ALL WORK FOR T41S PROJECT SHALL CONFORM TO THE REQUIREMENTS OF ALL
APPLICABLE CODES AND AUTHORITIES HAVING JURISDICTION.
THE CONTRACTORS SHALL:
REVIEW THE CONTRACT DOCUMENTS OF ALL TRADES TO FULLY INFORM THEMSELVES
OF THE SCOPE OF THE WORK REQUIRED FOR THIS PROJECT
ARRANGE TO VISIT THE PROJECT S17F BEFORE SUBMITTING THEIR BID ON THE PROJECT.
THE CONTRACTORS ARE RESPONSIBLE FOR PLACING THEIR OWN INTERPRETATION ON
EXISTING COND177ONS AND LIMITATIONS.
PROVIDE AND INSTALL ACCESS PANELS AND DOORS AS REQUIRED TO ALLOW PROPER
ACCESS TO MECHANICAL WORK.
REMOVE ALL RUBBISH AND WASTE FROM THE PROJECT S1 TE AS IT IS GENERA TED (AT
LEAST DAILY).
PROVIDE ALL CUTTING AND PATCHING NECESSARY FOR THE INSTALLATION OF
MECHANICAL WORK. CUTTING OF STRUCTURAL MEMBERS SHALL NOT PROCEED
WI THOUT THE WRI TTEN AUTHORIZA T/ON OF THE STRUCTURAL ENGINEER.
OBTAIN AND PAY FOR (AS A PART OF THE QUOTED PRICE FOR THE WORK) ALL
NECESSARY PERMITS, LICENSES AND FEES.
GUARANTEE ALL NEW MA7ERIALS, EQUIPMENT AND INSTALLATION FROM ALL
DEFECTS IN WORKMANSHIP AND /OR MATERIALS FOR A PERIOD OF ONE YEAR,
BEGINNING W17H THE DATE OF PROJECT SUBS TAN77AL COMPLETION. EQUIPMENT
MANUFACTURERS WARRANTIES SHALL BE EXTENDED AS NECESSARY TO FULFILL THIS
REQUIREMENT.
SUBMIT SIX COPIES OF SHOP DRAWINGS FOR ENGINEERS REVIEW. SHOP DRAWINGS
SHALL BE SUBMITTED ON EQUIPMENT, RTU, ELECTRIC HEATERS, HUMIDIFIERS, GRILLES,
REGISTERS, DIFFUSERS, VALVES, DUCTWORK, TEMPERATURE CONTROLS, ETC..
COORDINA IF THE INSTALLATION OF MECHANICAL WORK WT TH THE WORK OF ALL
OTHER TRADES 774E DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT
INTENDED TO INDICATE ALL OFFSETS AND FITTINGS THAT MAY BE REQUIRED TO
COMPLETE THE PROPER INSTALLATION OF ALL SYSTEMS SHOWN. IT 1S 7HE
CONTRACTORS RESPONSIBLLI TY TO PROVIDE FINAL COORD/NA TION OF THE
/NSTALLA 77ON DETAILS OF THEIR SYSTEMS.
BASIC MATERIALS AND METHODS
MARK ALL NEW PIPING SYSTEMS WITH SETMARK" IDEN77F /ES (SETON CORPORATION)
PIPING SHALL BE MARKED ON EACH SIDE OF EACH WALL PENETRATION AND
AT 20 FOOT INTERVALS WITHIN A ROOM.
TAG ALL NEW VALVES WITH A BRASS TAG ATTACHED TO THE VALVE W/TH A NYLON
DRAW BAND. VA VE /DENT/FICA RON SYSTEM SHALL BE AS APPROVED BY THE OWNER
BEFORE INSTALLATION. PROVIDE A REDUCED SCALE PLAN TO THE OWNER /NDICA77NG
THE LOCATION OF EACH VALVE, SIZE, SERVICE, ETC. (INCLUDE EXISTING VALVES
WHERE APPROPRIATE TO THE NEW SYSTEMS). NUMBER ALL VALVES SEQUENTIALLY
AND LIST THE APPLICABLE SERVICE.
INSULA /TON
REFRIGERANT SUCTION LINES ARE TO BE COVERED WITH 112" THICK ARMAFLEX.
ALL CONCEALED INTERIOR DUCTS -ARE TO BE INSULATED WITH 2" THICK FIBERGLAS
WITH FRK FACING, 314 POUND PER CUBIC FOOT DENSITY. WELD IMPALING PINS TO BOTTOM
OF DUCTS SO SUPPORT IS AT 12" CENTERS IN ALL DIRECTIONS SECURE INSULATION
TO 774ESE PINS WI TH APPROPRIA TE FASTENERS.
Pl lNG
REFRIGERANT PIPING:
COPPER TUBING — ASTM B 280, TYPE ACR, HARD —DRAWN STRAIGHT LENGTHS,
AND SOFT— ANNEALED COILS, SEAMLESS COPPER TUBING. TUBING SHALL BE FACTORY CLEANED, READY FOR
INSTALLATION, AND HAVE ENDS CAPPED TO PR07ECT CLEANLINESS OF PIPE INTERIORS PRIOR TO SHIPPING.
FI T RNGS:
WROUGHT— COPPER F/TT/NGS — ANSI B16.22, STREAMLINED PA TTERN.
JOINING MA TER/ALS
BRAZING FILLER METALS — AWS A5.8, CLASSIFICATION BAG -1 (SILVER)
REFRIGERANT.•
REFRIGERANT NO. 22, IN ACCORDANCE WITH ASHRAE STANDARD 34.
CHARGE SYSTEM USING THE FOLLOWING PROCEEDURE.
INSTALL CORE IN F/L TER DRYER AFTER LEAK TEST, BUT BEFORE EVACUA RON.
EVACUATE REFRIGERANT SYSTEM WITH VACUUM PUMP; lIN77L TEMPERATURE OF 35' F. IS INDICATED ON
VACUUM DEN YDRARON INDICATOR.
DURING EVACUATION, APPLY HEAT TO POCKETS, ELBOWS, AND LOW SPOTS IN PIPING.
MAINTAIN VACUUM ON SYSTEM FOR MINIMUM OF 5 HOURS AFTER CLOSING VALVE
BETWEEN VACUUM PUMP AND SYSTEM.
BREAK VACUUM WITH REFRIGERANT GAS, ALLOW PRESSURE TO BUILD UP TO 2 PSI,
COMPLETE CHARGING OF SYSTEM, USING NEW FILTER DRYER CORE IN CHARGING LINE.
PROVIDE FULL OPERA 77NG CHARGE.
PROVIDE AND INSTALL ADJUSTABLE COPPER PLA7ED CLEWS HANGERS FOR ALL
HORIZONTAL RUNS OF COPPER PIPING. SUPPORT EACH PIPE ON MAXIMUM 8'— 0"
CENTERS WITH A MINIMUM 3/8" HANGER ROD. MULTIPLE PIPING RUNS MAY BE
ACCOMMODA TED WI TH APPROPRIA TE TRAPEZE HANGERS A T THE CONTRACTORS
DISCRETION.
ALL PIPING SHALL BE CONCEALED ABOVE CEILINGS, IN WALLS, IN CHASES, ETC.,
UNLESS SPECIFICALLY NOTED TO THE CONTRARY ON THE DRAWINGS.
WHERE PIPING PASSES THROUGH FIRE AND /OR SMOKE RATED PAR 77TIONS (REFER TO
ARCHITECTURAL DRAWINGS), PROVIDE SLEEVES AND APPROPR /A TEL Y RA TED SEALING
MATERIALS AS REQUIRED TO MAINTAIN FIRE RATED ENCLOSURE.
SHEET METAL
ALL NEW DUCTWORK SHALL BE GALVANIZED SHEET STEEL CONFORMING TO
ANSI /ASTM A 527, LOCKFORM/NG QUALITY AND ANSI /ASTM A 525, G90 ZINC COATING.
DUCT SEALANT.- NONHARDEN/NG, NONMIGRA TING MASTIC OR LIQUID ELASTIC
SEALANT (TYPE APPLICABLE FOR FABRICA TION //NSTALLA T70N DETAIL) AS
COMPOUNDED AND RECOMMENDED BY MANUFACTURER SPECIFICALLY FOR SEALING
JOINTS AND SEAMS IN DUCTWORK.
DUCT CEMENT- NONHARDEN/NG MIGRATING MASTIC OR LIQUID NEOPRENE BASED
CEMENT (TYPE APPLICABLE FOR FABRICA 770NIINSTALLA 77ON DETAIL) AS
COMPOUNDED AND RECOMMENDED BY MANUFACTURER SPECIFICALLY FOR
CEMEN77NG FITTING COMPONENTS, OR LONGITUDINAL SEAMS IN DUCTWORK.
FABRICATE DUCT TRANS/BONS TO MA TCH ADJOINING EQUIPMENT AND TO COMPLY
WITH DUCT REQUIREMENTS AS APPLICABLE TO FITTINGS. LIMIT ANGULAR TAPERS TO
30 DEGREES FOR EXPANDING TAPERS.
INSTALL A BALANCE DAMPER AT EACH DUCT BRANCH TAKE —OFF ON EACH DUCT
SYSTEM. PROVIDE LOCKING QUADRANT, EXTENDED AS NECESSARY FOR DUCT
INSULATION.
CONSTRUCT AND SUPPORT ALL NEW DUCTWORK IN ACCORDANCE WITH SMACNA
STANDARDS FOR LOW PRESSURE DUCTWORK.
INSULA TED FLEXIBLE DUCT SHALL BE USED AT THE FINAL CONNECTION TO
DIFFUSERS FLEXIBLE DUCT SHALL BE LIMITED TO A MAXIMUM LENGTH
OF 5' -0" AND A TOTAL OF 90 DEGREES IN TURNS (AT EACH LOCATION).
—.0
TEMPERATURE CONTROLS
RTU -1
DURING OCCUPIED CYCLE, THE SUPPLY AIR FAN SHALL BE ON AND THE MINIMUM OUTSIDE
AIR DAMPER SHALL BE OPEN. STAGES OF COOLING SHALL BE ENERGIZED AND HOT GAS BYPASS
VALVE SHALL MODULA TE TO MAINTAIN 55' DISCHARGE AIR TEMPERA TURF.
DURING UNOCCUPIED CYCLE, THE SUPPLY AIR FAN SHALL BE OFF AND THE MINIMUM OUTSIDE
AIR DAMPER SHALL BE CLOSED. IF THE TEMPERATURE AT THE NIGHT SETBACK THERMOSTAT
DROPS TO NIGHT SETBACK TEMPERATURE OF 60; THE SUPPLY AIR FAN SHALL START,
ANO ENABLE THE DUCT COILS TO MAINTAIN NIGHT SETBACK TEMPERATURE.
FAN COIL UNITS
FAN COIL UNITS SHALL BE CONTROLLED BY EXISI RIG, RELOCATED WALL MOUNTED THERMOSTATS.
WHERE AN OUTSIDE AIR DUCT ANO MOTORIZED DAMPER ARE INDICATED, THE DAMPER SHALL OPEN
WHEN THE FAN OPERA TES
EXHAUST FANS
EXHAUST FAN EF -1 SHALL OPERA IF DURING OCCUPIED CYCLE OF RTU -1.
EXHAUST FAN EF -2 SHALL OPERATE WHEN THE TOILET ROOM LIGHT IS ON. CONTROL AND
POWER WIRING FOR THIS FAN SHALL BE BY THE E. C.
DUCT COILS
ELECTRIC DUCT COILS SHALL BE ENERGIZED BY FIELD MOUNTED WALL THERMOSTATS PROVIDED
BY THE MANUFACTURER.
HUMIDIFIERS
ELECTRONIC HUMIDIFIERS SHALL BE ENERGIZED BY FIELD MOUNTEO WALL HUM /D/STATS PROVIDED
BY THE MANUFACTURER.
SY57EM BALANCE
AIR BALANCE SHALL BE COMPLE7ED BY A NEEB CERTIFIED CONTRACTOR.
PROVIDE A TYPED WRIT7EN REPORT /NDICA77NG THE COMPLETE READ —OUT OF EACH
AIR INLET AND OUTLET, AND FAN PERFORMANCE. SUBMIT FINAL
REPORT TO 774E ENGINEER FOR REVIEW.
P/ TCH DOWN
TOWARD D° A'"'
CLEAN OUT-1
DRAIN LINE SHALL BE AT LEAST
774E SAME SIZE AS THE NIPPLE
ON THE DRAIN PAN ---\
CLEAN OUT
I " FL OOR
TLxj DRAIN
�—DRAIN PAN OF
A v AHU OR FCU
2" MIN. FOR AHU S,
— —
I" MIN. FOR FCU S
Q,
UNI T TYPE A B
DRAW THROUGH P + I" P
P =STA 77C PRESSURE AT DRAIN PAN
CONDENSATE DRAIN TRAP DETAI
NO SCALE
FLEXIBLE S7FAM SUPPL Y
HOSE AND COND. RETURN
HOSE PROVIDED BY HUMIDIFIER
MANUFACTURER, INSTALLED
" T"IBUTION
'E
HUMI1
NO SCALE
GRAIN LINE FROM
HUMIDIFIER
ER PIPING DETAIL
PACKAGED ROOFTOP UNIT SCHEDULE
EXAMPLE SUPPLY FAN DATA COOLING COIL DATA CONDENSER ELECTRICAL DATA
MARK MANUFACTURER CFM ESP FAN MOTOR MIN_ TOTAL SENS_ EAT LAT AMB. NO. OF
MODEL NO. RPM H.P_ O.A_ MBH MBH WB /DB WB /DB TEMP_ FANS VOLTS PH. FLA MFS
R TU -1 AAON RK -13 -3 3900 3.0 1919 5 630 151.8 123 4 830164.9 539151.5 95 2 460 3 33 40
REMARKS:
1O
UNIT SHALL BE DOUBLE WALL CONSTRUCTION, HAVE DUAL REFRIGERATION CIRCUITS, HAVE HOT GAS BYPASS ON ONE CIRCUIT,
HA VE LOW AMBIENT CONTROLS
TO OPERA TE TO 0 ; HA VE FUSED DISCONNECT, HA VE MO TOR /ZED OU TS /DE A/R DAMPER, HA VE 309 PREF /L TERS, AND HA VE 907 FINAL F/L TERS. PROVIDE 30"
TALL ROOF CURB, EQUIPPED WI TH FINAL FILTER HOLDING FRAME TO CONTAIN THE FINAL F/L TER.
J
REMARKS
DUCT COIL SCHEDULE
MARK
EXAMPLE
MANUFACTURER
MODEL NO,
AIR SIDE DATA
CAP'
K.W.
STAGES
ELECTRICAL
SIZE
REMARKS
CFM
EAT
LAT
VOLTS
PHASE
WIDTH
HEIGHT
DC -1
/NDEECO TYPE QUA
500
55
85
5.0
2
480
3
12
10
1
DC -2
/NDEECO TYPE QUA
500
55
85
5.0
2
480
3
12
10
1
DC -3
/NOEECO TYPE QUA
1645
55
85
175
4
480
3
24
12
DC -4
/NDEECO TYPE QUA
1255
55
80
10.0
2
480
3
18
12
DC -5
/NDEECO TYPE QUA
210
55
80
1.7
1
480
3
8
8
DC -6
/NDEECO TYPE QUA
135
55
95
1.8
1
480
3
8
8
DC-7
/NDEECO TYPE QUA
350
55
95
5.0
2 1
480
3
10
8
REMARKS:
O1 PROVIDE WITH CONTROL OPTION "G" WALL MOUNTED ROOM THERMOSTAT, AND MERCURY CONTACTORS.
FAN SCHEDULE
MARK
EXAMPLE
MANUFACTURER
MODEL NO,
LOCATION
SERVICE
CFM
T.S.P.
RPM
DRIVE
TYPE
MOTOR DATA
REMARKS
HP /WATTS
RPM
VOLTS
PHASE
EF -1
GREENHECK GB -80
ROOF
EXHAUST
375
0.5
1230
BEL T
114 HP
1230
115
1
2
EF -2
GREENHECK SP -218
CE /LING
EXHAUST
150
0.25
1400
DIRECT
113 WATTS
1750
115
1
O
REMARKS
Ol PROVIDE WITH CURB MOUNTED ROOF VENT MODEL GRS -10.
2O PROVIDE WITH ROOF CURB, BACKDRAFT DAMPER, AND DISCONNECT SWITCH.
HUMIDIFIER SCHEDULE
MARK
EXAMPLE
MANUFACTURER
MODEL NO_
CFM
DUCT SIZE
CAPACITY
LBS /HR
STEAM
PSIG
STEAM
DISTRIBUTOR
ELECTRICAL
REMARKS
K. W.
VOLTAGE
PHASE
H -1
NORTEC NHB -010
1000
14 x 12
11
0
ASD -12
38
480
1
1
H -2
NOR7EC NHB -005
520
12 x 10'
5
0
ASD -12
1.9
120
1
Ol
REMARKS:
Ol PROVIDE WITH WALL MOUNTED ON /OFF HUMIISTAT, DUCT MOUNTED AIR FLOW SWITCH, AND DUCT MOUNTED HIGH LIMIT HUMIDISTAT.
�O SST 4
�\ 'F.G
No. °
13815
s, STATE
an1►mimn , / /�'��
A PROFESSIONAL CORPORATION
9245 N. Meridian Street, Suite 105
Indianapolis, Indiana 46260.1812
317.848.5045 PH 317.848.2765 FX
St. ViBent Carmel Hospital
13600 N. Maridlan SYrset
P.O. Boz 1903
Carmel Ind/am 48082
MO TOR cc DOME
CARMEL
INTEGRAL WOOD NAILER = MEDICAL
ROUTE ROOF MEMBRANE UP TO BIRDSCREEN BUILDING
UNDER COUNTER FLASHING AND
SECURE TO W000 NAILER AT No. 1
TOP OF CURB
SET IN SEALANT
20' 30' ROOF INSULA 77ON
GYP. BOARD SUITE 315/355
Carmel, Indiana
4 "x4 X3/16" ANGLE
ALL AROUND
20' 30' MECHANICAL
NOTE,
BACKDRAFT DAMPER J SPECIFICATIONS,
THE / TFD ANGLES OF SCHEDULES & DETAILS EXPANSION NSION & CONTRACTION ARE
THE RECOMMENDED MAXIMUMS
CONTROL PANEL
SCALE 1/8" - 1' -0" CLIENT NO.
ROOF OPENING
DUCT TRANSITION TO REHEAT COIL DATE 9 -29 -97 COMMISSION 87055
3 NO SCALE ROOF MOUNTED DOME EXHAUST
4 NO SCALE COORD DWS
DRAWN DWS \TR M3
APPROVED GLP