HomeMy WebLinkAboutEELECTRICAL NOTES GENERAL REQUIREMENTS CONDUITS AND WIRING THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS, ALL CONDUIT SHALL BE Y2" MINIMUM RIGID GALVANIZED STEEL OR ELECTRIC METALLIC TUBING. FEEDER CONNECTION POINTS, AND EQUIPMENT REQUIREMENTS FOR EQUIPMENT PROVIDED BY RIGID CONDUIT OR SCHEDULE 40 PVC SHALL BE USED UNDER SLAB. FLEXIBLE STEEL CONDUIT OTHERS BY VISITING THE JOB SITE AND EXAMINING THE INSTALLATION DOCUMENTS, AND IS TO SHALL BE USED FOR CONNECTIONS TO LIGHTING FIXTURES AND WHERE SHORT CONNECTIONS REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BIDDING. MAKE RIGID CONDUIT IMPRACTICAL. GALVANIZED STEEL CONDUIT SHALL USE THREADED NUMBER FITTINGS. EMT FITTINGS SHALL BE COMPRESSION TYPE ALL CONDUIT SHALL BE CONCEALED ELECTRICAL CONTRACTOR SHALL VERIFY FINAL EQUIPMENT REQUIREMENTS AND LOCATION WHERE POSSIBLE SUPPORT CONDUIT AT NOT MORE THAN 5 CENTERS. PRIOR TO ROUGH -IN. TYPE ANSI INPUT (V) HANGERS AND SUPPORTS LISTED FOR THE PURPOSE SHALL BE USED TO SUPPORT ELECTRICAL ANY MATERIAL OR LABOR WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AS DEVICES. THESE SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE OR MASONRY. HANGERS DESCRIBED IN THESE DRAWINGS SHALL BE PROVIDED AS PART OF THIS CONTRACT. SHALL NOT INTERFERE WITH ACCESS TO EQUIPMENT. ALL ELECTRICAL EQUIPMENT AND 120V MATERIALS SHALL COMPLY WITH THE NEC- ALL EQUIPMENT DEVICES AND ELECTRICAL SUPPLIES SHALL BE LISTED IN A MANNER RECOGNIZED BY THE NATIONAL ELECTRIC CODE WHERE APPLICABLE ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID TIGHT T8/CW FLEXIBLE METAL CONDUIT, NOT LESS THAN 12'N LENGTH, NOR GREATER THAN 36" IN LENGTH. MANUFACTURER AND NEC REQUIRED CLEARANCES SHALL BE MAINTAINED AROUND EQUIPMENT. (DESIGN STANDARD) THESE CLEARANCES SHALL BE CONFIRMED BEFORE INSTALLATION. CONDUCTORS SHALL BE COPPER THWN #12 MINIMUM. CONDUCTORS FOR FEEDERS OF 100 AMPS O OR GREATER MAY BE ALUMINUM. THHN MAY BE USED ABOVE GRADE IN INTERIOR LOCATIONS THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH ALL LOCAL CODES, ONLY. OBTAINING NECESSARY PERMITS, PAYING REQUIRED FEES, AND MAKING ALL ARRANGEMENTS FOR LINE NECESSARY INSPECTIONS, TESTS, ETC ALL WORK SHALL COMPLY WITH OSHA STANDARDS AS WELL MC CABE MAY BE USED WHERE NOT EXPOSED. AS COMPLY WITH LOCAL REGULATIONS. 1,2,5 HVAC CONTROL WIRING FURNISHED AND INSTALLED BY DIVISION 15. COORDINATE INSTALLING OF ELECTRICAL MATERIALS WITH GENERAL CONSTRUCTION WORK. LITHONIA 2PM3N- G- B- 2- 32 -12 -LS -PAF 180, WIRE OUTLETS WITH AT LEAST 6 INCHES OF SLACK. OUTLET BOXES SHALL BE A MINIMUM OF 4"X 2 PROVIDE FIRESTOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE -RATED FLOORS AND 1/8" X 21/8" FOR SINGLE GANG AND 4"X 4"X 21/8" FOR TWO GANG. WALLS TO MAINTAIN FIRE RATING. WILLIAMS HE3G- D24-232- 265 - EB3 -XV ALL CIRCUITS SHALL HAVE AN INSULATED EQUIPMENT GROUND CONDUCTOR, IN ADDITION TO ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING MATERIAL. GROUND CONTINUITY OF THE CONDUIT SYSTEM INSTALL EQUIPMENT IDENTIFICATION LABELS ON EACH UNIT OF EQUIPMENT IN POWER, LIGHTING, RECEPTACLES SHALL BE INDUSTRIAL SPECIFICATION GRADE RATED 20A UNLESS OTHERWISE COMMUNICATION, SIGNAL, AND ALARM SYSTEMS, INCLUDING THE MAIN UNIT OF EACH SYSTEM. INDICATED. USING Yz" HIGH WHITE LETTERS ON BLACK ENGRAVED PLASTIC LAMINATE, PROVIDE A I K- HIGH WSD PDT 2P LABEL FOR ONE LINE OF TEXT OR A 2" HIGH LABEL FOR TWO LINES. JUNCTION AND PULL BOXES SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE, PAINT AFTER FABRICATION SUPPORTED INDEPENDENTLY FROM THE CONDUIT SYSTEM, AND SHALL BE LABELED WITH CIRCUIT PROVIDE CIRCUIT IDENTIFICATION ON EACH POWER OR COMMUNICATION CIRCUIT IN EACH NUMBER AND SYSTEM TYPE ON COVER- VAULT, PULL, AND JUNCTION BOX AND PANEL. PER POLE ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. INSTALL ENGRAVED PLASTIC-LAMINATED INSTRUCTION SIGNS WITH APPROVED LEGEND WHERE LITHONIA 2GT8- 2- 32- AI2125 INSTRUCTIONS ARE NEEDED FOR SYSTEM OR EQUIPMENT OPERATION. EMPTY CONDUITS SHALL BE TERMINATED WITH A SUITABLE CAP. ALL CONDUIT CONNECTIONS TO DUAL OTHER CONDUITS, BOXES AND EQUIPMENT SHALL BE PROVIDED WITH APPROPRIATE FITTINGS. ANY DEVIATION FROM SPECIFIED PRODUCT MANUFACTURER MUST BE APPROVED IN WRITING BY PROVIDE PULL WIRE IN ALL CONDUITS. THE ENGINEER PRIOR TO BIDDING. 1 ALL EQUIPMENT IN OUTDOOR LOCATIONS SHALL BE WEATHERPROOF. PANELBOAKDS AND CIRCUIT BREAKERS ALL WORK SHALL BE DONE IN A NEAT AND PROFESSIONAL MANNER. ANY UNSATISFACTORY EXISTING WORKMANSHIP SHALL BE REMOVED AND REPLACED BY AND AT THE EXPENSE OF THE ELECTRICAL CONTRACTOR FUSES AND DISCONNECTS INSPECT FINISHED WORK. CUT, PATCH, REFINISH, CLEAN AND TOUCH-UP AS NEEDED. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE TESTED DISCONNECTS SHALL BE EXTERNALLY OPERATED, GENERAL -DUTY METAL ENCLOSED, AND SIZED AND DEFECTS CORRECTED. TO PROTECT THE DESIGNATED LOAD. THE CONTRACTOR SHALL GUARANTEE FOR ONE YEAR THAT ALL WORK IS FREE OF DEFECTS AND EACH FUSED DISCONNECT SHALL BE PROVIDED WITH A COMPLETE SET OF UL CLASS RK5 DUAL SHALL CORRECT ANY DEFECTIVE WORK FOUND DURING THAT PERJOD, AS WELL AS ANY DAMAGE ELEMENT FUSES FOR MOTOR LOADS AND UL CLASS RKI FOR RESISTIVE LOADS. RESULTING FROM SAID DEFECT. LINE 1560/3600 PROVIDE SPARE FUSES OF EACH SIZE AND TYPE SUBMITTALS 1,2,3 6" DIAMETER FLUORESCENT CAN LIGHT W/ CLEAR SELF FLANGED MOTORS PROVIDE MANUFACTURER'S LITERATURE ON ALL ELECTRICAL EQUIPMENT. THE FOLLOWING SHALL FLANGE BE INCLUDED WHERE APPLICABLE ALL MOTORS SHALL BE PROVIDED WITH INTEGRAL OVERLOAD PROTECTION. 1. STANDARD SCHEMATIC DRAWINGS, MODIFIED FOR SPECIFIC MODEL AND GROUNDING ACCESSORIES PROVIDED. PROVIDE A COMPLETE GROUNDING CONDUCTOR SYSTEM AS REQUIRED BY THE NEC AND LOCAL 2. CUT SHEETS IDENTIFYING PERTINENT MATERIALS AND PRODUCTS REQUIRED. CODES. 3. EQUIPMENT DIMENSIONS, SHIPPING SPLITS, AND CONSTRUCTION CLEARANCES. ALL CONDUIT SHALL BE GROUNDED WITH A GREEN GROUNDING CONDUCTOR- 4. MAINTENANCE REQUIREMENTS. PROVIDE BONDING JUMPERS WITH PLUMBING SYSTEM, COORDINATING WITH PLUMBING PER POLE CONTRACTOR- 5. PERFORMANCE SPECIFICATIONS. E ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM 6. WIRING AND CONTROL DIAGRAMS. STANDARD 20' ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL BE BONDED TO THE CONDUIT 7. SAFETY INSTRUCTIONS. SYSTEM. OUTLET BOXES SHALL BE BONDED WITH A BONDING JUMPER. 8. THE FULL MANUFACTURERS MODEL NUMBER SHALL BE CLEARLY SHOWN ON THE ALL ENCLOSURES AND NONCURRENT- CARRYING METAL PARTS ARE TO BE GROUNDED. TOP OF THE FIRST AND THE BOTTOM OF THE LAST PAGE CONDUITS ARE TO BE ELECTRICALLY CONTINUOUS. LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES. 9. IDENTIFICATION OF COLOR OR FINISHES. GROUND WIRES SHALL BE PROTECTED FROM MECHANICAL INJURY. 10. THE CONTRACTOR'S STAMP, SIGNATURE, AND CONTACT DATA SHALL BE AFFIXED TO EACH SUBMITTAL LIGHTING 11. WARRANTY INFORMATION AND SERIAL NUMBER LIGHTING SHALL BE EXACT MODEL NUMBERS AS SHOWN ON THE SCHEDULE UNLESS A COMPLETE ALTERNATE PACKAGE IS SUBMITTED AND APPROVED BEFORE BIDDING. AN OPERATIONS MANUAL CONTAINING EQUIPMENT DRAWINGS AND RELATED INFORMATION, INCLUDING THE DATA LISTED ABOVE, SHALL BE SUBMITTED TO THE OWNER AFTER PROJECT BALLASTS SHALL BE ENERGY EFFICIENT ELECTRONIC TYPE, AND SHALL BE HIGH POWER FACTOR/ COMPLETION. RECORD DRAWINGS, OR `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f277V) (DESIGN STANDARD) O WALL DUAL STANDARD 20' LINE 800/1200 1 WSD PDT 1,2,5 B LITHONIA 2PM3N- G- B- 2- 32 -12 -LS -PAF 180, 2/F32/ 120V 63 2'X4' PARABOLIC TROFFER W/ 3" DEEP 12 CELL SEMI- SPECULAR WILLIAMS HE3G- D24-232- 265 - EB3 -XV GRID WALL DUAL STANDARD AY LINE 800/1200 2 WSD PDT 2P 112,3 PAINT AFTER FABRICATION 180` PER POLE C LITHONIA 2GT8- 2- 32- AI2125 OE WALL DUAL EXTENDED 26' LINE 1560/3600 1 LWS PDT 1,2,3 THICK AI2 LENS 180` PROGRAMMED 2 WALL DUAL EXTENDED 26' LINE 1560/3600 2 LWS PDT 2P 1,2,3 6" DIAMETER FLUORESCENT CAN LIGHT W/ CLEAR SELF FLANGED OE SPECTRUM SP7HFT32- E- X/7510CL FLANGE CFM ELECTRONIC REFLECTOR PROGRAMMED 180, PER POLE START BALLAST E WALL DUAL STANDARD 20' LOW N/A N/A WSD PDT LV 1,2,5 T8/CW ELECTRONIC & BATTERY EMERGENCY PACK PROGRAMMED 180` START BALLAST X LITHONIA LQM- S-W-1-R-120277 -ELNSD O CEILING DUAL STANDARD 12' LINE 800/1200 1 CMR PDT 9 1,2,3,4 LIGHT W/ WHITE FRAME & FACE 360° RED LETTERS & NICKEL CADMIUM OB CEILING DUAL STANDARD 12' LINE 800/1200 2 CMRPDT92P 1,2,3,4 120V 1.5 POLYCARBONATE DOUBLE FACE EXIT 360` CHLORIDE SLN- 2- R-W -AD LIGHT W/ WHITE FRAME & FACE OC CEILING DUAL EXTENDED 28' LINE 800/1200 1 CMR PDT 10 1,2,3,4 360° X2 LITHONIA LHQM- S-W +R- 1201277-N -TD UNIVERSAL LED 120V 1.5 O CEILING DUAL EXTENDED 20 LINE 800/1200 2 CMR PDT 102P 1,2,3,4 HALOGEN 360° RED LETTERS, NICKEL CADMIUM O 0 CEILING DUAL STANDARD 12' LOW N/A N/A CM PDT 9 1,2,3,4,7,8 E PAR36 360' BATTERY AND 15 MIN. TIME DELAY MODULE NOTES: OF CEILING DUAL EXTENDED 28' LOW N/A N/A CM PDT 10 1,2,3,4,7,8 1350 LUMENS FOR 90 MINUTES, 2 LAMPS ILLUMINATED. 3. FLUORESCENT LAMPS SHALL BE 4100° 360' O CEILING PIR STANDARD 12' LINE N/A N/A CMR9 2,3,4,5 360` O CEILING PIR EXTENDED 28' LINE N/A N/A CMR 10 2,3,4,5 360° O CEILING PIR STANDARD 12' LOW N/A N/A Cm 2,3,4,5,7,8 360' O CEILING PIR EXTENDED 28' LOW N/A N/A CM 10 2,3,4,5,7,8 360` WALL PIR STANDARD 130' LINE 800/1200 1 HWR 13 2,3 K +T I/L WALL PIR STANDARD 130' LOW N/A N/A HW 13 2,3,7,8 vv +7' © CONCEALED N/A N/A N/A LOW 20AMP 1 PP 20 7 J.B. 2P CONCEALED N/A N/A N/A LOW 20AMP 2 PP 20 2P 7 J.B. ® CONCEALED N/A N/A N/A LOW 20AMP 1 SP 20 9 J.B. NOTES: 1. DUALPASSIVE INFRARED AND OVERLAPPING AUDIO TECHNOLOGY. 2. MINIMUM LAMP ON TIMER SET TO 15 MIN.. 3. 30 SECOND TO 20 MINUTE (ADJUSTABLE) OCCUPANCY TIMER ON SETTING. SET RESTROOMS, CORRIDORS AND OPEN OFFICE AREAS TO 20 MINUTES, SET ALL OTHER AREAS TO 5 MINUTES UNLESS DIRECTED OTHERWISE. 4. LOCATE SENSOR AWAY FROM HVAC DIFFUSERS TO MAXIMIZE AUDIO SENSITIVITY. S. CONNECT SENSOR TO ASSOCIATED POWER PACK WITH 34118 STRANDED PLENUM JACKETED CABLE. 6. PROVIDE LOW TEMP /HIGH HUMIDITY COATING WHERE DEVICE IS LOCATED IN UNHEATED ORHIGH HUMIDITY LOCATIONS. 7. POWER PACK SHALL PROVIDE 15VDC TO LOW VOLTAGE SENSOR AND PROVIDE RELAY SWITCHING. 8. SENSOR SHALL BE WIRED CONTINOUSLY HOT BEFORE ROOM SWITCH IF PROVIDED. 9. SLAVE RELAY. i1 E 1�1 ( X1 p HA I OA LA11 �o LA J1 D 1-00 I J� 0 I \6D I � I D I "\ DUCT Q DETE \EXIST. 4 TON ]UNIT Partial Second Electrical Plan 11/4' - T-V 30A U1P DISCONNECT J 2-010 CU -1 1 -010 GND W044 w CU -1 a First Floor 1/4' - T -V I �✓ Ir�lr� 0Y —00 0 II FIXTURE SCHEDULE NORTH TYPE MANUFACTURER'S CAT. # MOUNT LAMPS BALLAST ANSI INPUT (V) REMARKS A LITHONIA 2PM3N- G- B- 3- 32 -18 -LS -PAF RECESS 3/F32/ 120V 91 2'X4' PARABOLIC TROFFER W/ 3" DEEP 18 CELL SEMI - SPECULAR WILLIAMS HE3G -D24- 332 - 365 - EB3 -XV GRID T8/CW ELECTRONIC LOW- IRIDESCENT LOUVER. , PROGRAMMED PAINT AFTER FABRICATION START BALLAST B LITHONIA 2PM3N- G- B- 2- 32 -12 -LS -PAF RECESS 2/F32/ 120V 63 2'X4' PARABOLIC TROFFER W/ 3" DEEP 12 CELL SEMI- SPECULAR WILLIAMS HE3G- D24-232- 265 - EB3 -XV GRID T8/CW ELECTRONIC LOW - IRIDESCENT LOUVER. PROGRAMMED PAINT AFTER FABRICATION START BALLAST C LITHONIA 2GT8- 2- 32- AI2125 RECESS 2/F32/ 120V 63 2'X4' FLUORESCENT TROFFER W.125" WILLIAMS LPT 24 232 SA EB8P2 UNV GRID T8/CW ELECTRONIC THICK AI2 LENS PROGRAMMED START BALLAST D GOTHAM AFV- 32TRT -6 -AR RECESS VCF32/ 120V 36 6" DIAMETER FLUORESCENT CAN LIGHT W/ CLEAR SELF FLANGED SPECTRUM SP7HFT32- E- X/7510CL FLANGE CFM ELECTRONIC REFLECTOR PROGRAMMED START BALLAST E ITHONIA WP- 2- 32- MVOLT -EL14 WALL 2/F32/ 120V 63 FLUORESCENT FIXTURE WITH UP/DOWN LIGHT DISTRIB. WILLIAMS 29 4- 232- A- EM71132-X T8/CW ELECTRONIC & BATTERY EMERGENCY PACK PROGRAMMED START BALLAST X LITHONIA LQM- S-W-1-R-120277 -ELNSD UNIVERSAL LED 120V 1.5 POLYCARBONATE SINGLE FACE EXIT EXITRONIX GVEX U BP WB WH R2 LIGHT W/ WHITE FRAME & FACE RED LETTERS & NICKEL CADMIUM BATTERY AND SELF-DIAGNOSTICS X1 LITHONIA LQM- S- W- 3- R- 120277-ELNSD UNIVERSAL LED 120V 1.5 POLYCARBONATE DOUBLE FACE EXIT CHLORIDE SLN- 2- R-W -AD LIGHT W/ WHITE FRAME & FACE RED LETTERS & NICKEL CADMIUM BATTERY AND SELF - DIAGNOSTICS X2 LITHONIA LHQM- S-W +R- 1201277-N -TD UNIVERSAL LED 120V 1.5 POLYCARBONATE COMBINATION SINGLE FACE EXIT /EMERGENCY CHLORIDE ERCI- TIMEDELAY 2/6W LIGHT W/ WHITE FRAME & FACE & 2 EMERGENCY HEADS HALOGEN RED LETTERS, NICKEL CADMIUM BATTERY & 15 MIN TIME DELAY Z CHLORIDE S- 50N- H7- W -ADTD SURFACE 2/8W/ 120V BATTERY EMERGENCY LIGHT WITH NICKOL CADMIUM LITHONIA ELM654 -N -TD PAR36 BATTERY AND 15 MIN. TIME DELAY MODULE NOTES: 1. "-2" AFTER FIXTURE LETTER INDICATES DUAL BALLAST FOR SWITCHING. SEE FLOOR PLANS FOR LOCATIONS. 2. EMERGENCY BATTERY INVERTER UNIT FOR FLOORESCENT FIXTURES SHALL PRODUCE 1350 LUMENS FOR 90 MINUTES, 2 LAMPS ILLUMINATED. 3. FLUORESCENT LAMPS SHALL BE 4100° K JOHN MOSELE ARCHITECT ARCHITECTURE PLANNING INTERIOR ARCHITECTURE 317.574 -9408 \�0 SV E R I Ck .' REGISTERED p Ir` 33389 - STATE OF INDIANA ? );44 r� TENANT IMPROVEMENTS FOR ROBERGE & ROBERGE SUITE 201 REGENTS BUILDING 12775 HORSEFERRY CARMEL, IN 46032 reV151on: date: de5crlptlon: Electrical Plan Details, Notes Schedules date: July 15, 201 2 project: 1207 scale: A5 noted coord.: JM drawn: JM A1.4 checked: JM