EW
EXISTING
MB
W4TOILET
N :R0
0 - ___ k 0 _:OMS
MEN'S 2
TOILET
RM 104 O
3
EXISTING
LAV
O /
EXISTING " io °
FD \ �\
EXISTING y
HWC (o)
EXISTING
LAV
EXISTING
FD
WOMEN'S
HDF EXISTING
TOILET
��L HWC RM 105
O
1 I ENLARGED PLUMBING PLAN
P1 J SCALE: 3/8" = V -O"
MOP
HANGER
co
It
in
cn
EYEWASH (EW)
;RACKET
-ING MOP BASIN (M
I
— FINISHED FLR.
WALL BASE
2 I ELEVATION AT MOP BASIN
P1 j SCALE: NOT TO SCALE
(SIMILAR)
KEY NOTES:
OROUTE NEW SANITARY IN WALL AND DROP TO 3" (MINIMUM) SANITARY AT WATER CLOSETS TO
MINIMIZE WORK BELOW THE SLAB. EXTEND NEW 1 -1/2" VENT PIPING UP AND CONNECT TO
NEAREST EXISTING VENT OF SAME SIZE OR LARGER. FIELD VERIFY EXACT SIZE, LOCATION,
PRESSURE, ETC. OF EXISTING PIPING PRIOR TO ROUGHING IN OR INSTALLING NEW PIPING.
0 EXISTING WATER HEATER TO REMAIN. CONTRACTOR SHALL VERIFY EXACT LOCATION &
CONDITION OF WATER HEATER AND CONNECTED PIPING PRIOR TO SUBMITTING BID.
CONTRACTOR SHALL DRAIN, CLEAN AND RESTORE TO "LIKE NEW" CONDITION OR CONTACT
OWNER'S REPRESENTATIVE IMMEDIATELY IF REPLACEMENT IS RECOMMENDED. CONTRACTOR
SHALL VERIFY PRESENCE AND CONDITION OF EXISTING T &P VALVE AND REPLACE IF NOT IN
PROPER WORKING ORDER. ROUTE DRAIN PIPING INTO MOP BASIN AS REQUIRED.
OEXISTING FIXTURE TO REMAIN AND BE REUSED. CONTRACTOR SHALL CLEAN AND REFURBISH
TO "LIKE NEW" CONDITION AND ENSURE ALL DRAINS AND PIPING IS FREE - FLOWING, OR CONTACT
OWNER'S REPRESENTATIVE IMMEDIATELY IF REPLACEMENT IS RECOMMENDED.
4O EXTEND NEW 1/2" COLD WATER TO DRINKING FOUNTAIN FROM NEAREST EXISTING 3/4" OR
LARGER COLD WATER PIPING. FIELD VERIFY EXACT SIZE, LOCATION, PRESSURE, ETC. OF
EXISTING PIPING PRIOR TO ROUGHING IN OR INSTALLING NEW PIPING.
5O INSTALL NEW EYEWASH AS INDICATED IN PLAN AND DETAILS, THIS SHEET. VERIFY PRIOR TO
PLACING FIXTURE ORDERS THAT NEW EYEWASH IS COMPATIBLE WITH EXISTING MOP BASIN
FAUCET. IF IT IS NOT, PROVIDE NEW FAUCET PER PLUMBING FIXTURE SCHEDULE, THIS SHEET.
6O INSTALL MOP BASIN ACCESSORIES (SEE MB ON FIXTURE SCHEDULE AND DETAIL #2 /P1), IF NOT
ALREADY EXISTING.
PLUMBING FIXTURE SCHEDULE
CU
CHECKED:
g4 v S. p
DATE:
08/
PIPING REQUIREMENTS
0
APPROVED
MARK
DESCRIPTION
MANUFACTURER
CATALOG NO.
ACCESSORIES
REMARKS
MANUFACTURERS
WASTE
VENT
SUPPLY
HANDICAP ACCESSIBLE
HWC
WATER CLOSET
NOT USED
(TANK TYPE)
HANDICAP ACCESSIBLE
LAV
LAVATORY
NOT USED
(WALL MOUNTED)
HDF
BARRIER -FREE TWO
STATION HI /LO
ELKAY
EZSTL8LC
ACCESSORY APRON #LKAPREZL ON UPPER UNIT
1 -1/2"
1 -1/2"
1/2"
UPPER HEIGHT 40" A.F.F.
LOWER HEIGHT 33" A.F.F.
HALSEY TAYLOR
(THREE SIDES OF CONTROL)
(ADA COMPLIANT WHEN MOUNTED ON EXPOSED WALL)
ADA COMPLY
DRINKING FOUNTAIN
FD
FLOOR DRAIN I
NOT USED
CO
CLEANOUT (INTERIOR)
NOT USED
TMV
THERMAL MIXING VALVE
NOT USED
TP
TRAP PRIMER
NOT USED
WHA
WATER HAMMER
NOT USED
ARRESTER
FIAT #832 -AA HOSE /BRACKET & #889 -CC -24 HANGER
3"
2"
3/4"
WITH VACUUM BREAKER
HAWS, ZURN
MB
MOP BASIN
EXISTING TO REMAIN
SPEAKMAN SC- 5811 -RCP FAUCET
EW
EYE WASH
SPEAKMAN
SEF -9000
SEF -9000 EYE WASH
-
-
1/2"
-
-
BFP
BACKFLOW PREVENTOR
NOT USED
WH
WATER HEATER
NOT USED
NOTE:
1. COORDINATE ROUGH -IN OF ALL PLUMBING FIXTURES WITH ARCHITECTURAL DRAWINGS. 3. FOR HANDICAPPED - ACCESSIBLE WATER CLOSETS, FURNISH AND INSTALL WITH FLUSH HANDLE ON THE
WIDE SIDE OF THE RESTROOM.
2. SINKS AND LAVATORIES FOR HANDICAPPED ACCESS SHALL BE INSTALLED WITH OFFSET TAILPIECES. ALL SINK
AND LAVATORY DRAIN AND WATER LINES SHALL BE INSULATED WITH PROTECTIVE DEVICES EQUAL TO "McGUIRE"
#PW 2150 WC WHITE MOLDED CLOSED CELL VINYL, OR "TRUEBRO" #103W, WHITE MOLDED VINYL.
PIPING LEGEND
— — — EX GAS — — — EXISTING GAS PIPING
GAS NEW GAS PIPING
—�— W WATER (BELOW GRADE)
-- HW — — HOT WATER
CW —
S
S —f—
O
COLD WATER
WASTE
WASTE (BELOW GRADE)
VENT
WATER HAMMER ARRESTER
FLOOR DRAIN, SEE SCHEDULE
GENERAL PLUMBING NOTES:
1. DRAWING IS DIAGRAMMATIC AND IS NOT TO BE SCALED. REFER TO ARCHITECTURAL PLANS FOR
DIMENSIONS.
2. ALL PLUMBING WORK IS TO BE DONE IN ACCORDANCE WITH THE APPLICABLE CODE(S) NOTED ON
THE COVER SHEET.
3. PIPING MATERIAL (UNDERGROUND & ABOVE GROUND WATER, DRAIN, WASTE & VENT) SHALL BE
PER APPLICABLE CODE NOTED ON THE COVER SHEET.
4. VALVES ON WATER LINES SHALL BE BRONZE BALL VALVES. DO NOT SUBSTITUTE GATE OR GLOBE
VALVES. VALVES SHALL BE THE SAME SIZE AS THEIR INLET PIPING.
5. ALL PLUMBING FIXTURES ARE TO BE FURNISHED COMPLETE WITH NECESSARY STOPS, TRAPS,
TAILPIECES, TRIM, ETC.
6. THE CONTRACTOR SHALL COOPERATE AND COORDINATE WITH ALL OTHER CONTRACTORS AND
SUBCONTRACTORS IN LAYING OUT AND INSTALLINGT HIS WORK.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE AND FUNCTIONAL
SYSTEM IN ACCORDANCE WITH THE INTENT OF THE PLANS, WHETHER OR NOT EVERY ELEMENT
THEREOF IS SPECIFICALLY CALLED OUT.
8. DO NOT INSTALL CAPPED AIR CHAMBERS AT FIXTURES. INSTALL WATER HAMMER ARRESTORS AS
CALLED FOR ON PLAN. ARRESTORS ARE TO BE RATED FOR INSTALLATION IN CONCEALED
LOCATIONS.
9. ALL HOT AND COLD WATER SUPPLY PIPING CONNECTIONS TO FIXTURES SHALL BE 1/2" UNLESS
NOTED OTHERWISE.
10. PLUMBING PIPING SHALL NOT BE INSTALLED ABOVE ELECTRICAL PANELS. PROVIDE REQUIRED
CLEARANCES PER "N.E.C. ". COORDINATE ELECTRICAL PANELS LOCATIONS WITH THE ELECTRICAL
CONTRACTOR.
11. INSTALL PIPE INSULATION ON ALL DOMESTIC WATERLINES ABOVE FINISHED FLOOR
INSULATIONTHERMAL CONDUCTIVITY 0.25 BTU- IN. /HR- SF - - °F.
12. CONTRACTOR SHALL COORDINATE WITH ALL STATE AND LOCAL BUILDING REGULATION AGENCIES
AND UTILITY COMPANY(S) IN THE PROCUREMENT OF AND PAYMENT OF ALL PERMITS, LICENSES,
FEES AND CHARGES REQUIRED FOR THE PERFORMANCE OF THE WORK.
13. PROVIDE CHROME ESCUTCHEON COVERPLATES AT ALL PIPE PENETRATIONS OF FINISHED WALL
SURFACES.
14. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ROUTE ALL WATER PIPING AROUND SPACES WITH
TEMPERATURES BELOW FREEZING (i.e. ATTICS, CHASES, EXTERIOR WALLS, ETC.) IF FREEZING OF
ANY WATER PIPING OCCURS IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR THE
PIPING THRU A NON - FREEZING SPACE TO THE FIXTURE / APPLIANCE ORIGINALLY SERVED BY THE
FROZEN PIPING.
15. ALL CAULKING ON BUILDING PENETRATIONS SHALL BE ELASTOMERIC POLYURETHANE (NO
EXCEPTIONS) EQUIVALENT TO "VULKEM" 116. ANY CONTRACTOR WHO USED SILICONE OR ANY
OTHER CAULKING WILL BE REQUIRED TO REMOVE AND REPLACE WITH ELASTOMERIC
POLYURETHANE AT HIS OWN EXPENSE.
16. CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FROM THE DATE OF ACCEPTANCE BY THE
OWNER ON ALL WORK PERFORMED.
17. PLUMBING SUB - CONTRACTOR SHALL INFORM THE ELECTRICAL SUB - CONTRACTOR OF THE
VOLTAGE AND POWER REQUIREMENTS OF ALL PLUMBING EQUIPMENT TO BE INSTALLED.
18. INSTALL ACCESS PANELS OR DOORS WHERE EQUIPMENT AND /OR VALVES ARE INSTALLED IN
CONCEALED LOCATIONS.
19. ALL WATER HEATERS AND HOT WATER STORAGE TANKS SHALL HAVE A DRAIN VALVE INSTALLED
AT THE BOTTOM OF THE TANK AS REQUIRED BY CODE.
r DISTRIBU7
O OWNER REVIE1
' PERMIT /BID
Jeffrey S. Ti
License #110,
Exp. Date: 7/:
Professional of I
SHEETS BEARING THIS SEAL A
RESPONSIBILITY FOR ALL OTHI
OR INSTRUMENTS ARE DISCLAI
O
w O
W r-
(� O CN
Z w ( N
o O
�-
�Z!! _ LJ;�
o�J C
Of O U) a
IM
N
F
a
CL
0
a
0
DRAWN:
CU
CHECKED:
g4 v S. p
DATE:
08/
JOB NO.: 31
0
G+'9
Jeffrey S. Ti
License #110,
Exp. Date: 7/:
Professional of I
SHEETS BEARING THIS SEAL A
RESPONSIBILITY FOR ALL OTHI
OR INSTRUMENTS ARE DISCLAI
O
w O
W r-
(� O CN
Z w ( N
o O
�-
�Z!! _ LJ;�
o�J C
Of O U) a
IM
N
F
a
CL
0
a
0
DRAWN:
CU
CHECKED:
JS'
DATE:
08/
JOB NO.: 31
SHEET:
1
c