1218.97.18
i ;ENERAL NOT )R WIR'. CRAMS &SCHEMATIC 1. USE MINIMUM X14 AWG CONTROL WIRING. FOR CIRCUITS OVER 50 FEET LONG USE MINIMUM 112 AWG. 2. PROVIDE RESET BUTTON IN COVER OF ALL MAGNETIC MOTOR STARTERS J. REFER TO EQUIPMENT, MOTOR, AND CONTROL SCHEDULE FOR MOTOR HORSEPOWER, STARTER SIZE AND TYPE, ETC. 4. ALL CONTROL CIRCUITS SHALL OPERATE AT 120VAC UNLESS NOTED OTHERWISE. 5. CONNECT COIL OF S TAR TERS TO GROUNDED SIDE OF CONTROL CIRCUIT. DO NOT WIRE CONTROL OR SAFETY DEVICES BETWEEN COIL AND GROUND. (EXCEPT OVERLOAD CONTACTS) 6. THESE DIAGRAMS ARE A GUIDE AS TO THE INTENDED MODE OF OPERATION AND REQUIRED INTERLOCKING WIRING. THE EC SHALL REFER TO AND COORDINA 7E WIN SHOP DRAWINGS AND MANUFACTURER'S RECOMMENDA BONS PROVIDED BY THE EQUIPMENT OR MOTOR SUPPLIER FOR PRECISE SIZES, CONNECTIONS, CONTROLS, SAFETY DEVICES, AND 0774ER SPECIFIC REQUIREMENTS 7 AUTOMATIC TEMPERATURE AND CONTROL DEVICES SUCH AS THERMOSTATS, MOTORIZED DAMPERS ( OTHER THAN SMOKE DAMPERS IN SMOKE WALLS ) ETC. ARE TO BE FURNISHED, INSTALLED AND WIRED COMPLETE BY THE MC /TCC. 8. ALL WIRING SHOWN ON THESE DIAGRAMS AND SCHEMATICS IS BY THE EC UNLESS NOTED OTHERWISE. 9. THE EC SHALL PROVIDE THE REQUIRED NUMBER OF AUXILIARY CONTACTS IN STARTERS 774E EC SHALL COORDINATE THE CONTROL TRANSFORMER VA RATING REQUIREMENTS WITH THE TEMPERATURE CONTROL CONTRACTOR AND SHALL PROVIDE ADEQUATELY SIZED TRANSFORMERS IN STARTERS AS REQUIRED BY COIL BURDEN AND TEMPERATURE CONTROL DEVICE LOADS. 10. COORDINATE EXACT LOCAT70N OF MOTORS WITH THE MECHANICAL AND PLUMBING DRAWINGS AND WITH THE MC, PC, ANO TCC SHOP DRAWINGS 11. THE INDIVIDUAL DIAGRAMS SHOWN ARE APPLICABLE WHEN REFERENCED ON THE EQUIPMENT, MOTOR, AND CONTROL SCHEDULE, MAGNETIC STARTER - DIAGRAM" COLUMN, DRAWINGS OR OTHER DIAGRAMS THE "TYPICAL MAGNETIC STARTER WIRING DIAGRAM" IS APPLICABLE TO ALL MAGNETIC FVNR STARTERS. 200V OR 460V - 30 POWER SOURCE AS SHOWN ON DRAWINGS L1 11_2 L3 COMBINATION MAGNETIC O STARTER 4 2 n CONTROL �J CIRCUIT FUSE r M OL T1 T2 13 X1 120VAC CONTROL CIRCUIT X2 PRIMARY CONTROL FUSES, SIZE AS REQUIRED BY CODE T1 T2 T3 3 NO TES. MOTOR 1. THIS DIAGRAM FOR SINGLE SPEED, SINGLE WINDING, FVNR, INTEGRAL HORSEPOWER, SQUIRREL CAGE, INOUC77ON MOTORS IS TYPICAL FOR ALL SUCH MOTORS. REFER TO APPROPRIATE CONTROL DIAGRAMS FOR CONTROL CONNECTIONS TO X1 AND X2. 2. CONTROL TRANSFORMER FOR 480 TO 120 VOLTS OR 208 TO 120 VOLTS, SINGLE PHASE AS REQUIRED. VA RA 77NG SHALL BE ADEQUA IF TO POWER ALL CONTROL CIRCUIT LOAOS (COORDINATE REQUIREMENTS WITH THE MC, PC, TCC OR APPROPRIATE CONTRACTOR). FOR 208 VOLT SYSTEMS, THE EC HAS THE OPTION OF ROUTING A NEUTRAL CONDUCTOR TO THE STARTER AND OMITTING THE CON7ROL TRANSFORMER BY OBTAINING CONTROL POWER FROM A FUSED PHASE LEG AND THE NEUTRAL. 3 DISCONNECT AT MOTOR WHEN INDICATED ON PLAN AND / OR MOTOR CONTROL SCHEDULE, OR REQUIRED BY CODE. FOR ROOF EXHAUST FANS, DISCONNECT IS PART OF FAN ASSEMBLY AND IS PROVIDED WI TH UNI T BY THE MC, UNLESS OTHERWISE INDICA TED. 4. FUSED SWITCH OR CIRCUIT BREAKER. PROVIDE A FOURTH AUXILIARY POLE FOR THE CONTROL CIRCUIT WHEN THE CONTROL POWER IS PROVIDED FROM A SEPARATE SOURCE OUTSIDE OF THE STARTER ENCLOSURE. ( CURRENT LIMITING FUSE PROTECTION WITH SWITCH SHOWN. ) 5. CURRENT LIMITING TIME DELAY FUSE. TYPICA O X1 O MA A ETIC STARTER WIRING, N. T. S NO TES: k__0O MS 0_�O 1. HAND - OFF - AUTOMA TIC SELECTOR S 14 TCH IN STARTER COVER. 2. CONTACT IN CONTROLLING DEVICE OUTSIDE OF STARTER ENCLOSURE. CIRCUIT BREAKER QUANTITIES TYPICAL DEVICES INCLUDE THERMOSTATS, BMS, AUXILIARY CONTACTS IN INTERLOCKING STARTERS, FLOAT SWITCHES, ETC. J. MOTOR STARTER OPERATING COIL RATED 120VAC UNLESS N07ED OTHERWISE. 4. GREEN PILOT LIGHT IN STARTER COVER, INDICATES A RUN CONDITION. 5. AUXILIARY CONTACTS FOR CONTROL OR INTERLOCK OF OTHER EQUIPMENT, U � O 0z MOTORS, DAMPER OPERATOR, ETC. PROVIDE QUAN77TY REQUIRED; WHERE ° W ° o tY >- am QUANTITY REQUIRED EXCEEDS THE NUMBER AVAILABLE W1TV THE COIL, J o z O U PROVIDE A CONTROL RELAY IN THE STARTER AND CONNECT COIL IN a U o PARALLEL WITH THE STARTER COIL. USE CONTROL RELAY CONTACTS 1 (QUANTITY AS REQUIRED) FOR INTERLOCKING OF OTHER FUNCTIONS. 114 HP ( 1 - NO AND 1 - NC SHOWN FOR REFERENCE, • 120VAC. ) 6. SAFETY DEVICE OR SHUT DOWN FUNCTION CONTACT OUTSIDE OF STARTER 3 ENCLOSER. TYP /CAL DEVICES INCLUDE FREEZE STAIS, LIMIT SWITCHES, ALARM - CONTACTS, ETC. 7 WHERE CONTROL VOL TAGS IS NOT DERIVED INSIDE STARTER ENCLOSURE, PROVIDE - AUXILIARY CONTACT ON STARTER DISCONNECT SWITCH (OR CIRCUIT BREAKER) TO - DISCONNECT CONTROL VOLTAGE. TYPICAL H-0-A SWITCH DIAGRAM 3 oo N. T. S GRAM PANELBOARD SCHEDULE-- PLAN N0. ® EQUIPMENT OR MOTOR DESIGNATION LOAD CIRCUIT BREAKER QUANTITIES BRANCH CIRCUIT MAGNETIC STARTER VOLTAGE- PHASE- WIRES AIC 111 ZJ 0 Wz O aU REMARKS • PANEL OR MCC U � O 0z WIRE AND CONDUIT ° W ° o tY >- am M- J o z O U �'~ ocn a U o " Q o 1 EF -1 114 HP 120 -1 1P -20A 3B1 3 �aBaB - EC 1 HOA - - - - IN M - oo EF -2 ©am00000000000000000000000000o 120 -1 1P -20A 3B1 41 3#12AWG -3/4 "C - - - - - - - - - I - 2 3 H -1 (HUMIDIFIER) 38 KW 480 -1 2P -20A HJA 19 3112A WG -3/4 "C - - - - - - v o� EC oe 4 ©am H -2 (HUMIDIFIER) 1.9 KW ©000000000aova000v000000amo 1P -20A 3B1 5 3#12AWG -3/4 "C - - - - - - - - EC /NT 4 5 RTU -1 33 FLA 480 -3 3P -40A HJA 13 3 #8, #TOG., 314 "C - - - - v o� - o ,. ©m00000000000000voovooee0000mo - 6 DC -1 5.0 KW 480 -3 3P -20A HJA 7 4jf12AWG -314 "C - - - - - - - - M /NT - 7 DC-2 5.0 KW 480 -3 3P -20A HJA 8 4 ,f 12AWG -314 "C - -:, - v - - ovoomoovaovov000aooav000000ev000 - - M /NT - 8 9 DC -3 DC -4 175 KW 10.0 KW 480 -3 480 -3 3P -30A 3P -20A HJA HJA 2 14 4 #1OAWG -314 "C 4112AWG -314 "C - - - - - - - - - - - - - - - - M M /NT /NT - - 10 DC -s 1.7 KW 480 -3 3P -20A HJA 1 4 #12AWG -314 "C e�oi - - - - - - - M IN - 11 DC -6 1.8 KW 480 -3 3P -20A HJA 1 4,#12AWG -314 "C - - - - - - - - M /NT - 12 DC -7 5.0 KW 480 -3 3P -20A H3A 1 4,112AWG -314 "C - veaveveveveveveeveeveveveeeeeeve - - - - - - M /NT - v PANELBOARD SCHEDULE NOTES: 1. EACH DOUBLE OR MULTIPLE SECTION PANELBOARD SHALL HAVE SECTIONS OF EQUAL HEIGHT MOUNTED SIDE -BY -SIDE. EACH SECTION (EXCEPT LAST) SHALL HAVE SUBFEED LUGS FOR CABLE CONNECTION TO NEXT SECTION. 2. PROVIDE THE FOLLOWING CIRCUI T BREAKERS WHERE INDICA TED: ST= CB WI TH SHUNT TRIP COIL, GFI= GROUND FA UL T CIRCUI T INTERRUPTER FOR PERSONNEL PROTECTION, GFP= GROUND FAULT PROTECTION FOR EQUIPMENT, SFCB= CB MOUNTED IN SUBFEED POSITION AND CONNEC7E0 AHEAD OF THE MAIN CIRCUIT BREAKER, FTL= PANELBOARD WITH FEED - THROUGH LUGS. J. MINIMUM AIC FAULT CURRENT SHALL BE 10,000 AMPS FOR 208YI120 AND 1201240 VOLT PANELBOARDS AND 14,000 AMPS FOR 480YI277 VOLT PANELBOARDS WHEN NOT SPECIFICALLY NOTED OTHERWISE ABOVE. 4. REMARKS NO TES: Ol THE PANELBOARD IS EX/S77NG. PROWOE ADDITIONAL BRANCH BREAKERS AS INDICATED. EQUIPMENT, MOTOR & CONTROL SCHEDULE PLAN N0. ® EQUIPMENT OR MOTOR DESIGNATION LOAD VOLTAGE -PHASE BRANCH CIRCUIT J� ,_,, D � z < Q t- Mcn MAGNETIC STARTER w -im FE a �° <w >L. vw oa ZD zoos " (/)� oa ZJ 0 Wz O aU REMARKS OCP DEVICE PANEL OR MCC U � O 0z WIRE AND CONDUIT ° W ° o tY >- am �' N in J o z O U �'~ ocn a U o " Q o 1 EF -1 114 HP 120 -1 1P -20A 3B1 3 3J12AWG -314 "C - EC 1 HOA - - - - IN M - 2 EF -2 113 W 120 -1 1P -20A 3B1 41 3#12AWG -3/4 "C - - - - - - - - - I - 2 3 H -1 (HUMIDIFIER) 38 KW 480 -1 2P -20A HJA 19 3112A WG -3/4 "C - - - - - - - - EC INS 4 4 H -2 (HUMIDIFIER) 1.9 KW 120 -1 1P -20A 3B1 5 3#12AWG -3/4 "C - - - - - - - - EC /NT 4 5 RTU -1 33 FLA 480 -3 3P -40A HJA 13 3 #8, #TOG., 314 "C - - - - - - - - M /NT - 6 DC -1 5.0 KW 480 -3 3P -20A HJA 7 4jf12AWG -314 "C - - - - - - - - M /NT - 7 DC-2 5.0 KW 480 -3 3P -20A HJA 8 4 ,f 12AWG -314 "C - - - - - - - - M /NT - 8 9 DC -3 DC -4 175 KW 10.0 KW 480 -3 480 -3 3P -30A 3P -20A HJA HJA 2 14 4 #1OAWG -314 "C 4112AWG -314 "C - - - - - - - - - - - - - - - - M M /NT /NT - - 10 DC -s 1.7 KW 480 -3 3P -20A HJA 1 4 #12AWG -314 "C - - - - - - - - M IN - 11 DC -6 1.8 KW 480 -3 3P -20A HJA 1 4,#12AWG -314 "C - - - - - - - - M /NT - 12 DC -7 5.0 KW 480 -3 3P -20A H3A 1 4,112AWG -314 "C - - - - - - - - M /NT - EQUIPMENT MOTOR & CONTROL SCHEDULE NOTES: 1. LOAD: A= AMPERES, FHP= FRACTIONAL HORSEPOWER, HP= HORSEPOWER, KVA= KILOVOLT- AMPERES, KW= KILOWATTS, W= WATTS. 2 OVERCURRENT PROTECTION (OCP): 3P -60A= 3 POLE, 60 AMPERE CIRCUIT BREAKER, 60AF= SWITCH WITH 60 AMPERE FUSE(S). J. RESPONSIBILITY- E= [Ll�_ ICAL CONTRACTOR, EX= EXISTING, G= GENERAL CONTRACTOR, TNT= INTEGRAL WITH EQUIPMENT, M= MECHANICAL CONTR�G tOR 0= OWNER. FURNISH AND INSTALL: XF INDICA 7ES FURNISHED BY X AND YI INDICA TES INSTALLED BY Y (EXAMPLE. MFEI= MECHANICAL CONTRACTOR TO FURNISH AND ELECTRICAL CONTRACTOR TO INSTALL). SINGLE RESPONSIBILITY INDICATES BOTH FURNISH AND INSTALL. 4. CONTROLS: HOA= HAND - OFF- AUTOMA7IC SWITCH, S =ON -OFF SWITCH, HL= HIGH -LOW SWITCH, HLO= HIGH - LOW -OFF SWITCH, M= MOMENTARY ON -OFF SWITCH, ML= MOMENTARY HIGH -LOW SWITCH, MLO= MOMENTARY HIGH- LOW -OFF SWITCH, LOR= LOCAL - OFF -REMO TE SWITCH. 5. REMARKS NOTES Ol SEE ONE LINE DIAGRAM FOR ADD/ T70NAL REQUIREMENTS AND INFORMATION. OZ CONNECT EXHAUST FAN TO THE LIGHT SW/ TCH SERVING THE ASSOCIA 7ED TOILET ROOM. O3 COORDINATE EXACT MOTOR ANO WIRING REQUIREMENTS WITH THE EQUIPMENT CONTRACTOR. VERIFY EXACT MOTOR TYPE BEING FURNISHED PRIOR TO ORDERING STARTER. EQUIPMENT CONTRACTOR MUST PROVIDE THE MOTOR FULL LOAD AMPS AT EACH SPEED TO THE STARTER CONTRACTOR. 4O THE EC SHALL SUPPLY AND INSTALL A FUSED DISCONNECT ADJACENT TO THE EQUIPMENT, 9/32" L' . STEEL ROD SUSPENSION FROM 3LOG. STRUCTURE WITHIN 3' OF OUTLET 3OX (TYPICAL) 3' MAX SPACING 3ETWEEN HANGERS (TYP.) STEEL OUTLET BOX- SIZED PER N.E.C. 4ND SUPPORTED RIGIDLY FROM STRUCTURE � TYP.). INSTALL NO CLOSER THAN 1'-0" 7ROM ANY FIXTURE. I-oNDUI T (TYP.) 4' MIN., 6' MAX. LENGTH - 318" FLEX ;ONDUIT W/ 3 -J18 CONDUCTORS; 7ACTORY WIRE INTO FIXTURE (TYP.) 2 RECESSED FLU CENT TING INSTALLA RM 119 TYPICAL 2X4' LAY -IN -_ RECESSED FLUORESCENT LIGHT FIXTURE (TYP.) - SECURE FIXTURES TO GRID BY 8742 -12 MECHANICAL MEANS OR WITH STATUS /CONTROL CLIPS PER N.E.C. (TYP.) MASTER T -BAR LAY -IN CEILING SUSPENSION SYSTEM (TYP.) NOTE: DO NOT SUPPORT CONDUIT OR BOX FROM CE /LING GRID HANGERS POWER SUPPLY 3B1 -1 0- RM 105 a = RM 109 a = RM 111 RM 114 MDL 8773 U ROOM CON TROL S TA TION NURSE CALL RISER BSA DESIGN 6810 N SHADELAND AVE INDIANAPOLIS INDIANA 46220.4287 317.849.7878 PH 317.849.2288 FX ��\ �O ✓'�\ S T No. 13815 j ti STATE OF . 14�/ % �*-. Np t ANP% s ��.L ;i MOORE ENGINEERS A PROFESSIONAL CORPORATION 9245 N. Meridian Street, Suite 105 Indianapolis, Indiana 46260.1812 317.848.5045 PH 317.848.2765 FX St vificenI Carmel hospital 13500 N. Meridian Street MDL, 8807 P.O. BOX 1905 Carm DOME LIGHT e.& Indians 4603,2 (THREE -LAMP) CARMEL MEDICAL BUILDING No. 1 SUITE 315/355 Carmel, Indiana ELECTRICAL SCHEDULES AND DETAILS SCALE NONE CLIENT NO. DATE 9 -29 -97 COMMISSION 97055 COORD BKS DRAWN BKS E5 APPROVED TMW