
supply valves and adjustable "P" trap.
SK -1
Sink shall be single compartment, self - rimming, 18 gauge, type 304 stainless steel, with
underside coating, approved equal to Elkay 4LR2219, 7 1/2" deep, 3 holes, with Elkay #LK -35
stainless steel strainer, 1 1/2" "P" -trap, and American Standard "Heritage" #72_30.372h faucet
set with wrist blade handles and ooseneck swing spout.
SK -2
Sink shall be single compartment, self- rimming, 18 gauge, type 304 stainless steel, with
underside coating, approved equal to Elkay #lr2219, 7 1/2" deep, 3 holes, 1 1/2" "P" -trap, and
American Standard "Heritage" #7230.34211 faucet set with lever handles and gooseneck swing
spout. Provide garbage disposal on sink, equal to In- Sink - Erator Model 333/SS, continuous
feed, 1/2 hp, 115 volt, single phase, finished with sink mounting.
SK -3
I-land sink shall be wall hung, white vitreous china, front overflow, 20 "x18 ", self - draining deck,
backsplash, American Standard "Lucerne" 0355.012 or approved equal, with centerset trim
American Standard "Heritage" 97400.1721-1 with gooseneck spout and wrist blade handles, or
approved equal with grid drain, supply pipes and valves, and "p" trap. Provide^ concealed arm
carrier Josam 17100 floor mounted
SK -4
Prep sink shall be 14 gauge stainless steel double compartment sink equal to Elkay WNSF-
8236, with 1/4" radii coved corner construction,; integral backsplash, supported on stainless
steel legs, with continuous waste fitting,- 1 1/2" "P" -trap, and LK -66C swing spout faucet.
(Overall dimensions 39 "x27 1/2"
SK -5
Pot and pan sink shall be 14 gauge stainless steel triple compartment sink and drainboard
combination equal to Elkay WNSF- 8354 -1, with 1/4" radii coved corner construction, integral
backsplash, supported on stainless steel legs, with continuous waste fitting; 2" "P" -trap and (2)
two LK -66C swing spout faucets. Overall dimensions 79 1/2" x 27 1/2"
SK -6
Mop basin shall be equal to Fiat MSB -3624 mop sink 36" wide by 24" deep by 10" high,
molded -stone basin, white with black accents, set as shown on the plans. Furnish and stainless
steel strainer, #830 -AA service faucet with vacuum breaker, integral stops, adjustable wall
b•ace, pail hook and hose thread, vinyl bumperguard, 24" long mop hanger, and 30" flexible
5/8" hose and hose bracket. Caulk basin at wall.
EWC
Electric water cooler shall be wall mounted Haws Model HWCA8 or approved equal, with the
capacity to cool 7.5 gallons per hour from 80 °F to 50 °F at an ambient temperature of 90 °F,
chrome plated brass bubbler with front and side push pad activation, stainless steel receptor, 1
1/4" brass outlet tube for attaching trap, hermetically sealed 1/5 hp, 120 volt, motor with fan
cooled condenser.
DF
Drinking fountain shall be wall mounted stainless steel freeze resistant, push button valve
system, chrome plated bubbler, vandal resistant bottom plate, support carrier, waste elbow, and
"P"-trap. Unit to be installed on building exterior where indicated on drawings.
FD
Floor drain (at grade), shall be Josant 30500 -A, cast iron polished brass finish, with integral
deep seal trap, side outlet, round top, adjustable grate, and flush floor cleanout.
FD
Floor drain (above grade), shall be equal to Josant #30000 -A, cast iron, two piece body with
double drainage flange, invertible non - puncturing flashing collar, & adjustable satin nikaloy
si, i ainer. Provide 7" diameter strainer for 2" drains.
SC
Sill cock, shall be non - freeze unit, with vacuum breaker and key control operation, automatic
drain, Josarn 71050, Woodford 65C or approved equal, with cast bronze finish.
I-iB
Shall be wall faucet type with vacuum breaker, wheel handle, brass construction with teflon
packing, Woodford Model 24 or approved equal.
GWH -i
Gas fired water heater equal to A.O. Smith Model FSG -100, 100 gallon capacity, 80,000 BTU
input, 80.8 gal per hour recovery with a 90° rise. Water temperature to be sct at 140 °F for
kitchen rise. Provide P &T relief valve.
EWH-
Electric water heater equal to a.o. smith model eec -40, 40 gallon capacity, 4.5 kW upper and
2,3,4
lower elements, 240 volt, single phase. Provide P &T relief valve and thermostatic mixing
valve equal to Leonard #TM -15 rated at 10 gptn at 20 psi drop.
CiRC
(i required for each water heater system) Hot water recirculating pump, with the capacity to
PUMP
circulate 5 gpm at 10 feet head with a I /12 hp, 120 volt, single phase motor. The pump shall
be all bronze, B & G LR -15B or equal. Furnish & install a line voltage aquastat in the return
water line set at 95 °F to cycle the pilijM on & off to maintain water temperature in the line.
16
17
18.
19.
20.
21.
22
23
24
25
26
27
28
►M'
L
All electrical work shall conform to the latest edition of the National Electrical Codes and
all State and Local Codes.
Obtain all permits and pay all fees required by this work.
Do all excavation and backfill required for the installation of the work.
All conduit under floor slabs or exposed under five feet shall be galvanized rigid steel
conduit.
All ;onduit concealed in walls or above ceiling or exposed above five feet shall be EMT
conduit.
Minimum size conduit shall be 3/4" except low voltage or control conduit may be 1/2 ".
Conductors shall be Type THHN, minimum # 12 gauge, copper, for power and # 18 gauge,
copper, for control and low voltage.
Connectors shall be Scotch -Lac for #8 gauge and smaller, split bolt type for larger
conductors.
Junction boxes shall be galvanized steel with removable cover plate or hinged doors, and
shall be accessible.
Outside wiring shall have weatherproof enclosures.
Final connections to motorized equipment shall be "UA" Sealtite.
Disconnect switches shall be heavy duty, NEMA I enclosure, fused with fusetrons.
Wiring devices shall be ivory plastic.
Wall plates shall be smooth ivory plastic.
Swit,:hes shall be 20 amp, r rated, quiet type, single pole, three way and pilot light as
indicated.
Receptacles shall be 15 or 20 ampere, duplex grounded type.
Furnish and install all light fixtures complete with lamps and ballasts as shown on the plans
and a s scheduled.
All ballasts shall be high efficiency electronic; solid state type.
Fluorescent lamps shall be T8 cool white.
Incandescent lamps shall be inside frosted.
Furnish and install a new 800 ampere, 120/240 volt, single phase, three wire, underground
electrical service from a new pad mounted transformer to a new 800 ampere main
distribution panel, complete with 800a2P main circuit breaker and all the branch circuit
breakers and spaces as indicated.
The main distribution panel shall be service entrance rated, surface mounted, circuit
breaker type as shown and scheduled on the plans.
Furnish and install all the branch circuit breaker
P
c t b cake h n
s a s shown c m a d scheduled on
the plans, surface or flush mounted, with typed directory, bolt -in type design, with 20
ampere minimum breaker size.
Furnish and install a concrete pad for the pad mounted transformer furnished and installed
by PSI as shown on the plans, including incoming primary conduit and the secondary
conduits and cables as shown on the wiring diagram.
Underground service cables shall be type XI-iHW encased in PVC Schedule #40 conduit.
Ground and bond the entire electric box and conduit system according to the N.E.C. to
the water service piping.
Furnish and install typewritten directories under plastic in frames for each and every circuit
in the panelboards and the main distribution panel.
Furnish and install ground fault interrupter type receptacles or circuit breakers for all
circuits with receptacles in outside walls or toilet rooms or adjacent to sinks or other
sources of water.
Furnish and install semi - recessed wall cabinet unit heaters with the capacities as shown on
the plans, equal to Markel Series 3420, 240 volts, single phase, UL approved, with built -in
tamper -proof thermostat, dark branae finish, with the bottom at least 8 inches above the
finished floor.
Furnish and install all power wiring as follows:
a. Condensing Units - furnish and install a weather -proof two pole fused disconnect
switch and wire complete to the lin! voltage terminals of the condensing unit with
the proper number of wires in conduit from a two pole circuit breaker in the panel
indicated.
b. Furnaces - furnish and install a tvo pole non -fused disconnect switch and wire
complete to the line voltage terminals of the furnace with the proper number of
wires in conduit from a single prole circuit breaker in the panel indicated.
C. Water Heaters - furnish and install a two pole fused disconnect switch t,nd wire
complete to the line voltage terminals of the electric water heater from a two pole
circuit breaker in the panel indicate(!.
d. Hot Water Recirculating Pump - furnish and install a motor starting switch with
thermal overload protection and a neon pilot light, and wire complete to the line
voltage terminals of the recirculating pump with the proper number of wire in
conduit from the fused disconnect s Hitch to serve the adjacent water heater.
e. Water Softener - furnish and insta!I a duplex receptacle and wire complete to a
single pole circuit breaker in the panel indicated to serve the timer and control
circuit associated with the water softener.
f Kitchen Equipment - furnish and install special outlets, standard receptacles or
outlet boxes, and wire complete to the line voltage terminals on the unit if it is to
be hard wired to all outlet box, with the proper number and size of wires in seal -
tite conduit, from a single pole or two pole circuit breaker in the panel indicated.
g. Range Hood - furnish and install motor starting switch with thermal overload
protection and neon pilot light for the range hood supply fan and range hood
exhaust fan, and wire complete to the line voltage terminals with the proper
number and size of wires, frog, a single pole circuit breaker in the panel indicated.
Also, wire complete to the line voltage terminals in the range hood with 3 #12 in a
3/4" conduit from a 20a1P circuit breaker in the panel indicated. Also, wire
complete to the fire extinguishing equipment furnished with the range hood as
required.
h. Exhaust Fans (2) - furnish and install a fused disconnect switch at the fan locations
and wire complete with 2 #12 in a 3/4" conduit through a motor starting switch
with thermal overload protection and neon pilot light located in Conference Room
104 from a 20a I P circuit breaker in the panel indicated.
i. Supply Fans (4) - furnish and instal a fused disconnect switch at the fan locations
and wire complete with 2 #12 in a 3/4" conduit through a motor starting switch
with thermal overload protection and neon pilot light located in Conference Room
104 from a 20a1P circuit breaker in the panel indicated.
j. Ceiling Fans - install the variable speed fan motor switch furnished by the
equipment supplier and wire complete to the 120 volt ceiling fans with 2 #12 in a
3/4" conduit from a 20a 1 P circuit breaker in the panel indicated.
k. Disposal - furnish and install a toggle switch in the wall above the backsplash and
wire complete to the 120 volt disposal motor through a water flow switch with 2
# 12 in a 3/4" conduit from a 20a I P circuit breaker in the panel indicated.
i. Aquarium - furnish and install three (3) grounded duplex receptacles as shown or
required, and wire complete with 2 412 in a 3/4" conduit from a 20a l P circuit
breaker in the panel indicated.
M. Lavatory Faucet Sensors - furnish and install three (3) outlet boxes and wire
complete to the line voltage terminals of the water faucet sensors with 2 #12 in a
3/4" conduit from a 20a I P circuit breaker in the panel indicated.
n. Clothes Dryer - furnish and install a dryer receptacle and wire complete with 3 #10
in a 3/4" conduit from a 30a2P circuit breaker in Panel B.
o. Clothes Washer - furnish and install a grounded duplex receptacle and wire
complete with 2 # 12 in a 3/4" conduit from a 20a 1 P circuit breaker in Panel B.
31. Furnish and install a 20 ampere, 2 pole electrically held contactor in a Nema I enclosure,
controlled by a photocell located above the roof and facing north, through a 2 pole test
switch, and wire complete to the five (5) GLA parking lot pole lights with 3 #8 in a 1"
conduit as shown on the plans.
32. Furnish and install a 20 ampere, 2 pole electrically held contactor in Nema I enclosure,
controlled by the same photocell that controls the GLA's, and through a separate 2 pole
test switch, and wire complete to the two (2) GLB play yard lamp posts with 3 #10 in a
3/4" conduit as shown on the plans.
33. Furnish and install a 20 ampere, 2 pole electrically held contactor in a Nema 1 enclosure,
conk olled by the same photocell that controls the GLA's, and through a separate 2 pole
test switch, and wire complete to the two (2) GLC flood lights with 3 #12 in a 3/4"
conduit as shown on the plans.
34. Furnish and install all outdoor parking lot, play yard and building flood lights, complete
with concrete foundation and anchor bolts as shown and scheduled on the plans.
35. Furnish and install weather -proof grounded duplex receptacles on the outside wall of the
building along the sides of the gymnasium and wire complete with 2 # 12 in a 3/4" conduit
through a photocell control devices located above the roof from a 20a l P circuit breaker in
the panel indicated.
36. Furnish and install a complete fire alarm system, including a master fire alarm panel, semi -
recessed in the wall behind the reception counter, and all the manual pull stations, ceiling
smoke detectors, visual and audible fire alarm warning devices, duct smoke detectors and
connection to the range hood fire suppression system, and wire complete with the proper
number of wires in conduit. Fire alarm zones shall include the following:
a. First Floor Manual
b. First Floor Automatic
C. Second Floor Manual
d. Second Floor Automatic
e. Range Hood
f Furnace #1
g. Furnace #2
h. Furnace #3
i. Furnace #4
j. Furnace #5
k. Furnace #6A and 6B
1. Furnace #7
rn, Furnace #8A and 8B
n. Three (3) spaces for future zones.
37. Furnish and install a new underground 2" PVC telephone conduit from the telephone pole
as shown on the Site Plan, to a new 18" x 24" x 4" telephone panel in the Mech. Room
140, complete with pull wire. The telephone panel shall have a 3/4" plywood back board,
front with latched door. Also, furnish and install standard single gang outlet boxes flush
with the wall at each telephone outlet and extend a 1/2" conduit with pull wire up to an
accessible location in the attic, or back to the telephone panel if necessary. Also, extend
two (2) 1 1/4" conduits from the telephone panel up to an accessible location in the attic,
complete with pull wires.
38. Do all cutting and patching required by the installation of this work.
39. Remove all items related to this work that interferes with new construction and patch
surfaces as required and leave it a safe condition for other trades.
40. Remove all debris and surplus material front the premises as progress of the work dictates.
41. Clean all fixtures inside and outside and leave all equipment ready for painting by others.
H O C H
M Y N H I E R
R A J C H E L
A R C H I T E C T S
809 South Calhoun Street
Suite 500
Fort Wayne, Indiana
46802
Phone: 219.422.2661
Fax: 219.422.1698
i
HATSON CIONSULTING tuna
4�4a WEST JEMMON .OVIIVARQ
foRT WAr14E. Ni01M1A 4N04
►NONE& (210) 43: -ss.o
fAxt (219) 432-00"
r 10. :
- i 8801074 ,
STATE CF ; {�
a
F an original design, created by HOGH, RAJCHEL ARCHITECTS. The concepts.
n n it r th I r f
a s o d Beta s a e a so e p operty o YNHIER, RAJCHEL ARCHITECTS. None oncepts, ideas, plans or details shall be
any person, firm or corporation for any
without the prior written perm ssion of
YNHIER, RAJCHEL ARCHITECTS.
0 REVISION NO.: DATE PROJECi
! ! _7___� 1
F 4600
SCALE:
N/A
JANUARY 20, 1995
CAD FILE NAME.
TITLE: SHEET
Specifications
SHEET NO.:
MSPEC -1
O
4)
O
is
O
m
bin
4)
1
C
bm
O
CV
him
M
O
CL
C
CD
Z%
c
r
O
a
r
r
�
V
0 REVISION NO.: DATE PROJECi
! ! _7___� 1
F 4600
SCALE:
N/A
JANUARY 20, 1995
CAD FILE NAME.
TITLE: SHEET
Specifications
SHEET NO.:
MSPEC -1