I I
,' EG1 I REMOVE AS
INDICATED
I
MECHANICAL FLOOR PLAN
16 "X10"
ROUTE TIGHT TO
BOTTOM OF BEAM
AT 9' -4" AFF, THEN
RISE TO STUCTURE
ROUTE TIGHT TO
BOTTOM OF BEAM
AT 9' -4" AFF, THEN
—T RISE TO STUCTURE
n.
DROPS
GENERAL NOTES
A. A MAXIMUM OF FIVE FEET OF FLEXIBLE DUCTWORK MAY
BE USED AT ALL SUPPLY DIFFUSERS. BRANCH DUCTWORK
TO DIFFUSER SHALL BE SAME SIZE AS DIFFUSER INLET.
REFER TO DIFFUSERS IN EQUIPMENT LIST FOR INLET SIZES.
BALANCE DAMPERS SHALL BE LOCATED AT BRANCH
CONNECTION TO MAIN. AVOID SHARP BENDS IN FLEXIBLE
DUCTWORK WHICH MAY CAUSE EXCESSIVE NOISE. DUCT
SIZING BASED UPON 0.10" S.R. DROP PER 100' DUCT.
B. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST
QUALITY STANDARDS OF THE TRADE, AND SHALL CONFORM
WITH ALL FEDERAL, STATE, AND LOCAL CODES AND
STANDARDS. THE SAME ARE MADE A PART OF THESE
CONTRACT DOCUMENTS, THE SAME AS IF REPEATED
HEREIN.
C. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
EXACT LOCATION OF CEILING MOUNTED MATERIALS
INCLUDING ALL DIFFUSERS, GRILLES, AND REGISTERS.
D. CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS
REQUIRED TO COMPLETELY AND PROPERLY INSTALL ALL
WORK REQUIRED FOR THE PROJECT.
E. CONTRACTOR SHALL THOROUGHLY EXAMINE THE WORK OF
OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
F. CLEARANCE BETWEEN CEILING AND STRUCTURE ABOVE THE NODE
ROOM IS AT 0' -9 ". CLEARANCE ELSEWHERE IS A MAXIMUM
OF 1' -10 ". KEEP ALL DUCTWORK TIGHT TO BOTTOM OF
STRUCTURE. COORDINATE ROUTING WITH LIGHTING, ETC.
BEFORE INSTALLATION.
G. WALLS AROUND PERIMETER OF BATTERY AND NODE ROOMS SHALL BE
TO DECK. ALL PENETRATIONS THROUGH WALL SHALL BE SEALED
AIRTIGHT.
HVAC PLAN NOTES Z
Oi FM200 EVACUATION FAN FOR FIRE /SMOKE ZONE. REFER TO SHEET FP201.
UNIT SHALL BE SUSPENDED FROM STRUCTURE ABOVE WITH VIBRATION ISOLATORS
AND FLEXIBLE CONNECTIONS AT DUCTWORK. REFER TO ELECTRICAL DRAWINGS FOR
POWER CONNECTION, LOCATION OF MANUAL PULL STARTER, AND INTERLOCK WITH
TRANSFER DUCT MOTORIZED DAMPER.
2O REMOVE EXISTING 60 "X18" GLAZING AT BOTTOM OF EXTERIOR WALL. PROVIDE
60"X18" EXTERIOR WEATHERPROOF LOUVER, ANODIZED TO MATCH EXISTING
BUILDING EXTERIOR FINISH. PROVIDE BACKDRAFT DAMPER AND PLENUM BEHIND
LOUVER FOR CONNECTION OF 24 "X12" EXHAUST DUCTS FROM ABOVE.
3O EXTERIOR CONDENSING UNIT FOR LIEBERT ENVIROMENTAL UNIT. PROVIDE 4"
THICK CONCRETE PAD BENEATH UNIT.
a0 10 TON LIEBERT UNIT: PROVIDE SHEET METAL DISCHARGE PLENUM ON TOP UNIT,
EXTENDED THROUGH CEILING FOR CONNECTION BY SUPPLY DUCTWORK AT EACH
END. PROVIDE OPENING THROUGH WALL FOR TRANSFER OF RETURN AIR AS
SPECIFIED IN PLAN NOTE #10. ROUTE REFRIGERANT AND 1" CONDENSATE PIPING
UP THROUGH CEILING, THROUGH STRUCTURE, DOWN AND OUT EXTERIOR WALL.
CONDENSATE PIPING SHALL SLOPE MINIMUM OF 1/4" PER FOOT TOWARDS EXTERIOR.
UNIT MANUFACTURER SHALL SIZE REFRIGERANT PIPING. PROVIDE SECONDARY DRAIN
PAN WITH 2" SIDES UNDERNEATH ENTIRE UNIT. REFER TO SHEET M501 FOR
SPECIFICATIONS AND ELECTRICAL DRAWINGS FOR POWER CONNECTION.
5O TAP TOP OF DUCTWORK WITH SPIN —IN FITTING AND DAMPER. ROUTE FLEXIBLE
DUCTWORK THROUGH STRUCTURE AND DOWN TO DIFFUSER.
6� PROVIDE TRANSFER DUCT, GRILLE, AND MOTORIZED DAMPER THROUGH CORRIDOR
WALL. DAMPER SHALL BE INTERLOCKED WITH FM200 EXHAUST FAN TO OPEN
DURING FAN OPERATION. REFER TO ELECTRICAL DRAWINGS FOR WIRING.
O RELOCATE EXISTING VAV BOX WITH ELECTRIC REHEAT TO POSITION INDICATED.
EXTEND EXISTING ELECTRICAL SERVICE FROM EXISTING LOCATION. PROVIDE
JUNCTION BOX, SPLICES, CONDUIT, AND WIRE AS REQUIRED.
8O REMOVE EXISTING VAV BOX, DUCTWORK, ETC. AS INDICATED. REMOVE TEMPERATURE
CONTROLS BACK TO SOURCE.
9Q ROUTE 6 7X6" EXHAUST DUCT DOWN IN CORNER OF ROOM TO BELOW RAISED FLOOR
FOR EVACUATION OF FM200. BALANCE TO 125 CFM. PROVIDE ONE (1) PERFORATED
FLOOR PANEL AT OPPOSITE END OF ROOM FOR TRANSFER OF AIR THROUGH AREA
BELOW THE RAISED FLOOR.
10 PROVIDE TRANSFER DUCT, GRILLE, AND MOTORIZED DAMPER THROUGH BATTERY
WALL. DAMPER SHALL BE INTERLOCKED WITH LIEBERT UNIT L -1 TO OPEN
DURING UNIT OPERATION FOR RETURN AIR. REFER TO ELECTRICAL DRAWINGS
FOR WIRING. (.�4
EQUIPMENT LIST
L -1 LIEBERT ENVIROMENTAL UNIT M# UH 125, 208/60/3
CU -1 CONDENSING UNIT FOR L -1 M# DCDF LP, 208/60/3
EF -1 GREENHECK M# SQ -140 IN —LINE CABINET EXHAUST FAN,
1800 CFM ® 0.5" SP, 1/2 HP, PROVIDE WITH DISCONNECT.
EF -2 GREENHECK M# SO-140 IN —LINE CABINET EXHAUST FAN,
1650 CFM ® 0.5" SP, 1/2 HP, PROVIDE WITH DISCONNECT.
EG1 24 "X24" TITUS MODEL 50F, 1/2" ALUMINUM EGGCRATE RETURN
GRILLE, FRAME FOR LAY —IN CEILING
EG2 12 "X12" TITUS MODEL 50F, 1/2" ALUMINUM EGGCRATE RETURN
GRILLE, PERIMETER FRAME FOR WALL MOUNTING.
LD1 48" TITUS MODEL TBD -10 HIGH CAPACITY PLENUM SLOT DIFFUSERS,
WITH (2) 1" SLOTS AND 8" OVAL INLET. "
PD1 24"X24" TITUS MODEL TMSA, ALUMINUM 10 NECK SQUARE SUPPLY
DIFFUSER.
PD2 24 "X24" TITUS MODEL TMSA, ALUMINUM 8" NECK SQUARE SUPPLY
DIFFUSER.
=Archit
Engineers&
9100 Keystone Crosse
Suite 200
Indionopolis, Indiono
317.848.7800
FAX 317.574.0957
��nd
I�Irlm
I►rd,ll.a
Interior
00"rip Im
D a W, Osseo
"'" 0"m
4/3/95 F0
Z
JQCL
a:
8�
J
LL
.J
Q
z W
a Z
w
oil,
icy �..�. •. �;
go
ceriw ay
- N
x:860
0 .Q I. STAT
::y01
lom
/fill
carom ®y
BNset No.
Of minim
Fie N0.
FM-