ELECTRICAL SPECIFICA TIONS
CONTINUED
MUSIC DISTRIBUTION SYSTEM
GENERAL: PROVIDE A MUSIC DISTRIBU77ON SYSTEM WITH ALL FEATURES, FUNCTIONS
AND COMPONENTS SPECIFIED HEREIN AND /OR REQUIRED ON THE DRAWINGS
SYSTEMS PROVIDED PER THESE SPECIFICATIONS INCLUDE THE FOLLOWING
COMPONENTS.-
EQUIPMENT RACK
POWER AMPLIFIER
CASSETTE TAPE PLAYER
COMPCT DISK PL YER
LOUDSPEAKERS
VOLUME CONTROLS
WIRE AND CABLE
CODE COMPLIANCE. PROVIDE WORK COMPLYING WITH APPLICABLE REQUIREMENTS
OF NFPA 70 NATIONAL ELECTRICAL CODE".
EIA COMPLIANCE: COMPLY WITH THE FOLLOWING ELECTRONICS INSTITUTE ASSOCIATION
STANDARDS:
SOUND SYSTEMS, EIA -150
LOUDSPEAKER, DYNAMIC MAGNETIC STRUCTURES, AND IMPEDANCE, EIA -299A
RACKS, PANELS AND ASSOCIATED EQUIPMENT, EIA -310A
AMPLIFIERS FOR SOUND EQUIPMENT, SE -101A
SPEAKERS FOR SOUND EQUIPMENT, SE -103
UL COMPLIANCE. COMPLY WITH REQUIREMENTS OF UL50.
MANUFACTURERS.
A TLAS/SOUNDOLIER
BOGEN CORP.
DUKANE CORP.
RAULAND -BORG CORP.
UNI VERSI TY SOUND
EQUIPMENT LIST- PROVIDE EQUIPMENT FROM AN APPROVAL MANUFACTURER EQUAL
TO THE FOLLOWING:
EQUIPMENT RACK
SOUNDOL/ER
300
POWER SUPPL Y
DUKANE
17A365
MIXER /POWER AMPLIFIER
DUKANE
1A 1635
CASSETTE TAPE DECK (RACK MOUNT)
DUKANE
1OA1901438 -725
MUL77 -00 PLAYER (RACK MOUNT)
DUKANE
CH6000R 1438 -726
RECESSED SPEAKERS
SOUNDOL/ER
F072W/CS95- 8NS181 -8
VOLUME CONTROL
SOUNDOL/ER
A T -10
SYSTEM WIRING MATERIALS AND REQUIREMENTS
ALL WIRING SHALL BE INSTALLED AS DIRECTED BY MANUFACTURERS SHOP DRAWINGS
COORDINATE ALL CABLE REQUIREMENTS WITH MANUFACTURER. ALL CABLES SHALL
BE UL LISTED FOR THEIR USE.
CONCEAL ALL WIRING ANO RACEWAYS EXCEPT IN UNFINISHED SPACES.
PROVIDE WIRING OF ONE OF THE FOLLOWING:
OPEN CABLE WITHOUT A CONDUIT SYSTEM WHERE ABOVE ACCESSIBLE CEILING
AREA.
OPEN PLENUM CABLE WITHOUT A CONDUIT SYSTEM WHERE ABOVE ACCESSIBLE
CEILING AREAS
CABLE INSTALLED IN AN EMT CONDUIT SYSTEM,
INSTALLA T70NS WITH STRANDED WIRE COMPLY WITH THE FOLLOWING:
PROVIDE WIRE AND CABLE IN ACCORDANCE WITH REQUIREMENTS OF
MANUFA C 7URER.
PROVIDE MUL 77CONDUCTOR CABLES FOR WIRE SIZES SMALLER THAN AWG #14.
IN ACCESSIBLE CEILING AREAS 7HE ELECTRICAL CONTRACTOR MAY INSTALL WIRING
OPEN ABOVE CEILING SYSTEM AS DIRECTED FOR EXPOSED CABLES IN ACCESSIBLE
CEILINGS USED FOR ENVIRONMENTAL AIR RETURN OR SUPPLY THE ELECTRICAL
CONTRACTOR MAY INSTALL CABLES IN METAL CONDUIT SYSTEM OR USE UL LISTED
PLENUM CABLE. COORDINA7E AVAILABILITY OF UL LISTED PLENUM CABLE WHICH
WILL MEET SYSTEM MANUFACTURER REQUIREMENTS BEFORE INSTALLATION.
CTRICAL DEMOLITION WORK
GENERA : THIS CONTRACTOR SHALL DEMOLISH THE ELECTRICAL SYSTEMS IN THE
EXISTING FACILITY AS SHOWN ON THE DRAWINGS, AS REQUIRED BY THE N07ES OR
AS REQUIRED TO ACCOMMODATE NEW CONSTRUCTION. ALL EQUIPMENT, CONDUIT,
WIRING, FIXTURES, ETC. WHICH ARE NOT TO BE REUSED` SHALL BE REMOVED FROM
THE PREMISES AS THEY ARE REMOVEO EXCEPT THA T THE CONTRACTOR SHALL NOT
REMOVE FROM THE PREMISES ANY EQUIPMENT THAT MAY HAVE MAINTENANCE
VALUE TO THE 0WNER WITHOUT PERMISSION OF THE OWNER. SALVAGED
MA 7ER/ALS TO BE TURNED OVER TO THE OWNER SHALL BE CAREFULL Y REMOVED,
CLEANED AND STORED.
INSPECTION: PRIOR TO COMMENCEMENT OF SELECTIVE DEMOLI T70N WORK,
INSPECT AREAS IN WHICH WORK WILL BE PERFORMED. PHOTOGRAPH EXISTING
CONDITIONS TO STRUC7URE SURFACES, EQUIPMENT OR TO SURROUNDING
PROPERTIES WHICH COULD BE MISCONSTRUED AS DAMAGE RESULTING FROM
SELECTIVE DEMOLITION WORK, AND FILE KITH THE OWNERS REPRESEN TA 77VE
PRIOR TO S TAR 77NG WORK.
PREPARATION. PROVIDE TEMPORARY BARRICADES AND OTHER FORMS OF
PROTECTION AS REQUIRED TO PROTECT THE OWNERS PERSONNEL AND THE
GENERAL PUBLIC FROM INJURY DUE TO SELECTIVE DEMOLITION WORK. MAINTAIN
EXISTING UTILITIES WHICH ARE TO REMAIN, KEEP THEM IN SERVICE, AND PR07ECT
THEM AGAINST DAMAGE DURING OEMOL177ON AND CONSTRUCTION. PROVIDE
INTERIOR AND EXTERIOR SHORING, BRACING OR SUPPORT TO PREVENT MOVEMENT,
SETTLEMENT OR COLLAPSE OF 774E STRUCTURE TO BE DEMOLISHED AND ADJACENT
FACILITIES WHICH ARE TO REMAIN. COVER AND PROTECT FURNITURE, EQUIPMENT
AND FIXTURES WHICH ARE TO REMAIN FROM SOILING OR DAMAGE DURING
DEMOLI TION WORK IN THOSE AREAS FROM WHICH SUCH I TEMS HA VE NOT BEEN
REMOVED.
DEMOLITION: PROTECT ADJACENT MATERIALS INOICA TED TO REMAIN. LOCATE,
IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH THE
DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS.
MAINTAIN EXISTING ELECTRICAL SERVICES AND FEEDERS TO OCCUPIED AREAS AND
OPERA77ONAL FACIL177ES PERFORM SELECTIVE DEMOLITION WORK IN A
SYSTEMA 77C MANNER. USE SUCH METHODS AS REQUIRED TO COMPLETE WORK
INOICA TED ON THE DRAWINGS IN ACCORDANCE WI TH GOVERNING REGULA TIONS.
HAZARDOUS MATERIALS. IF HAZARDOUS MATERIALS ARE ENCOUN7ERED OR
BELIEVED TO BE ENCOUNTERED DURING DEMOLITION OPERATIONS, THE
CONTRACTOR SHALL STOP WORK AT THAT PARTICULAR LOCATION AND NOT /FY THE
OWNER OF THE HAZARDOUS MATER /AL. THE CONTRACTOR SHALL CONTINUE WORK
AFTER REMOVAL OF HAZARDOUS MATERIALS.
DISPOSAL: REMOVE DEBRIS, RUBBISH AND OTHER MA TERIALS RESUL TING FROM
DEMOLITION OPERA TIONS FROM THE BUILDING SI FE TRANSPORT AND LEGALLY
DISPOSE OF MA7ERIALS OFF SITE. BURNING OF REMOVED MATERIALS IS NOT
PERMITTED ON THE PROJECT S1 7E
BALLASTS AND LAMPS: EXIS77NG BALLASTS, HID AND FLUORESCENT LAMPS MAY
CONTAIN PCB, MERCURY AND OTHER HAZARDOUS MATERIALS. THESE
COMPONENTS SHALL BE RECYCLED WHERE POSSIBLE AND NON- RECYCLED
MA7FR/ALS SHALL BE DEPOSITED AT AN EPA APPROVED HAZARDOUS WASTE
LANDFILL. THE DISPOSAL AND MANIFEST OF DISPOSAL OF THESE COMPONENTS
SHALL BE CER77FIED. THE COMPONENTS SHALL NOT BE DEPOSITED IN GENERAL
WASTE REMOVAL OUMPSTERS. THE RESPONSIBLE PARTY SHALL FURNISH
TRANSPORT CONTAINERS AT THE 10851 IF FOR STORAGE OF COMPONENTS
CLEAN -UP AND REPAIR: UPON COMPLET70N OF ELECTRICAL DEMOLITION WORK,
REMOVE TOOLS, EQUIPMENT AND DEMOLISHED MA 7FR/ALS FROM THE SITE
REMOVE PROTEC77ONS AND LEAVE INTERIOR AREAS BROOM CLEAN. REPAIR
DEMOL/ TION PREFORMED IN EXCESS OF THA T REQUIRED. RETURN STRUCTURES
AND SURFACES WHICH ARE TO REMAIN TO COND177ONS EXISTING PRIOR TO
COMMENCEMENT OF SELECTIVE DEMOLI770N WORK. REPAIR ADJACENT
CONSTRUCTION OR SURFACES SOILED OR DAMAGED BY SELECTIVE DEMOLITION
WORK.
END OF SPEC
BSA DESIGN 6810 N SHADELAND AVE
INDIANAPOLIS INDIANA 46220.4287
317.849.7878 PH 317.849.2288 Fx
F10
No. e
13815 WY
STATE OF
MOORS
ENGINEERS
A PROFESSIONAL CORPORATION
9245 N. Meridian Street, Suite 105
Indianapolis, Indiana 46260 -1812
317.848.5045 PH 317.848.2765 FX
St. Vinceut Carmel Hospital
13600 N. Meridian Street
P.O. Boz 1903
Camel lnd/ana 48082
CARMEL
MEDICAL
BUILDING
No. 1
SUITE 315/355
Carmel, Indiana
ELECTRICAL
SPECIFICATIONS
SCALE NONE CLIENT NO.
DATE 9 -29 -97 COMMISSION 97055
COORD BKS
DRAWN BKS E7
APPROVED TMW