HomeMy WebLinkAboutplan-plans-21_M0.1 Mech Symbols & Abbrv.PDFABBREVIATIONS AND TERMS
� DIAMETER, PHASE ET EXPANSION TANK OAT OUTSIDE AIR TEMPERATURE ('F)
'F DEGREES FAHRENHEIT EW EMERGENCY EYEWASH OBD OPPOSED BLADE DAMPER
A/C AIR CONDITIONING EWC ELECTRIC WATER COOLER OD OUTSIDE DIAMETER, OVERFLOW DRAIN
ACC AIR COOLED CONDENSER EWT ENTERING WATER TEMPERATURE ('F) OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
ACCU AIR COOLED CONDENSING UNIT EXH EXHAUST OSD OPEN SITE DRAIN
AD AREA DRAIN, ACCESS DOOR EXIST EXISTING OZ OUNCE
AFF ABOVE FINISHED FLOOR F FURNACE P PUMP
AFMS AIR FLOW MEASURING STATION F&T FLOAT AND THERMOSTATIC STEAM TRAP PBD PARALLEL BLADE DAMPER
AGA AMERICAN GAS ASSOCIATION FCO FLOOR CLEANOUT PC PLUMBING CONTRACTOR
AHU AIR HANDLING UNIT FCU FAN COIL UNIT PD PRESSURE DROP
AL ACOUSTICALLY LINED, ALUMINUM Fp FLOOR DRAIN, FIRE DAMPER PE PNEUMATIC ELECTRIC
AMB AMBIENT FDC FIRE DEPARTMENT CONNECTION PH PHASE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE FDTN FOUNDATION PIV POST INDICATOR VALVE
AO ANALOG OUTPUT FE FIRE EXTINGUISHER PPM PARTS PER MILLION
AP ACID PROOF, ACCESS PANEL FHC FIRE HOSE CABINET PRV PRESSURE REDUCING VALVE
APD AIR PRESSURE DROP (IN. WC.) FLR FLOOR PSI POUNDS PER SQUARE INCH
ARCH ARCHITECT FM FACTORY MUTUAL PSIA POUNDS PER SQUARE INCH ABSOLUTE
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE FOV FUEL OIL VENT PSIG POUNDS PER SQUARE INCH GAUGE
ARV AIR RELIEF VALVE FPM FEET PER MINUTE PTAC PACKAGED TERMINAL AIR CONDITIONER
AS AIR SEPARATOR FPVAV FAN POWERED VAV UNIT PVC POLYVINYL CHLORIDE
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING FS FLOOR SINK R REGISTER
AND AIR CONDITIONING ENGINEERS FSC FIRE SUPPRESSION CONTRACTOR R12 REFRIGERANT (12, 22, ETC.)
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS FSD COMBINATION FIRE/SMOKE DAMPER RA RETURN AIR
ASPE AMERICAN SOCIEfY OF PLUMBING ENGINEERS FT FOOT, FEET RADN RADIATION
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS FTG FOOTING RAT RETURN AIR TEMPERATURE ('F)
ATM ATMOSPHERE FTR FINNED TUBE RADIATION RCP REINFORCED CONCRETE PIPE
AUTO AUTOMATIC G NATURAL GAS RD ROOF DRAIN
AVG AVERAGE GA GAGE OR GAUGE REV REVOLUTIONS
AVS ACID VENT STACK GAL GALLON RF REfURN FAN
AW ACID WASTE GC GENERAL CONTRACTOR RG REfURN GRILLE
AWWA AMERICAN WATER WORKS ASSOCIATION GIV GRAVITY INTAKE VENTILATOR RH RELATIVE HUMIDITY, RODDING HOLE
BD BUTTERFLY DAMPER GPD GALLONS PER DAY RM ROOM
BDD BACKDRAFT DAMPER GPH GALLONS PER HOUR RP RADIANT PANEL
BE BOTTOM ELEVATION GPM GALLONS PER MINUTE RPM REVOLUTIONS PER MINUTE
BF BARRIER FREE GR GRILLE, GRAINS RPS REVOLUTIONS PER SECOND
BFC BELOW FINISHED CEILING GRV GRAVITY RELIEF VENTILATOR RTU ROOF TOP UNIT
BHP BRAKE HORSEPOWER GT GREASE TRAP RV RELIEF VALVE, ROOF VENT
BLDG BUILDING HB HOSE BIBB SA SUPPLY AIR
BOD BOTTOM OF DUCT HD HEAD (FT.) SAN SANITARY
BOP BOTTOM OF PIPING Hg MERCURY SD SUPPLY DIFFUSER, SMOKE DAMPER
BSMT BASEMENT HHWP HEATING HOT WATER PUMP SEER SEASONAL ENERGY EFFICIENCY RATIO
BT BATHTUB HO HUB OUTLET SF SQUARE FOOT, SUPPLY FAN, SAFETY FACTOR
BTM BOTTOM HORIZ HORIZONTAL SG SUPPLY GRILLE
BtuH BRITISH THERMAL UNIT PER HOUR HP HORSEPOWER, HEAT PUMP SH SHOWER
CA COMPRESSED AIR HR HOUR(S) SK SINK
CAV CONSTANT AIR VOLUME HRTU HEATING ONLY ROOFTOP UNIT SMACNA SHEET METAL AND AIR CONDITIONING
CB CATCH BASIN HX HEAT EXCHANGER CONTRACTORS NATIONAL ASSOCIATION
CCW COUNTERCLOCKWISE Hz HERTZ SP STATIC PRESSURE
CD CONDENSATE DRAIN IB INVERTED BUCKET STEAM TRAP SPEC SPECIFICATION
CO2 CARBON DIOXIDE ID INSIDE DIAMETER SQ SQUARE
CF CEILING FAN IE INVERT ELEVATION SR SUPPLY REGISTER
CFM CUBIC FEET PER MINUTE IN INCH, INCHES SRV SAFETY RELIEF VALVE
CH CHILLER INT INTERIOR SS SERVICE SINK, STAINLESS STEEL
CHWP CHILLED WATER PUMP INV INVERT STD STANDARD
CI CAST IRON IPS INTERNATIONAL PIPE STANDARD SV STEAM VENT
CMP CORRUGATED METAL PIPE IW INDIRECT WASTE TCC TEMPERATURE CONTROL CONTRACTOR
CO CLEANOUT K KELVIN TCP TEMPERATURE CONTROL PANEL
COMPR COMPRESSOR KEC KITCHEN EQUIPMENT CONTRACTOR TD TEMPERATURE DIFFERENCE
COND CONDENSER kW KILOWATT TE TOP ELEVATION
CONV CONVECTOR LAB LABORATORY TEMP TEMPERATURE
CP CONDENSATE PUMP LAT LEAVING AIR TEMPERATURE ('F) TF TRANSFER FAN
CPVC CHLORINATED POLYVINYL CHLORIDE LAV LAVATORY TG TRANSFER GRILLE
CT COOLING TOWER LBS POUNDS TMV THERMOSTATIC MIXING VALVE
CU CONDENSING UNIT LD LINEAR DIFFUSER TONS TONS OF REFRIGERATION
CUH CABINET UNIT HEATER LP LIQUID PETROLEUM TP TRAP PRIMER
CUV CLASSROOM UNIT VENTILATOR LTG LIGHTING TRANS TRANSITION
CV CONTROL VALVE LWT LEAVING WATER TEMPERATURE ('F) TS TAMPER SWITCH
CW CLOCKWISE MA MIXED AIR TSP TOTAL STATIC PRESSURE (IN. WC.)
CWP CONDENSER WATER PUMP MAT MIXED AIR TEMPERATURE ('F) TXV THERMAL EXPANSION VALVE
dB DECIBEL MAX MAXIMUM TYP TYPICAL
DB DRY BULB MB MOP BASIN UCD UNDERCUT DOOR
DF DRINKING FOUNTAIN MBH THOUSAND Btu PER HOUR UH UNIT HEATER
DG DOOR GRILLE MC MECHANICAL CONTRACTOR UL UNDERWRITERS LABORATORIES
DH DUCT HEATER MCA MINIMUM CIRCUIT AMPS UON UNLESS OTHERWISE NOTED
DI DIGITAL INPUT MCC MOTOR CONTROL CENTER UR URINAL
DIA DIAMETER MD MOTORIZED DAMPER US UP STREAM
DIFF DIFFUSER MFR MANUFACTURER UV UNIT VENTILATOR
DN DOWN MH MANHOLE V VOLTS, VENT
DO DIGITAL OUTPUT MIN MINIMUM VAC VACUUM
DS DOWNSPOUT, DOWN STREAM MISC MISCELLANEOUS VAV VARIABLE AIR VOLUME
DW DISTILLED WATER MS MOP SINK VB VACUUM BREAKER
DWG DRAWING MTD MOUNTED VD VOLUME DAMPER
DWH DOMESTIC WATER HEATER MV MANUAL VENT VEL VELOCITY
DWV DRAIN, WASTE & VENT N NITROGEN VERT VERTICAL
DX DIRECT EXPANSION NA NOT APPLICABLE VF VENTILATION FAN
EA EXHAUST AIR NC NOISE CRITERIA, NORMALLY CLOSED VFD VARIABLE FREQUENCY DRIVE
EAT ENTERING AIR TEMPERATURE ('F) NEC NATIONAL ELECTRIC CODE VTR VENT THROUGH ROOF
EC ELECTRICAL CONTRACTOR NFC NATIONAL FIRE CODE VUV VERTICAL UNIT VENTILATOR
ECO EXTERIOR CLEANOUT NFPA NATIONAL FIRE PROTECTION ASSOCIATION W WASTE, WATT
EDR EQUIVALENT DIRECT RADIATION NFWH NON-FREEZE WALL HYDRANT WC WATER COLUMN
EER ENERGY EFFICIENCY RATIO NIC NOT IN CONTRACT WB WET BULB
EF EXHAUST FAN NO NORMALLY OPEN, NITROUS OXIDE WC WATER CLOSEf
EFF EFFICIENCY NOM NOMINAL WCO WALL CLEANOUT
EG EXHAUST GRILLE NPW NON-POTABLE WATER WH WALL HYDRANT
EL ELEVATION NTS NOT TO SCALE WPD WATER PRESSURE DROP (FT. HD.)
EOM END OF MAIN DRIP 0 OXYGEN WSHP WATER SOURCE HEAT PUMP
ES EMERGENCY SHOWER OA OUTSIDE AIR YD YARD DRAIN
ESP EXTERNAL STATIC PRESSURE (IN. WG.) OAI OUTSIDE AIR INTAKE
PIPING LINESYMBOLS
HIGH PRESSURE STEAM (>61 PSIG) HPS STORM DRAIN ST
MEDIUM PRESSURE STEAM (16-60 PSIG) MPS FOOTING/FOUNDATION DRAIN FD
LOW PRESSURE STEAM (<15 PSIG) LPS SANITARY WASTE (W)
HIGH PRESSURE CONDENSATE --- HPC --- SANITARY GREASE SG
MEDIUM PRESSURE CONDENSATE --- MPC --- SANITARY FORCED MAIN FM
LOW PRESSURE CONDENSATE --- LPC --- SANITARY VENT (V)
BOILER BLOW DOWN BBD ACID WASTE AW
BOILER FEED BF ACID VENT AV
PUMPED CONDENSATE PC DRAIN D
VACUUM PUMP DISCHARGE VPD INDIRECT WASTE IW
HUMIDIFICATION H PUMP DISCHARGE PD
MAKE UP WATER MU DOMESTIC COLD WATER (CW) - - -
AIR RELIEF VENT ARV DOMESTIC HOT WATER SUPPLY (HW) -- -- --
HEAT RECLAIM PIPING HR DOMESTIC HOT WATER RETURN (HWR) --- --- ---
HEATING WATER SUPPLY HHS 140'F HOT WATER 140'F
HEATING WATER RETURN HHR 140'F HOT WATER RETURN 140'F
REFRIGERANT DISCHARGE RD NON-POTABLE WATER - NPW -
REFRIGERANT SUCTION RS DRINKING WATER SUPPLY DWS
REFRIGERANT LIQUID RL DRINKING WATER RETURN DWR
REFRIGERANT HOT GAS RHG SOFT WATER SW
BRINE SUPPLY BS CHLORINATED WATER CL
BRINE RETURN BR DISTILLED WATER DI
CONDENSER WATER SUPPLY CS DEIONIZED WATER DE
CONDENSER WATER RETURN CR FIRE SUPPRESSION F
CHILLED WATER SUPPLY CWS NATURAL GAS (WC OR PSIG) G
CHILLED WATER REfURN CWR GAS VENT GV
DUAL TEMPERATURE SUPPLY DTS LIQUID PETROLEUM LP
DUAL TEMPERATURE RETURN DTR MEDICAL COMPRESSED AIR (WC OR PSIG) MA
HEAT PUMP WATER SUPPLY HPWS MEDICAL VACUUM MV
HEAT PUMP WATER RETURN HPWR OXYGEN 0
GLYCOL HEATING SUPPLY GHS NITROGEN N
GLYCOL HEATING RETURN GHR NITROUS OXIDE NO
FUEL OIL SUPPLY FOS CARBON DIOXIDE CO2
FUEL OIL RETURN FOR WET VACUUM CLEANING WVC
FUEL OIL VENT FOV DRY VACUUM CLEANING DVC
CONDENSATE DRAIN CD COMPRESSED AIR (WC OR PSIG) A
CONTROL WIRING • • • • TEMPERED WATER SUPPLY TWS
TEMPERED WATER RETURN TWR
PIPING IDENTITY SYMBOLS
- ► � - FLOW DIRECTION ARROW, PITCH DIRECTION ARROW
O O PIPE RISE
� � - PIPE DROP
3 PIPE CAP
- - S PIPE CONTINUES (REFERENCE ELSEWHERE)
PIPE GUIDE
X - PIPE ANCHOR
� FLEXIBLE CONNECTOR
- - o - - EXPANSION COMPENSATOR
�L. : EXPANSION LOOP
DI °I - CONCENTRIC, ECCENTRIC FITTINGS
� I F � I I F UNION, FLANGED UNION
- - DQ - - GATE VALVE
I � f BALL VALVE
DoQ - GLOBE VALVE
I r BUTTERFLY VALVE
- - I�JI - - PLUG VALVE
1\I CHECK VALVE
��� ,. PRESSURE REDUCING VALVE
� � REDUCED PRESSURE BACKFLOW PREVENTER
- D �� 4 - DOUBLE CHECK BACKFLOW PREVENTER
♦ ♦
O DOUBLE DETECTOR CHECK VALVE ASSEMBLY
� " ANGLE VALVE
� RELIEF VALVE
� VALVE WITH OUTSIDE STEM & YOKE
D�Q PNEUMATIC TWO-WAY CONTROL VALVE
� - PNEUMATIC THREE-WAY CONTROL VALVE
. . p�Q :. . .. ELECTRIC TWO-WAY CONTROL VALVE
- - � . - - - ELECTRIC THREE-WAY CONTROL VALVE
,� , SOLENOID VALVE
� FLOW SWITCH
, Q , PRESSURE SWITCH
� AQUASTAT
I;I ORIFICE FLOW METER
�� - VENTURI FLOW METER
[�] TURBINE FLOW METER
- - � - - CALIBRATED BALANCE VALVE
� AUTOMATIC FLOW CONTROL VALVE
I�I - STRAINER
� STRAINER WITH CAPPED BLOWDOWN
� MANUAL AIR VENT
_ _ Q _ _ AUTOMATIC AIR VENT
`� ,. VACUUM BREAKER
, Y , TEMPERATURE/PRESSURE TAP
Q THERMOMETER
_ _ Q _ _ PRESSURE GAUGE
�F&T - STEAM TRAP WITH DESIGNATION
0 o REFRIGERATION SIGHT GLASS
- - O - - AIR FILTER/DRYER
� REFRIGERATION THERMAL EXPANSION VALVE
� - INLINE PUMP
� DIFFERENTIAL PRESSURE TRANSMITTER
� WHA-A WATER HAMMER ARRESTER WITH SCHEDULE TYPE
�O FD P-TRAP AND RISER
� 2�FD-1 FLOOR DRAIN WITH SIZE & SCHEDULE TYPE
�� CO END OF PIPE CLEANOUT
O FCO FLOOR CLEANOUT
T W�� WALL CLEANOUT
Q ECO EXTERIOR CLEANOUT OR RODDING HOLE
�TMV-1 THERMOSTATIC MIXING VALVE WITH SCHEDULE TYPE
--� HB-1 --� WH-1 HOSE BIBB, WALL HYDRANT WITH SCHEDULE TYPE
101 . WATER METER
I M�I. GAS METER
O4"RD O 4"OFD ROOF DRAIN, OVERFLOW DRAIN WITH SIZE
- - � - - POST INDICATOR VALVE
� FIRE DEPARTMENT CONNECTION
VALVE TAMPER SWITCH
O UPRIGHT SPRINKLER HEAD
- - O - - PENDANT SPRINKLER HEAD
� DRY PENDANT SPRINKLER HEAD
i!; CONCEALED SPRINKLER HEAD
� SIDEWALL SPRINKLER HEAD
HVAC I DENTITY SYM BOLS
RECTANGULAR DUCTWORK ROUND SPIRAL DUCTWORK FLAT OVAL DUCTWORK
24/12 DESIGNATION IN INCHES, FIRST 24� DESIGNATION IN INCHES 24/12$ DESIGNATION IN INCHES, FIRST
DIMENSION IS SIDE SHOWN DIMENSION IS SIDE SHOWN
RECTANGULAR SUPPLY AIR, ROUND SPIRAL SUPPLY AIR, FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK RISE OUTSIDE AIR DUCTWORK RISE OUTSIDE AIR DUCTWORK RISE
RECTANGULAR SUPPLY AIR, ♦ ROUND SPIRAL SUPPLY AIR, ^ FLAT OVAL SUPPLY AIR,
OUTSIDE AIR DUCTWORK DROP �� OUTSIDE AIR DUCTWORK DROP v OUTSIDE AIR DUCTWORK DROP
RECTANGULAR RETURN AIR, ROUND SPIRAL RETURN AIR, FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK TRANSFER AIR DUCTWORK TRANSFER AIR DUCTWORK
RISE RISE RISE
RECTANGULAR RETURN AIR, ROUND SPIRAL RETURN AIR, FLAT OVAL RETURN AIR,
TRANSFER AIR DUCTWORK �) TRANSFER AIR DUCTWORK � TRANSFER AIR DUCTWORK
DROP DROP DROP
RECTANGULAR EXHAUST AIR, ROUND SPIRAL EXHAUST AIR, FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK RISE RELIEF AIR DUCTWORK RISE RELIEF AIR DUCTWORK RISE
RECTANGULAR EXHAUST AIR, ROUND SPIRAL EXHAUST AIR, � FLAT OVAL EXHAUST AIR,
RELIEF AIR DUCTWORK DROP �� RELIEF AIR DUCTWORK DROP �� RELIEF AIR DUCTWORK DROP
DUCTWORK CONSTRUCTED OF DUCTWORK RISE IN DIRECTION DUCTWORK DROP IN
AL SS ALUMINUM, STAINLESS STEEL R� OF FLOW �� DIRECTION OF FLOW
20' 30' STANDARD DEGREE ANGLE RETURN AIR, EXHAUST AIR,
� TRANSITION IN DIRECTION OF � SUPPLY AIR, OUTSIDE AIR IN ,�j TRANSFER AIR, RELIEF AIR IN
FLOW DIRECTION OF FLOW DIRECTION OF FLOW
ECCENTRIC DUCT TRANSITION CONCENTRIC DUCT TRANSITION RECTANGULAR TO ROUND,
FLAT OVAL DUCT TRANSITION
i VOLUME DAMPER ��� ACCESS DOOR DUCTWORK CAP
AD
M FD SD
i MOTORIZED DAMPER WITH FIRE DAMPER WITH ACCESS SMOKE DAMPER WITH ACCESS
� ACCESS DOOR DOOR DOOR
BDD AMS FSD
i BACK DRAFT DAMPER WITH i AIRFLOW MEASURING STATION FIRE AND SMOKE DAMPER
� ACCESS DOOR � WITH ACCESS DOOR WITH ACCESS DOOR
D
i PRESSURE SENSOR WITH i TEMPERATURE SENSOR WITH i SMOKE DETECTOR WITH
� ACCESS DOOR � ACCESS DOOR � ACCESS DOOR
STATIC PRESSURE CHANGE IN FLEXIBLE DUCTWORK DUCTWORK LINING OR DOUBLE
3 INCHES CONNECTION ____ WALL DUCTWORK, DESIGNATION
SHOWN IS FREE AREA
45' BEVELED FITTING FOR RADIUS DUCTWORK ELBOW
RECTANGULAR TO (CENTERLINE RADIUS 1.5xW) sA SOUND ATTENUATOR
RECTANGULAR DUCTWORK
CONICAL FITTING FOR ROUND RADIUS DUCTWORK ELBOW
OR FLAT OVAL TO � WITH TURNING VANES MITERED DUCTWORK ELBOW
RECTANGULAR DUCTWORK
CONICAL FITTING FOR ROUND WYE RADIUS DUCTWORK •' MITERED DUCTWORK ELBOW
OR FLAT OVAL TO ROUND OR ELBOW WITH TURNING VANES
FLAT OVAL DUCTWORK
45' LATERAL FITfING FOR ROUND 45' RADIUS DUCTWORK ELBOW TRANSFER AIR ELBOW WITH
OR FLAT OVAL TO ROUND OR � DUCTWORK STUBS FOR
FLAT OVAL DUCTWORK (CENTERLINE RADIUS 1.5xW) SOUND ATTENUATION
SPIN-IN FITTING FOR ROUND CEILING PANEL SUPPLY AIR
TO RECTANGULAR DUCTWORK, � DIFFUSER � ROUND SUPPLY AIR DIFFUSER
LOW PRESSURE DUCTWORK
FLEXIBLE DUCTWORK RECTANGULAR SUPPLY AIR RETURN AIR, EXHAUST AIR,
CONNECTION TO DIFFUSER, � REGISTER � TRANSFER AIR REGISTER OR
MAXIMUM SIX FEET GRILLE
SIDEWALL SUPPLY AIR SIDEWALL RETURN AIR, � LINEAR SLOT SUPPLY AIR
�� REGISTER OR GRILLE �� EXHAUST AIR, TRANSFER AIR DIFFUSER
REGISTER OR GRILLE
THERMOSTAT WITH ASSOCIATED DOOR GRILLE OR UNDERCUT
0 EQUIPMENT DESIGNATION O TEMPERATURE SENSOR � DOOR
(TU-�2.34) (OPTIONAL) �y,
HUMIDISTAT WITH ASSOCIATED
� EQUIPMENT DESIGNATION CO3 CARBON DIOXIDE SENSOR CEILING DESTRATIFICATION FAN
(TU-�2.34) (OPTIONAL)
� TEMPERATURE CONTROL � VARIABLE FREQUENCY DRIVE ��� CENTRIFUGAL ROOF EXHAUST
PAN EL FAN
HYDRONIC REHEAT COIL WITH TERMINAL UNIT WITH ��
ACCESS DOOR HYDRONIC REHEAT COIL INLINE FAN
ELECTRIC REHEAT COIL WITH TERMINAL UNIT WITH ELECTRIC SERIES/PARALLEL FAN
ACCESS DOOR REHEAT COIL POWERED TERMINAL UNIT
� BASE MOUNTED PUMP UNIT VENTILATOR �� UNIT HEATER
� HEAT EXCHANGER � AIR SEPARATOR o FINNED TUBE RADIATION
REFERENCE SYM BOLS
SECTION INDICATOR: REFERENCE SECTION LOCATION THROUGH AN AREA FOR KEYNOTE INDICATOR: REFERENCE SHEET KEYNOTE LOCATION FOR ADDITIONAL
ADDITIONAL INFORMATION. INFORMATION.
SECTION LOCATION BEYOND AREA KEYNOTE INDICATORS
IN DRAWING MODULE EXTENSION NUMERIC CHARACTER
PLAN RELATES TO ITEM
X POINT LEADER X X X
X
AREA LEADER
SECTION LOCATION AT SUBSET SHEET LINE LEADER
DETAIL INDICATOR: REFERENCE DETAIL LOCATION FOR ADDITIONAL DRAWING BLOCK TITLE REFERENCE DRAWING MODULE LOCATION FOR
INFORMATION. INDICATOR: ADDITIONAL INFORMATION.
LARGE SCALE VIEW LOCATION DETAIL LOCATION IN DRAWING MODULE LOCATION
IN DRAWING MODULE DRAWING MODULE (IDENTIFYING LOWER LEFT OF MULTIPLE MODULES)
� � ^ `
� DRAWING BLOCK TITLE N
X X
X I X , � SCALE: 1/8° = 1'-0" 0 4' 8' 16'
♦_♦ `� �'
NUMERIC SCALE GRAPHIC SCALE NORTH ARROW
LARGE SCALE VIEW LOCATION DETAIL LOCATION AT
AT SUBSET SHEET SUBSET SHEET
MATCH LINE INDICATOR: REFERENCE SHEET LOCATION FOR ADDITIONAL REVISION INDICATOR: REFERENCE TITLE BLOCK LOCATION FOR ADDITIONAL
INFORMATION. INFORMATION.
FLOOR PLAN OVERLAP BEYOND AREA REVISION INDICATOR
� EXTENSION
SEE XXX X
� �� �
REFER TO ADDITIONAL PLAN
SHEET FOR CONTINUATION
- - - REVISION CLOUD
EQUIPMENT INDICATOR: REFERENCE SCHEDULE LOCATION FOR ADDITIONAL DIFFUSER, GRILLE, REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION. REGISTER INDICATOR: INFORMATION.
TU-XL. � NUMERIC CHARACTER RELATES TO ITEM MULTIPLIER
� (OPTIONAL) SCHEDULE TYPE
ALPHANUMERIC CHARACTER RELATES TO BUILDING LEVEL (OPTIONAL) X X
ALPHANUMERIC CHARACTER RELATES X
TO ASSOCIATED AIR HANDLER (OPTIONAL) AIRFLOW (CUBIC FEET PER MINUTE)
EQUIPMENT TYPE
-� � � �
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE BEST QUALITY
STANDARDS OF THE TRADE, AND SHALL CONFORM WITH ALL FEDERAL,
STATE, AND LOCAL CODES AND STANDARDS. THE SAME ARE MADE A
PART OF THESE CONTRACT DOCUMENTS AS IF REPEATED HEREIN.
B. CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND
DRAWINGS, AND BOTH ARE INTENDED TO BE COMPLEMENTARY.
ANYTHING APPEARING ON EITHER MUST BE EXECUTED THE SAME AS IF
SHOWN ON BOTH.
C. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS
REQUIRED TO COMPLETELY AND PROPERLY INSTALL ALL WORK REQUIRED
FOR THE PROJECT, AND SHALL EXAMINE THE SCOPE OF WORK OF
OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
D. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS
POSSIBLE, HOWEVER, SYSTEMS HAVE BEEN SHOWN DIAGRAMATICALLY AND
IN SOME CASES, ENLARGED FOR CLARITY. ANY OFFSETS, ADDITIONAL
FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE A COMPLETE
AND COORDINATED SYSTEM SHALL BE BORNE BY THE CONTRACTOR.
E. THE ENGINEERING DRAWINGS ARE OF EQUAL IMPORTANCE WITH THE
ARCHITECTURAL DRAWINGS IN DEFINING THE WORK OF THE CONTRACT
DOCUMENTS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO CHECK WITH THE ARCHITECTURAL DRAWINGS BEFORE THE
INSTALLATION OF ENGINEERING WORK. SHOULD THERE BE A
DISCREPANCY BETWEEN THE ARCHITECTURAL DRAWINGS AND THE
ENGINEERING DRAWINGS THAT WOULD CAUSE AN AWKWARD OR IMPROPER
INSTALLATION, THE DISCREPANCY SHALL BE BROUGHT TO THE
ARCHITECTS/ENGINEERS ATTENTION FOR CLARIFICATION PRIOR TO
INSTALLATION OF SAID WORK. ANY WORK INSTALLED IN CONFLICT WITH
THE ARCHITECTURAL DRAWINGS SHALL BE CORRECTED BY THE
CONTRACTOR AT HIS EXPENSE AND AT NO ADDITIONAL COST TO THE
OWNER OR ARCHITECT/ENGINEER.
F. DO NOT SCALE THE DRAWINGS. THE DRAWINGS ARE NOT NECESSARILY
TO SCALE. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE PRIOR TO THE START OF CONSTRUCTION.
IF DISCREPANCIES ARE FOUND, THE ARCHITECT/ENGINEER SHALL BE
NOTIFIED FOR CLARIFICATION BEFORE COMMENCING THE WORK. EXPLICIT
DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALE.
G. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO
BIDDING OR BEGINNING WORK ON THIS PROJECT.
H. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN.
WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE
DETERMINED, CONSULT THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH THE WORK.
�• ANY DETAILS, SYSTEMS AND/OR MATERIALS WHICH ARE PROPOSED TO
BE CHANGED MUST FIRST BE REVIEWED BY THE OWNER AND
ARCHITECT/ENGINEER PRIOR TO THE PREPARATION OF SHOP DRAWINGS.
�• REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND TEMPLATE
DRAWINGS FOR ALL MECHANICAL EQUIPMENT SUPPORTS, BOLT SETTING
TEMPLATES, ISOLATORS, SPRING ISOLATION, ETC., NOT SHOWN ON THE
DRAWINGS.
K. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LOCATION OF CEILING MOUNTED MATERIALS INCLUDING ALL DIFFUSERS,
GRILLES, AND REGISTERS.
L. CONTRACTOR SHALL CLOSE ALL UNUSED OPENINGS IN EXISTING
DUCTWORK.
M. ALL DUCTWORK DESIGNATIONS REFER TO NET FREE AREA INSIDE THE
DUCTWORK.
N. VOLUME DAMPERS SHALL BE LOCATED AT BRANCH CONNECTION TO THE
MAIN.
0. A MAXIMUM OF SIX FEEf OF FLEXIBLE DUCTWORK MAY BE USED AT ALL
SUPPLY DIFFUSERS. BRANCH DUCTWORK TO DIFFUSER SHALL BE SAME
SIZE AS DIFFUSER INLET UNLESS SPECIFICALLY LABELED OTHERWISE.
REFER TO DIFFUSER SCHEDULE FOR INLET SIZES. AVOID SHARP BENDS
IN FLEXIBLE DUCTWORK WHICH MAY CAUSE EXCESSIVE NOISE.
P. BRANCH DUCTWORK TO TERMINAL UNITS SHALL BE SAME SIZE AS
TERMINAL UNIT INLET UNLESS SPECIFICALLY LABELED OTHERWISE.
REFER TO TERMINAL UNIT SCHEDULE FOR INLET SIZES.
NOTATION DESIGNATORS
GENERAL NOTES: NOTES THAT APPLY EQUALLY TO ALL DISCIPLINES
WITHIN THE DRAWING SET.
GENERAL MECHANICAL NOTES THAT APPLY EQUALLY TO ALL SHEETS WITHIN
NOTES: THE DISCIPLINE.
GENERAL SHEET NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET ON
NOTES: WHICH THEY APPEAR.
SHEET KEYNOTES: NOTES THAT APPLY ONLY TO THE SPECIFIC SHEET ON
WHICH THEY APPEAR AND USE A KEYNOTE INDICATOR
TO IDENTIFY ITEMS.
SUBSET DESIGNATORS
G-000 GENERAL
A-000 ARCHITECTURAL
F-000 FIRE SUPPRESSION
P-000 PLUMBING
M-000 MECHANICAL
E-000 ELECTRICAL
T-000 TELECOMMUNICATION
SHEET TYPE DESIGNATORS
M-000 GENERAL (SYMBOLS, ABBREVIATIONS, NOTES)
M-100 PLANS (DEMOLITION, SITE, FOUNDATION)
M-200 PLANS (DUCTWORK, PLUMBING)
M-300 PLANS (HYDRONIC PIPING)
M-400 LARGE SCALE VIEWS (PLANS, SECTIONS)
M-500 DETAILS
M-600 SCHEDULES
M-700 SHORT SPECIFICATIONS
M-800 DIAGRAMS (CONTROLS, RISERS, ONE-LINES)
M-900 3D REPRESENTATIONS (ISOMETRICS)
LINETYPE DESIGNATORS
THIN CONTINUOUS LINETYPE INDICATE EXISTING ITEMS TO
REMAIN.
______ INTERMEDIATE DASHED LINETYPE INDICATE EXISTING ITEMS TO
BE REMOVED.
INTERMEDIATE OR WIDE CONTINUOUS LINETYPE INDICATE NEW
— ITEMS.
THIN HALFTONE LINETYPE INDICATE ITEMS BY OTHER
DISCIPLINE.
� INDICATES POINT OF NEW CONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
� INDICATES POINT OF DISCONNECTION TO EXISTING
EQUIPMENT, PIPING OR MATERIALS.
•
1
�
�
�
�
�I
�I
�
�
•
�
�
�1
�I
�
•
1
•
1
•
�
�
n
�I
i
L AC UIS
CONSULTING ENGINEERS
9229 DELEGATES ROW, SUITE 550
INDIANAPOLIS, IN 46240
317.706.2075
WWW.LACQUIS.COM
Engineer:
Y% /' 9.G. LL'!' ('9lFx.
��,m,�r s 3 r� a� »
�4 #� f ;a� Y;,�> � }�s.��.
By:
KEY P
BLDG B
9GNE NI5
�- - ..-
� � � �.
`� , `� ,
;�;
Project:
��
■
� M
� �
� r
� �
�--+
._
� �
� �
� �
�+ V
� �
� �
�
�
i
0
�
�
Z
�
��
.�
�
�
•
\
�
•
�
�
�
•
�
-
�
�
�
�
U
COPYRIGHT & OWNERSHIP OF DOCUMENTS
THIS DOCUMENT IS AN INSTRUMENT OF SERVICES AND IS THE SOLE
PROPERTY OF THE ARCHITECT AND PEDCOR DESIGN GROUP,LLC. ALL
INFORMATION CONTAINED HEREIN IS CONFIDENTIAL. ITS SUBMISSION
AND DISTRIBUTION TO OTHER PARTIES IS NOT TO BE CONSTRUED AS
PUBLICATION IN DEROGATION OF COMMON LAW COPYRIGHT,
INTELLECTUAL PROPERTY RIGHTS OR OTHER RESERVED RIGHTS. ALL
INFORMATION CONTAINED HEREIN CONSTITUTES THE ORIGINAL AND
UNPUBLISHED WORK OF THE ARCHITECT, JAMES R. STUTZMAN, AND
PEDCOR DESIGN GROUP, LLC. NO PART OR WHOLE OF THIS DESIGN,
THESE DRAWINGS, OR THE RESULTING BUILDING OR BUILDINGS, OR
PORTIONS OF THE RESULTING BUILDING OR BUILDINGS MAY BE
DUPLICATED, COPIED, EXHIBITED, PHOTOGRAPHED, PUBLISHED,
MODIFIED OR OTHERWISE DISTRIBUTED IN ANY WAY WITHOUT THE
SPECIFIC AND PRIOR WRITTEN CONSENT OF THE ARCHITECT, JAMES R.
STUTZMAN AND PEDCOR DESIGN GROUP, LLC. m COPYRIGHT2006,
2007, 2008, 2009, 2070, 2071 JAMES R. STUTZMAN, AIA, CARMEL, INDIANA
STATE RELEASE SET
Issue Date Drawn By Checked By
10/26/2012 SJO SJO
Revisions:
STATE RELEASE SET -11/30/2012
L'Acquis Project Number:
12226
Sheet Title:
MECHANICAL
SYMBOLS &
ABBREVIATIONS
Sheet Number:
■