HomeMy WebLinkAbout0353.95.5L SCOPE: This specification outlines the requirements for on FM -200 total flooding fire suppression system with automatic detection and control. The work described in this specification includes oil engineering, labor, materials, equipment and services necessary, and required, to complete and test the suppression system. II. APPLICABLE STANDARDS AND PUBLICATIONS: The design, equipment, installation, testing and maintenance of the FM -200 suppression system sholl be in accordance with the applicable requirements set forth in the latest edition of the following codes and standards: 1 NFPA No. 2001 - Clean Agent Fire Extinguishing Systems 2 NFPA No. 12A - Holon 1301 Fire Extinguishing Systems 3 NFPA No. 70 - National Electrical Code 4 NFPA No. 72 - Standard For Protective Signaling 5 NFPA No. 75 - Electronic Computer Systems 6 Factory Mutual Approval Guide 7 U.L Listings 8 Requirements of the Authority Having Jurisdiction (AHJ) The standards listed, as well as all other applicable codes and standards, shall be used as "minimum" design stondards. Also to be considered ore the requirements of the "Authority Having Jurisdiction" and good engineering practices. III. REQUIREMENTS: The FM -200 Suppression System installation shall be made in accordance with the drawings, specifications and applicable standards. Should a conflict occur betweenthe drawings and specifications, the specifications shall prevail. IV. EXCLUSIONS: The work listed below sholl be provided by others or under other sections of this specification: 1 120 VAC power supply to the FM -200 control panel 2� Interlock wiring and conduit for shutdown of HVAC, dampers and /or electric power supplies, relays or shunt trip breakers 3) Connection to local or remote fire olorm systems or listed central alarm stations) V. QUALITY ASSURANCE: A) MANUFACTURER: 1) The manufacturer of the FM -200 suppression system hardware and detection components shall have a minimum of 10 years experience in the design and manufacture of similar types of suppression systems and who can refer to similar installotions providing satisfactory service. 2) All devices, components and equipment shall be the products of the some manufacturer. 3 All devices and equipment shall be U.L listed and /or FM approved. B. INSTALLER: 1) The installing contractor sholl be trained by the manufacturer to design, install, test and maintain FM -200 fire suppression systems. 2) The installing contractor must have a minimum of five (5) years experience in the design, installation and testing of FM -200, or similar, fire suppression systems. A list of systems of a similar nature and scope shall be provided on request. C SUBMITTALS: 1) The installing contractor sholl submit the following design information and drawings for approval prior to starting work on this project: a) Field installation layout drawings having a scale of not less than 118" =1' -0" detailing the location of oil agent storage tanks, pipe runs including pipe sizes and lengths, control panel(s), detectors, manual pull stations, abort stations, audible and visual alarms, etc. b) Graphic Annunciator wiring schematics and dimensioned display panel illustration shall be provided. c) Complete hydraulic flow calculations, from a U.L. listed computer program, sholl be provided for oil engineered FM -200 systems. Calculation sheet(s) must include the manufacturers name and U.L. listing for verification. The individual sections of pipe and each fitting to be used, as shown on the isometrics, must be identified and included in the calculation. Total agent discharge time must be shown and detailed by zone. VI. SYSTEM DESCRIPTION AND OPERATION: A) The system shall be a total flooding FM -200 extinguishing system manufactured by: FIKE 'FM200' FIRE SUPPRESSION SYSTEM LIEBERT ENVIROMENTAL CONTROL UNIT L -1 ENVIRONMENTAL CONTROL SYSTEM (L -1) SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY These specifications describe requirements for a computer room environmental control system. The system shall be designed to maintain temperature and humidity conditions in the rooms containing electronic equipment. The manufacturer sholl design and furnish all equipment to be fully compatible with heat dissipation requirements of the room. 1.2 DESIGN REQUIREMENTS The computer room environmental control system shall be o self - contained factory assembled unit with down -flow air delivery and rear return. The system shall have a total cooling capacity of 120,100 BTU /HR, with a sensible cooling capacity of 109,500 BTU /HR based on on entering air temperature of 72 degrees Fahrenheit dry bulb and 60 degrees Fahrenheit wet bulb. The unit is to be supplied with 208 volt 3 ph 60 Hz electrical service. 1.3 SUBMITTALS Submittals sholl be provided with the proposal and shall include: Single -Line Diagrams; Dimensional, Electrical, and Capacity data; Piping and Electrical Connection Drawings. 2.0 PRODUCTS 2.1 Cabinet and Frame Construction The frame shall be constructed of heliorc welded tubular steel. The exterior panels shell be insulated with a minimum 1 in., 1.5 lbs. density fiber insulation. The main front panel shall hove captive 1/4 turn fasteners. The main unit color shall be as selected by the architect. 2.2 Filter Chamber The filter chambers sholl be on integral port of the system, located within the rear return plenum serviceable from either end of the unit. The filters sholl be rated not less than 20% efficiency (based on ASHRAE 52 -76). 2.3 Fan Section The fon shall be the centrifugal type, double width double inlet, and shall be statically and dynamically balanced as o completed assembly to a maximum vibration level of two mils in any plane. The shaft shall be heavy duty steel with self - aligning boll bearings with a minimum life span of 100,000 hours. The fon motor shell be 2 hp at 1750 RPM and mounted on on adjustable slide base. The drive package sholl be two -belt, variable speed, sized for 200% of the fan motor horsepower. The fops sholl be located to draw air over the A -frame coil to ensure even air distribution and maximum coil performance. Blow through coil designs will not be accepted. 2.5 Control Processor The control system sholl be microprocessor based. The system shall be provided with two .43 inch high, seven segment LED numerical displays to allow observation of room temperature and humidity and each settoble function: Temperature Setpoint 65 -85 degrees Fahrenheit Temperature Sensitivity 1 to 5 degrees Fahrenheit Humidity Setpoint 40 -60% R.H. Humidit Sensitivity 1% to 10% R.H. Humidifier Flush Rote. Normal Operating Modes (Heating, Cooling, Dehumidification) shall be indicated by colored LEDs on the unit - mounted display panel. The control system shall monitor unit operation and activate on audible and visual olorm in the event the following factory preset olorm conditions: High Temperature Low Temperature High Humidity Low Humidity Restricted Air Filters Loss of Air. A common alarm light shall be activated when any of the above conditions exist. The common alarm shell also indicate high head pressure, or water under floor. A compressor sequence feature shall be provided to change the lead /log sequence of the compressors. 2.6 Compressorized Systems 2.6.1 Dual Refrigeration Systems Each refrigeration circuit shall include hot gas mufflers, liquid line filter dryers, refrigerant sight glass with moisture indicator adjustable, externally equalized expansion valves, and liquid line solenoid valves. 2.6.2 Semi- Hermetic Compressors The compressors shall be located in a separate comportment so they may be serviced during operation of the equipment. The compressor shall be semi - hermetic with a suction gas cooled motor, vibration isolators, thermal overloads, oil sight gloss, manual reset high pressure switch, pump down low pressure switch, suction line strainer, reversible oil pumps for forced feed lubrication, a maximum operating speed of 1750 RPM, and a minimum EER of 11.4. Fully hermetic type compressors will not be accepted. 2.6.3 A - Frame D.X. Coil The evaporator coil shall be on A -Frame design and have 14.2 sq. ft. face area, 4 rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of 384 ft. per minute at 5650 CFM. Refrigerant of each system shall be distributed throughout the entire coil face area. A stainless steel condensate drain pan sholl be provided. 2.6.4 Air Cooled Systems 2.6.4.1 Fan Speed Control Condenser The Liebert manufactured air cooled condenser shall be the low profile, slow speed, multiple direct drive, propeller fon type. The condenser shall balance the heat rejection of the compressor at 95 degrees Fahrenheit ambient. The condenser sholl be constructed of aluminum and contain a copper tube, aluminum fin coil arranged for horizontal air discharge. The winter control system for the air cooled condenser shall be Liebert Fan Speed Control. The variable speed motor sholl operate from 0 to 230 volts single phase, 10 to 1050 rpm. It shall be designed with boll bearings, permanent lubrication, internal overload protection, 40 degrees Celsius rise at full speed, 65 degrees Celsius rise at 10 RPM. The control system sholl be complete with transducers, thermostats and electrical control circuit, factory pre- pockaged in the integral condenser control box. The transducer shalt automatically sense the highest head pressure of either operating compressor and control the variable speed fon on the air cooled condenser to properly maintain the head pressure. The fon speed control system shall provide positive start -up and operation in ambient temperature as low as -20 degrees Fahrenheit. The air cooled condenser shall have a 208 volt, 3 ph 60 Hz power supply. 2.6.4.2 Air Cooled Condenser Disconnect Switch Provide a disconnect switch factory mounted and wired to the condenser control panel, accessible from the exterior. 2.7 The computer room environmental control system shall be equipped with the following components. Disconnect Switch Non - Locking Type The non - automatic molded case circuit breaker shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible with the door closed. Condensate Pump The condensate pump shall have the capacity of 145 GPH at 20 ft. head. It shall be complete with integral float switch, pump and motor assembly, and reservoir. Floor Stand Provide optional floor stand under unit. 3.0 EXECUTION 3.1 Installation of Computer -Room Air Conditioning Units 3.1.1 General Install computer room air conditioning units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. 3.1.2 Electrical Wiring Install and connect electrical devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor. 3.1.3 Piping Connections Install and connect devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 3.2 Field Quality Control The system shall be check test and Started by the local manufactures representive in accordance with manufacturer's start up instructions. Test controls and demonstrate compliance with requirements. Warranty The system shall include a complete one year parts and labor warranty from dote of start up. The labor warranty shall be provided by the local manufactures representive. The dual semi hermetic compressors shall include a rive year ports warranty. CWArc h i to En ineers &I -9 — 9100 Keystone Crossini Suite 200 Indianapolis, Indiana 46 317.848.7800 FAX 317.574.0957 Archie t" Land Archilacbs do km F�I�tOrIC De0IIgn Spam Pkireft 60pyrf A Im rwr. trarAiwe i w w sr eMa 4/3/96 1 RDM 0) O U 4 LL Y� w C CL �2 J 3 U y�jF z a Z 2: V A o 2 `r �7►�ri+rr `X%1111111 No. =V8605 O S STATE 0 •AN i'0NAL. '/Mm' w 9" N0. a - shoots Re N0. for the Automatic Fire Detection and the Alarm System shall be a Fike Intello -Scon Fire Control the location of each sensor or other oddressoble device, including Liebert units and the pre- action FIKE Protection Systems System. The Control Panel shall be U.L. and U.L.C. listed and bear Factory Mutual test sprinkler system. The annunciator panel sholl be shown on the Floor pion with a designator, 704 South 10th Street laboratory approval. "YOU ARE HERE". Lamps shall remain illuminated until the system is reset. The graphic panel Blue Springs, MO. 64015 2) Enhanced Control Unit (ECU). This module shall control, supervise, and continuously monitor sholl have a lomp test switch. All communication sholl be accomplished through a single Tiber the entire system, through the use of on (industrial grade) Intel 15 Bit Microcontroller. This optic cable between control and graphic ponel(s). Fire Alarm and Suppression System Detection and distributed by. module shall include o back lit liquid crystal display (LCD) with up to 32 characters of are to be integrated within the some graphic ponel(s). (See drawings for panel quantity and alphanumeric information. This display is to provide individual custom messages associated with location). Fuller Engineering Co. any addressable device in the system. The ECU shall include touch membrane switches for each 6420 Ferguson Street of the following functions: 10) Motorized Dampers: Motorized dampers shall be furnished by the HVAC contractor. Dampers Indianapolis, IN 46220 a) Next Trouble: Displays, in chronological sequence, individual oddressoble devices in trouble shall be equipped, with 110 VAC low power holding coils, so that operation of units may be reporting to the ECU or a manufacturer specified message for devices supervised and controlled by auxiliary contacts within the automatic fire olorm system control panel (rated at B) The system sholl provide on FM -200 minimum design concentration of 7.5%, by volume, in all controlled by the ECU. 10A at 110 VAC). The HVAC contractor sholl be responsible for supplying contactors, or other areas and /or protected spaces at the minimum anticipated temperature within the protected area. b) Next Alarm: Displays the chronological sequence of individual oddressoble devices in alarm, such devices to operate or shut down motorized dampers. c) A 256 -event non - volatile history buffer shall be provided to store any abnormal event and shall C) The system shall be complete in all ways. It sholl include all mechanical and electrical installation, hove the ability to be downloaded at any time for hard copy records. The 256 -event history D) System Inspection and Checkout: all detection and control equipment, agent storage containers. FM -200 agent, nozzles, pipe and buffer shall be a non - volatile RAM memory with dual lithium battery backup. History events After the system installation has been completed, the entire system shh ll me checked inspected and fittings, manual release and abort stations, audible and visual alorm devices, auxiliary devices and shall be stored with time, dote and a description of the abnormal event. The system shall erout. functionally tested by qualified, trained personnel, in accordance wit h t e o nu octu s controls, shutdowns, alarm interface, caution/ advisory signs, functional checkout and testing, provide information on sensor contamination levels, fire levels, and other data necessary for recommended procedures and NFPA standards. training and all other operations necessary for a functional, U.L. Listed and /or F.M. approved, FM- future reference and analysis. 1) The complete system shall be functionally tested, in the presence of the owner or his 200 suppression system. d) This system sholl be fully field programmable and not require factory assistance for operating representative, and oil functions, including system and equipment interlocks, must be operational reconfiguration of any kind. at least five (5) days prior to the final acceptance tests. D) Provide two (2) inspections during the first year of service. Inspections shall be mode at 6 month e) For future expansion the Enhanced Control Unit will hove the capacity to accept a minimum of a) All system and equipment interlocks , such as door release devices, audible and visual devices, intervals commencing when the system is first placed into normal service. 1000 individual addresses. equipment shutdowns, local and remote alarms, etc. shall function as required and designed. f) All Fire Alorm /Agent Releasing controls are to be coordinated by this single panel. b) Each control panel circuit sholl be tested for trouble by inducing a trouble condition into the E) The general contractor shall be responsible for sealing and securing the protected spaces against 3) Manual Release Stations. Manuel pull stations shall be provided as a means of manually system. agent loss and /or leakage during the 10 minute "hold" period, activating the Fire alorm system. The manual pull stations shall be of dual- oction design and once activated, sholl not be capable of being restored to normal condition without a "keyed reset. E) As -Built Drawings: F) The system shall be actuated by the Intella -Scon analog detection and control system with photo Manual release stations shall be located at major points of egress and as shown on drawings. A Upon completion of each system, the installing contractor shall provide four (4) copies of system "As- electric analog sensors installed at o maximum spacing of 250 sq. ft. per detector, in both the room contact monitor module will be included with each station to give it a specific address (location) Built drawings to the owner. The drawings shall show actual installation details including all and sub -floor protected spaces. If the air now exceeds one air change per minute, photoelectric through the ECU. equipment locations (i.e.: control ponel(s), agent contoiner(s), detectors, olorms, manuals and detectors shall be installed at a spacing not to exceed 125 sq. ft. per detector.(Ref. NFPA No. 72 - 4) Alarm Horns. The vibrating horn sholl operate on 24 VDC with on output of 90 -94 dBA. The aborts, etc.) as well as piping and conduit routing details. Show all room or facilities modifications, 1993 edition) vibrating horn shall be polarized for supervisory purposes and consume only 0.035 amperes of 24 including door and /or domper installations completed. VDC. Field wiring connections shall be made to terminal strips located on the device. The horn VII) A) MATERIALS AND EQUIPMENT: General Requirements: shall be ruggedly constructed and have a red baked enomel finish. Location of these devices will be as noted on the project drawings. F) Acceptance Tests: 1) A room pressurization test sholl be conducted, in each protected space, to determine the presence 1) All devices and equipment shall be U.L Listed and /or FM approved. 5) Alarm Bells: The alarm bell sholl operate on 24 VDC and provide an output of 8690dBA. It of openings which would effect the FM -200 system concentration levels. The test(s) shall be shall be polarized for supervisory purposes and consume only 0.035 amperes at 24 VDC. Field conducted using the Retro -Tec Corp. Door Fan system, or equivalent, with integrated computer B) FM -200 Storage and Distribution: wiring connections shall be made to terminal strips and the olorm bell shall have a red baked program. All testing shall be in accordance with NFPA 2001. 1 The system design con be modular, control storage, or a combination of both design criteria. finish. Minimum bell diameter shall be six (6) inches. Location of these devices will be as noted 2) If room pressurization testing indicates that openings exist which would result in leakage and /or 2 Systems shall be designed in accordance with the manufacturer's guidelines. on the project drawings. loss of the FM -200 extinguishing agent, the installing contractor shall be responsible for Each I hell be located within the hazard area or as near as possible, to reduce the amount 6 Abort Station. The abort station shall be ?dead man? type and sholl be located next to each coordinating the proper sealing of the protected spoce(s) by the general contractor or his sub- of pipe and fittings required to install the item, 4) The FM -200 agent sholl be stored in FIKE P/N 70 -XXX Series Agent Storage Containers. 7) manual switch, Visuol Alarms. A visible signaling appliance shall operate on 24 VDC. The lomp shall be a contractor or a nt. The general contractor shall be responsible for adequately sealing all protected spacers) against agent loss or leakage. The installing contractor shall inspect all work to Containers shall be super - pressurized, with dry Nitrogen, to an operating pressure of 360 prig at xenon strobe type or equivalent with a minimum intensity of 100 candelo. The lens color sholl be ascertain that the protected space(s) have been adequately and properly sealed. THE FM -200 70F. Containers shall be of high- strength alloy steel construction that complies with the clear with the word "firer imprinted upon it. The location of these devices will be as noted on the INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE SUCCESS OF THE Department of Transportation regulation for refillable pressure vessels and conform to NFPA project drawings, or per ADAAG 4.28.3. ROOM PRESSURIZATION TESTS. If the first room pressurization test is not successful, in 2001. 8) Detection and Control Devices accordance with these specifications, the installing contractor shall direct the general contractor to 5) Containers shall be actuated by parallel wired initiators through o FIKE P/N 10 -1832 Agent a) Products of Combustion Sensor, Photoelectric Type, shall be a Fike 63 -020. The Photoelectric determine, and correct, the cause of the test failure. The installing contractor shall conduct Release Module (ARM) located at each agent container. Smoke Sensor shall be comprised of three main elements - the smoke sensing circuit, analog additional room pressurization tests, at no additional cost to the owner, until o successful test is 6) Each container shall have a pressure relief provision that automatically operates when the internal circuit, and transmission and address circuit. obtained. Copies of successful test results shall be submitted to the owner for record. by the the FM -200 system(s) sholl be placed in normol service. temperature exceeds 150F. b) The Intella -Scon control panel shall provide the command and interrogation signals which 3) Upon acceptance owner, completed 7) Each container sholl be fitted with a FIKE P/N 02 -2394- XX Liquid Level Device. It shall be confirm an olorm by comparing (with consecutive multiply posses of the "interrogation possible to determine the container agent quantity without removing the container from its mounting bracket, disconnecting the distribution piping, or removing the FM -200 system from window ") sensor information with stored data on fire conditions. The 63020 Analog /Addressable Photoelectric Sensor shall provide true linear analog data to the Enhanced G) FM -200 System Inspections., 1) The installing contractor shall provide two (2) inspections of each FM - 200 system, installed under service. (35 lb. and 60 lb. containers excluded) Control Unit in order for the ECU to differentiate between higher and lower values of smoke this contract, during the one -year warranty period. The first inspection shall be at the six month 8) Pre - engineered or engineered discharge nozzles shall be provided, within the manufacturers density and to established a working range of sensitivity levels unique to the particular interval, and the second inspection at the 12 month interval, after system acceptance. Inspections guidelines, to distribute the FM -200 throughout the protected spaces. The nozzles shall be FIKE environment. Any adjustments needed for sensor sensitivity to meet ambient conditions must sholl be conducted in accordance with the manufacturer's guidelines and shall comply with the P/N 80 -XXXX designed to provide proper agent quantity and distribution. Manufacturer shall be hove a minimum of 12 levels of adjustment within the U.L. standard. recommendations of NFPA 2001. capable of providing a U.L. approved computer flow calculation for each piping system. c) The system must have the capacity to automatically conduct a weekly functional test of each 2) Documents certifying satisfactory system(s) operation shall be submitted to the owner upon Computer program shall be specifically designed for use with FM200 (not holon), sensor which is accomplished by means of o test LED fitted within each sensor. When completion of each inspection. automatically activated by the control panel this test LED shall produce an infro -red signal level C. Control Equipment: The control system shall be the Fike Intello-Scon2 control panel. directly equivalent to that reflected by a given percentage of smoke entering the chamber. Any H) Warranty: 1) This panel shall process all input signals, sequence the levels of olorm and provide outputs to shut sensor not responding to its preset limits will be automatically readjusted to a programmed level 1) All FIKE FM -200 system components furnished, and installed under this contract, shall be down fans, activate dampers, activate pre - action of dry pipe sprinkler system, contact remote of sensitivity. guaranteed against defects in design, materials and workmanship for the full warranty period which monitoring or activate olorms. The system sholl have a standard standby battery supply to 9) Graphic Annunciator. Graphic Annunciator panel shall be flush mounted. Each panel shall be is standard with the manufacturer, but in no case less than one (1) year from the date of system provide a minimum of twenty -four (24) hours of emergency power. The Control Panel to be used provided with a room floor plan, drawn to scale, with remote alorm lumps mounted to represent occeptance. LIEBERT ENVIROMENTAL CONTROL UNIT L -1 ENVIRONMENTAL CONTROL SYSTEM (L -1) SPECIFICATIONS 1.0 GENERAL 1.1 SUMMARY These specifications describe requirements for a computer room environmental control system. The system shall be designed to maintain temperature and humidity conditions in the rooms containing electronic equipment. The manufacturer sholl design and furnish all equipment to be fully compatible with heat dissipation requirements of the room. 1.2 DESIGN REQUIREMENTS The computer room environmental control system shall be o self - contained factory assembled unit with down -flow air delivery and rear return. The system shall have a total cooling capacity of 120,100 BTU /HR, with a sensible cooling capacity of 109,500 BTU /HR based on on entering air temperature of 72 degrees Fahrenheit dry bulb and 60 degrees Fahrenheit wet bulb. The unit is to be supplied with 208 volt 3 ph 60 Hz electrical service. 1.3 SUBMITTALS Submittals sholl be provided with the proposal and shall include: Single -Line Diagrams; Dimensional, Electrical, and Capacity data; Piping and Electrical Connection Drawings. 2.0 PRODUCTS 2.1 Cabinet and Frame Construction The frame shall be constructed of heliorc welded tubular steel. The exterior panels shell be insulated with a minimum 1 in., 1.5 lbs. density fiber insulation. The main front panel shall hove captive 1/4 turn fasteners. The main unit color shall be as selected by the architect. 2.2 Filter Chamber The filter chambers sholl be on integral port of the system, located within the rear return plenum serviceable from either end of the unit. The filters sholl be rated not less than 20% efficiency (based on ASHRAE 52 -76). 2.3 Fan Section The fon shall be the centrifugal type, double width double inlet, and shall be statically and dynamically balanced as o completed assembly to a maximum vibration level of two mils in any plane. The shaft shall be heavy duty steel with self - aligning boll bearings with a minimum life span of 100,000 hours. The fon motor shell be 2 hp at 1750 RPM and mounted on on adjustable slide base. The drive package sholl be two -belt, variable speed, sized for 200% of the fan motor horsepower. The fops sholl be located to draw air over the A -frame coil to ensure even air distribution and maximum coil performance. Blow through coil designs will not be accepted. 2.5 Control Processor The control system sholl be microprocessor based. The system shall be provided with two .43 inch high, seven segment LED numerical displays to allow observation of room temperature and humidity and each settoble function: Temperature Setpoint 65 -85 degrees Fahrenheit Temperature Sensitivity 1 to 5 degrees Fahrenheit Humidity Setpoint 40 -60% R.H. Humidit Sensitivity 1% to 10% R.H. Humidifier Flush Rote. Normal Operating Modes (Heating, Cooling, Dehumidification) shall be indicated by colored LEDs on the unit - mounted display panel. The control system shall monitor unit operation and activate on audible and visual olorm in the event the following factory preset olorm conditions: High Temperature Low Temperature High Humidity Low Humidity Restricted Air Filters Loss of Air. A common alarm light shall be activated when any of the above conditions exist. The common alarm shell also indicate high head pressure, or water under floor. A compressor sequence feature shall be provided to change the lead /log sequence of the compressors. 2.6 Compressorized Systems 2.6.1 Dual Refrigeration Systems Each refrigeration circuit shall include hot gas mufflers, liquid line filter dryers, refrigerant sight glass with moisture indicator adjustable, externally equalized expansion valves, and liquid line solenoid valves. 2.6.2 Semi- Hermetic Compressors The compressors shall be located in a separate comportment so they may be serviced during operation of the equipment. The compressor shall be semi - hermetic with a suction gas cooled motor, vibration isolators, thermal overloads, oil sight gloss, manual reset high pressure switch, pump down low pressure switch, suction line strainer, reversible oil pumps for forced feed lubrication, a maximum operating speed of 1750 RPM, and a minimum EER of 11.4. Fully hermetic type compressors will not be accepted. 2.6.3 A - Frame D.X. Coil The evaporator coil shall be on A -Frame design and have 14.2 sq. ft. face area, 4 rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of 384 ft. per minute at 5650 CFM. Refrigerant of each system shall be distributed throughout the entire coil face area. A stainless steel condensate drain pan sholl be provided. 2.6.4 Air Cooled Systems 2.6.4.1 Fan Speed Control Condenser The Liebert manufactured air cooled condenser shall be the low profile, slow speed, multiple direct drive, propeller fon type. The condenser shall balance the heat rejection of the compressor at 95 degrees Fahrenheit ambient. The condenser sholl be constructed of aluminum and contain a copper tube, aluminum fin coil arranged for horizontal air discharge. The winter control system for the air cooled condenser shall be Liebert Fan Speed Control. The variable speed motor sholl operate from 0 to 230 volts single phase, 10 to 1050 rpm. It shall be designed with boll bearings, permanent lubrication, internal overload protection, 40 degrees Celsius rise at full speed, 65 degrees Celsius rise at 10 RPM. The control system sholl be complete with transducers, thermostats and electrical control circuit, factory pre- pockaged in the integral condenser control box. The transducer shalt automatically sense the highest head pressure of either operating compressor and control the variable speed fon on the air cooled condenser to properly maintain the head pressure. The fon speed control system shall provide positive start -up and operation in ambient temperature as low as -20 degrees Fahrenheit. The air cooled condenser shall have a 208 volt, 3 ph 60 Hz power supply. 2.6.4.2 Air Cooled Condenser Disconnect Switch Provide a disconnect switch factory mounted and wired to the condenser control panel, accessible from the exterior. 2.7 The computer room environmental control system shall be equipped with the following components. Disconnect Switch Non - Locking Type The non - automatic molded case circuit breaker shall be mounted in the high voltage section of the electrical panel. The switch shall be accessible with the door closed. Condensate Pump The condensate pump shall have the capacity of 145 GPH at 20 ft. head. It shall be complete with integral float switch, pump and motor assembly, and reservoir. Floor Stand Provide optional floor stand under unit. 3.0 EXECUTION 3.1 Installation of Computer -Room Air Conditioning Units 3.1.1 General Install computer room air conditioning units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances. 3.1.2 Electrical Wiring Install and connect electrical devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor. 3.1.3 Piping Connections Install and connect devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor. 3.2 Field Quality Control The system shall be check test and Started by the local manufactures representive in accordance with manufacturer's start up instructions. Test controls and demonstrate compliance with requirements. Warranty The system shall include a complete one year parts and labor warranty from dote of start up. The labor warranty shall be provided by the local manufactures representive. The dual semi hermetic compressors shall include a rive year ports warranty. CWArc h i to En ineers &I -9 — 9100 Keystone Crossini Suite 200 Indianapolis, Indiana 46 317.848.7800 FAX 317.574.0957 Archie t" Land Archilacbs do km F�I�tOrIC De0IIgn Spam Pkireft 60pyrf A Im rwr. trarAiwe i w w sr eMa 4/3/96 1 RDM 0) O U 4 LL Y� w C CL �2 J 3 U y�jF z a Z 2: V A o 2 `r �7►�ri+rr `X%1111111 No. =V8605 O S STATE 0 •AN i'0NAL. '/Mm' w 9" N0. a - shoots Re N0.